design of rc building
TRANSCRIPT
-
8/11/2019 Design of RC Building
1/54
-
8/11/2019 Design of RC Building
2/54
-
8/11/2019 Design of RC Building
3/54
-
8/11/2019 Design of RC Building
4/54
-
8/11/2019 Design of RC Building
5/54
-
8/11/2019 Design of RC Building
6/54
-
8/11/2019 Design of RC Building
7/54
-
8/11/2019 Design of RC Building
8/54
-
8/11/2019 Design of RC Building
9/54
-
8/11/2019 Design of RC Building
10/54
-
8/11/2019 Design of RC Building
11/54
-
8/11/2019 Design of RC Building
12/54
-
8/11/2019 Design of RC Building
13/54
-
8/11/2019 Design of RC Building
14/54
-
8/11/2019 Design of RC Building
15/54
-
8/11/2019 Design of RC Building
16/54
-
8/11/2019 Design of RC Building
17/54
-
8/11/2019 Design of RC Building
18/54
-
8/11/2019 Design of RC Building
19/54
-
8/11/2019 Design of RC Building
20/54
-
8/11/2019 Design of RC Building
21/54
-
8/11/2019 Design of RC Building
22/54
-
8/11/2019 Design of RC Building
23/54
-
8/11/2019 Design of RC Building
24/54
-
8/11/2019 Design of RC Building
25/54
-
8/11/2019 Design of RC Building
26/54
-
8/11/2019 Design of RC Building
27/54
-
8/11/2019 Design of RC Building
28/54
-
8/11/2019 Design of RC Building
29/54
-
8/11/2019 Design of RC Building
30/54
-
8/11/2019 Design of RC Building
31/54
-
8/11/2019 Design of RC Building
32/54
-
8/11/2019 Design of RC Building
33/54
-
8/11/2019 Design of RC Building
34/54
-
8/11/2019 Design of RC Building
35/54
-
8/11/2019 Design of RC Building
36/54
-
8/11/2019 Design of RC Building
37/54
-
8/11/2019 Design of RC Building
38/54
-
8/11/2019 Design of RC Building
39/54
-
8/11/2019 Design of RC Building
40/54
Column size = 11 12 , Effective depth of footing = d
Punching Shear area A p = 2 (11 + d + 12 + d) d = 4 (11.5 + d) d
Punching Shear strength = 4 (f c ) = 4 0.85 (3000) = 186 psi = 0.186 ksi
0.186 {4 (11.5 + d) d} = 253.2 2.751 (11 + d) (12 + d)/(12) 2
d2 + 11.5 d = 339.9 (11 + d) (12 + d)/38.99 d = 12.48
Take footing thickness, t = 16.5 d = 12.5
Flexural Shear strength = 2 (f c ) = 2 0.85 (3000) = 93.1 psi = 13.41 ksf
Maximum shear force (according to SFD) = 141.6 k
Maximum flexural shear force = 141.6 27.51d [d is in ft]
13.41 10 d = 141.6 27.51d d = 0.876 = 10.52 12.5 , OK.
Maximum bending moment (according to BMD) = 288.6 k
Depth required by M is = (M/R u b) = {288.6/(0.781 10)} = 6.08 12.5 , OK.
As( ) = (f c/f y)[1 {1 2M
( )/( f c bd2)}]bd = 8.03 in 2
and A s(+) = (f c/f y)[1 {1 2M (+)/( f c bd 2)}]bd = 3.47 in 2 [using M (+) = 127.8 k ]
As(min) = (0.2/f y)bd = (0.2/40) 10.00 12 12.5 = 7.50 in2, which is A s
( ) but A s(+)
Provide 13 #7 bars at top and bottom.
Width of the transverse beams under columns = 11 + 12.5 = 23.5Load per unit length under C 8 = 253.2/10 = 25.32 k/
Maximum bending moment = 25.32 [(10 12/12)/2] 2/2 = 256.4 k
Depth required by M is = (M/R u b) = {256.4 12/(0.781 23.5)} = 12.95 11.5 .
