SCHEDULE TECHNICAL PARTICULARS: 100 KVA (11-15/0,415 KV) Ref No. Description Unit Data POLE MOUNTED DISTRIBUTION TRANSFORMER 1 Applicable Standards IEC 60076 2 Manufacture and Country of manufacture EREN TRAFO TURKEY 3 Manufacture’s Type Number ONAN 4 Rated Power output kVA 100 5 Number of phases 3 6 Rated frequency Hz 50 7 Rated Primary voltage / Current kV/A 11 - 15 8 Rated Secondary voltage / Current kV/A 0,415 9 Vector group Dyn 11 10 Off - load tapping of primary winding % 11 * (-/+)2,5%*3 15 * (-/+)2,5%*3 11 Ambient temperature °C 50 12 Temperature rise in Winding Top oil Core °C °C °C 55 50 50 13 Applied test voltage, 1min, 50 Hz Primary winding Secondary winding kV kV 28 3 14 Impulse test voltage, full wave, primary winding kV 75 at 11 kV 95 at 15 kV 15 No-load losses kW 300 16 Load losses kW 1800 17 Impedance voltage % 4 18 No- load current % 1 19 Terminal bolts Material Diameter, primary side Diameter, secondary side mm mm copper 12 12 20 Material of windings High voltage Low voltage COPPER COPPER 21 Mass Total mass Mass of oil Untanked mas kg kg kg 720 190 340 22 Termination Primary side Secondary side Open bushing Open bushing 23 ALTITUDE ABOVE SEA LEVEL M 2300 Signature:____________________ Date: ____________________

Upload: engnajeeb75

Post on 30-Nov-2015

230 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: DATA SHEET of Transformers -100-300-500-1000 kVA

SCHEDULE TECHNICAL PARTICULARS: 100 KVA (11-15/0,415 KV)

Ref No. Description Unit Data

POLE MOUNTED DISTRIBUTION TRANSFORMER 1 Applicable Standards IEC 60076 2 Manufacture and Country of manufacture EREN TRAFO TURKEY 3 Manufacture’s Type Number ONAN 4 Rated Power output kVA 100 5 Number of phases 3 6 Rated frequency Hz 50 7 Rated Primary voltage / Current kV/A 11 - 15 8 Rated Secondary voltage / Current kV/A 0,415 9 Vector group Dyn 11 10 Off - load tapping of primary winding % 11 * (-/+)2,5%*3

15 * (-/+)2,5%*3 11 Ambient temperature °C 50

12 Temperature rise in Winding

Top oil Core

°C °C °C

55 50 50

13 Applied test voltage, 1min, 50 Hz Primary winding Secondary winding

kV kV

28 3

14 Impulse test voltage, full wave, primary winding kV 75 at 11 kV 95 at 15 kV

15 No-load losses kW 300 16 Load losses kW 1800 17 Impedance voltage % 4 18 No- load current % 1 19 Terminal bolts

Material Diameter, primary side Diameter, secondary side

mm mm

copper

12 12

20 Material of windings High voltage Low voltage

COPPER COPPER

21 Mass Total mass

Mass of oil Untanked mas

kg kg kg

720 190 340

22 Termination Primary side Secondary side

Open bushing Open bushing

23 ALTITUDE ABOVE SEA LEVEL M 2300

Signature:____________________ Date: ____________________

Page 2: DATA SHEET of Transformers -100-300-500-1000 kVA

SCHEDULE TECHNICAL PARTICULARS: 300 KVA (11-15/0,415 KV)

Ref No. Description Unit Data

POLE MOUNTED DISTRIBUTION TRANSFORMER 1 Applicable Standards IEC 60076 2 Manufacture and Country of manufacture EREN TRAFO TURKEY 3 Manufacture’s Type Number ONAN 4 Rated Power output kVA 300 5 Number of phases 3 6 Rated frequency Hz 50 7 Rated Primary voltage / Current kV/A 11 - 15 8 Rated Secondary voltage / Current kV/A 0,415 9 Vector group Dyn 11 10 Off - load tapping of primary winding % 11 * (-/+)2,5%*3