Provide d = 13.5 , increase the thickness to 17.5 and put transverse rods at bottom
As(+) = (f c/f y)[1 {1 2M (+)/( f c bd 2)}]bd = 7.86 in 2 [Note: d = 13.5 here]
Similarly, A s(+) under C 6 = 6.21 in
2 and A s(+) under C 7 = 2.30 in
2
As(min) = (0.2/f y)bd = (0.2/40) 23.5 13.5 = 1.59 in2 As
(+) for all columns
Provide 11#7, 4#7 and 13#7 bars at bottom within the width of the transverse beams (23.5 )
under each column (in placing 13 #7 bars in 23.5 , be careful about minimum spacing).
Elsewhere, provide (0.2/f y)bd = 0.81 in 2/ft (i.e., #7 @ 9 c/c).
-
8/11/2019 Design of RC Building
41/54
Details of Individual Footing
11 # 7 bars
9.00
11 # 7 bars
9.00
11 # 7 bars
11 # 7 bars
Details of Combined Footing
11 # 7 bars 4 # 7 bars 13 # 7 bars
# 7@ 9 c/c 13 # 7 bars at top & bottom
15.5
10
20
17.5
-
8/11/2019 Design of RC Building
42/54
Seismic Detailing of RC Structures
1. Materials
Specification Possible Explanation
C o n c r e
t e f c 20 Mpa ( 3 ksi) for
3-storied or taller buildings
Weak concretes have low shear and bong strengths andcannot take full advantage of subsequent design provisions
S t e e
l f y 415 Mpa ( 60 ksi), preferably 250 Mpa (
36 ksi)
Lower strength steels have (a) a long yield region, (b) greaterductility, (c) greater f ult/f y ratio
2. Flexural Members (members whose factored axial stress f c /10)
Specification Possible Explanation
S i z e
b/d 0.3 To ensure lateral stability and improve torsional resistance b 8 To (a) decrease geometric error, (b) facilitate rod placement
d L c/4Behavior and design of deeper members are significantly
different
L o n g
i t u d i n a
l R e i n f o r c e m e n
t
N s(top) and N s(bottom) 2 Construction requirement0.1 f c /f y
(f c , f y in ksi)at both top and bottom
To avoid brittle failure upon cracking
0.025 at top or bottom
To (a) cause steel yielding before concrete crushing and(b) avoid steel congestion
As(bottom) 0.5A s(top) at joint and A s(bottom)/(top)
0.25A s(top) (max) at anysection
To ensure (a) adequate ductility, (b) minimum reinforcement
for moment reversal
Both top and bottom barsat an external joint must be anchored L d +10d b
from inner face ofcolumn with 90 bends
To ensure (a) adequate bar anchorage, (b) joint ductility
Lap splices are allowedfor 50% of bars, only
where stirrups are provided @ d/4 or 4 c/c
Closely spaced stirrups are necessary within lap lengths because of the possibility of loss of concrete cover
Lap splice lengths L d and are not allowed
within distance of 2dfrom joints or near
possible plastic hinges
Lap splices are not reliable under cyclic loading into theinelastic range
-
8/11/2019 Design of RC Building
43/54
2. Flexural Members (continued)
Specification Possible Explanation
W e b
R e i n f o r c e m e n
t
Web reinforcements mustconsist of closed verticalstirrups with 135 hooks
and 10d t ( 3 ) extensions
To provide lateral support and ensure strength developmentof longitudinal bars
Design shear force is themaximum of (a) shear
force from analysis, (b)shear force due to verticalloads plus as required forflexural yielding of joints
It is desirable that the beams should yield in flexure beforefailure in shear
Spacing of hoops within2d (beginning at 2 ) at
either end of a beam must be d/4, 8d b; elsewhere
St d/2
To (a) provide resistance to shear, (b) confine concrete toimprove ductility, (c) prevent buckling of longitudinal
compression bars
3. Axial Members (members whose factored axial stress f c /10)
Specification Possible Explanation
S i z e
bc/hc 0.4 To ensure lateral stability and improve torsional resistance
bc 12To avoid (a) slender columns,
(b) column failure before beams
L o n g i
t u d i n a
l R e i n f o r c e m e n
t Lap splices are allowedonly for 50% of bars,only where stirrups are provided @ b c/4 or 4
Closely spaced stirrups are necessary within lap lengths because of the possibility of loss of concrete cover
Lap splice lengths L d and only allowed in thecenter half of columns
Lap splices are not reliable under cyclic loading into theinelastic range
0.01 g 0.06To (a) ensure effectiveness and (b) avoid congestion of
longitudinal barsMc,ult 1.2 M b,ult
at jointTo obtain strong column weak beam condition to avoid
column failure before beams
T r a n s v e r s e
R e i n
f o r c e m e n
t
Transverse reinforcementmust consist of closedspirals or rectangular/
circular hoops with 135hooks with 10d t ( 3 )
extensions
To provide lateral support and ensure strength developmentof longitudinal bars
Parallel legs ofrectangular hoops must be spaced @ 12 c/c
To provide lateral support and ensure strength developmentof longitudinal bars
Spacing of hoops withinL0 ( d c, h c/6, 18 ) at each
end of column must be bc/4, 4 ; else S t bc/2
To (a) provide resistance to shear, (b) confine concrete toimprove ductility, (c) prevent buckling of longitudinal
compression bars
-
8/11/2019 Design of RC Building
44/54
3. Axial Members (continued)
Specification Possible Explanation
T r a n s v e r s e
R e i n f o r c e m e n
t
Design shear force is themaximum of (a) shear
force from analysis, (b)
shear force required forflexural yielding of joints
It is desirable that the columns should yield in flexure beforefailure in shear
Special confiningreinforcement (i.e., S t
bc/4, 4 ) should extend atleast 12 into any footing
To provide resistance to the very high axial loads and flexuraldemands at the base
Special confiningreinforcement (i.e., S t
bc/4, 4 ) should be provided over the entire
height of columnssupporting discontinued
stiff members and extendLd into the member
Discontinued stiff members (e.g., shear walls, masonry walls, bracings, mezzanine floors) may develop significant forces
and considerable inelastic response
For special confinement,area of circular spirals
0.11 S td (f c /f y)(A g/Ac 1),of rectangular hoops
0.3 S td (f c /f y)(A g/A c 1)
To ensure load carrying capacity upto concrete spalling,taking into consideration the greater effectiveness of circular
spirals compared to rectangular hoops.It also ensures toughness and ductility of columns
4. Joints of Frames
Specification Possible Explanation
T r a n s v e r s e
R e i n f o r c e m e n t
Special confiningreinforcement (i.e., S t bc/4, 4 ) should extend
through the joint
To provide resistance to the shear force transmitted byframing members and improve the bond between steel and
concrete within the joint
St bc/2, 6 through jointwith beams of width b
0.75b c
Some confinement is provided by the beams framing into thevertical faces of the joint