15 * (-/+)2,5%*3 11 Ambient temperature °C 50

12 Temperature rise in Winding

Top oil Core

°C °C °C

55 50 50

13 Applied test voltage, 1min, 50 Hz Primary winding Secondary winding

kV kV

28 3

14 Impulse test voltage, full wave, primary winding kV 75 at 11 kV 95 at 15 kV

15 No-load losses kW 700 16 Load losses kW 3550 17 Impedance voltage % 4 18 No- load current % 1 19 Terminal bolts

Material Diameter, primary side Diameter, secondary side

mm mm

copper

12 20

20 Material of windings High voltage Low voltage

COPPER COPPER

21 Mass Total mass

Mass of oil Untanked mas

kg kg kg

1170 300 650

22 Termination Primary side Secondary side

Open bushing Open bushing

23 ALTITUDE ABOVE SEA LEVEL M 2300

Signature:____________________ Date: ____________________

Page 3: DATA SHEET of Transformers -100-300-500-1000 kVA

SCHEDULE TECHNICAL PARTICULARS: 500 kVA (11-15/0,415 kV)

Ref No. Description Unit Data

GROUND MOUNTED DISTRIBUTION TRANSFORMER (ONAN) 1 Applicable Standards IEC 60076 2 Manufacture and Country of manufacture EREN TRAFO TURKEY 3 Manufacture’s Type Number ONAN 4 Rated Power output kVA 500 5 Number of phases 3 6 Rated frequency Hz 50 7 Rated Primary voltage / Current kV/A 11 - 15 8 Rated Secondary voltage / Current kV/A 0,415 9 Vector group Dyn 11 10 Off - load tapping of primary winding % 11 * (-/+)2,5%*3

15 * (-/+)2,5%*3 11 Ambient temperature °C 50

12 Temperature rise in Winding

Top oil Core

°C °C °C

55 50 50

13 Applied test voltage, 1min, 50 Hz Primary winding Secondary winding

kV kV

28 3

14 Impulse test voltage, full wave, primary winding kV 75 at 11 kV 95 at 15 kV

15 No-load losses kW 1100 16 Load losses kW 5500 17 Impedance voltage % 4,5 18 No- load current % 1 19 Terminal bolts

Material Diameter, primary side Diameter, secondary side

mm mm

COPPER

12 30-Bus Duct

20 Material of windings High voltage Low voltage

COPPER COPPER

21 Mass Total mass Mass of oil Untanked mass

kg kg kg

1770 450 970

22 Termination Primary side Secondary side

CABLE BOX CABLE BOX

23 ALTITUDE ABOVE SEA LEVEL M 2300

Signature:____________________ Date: ____________________

Page 4: DATA SHEET of Transformers -100-300-500-1000 kVA

SCHEDULE TECHNICAL PARTICULARS: 1000 kVA (11-15/0,415 kV)

Ref No. Description Unit Data

GROUND MOUNTED DISTRIBUTION TRANSFORMER (ONAN) 1 Applicable Standards IEC 60076 2 Manufacture and Country of manufacture EREN TRAFO TURKEY 3 Manufacture’s Type Number ONAN 4 Rated Power output kVA 1000 5 Number of phases 3 6 Rated frequency Hz 50 7 Rated Primary voltage / Current kV/A 11 - 15 8 Rated Secondary voltage / Current kV/A 0,415 9 Vector group Dyn 11 10 Off - load tapping of primary winding % 11 * (-/+)2,5%*3

15 * (-/+)2,5%*3 11 Ambient temperature °C 50

12 Temperature rise in Winding

Top oil Core

°C °C °C

55 50 50

13 Applied test voltage, 1min, 50 Hz Primary winding Secondary winding

kV kV

28 3

14 Impulse test voltage, full wave, primary winding kV 75 at 11 kV 95 at 15 kV

15 No-load losses kW 1700 16 Load losses kW 10500 17 Impedance voltage % 6,2 18 No- load current % 1 19 Terminal bolts

Material Diameter, primary side Diameter, secondary side

mm mm

12 42-Bus Duct

20 Material of windings High voltage Low voltage

COPPER COPPER

21 Mass Total mass Mass of oil Untanked mass

kg kg kg

2950 740

1500 22 Termination Primary side

Secondary side

CABLE BOX CABLE BOX

23 ALTITUDE ABOVE SEA LEVEL M 2300

Signature:____________________ Date: ____________________