-
8/11/2019 Design of RC Building
45/54
Seismic Detailing of a Typical Frame
Original Design of Frame (3)
Beams SF 1 (D) SF 2 (D) BM 1(D) BM 0(V=D) BM 2(D)B16 9.3 -9.6 -23.0 12.4 -22.9
B20 6.5 -5.6 5.5, -17.6 0.7 8.2, -13.7
The reinforcements are arranged as follows
2 #5 through 1 #7 extra
2 #5 through
C2 B16 C6 B20 C10
13
12
b f
12
4
12
10 #6 bars
#3 ties @ 12 c/c
Column Section(with reinforcements)
Beam + Slab Section(without reinforcement)
Beam Sections(with reinforcements)
Section a-a Section b-b Section c-c Section d-d Section e-e
#3 stirrups@ 6.75 c/c
e
e
c
c
a
a
b
b
d
d
12
4
All #5 barsExtra #7 bar
-
8/11/2019 Design of RC Building
46/54
1. Materials
Specification Design Condition Comments
C
o n c r e t e
f c 20 Mpa ( 3 ksi) for3-storied or taller
buildingsf c = 3 ksi OK
S t e e
l f y 415 Mpa ( 60 ksi), preferably 250 Mpa (
36 ksi)f y = 40 ksi OK
2. Flexural Members (members whose factored axial stress f c /10)
Specification Design Condition Comments
S i z e
b/d 0.3 b/d = 12/13.5 = 0.89 OK b 8 b = 12 OK
d L c/4 d = 13.5 , L c/4 = 3 and 1.5 OK
L o n g i
t u d i n a
l R e i n f o r c e m e n
t
N s(top) and N s(bottom) 2 N s(top) 2, N s(bottom) = 2 OK
0.1 f c /f y (= 0.0043)
at both top and bottom
As(top) = 0.62, 1.22 in 2 As(bottom) = 0.62 in
2 (top) = 0.0038, 0.0075
(bottom) = 0.0038
Both (top) and (bottom) are not OK
0.025 at top or bottom Maximum = 0.0075 OKAs(bottom) 0.5A s(top) at joint
and A s(bottom)/(top)0.25A s(top) (max) at any
section
As(top) = 0.62, 1.22 in2
As(bottom) = 0.62 in2
(through)OK
Both top and bottom barsat an external joint must be anchored L d +10d b
from inner face of columnwith 90 bends
Not specified in design Needs to be specified
Lap splices are allowedfor 50% of bars, only
where stirrups are provided @ d/4 (= 3.38 )
or 4 c/c
Not specified in design Needs to be specified
Lap splice lengths L d and are not allowed within
distance of 2d (= 27 )from joints or near
possible plastic hinges
Not specified in design Needs to be specified
-
8/11/2019 Design of RC Building
47/54
2. Flexural Members (continued)
Specification Design Condition Comments
W e b
R e i n f o r c e m e n
t
Web reinforcements mustconsist of closed verticalstirrups with 135 hooks,
10d t 3 extensions
Not specified in design Needs to be specified
Design shear force is themaximum of (a) shear
force from analysis, (b)shear force due to verticalloads plus as required forflexural yielding of joints
Design shear force is takenonly from analysis Needs to be checked
Spacing of hoops within2d (= 27 ), beginning at2 , at either end of a beam
must be d/4, 8d b (=3.38 , 5 ) elsewhere
St d/2 (= 6.75 )
St = 6.75 c/c (= d/2)throughout the beams
Not OK
3. Axial Members (members whose factored axial stress f c /10)
Specification Design Condition Comments
S i z e bc/hc 0.4 bc/hc = 12/13 = 0.92 OK
bc 12 b c = 12 OK
L o n g
i t u d i n a
l R e i n f o r c e m e n
t Lap splices are allowedonly for 50% of bars,only where stirrups are
provided @ bc/4 or 4
Not specified in design Needs to be specified
Lap splice lengths L d and only allowed in thecenter half of columns
Not specified in design Needs to be specified
0.01 g 0.06As = 4.40 in 2
g = 0.029OK
M c,ult 1.2 M b,ult at joint
Not specified in design Needs to be checked
T r a n s v e r s e
R e i n f o r c e m e n
tStirrups must be closed
rectangular/ circular hoopswith 135 hooks with 10d t
( 3.75 ) extensions
Not specified in design Needs to be specified
Parallel legs of rectangularhoops must be spaced
@ 12 c/c
Parallel legs of rectangularhoops spaced @ 10 c/c
OK
Hoop spacing within L 0dc, H c/6, 18 (= 10 , 18 ,
18 ) at each end of column bc/4 (= 3 ), 4 ; else S t
bc/2 (= 6 )
St = 12 c/c throughout thecolumns
Not OK
-
8/11/2019 Design of RC Building
48/54
3. Axial Members (continued)
Specification Design Condition Comments
T r a n s v e r s e
R e i n f o r c e m e n
t
Design shear force is themaximum of (a) shear
force from analysis, (b)
shear force required forflexural yielding of joints
Design shear force is takenonly from analysis Needs to be checked
Special confiningreinforcement (i.e., S t 3 )should extend at least 12
into any footing
Not specified in design Needs to be specified
Special confiningreinforcement (i.e., S t 3 )
should be provided overthe entire height ofcolumns supporting
discontinued stiff
members and extend L d into the member
Column supports no particular stiff member, but
soft first storey
Special confiningreinforcement (i.e., S t 3 )
over the entire height ofground floor columns
For special confinement,area of circular spirals
0.11 S td (f c /f y)(A g/Ac 1),of rectangular hoops
0.3 S td (f c /f y)(A g/A c 1)[= 0.3 3 9.5 (3/40)(156/90 1) = 0.47 in 2]
No special confinement provided and 0.22 in 2 hoop
area provided @ 12 c/c
Atleast 2-legged #4 or 4-legged #3 bars needed as
special confinement
4. Joints of Frames
Specification Design Condition Comments
T r a n s v e r s e
R e i n f o r c e m e n
t Special confiningreinforcement (i.e., S t 3 )should extend through the
joint
Not specified in design Needs to be specified
St bc/2 (= 6 ) and 6through joint with beams
of width b 0.75b c
b = 12 , b c = 12 , but nostirrups specified within
joints
Since b 0.75b c St 6 through joint
-
8/11/2019 Design of RC Building
49/54
Correct A s(min) for BeamsThe longitudinal steel ratio is (min) = 0.1 f c /f y (= 0.0043) in some cases
If all the #5 bars are changed to #6 barsAs(top) = 0.88, 1.48 in 2, A s(bottom) = 0.88 in 2
(top) = 0.0054, 0.0091, (bottom) = 0.0054, which are all (min) and (max) (= 0.025)
Check Shear Capacity of Beams
Beams SF (V) SF (D) SF (USD)B16 9.6 9.6 14.4B20 4.3 6.5 9.8
For Beam B 16, a = A sf y/0.85f c b = 1.48 40/(0.85 3 12) = 1.93Mult at joint1 = A sf y (d a/2) = 1.48 40 (13.5 1.93/2)/12 = 61.83 kSimilarly, A s = 0.88 in
2 M ult at joint2 = 37.91 kVDesign = 1.4 (61.83 + 37.91)/12 + 9.6 1.5 = 26.04 k
For Beam B 20, V Design = 1.4 (61.83 + 37.91)/6 + 4.3 1.5 = 29.72 k
Vc = 2 f c bd = 2 (3/1000) 12 13.5 = 17.75 k, V c1 = 6 f c bd = 53.24 kSmax = A sf yd/(V n Vc) = 0.22 40 13.5/(29.72/0.85 17.75) = 6.89
Stirrup spacing provided @6.75 is just adequate, but special transverse reinforcements arespaced @3 closer to the joints.
Check Shear Capacity of ColumnsSince the bending moments from analysis are small, shear forces are also assumed small;therefore the shear force is checked for flexural yielding of joints.Also the column size is 13 12 ; i.e., the dimension 12 works as h.
For Column C 2 at ground floor, P = 130.8 1.4 = 183.12 kP/( A gf c ) = 183.12/(0.7 13 12 3) = 0.56, = 7/12 0.6, = (40/2.55) 0.023 = 0.36
M/( bchc2f c ) = 0.18 M = 0.18 (0.9 13 12
2 3) = 909.79 k = 75.82 kVDesign = 1.4 (75.82 + 75.82)/9 = 23.59 k
For Column C 6, P = 140.2 1.4 = 196.28 kP/( A gf c ) = 196.28/(0.7 13 12 3) = 0.60, with = 0.6, = 0.36
M/( bchc2f c ) = 0.17 M = 0.17 (0.9 13 12
2 3) = 859.25 k = 71.60 kVDesign = 1.4 (71.60 + 71.60)/9 = 22.28 k
Vc = 2 f c bd = 2 (3/1000) 13 9.5 = 13.53 k, V c1 = 6 f c bd = 40.59 kSmax = A sf yd/(V n Vc) = 0.22 40 9.5/(23.59/0.85 13.53) = 5.88
Stirrup spacing provided @12 throughout the columns is not adequate; i.e., provide #3 ties @5c/c, moreover special transverse reinforcements are spaced @3 closer to the joints.
-
8/11/2019 Design of RC Building
50/54
Check Moment Capacity of Joints (for Weak Beam Strong Column)Since the first joint (between C 2 at two floors and B 16) consists of one beam only with twocolumns, the second joint (between C 6 at two floors and B 16, B 20) is checked first for the WeakBeam Strong Column.
For ground floor Column C 6, P = 140.2 1.4 = 196.28 kP/( A gf c ) = 0.60, with = 0.6, = 0.36 M = 71.60 k
For first floor Column C 6, P/( A gf c ) 3/4 0.60 = 0.45, with = 0.6, = 0.36M/( b chc
2f c ) = 0.19 M = 0.19 (0.9 13 122 3) = 960.34 k = 80.03 k
M c,ult = 71.60 + 80.03 = 151.63 k , 1.2 M b,ult = 1.2 (37.91 + 37.91) = 90.98 kM c,ult 1.2 M b,ult ; i.e., the Weak Beam Strong Column condition is satisfied.
The following sections are chosen as columns and beams
12
10 #6 bars
4-legged #3 ties @ 3 c/c (special) or 5 c/c
Column Section(with reinforcements)
13
135 hooks with 4 extensions
Beam Sections(with reinforcements)
Section a-a Section b-b Section c-c Section d-d Section e-e
12
4
All #6 barsExtra #7 bar 135 hooks with 4 extensions
-
8/11/2019 Design of RC Building
51/54
The reinforcements are arranged as follows
Sp 2-legged #3 stirrups @ 3 (length 27 )C-Sp 4-legged #3 stirrups @ 3 (through)
SpSpSp
#3 stirrups@ 6.75 c/c
C - S p
2 #6 through
2 #6 through
#3 stirrups@ 6.75 c/c
1 #7 extra
12
18
Anchorage at end joints L anch = L d + 10 d b Ld for #7 bars = 0.04 A s f y/ f c = 0.04 0.60 40/ (3/1000) 1.4 = 24.53Lanch = 24.53 + 10 7/8 = 33.29 ; i.e., 34
2.25
2.25
Lap-splices not allowed hereElsewhere, it is only allowed for 50% bars with special confinement
-
8/11/2019 Design of RC Building
52/54
Design of Shear Walls
ACI Provisions for Shear Wall Design
1. The thickness of the shear wall must be atleast 8 inch; i.e., h 8
2. Sections taken at L w/2 or H w/2 (whichever is less) from base is considered as critical for shear
3. In designing the horizontal shear forces or bending moments, the depth of the section is takenas d = 0.8L w
4. The nominal shear force, i.e., the permissible shear force in the section is(i) greater the design shear force, i.e., V n = V design / [V = V design in WSD](ii) summation of the shear force capacities of concrete and steel , i.e., V n = V c + V s(iii) cannot be greater than 10 f c hd; i.e., V n 10 f c hd [V 5 f c hd in WSD]
5. If N u is taken as negative for tensile forces (lbs)Vc can be taken as 2(1 + N u/500A g) f c hd [V c 1.1(1 + N u/500A g) f c hd in WSD]Using a more detailed analysis,
Vc 3.3 f c hd + N ud/(4 L w)and [0.6 f c + {1.25 f c + 0.2 N u/(h L w)}/{M u/(V uLw) 0.5}] hd[In WSD, take V c to be about half of these]
6. If V n V c/2, then the minimum horizontal reinforcements are provided
7. If V n V c, then the horizontal reinforcements are spaced ats2 = A vhf y d/(V n Vc) [s 2 = A vhf sd/(V V c) in WSD] or ; where s 2 L w/5, 3h, 18However, h = A vh/(hs 2) 0.0025; i.e., s 2 Avh/(0.0025 h)
8. The vertical reinforcements are spaced ats1 L w/3, 3h, 18
v = A vv/(hs 1) = 0.0025 + 0.5 (2.5 H w/Lw) ( h 0.0025)However, v 0.0025 and h
9. Flexural reinforcements are provided like normal beams
hLw
Hw s1
s2
Avv
Avh
-
8/11/2019 Design of RC Building
53/54
Shear Wall Design in the Long Direction of the BuildingThe long direction includes two Frame(1)s and two Frame (2)s.Here, the height of the wall H w = 40 , the length of the wall L w = 7Assuming only the rear wall to take all the loads (due to the large opening in the front wall), withsimilar seismic coefficients as taken initially for the frame analysis, the following lateral forcesare calculated in the long direction of the building.
1. Assumed thickness of the wall, h = 8
2. Sections taken at L w/2 (= 3.5 which is H w/2 = 20 ) from base can be considered as criticalThe nominal shear force, V = 28.54 + 21.40 + 14.27 + 7.13 = 71.24 k
3. The depth chosen for design is, d 0.8L w = 0.8 7 12 = 67.2
4. V = 71.24 k, while 5 f c hd = 5 (3/1000) 8 67.2 = 147.23 k V 5 f c hd OK
5. Since there is no net tensile force on the section, V c can be taken as = 1.1 f c hd = 32.39 k
6. Here V is not V c/2, then the minimum horizontal reinforcements are not sufficient
7. Using 2-legged #3 bars, the horizontal reinforcements are spaced ats2 = 0.22 20 67.2/(71.24 32.39) = 7.61Using 2-legged #4 bars, s 2 = 13.84Also s 2 (L w/5 =) 16.8 , (3h =) 24 , 18 , (A vh/0.0025 h =) 20
Use 2-legged #4 bars @ 14 c/ch = A vh/(hs 2) = 0.40/(8 14) = 0.0036
8. Using 2-legged #4 bars as vertical reinforcementsv = A vv/(hs 1) = 0.0025 + 0.5 (2.5 H w/Lw) ( h 0.0025)
0.40/(8s 1) = 0.0025 + 0.5 (2.5 40/7) (0.0036 0.0025) = 0.0008 s 1 = 64.26However, s 1 (L w/3 =) 28 , (3h =) 24 , 18 , (A vv/0.0025 h =) 20
Use 2-legged #4 bars @ 18 c/ch = A vv/(hs a) = 0.40/(8 18) = 0.0028, which is 0.0025 and h
2 (7.70 + 6.57) = 28.54 k
21.40 k
14.27 k
7.13 k
3.5
7
4@10= 40
Critical Section
-
8/11/2019 Design of RC Building
54/54
9. Flexural reinforcements are provided like normal beamsMmax = 7.13 10 + 14.27 20 + 21.40 30 + 28.54 40 = 2140 k-ft
As = M/(f s jd) = 2140 12/(20 0.87 67.2) = 21.97 in 2,Use 18 #10 bars on each side, to be curtailed over the height
7
40
# 4 @ 1 4 c / c
#4 @14 c/c#4 @18 c/c
#4 @18 c/c
18 # 10 bars 18 # 10 bars