ControlIT
1/16 DIN Controller/Alarm Unit
C50
High visibility dual 4-digit display– shows set point and process variable
Standard relay or logic control output– simple time proportioning or on/off control
Optional alarm relay– additional relay to give hi/lo process alarm
Universal process input– direct connection for any process signal
IP65 (NEMA3) protection and full noiseimmunity– reliability in the harshest environments
NEMA 4X / IP66 construction–hose-down protection
One-shot autotune–automatic setting of optimum PID values
C50 – the 1/16 DIN controller to suityour simplest applications
Data SheetSS/C50_7
1/16 DIN Controller/Alarm UnitC50 SS/C50_7
2
C50
The C50 Controller/Alarm unit is a compact single loopcontroller, with the capability to measure, indicate andcontrol a variety of process variables.
The unit is ideal for simple PID control, offering On/Off orTime proportioning control with a one shot self-tune facility.The C50 can also act as an independent alarm unit, forexample, as an over-temperature safety cutout unit forfurnaces or ovens.
The unit is quickly set up for most process signal inputsand, with IP65 (NEMA3) front panel protection, is suitablefor a wide range of applications.
Solid State Relay
Contactor
AlarmAnnunciator
Standard Option
• Thermocouple• RTD• Linear milliamps• Linear volts, millivolts
• Relay• Logic
Relay
Universal Process Input Primary Output
Additional Alarm Output
KEY:
1/16 DIN Controller/Alarm UnitC50 SS/C50_7
3
PID ControlThe unit’s primary relay or logic output can provide a time proportioning PID output,for control of contactors and solid state relays (SSR).
Override AlarmBy configuring the relay output as an overrange alarm, the C50 can act as anindependent alarm unit, providing protection for your process.
Ramping Set PointTo reduce shock to the process when changing set point, the C50 can be configuredto ramp up to the new set point over a preset period of time.
SP
t
1/16 DIN Controller/Alarm UnitC50 SS/C50_7
4
Specification
Summary
PID single loop controller/alarm unit
Autotune Facility
Fully User Configurable
IP65 (NEMA3) Front Face
OperationDisplay
High intensity, 7-segment, 2 x 4 red LED display
Size upper 10mm (0.39 in.)
lower 8mm (0.31 in.)
Configuration
User defined via front panel and internal links.
OutputsPrimary output (fitted as standard)
User configurable as either:
Relay:
SPDT 2A 120/240V AC
or
TTL Logic (SSR Drive):
Digital >4.2V DC for
Min load 1kΩ
Not isolated from input
Output functions
User configurable as either:
On/Off control output
Time proportioning PID control output
PhysicalSize
48mm (1.89 in.) x 48mm (1.89 in.)x 110mm (4.33 in.) (depth behind panel)
Weight
<200g (0.44lbs.) approx.
OptionSecond relay output, configurable for alarms, meets thespecification of the standard relay output.
ElectricalVoltage:
90 to 264 V AC 50/60 Hz
Power consumption:
<4VA
1/16 DIN Controller/Alarm UnitC50 SS/C50_7
5
Analog InputsSingle universal process input.
Type
Universally Configurable for:
Thermocouple (THC)
Resistance Thermometer (RTD)
Linear Millivolt
Linear Current
Linear DC voltage
Input Sampling Rate
1 sample/250ms
Input impedance:
Millivolts/THC/RTD >100MΩ
Volts >47KΩ
Current <4.7Ω
Linearizer functions
Automatic linearisation of THC types B, J, K, R, S, T, L, N andRTD Pt100
Broken Sensor protection
For the following options, break detected within two seconds andcontrol outputs DOWN scale to OFF (0% power):
THC, RTD, DC mV, DC Volts (1 – 5V and 2 – 10V),DC mA (4 to 20mA).
Cold junction compensation:
Automatic CJC incorporated as standard.
Input noise rejection
Common mode rejection: >120dB at 50/60Hz withbalanced lead.
Series mode rejection: >500% of span at 50/60Hz.
Accuracy
Measurement error: <± 0.25% of span ± 1LSD
Linearizer: Typically ±0.2 °C
Display range: –1999 to +9999
CJC accuracy: <± 0.05 °C /°C change in ambienttemperature
Temperature Limits
epyTCHT °C °F
485CEI&521SBNreP .niM .xaM .niM .xaM
RepyT 0 0561 23 2003
SepyT 0 9461 23 0003
JepyT
0 4.502 23 7.104
0 054 23 248
0 167 23 1041
TepyT002– 262 823– 305
0 6.062 23 105
KepyT002– 067 823– 9931
002– 3731 823– 3052
LepyT
0 7.502 23 2.204
0 054 23 148
0 267 23 3041
BepyT 001 2481 112 5133
NepyT0 9931 23 0552
0 008 0.23 1741
DTRepyT157CEI&06734NIDrep
9.001– 001 7.941– 9.112
002– 602 823– 204
9.001– 3.735 7.941– 999
0 9.001 23 6.312
0 003 23 175
0 008 0.23 1741
.etoN006wolebdeetnaraugtonsiycaruccaecnamrofreP ° 211(C ° SdnaR,Bsepytrof)F
.selpuocomreht
001,munitalperiw-3,DTR Ω 004ot0foegnarhtiw Ω.
Electrical Input Ranges
epyTtupnI.niMeulaV
eulaV.xaM.niMeulaV
eulaV.xaM
Vm 0 05 01 05
V 0 5 1 5
V 0 01 2 01
Am 0 02 4 02
1/16 DIN Controller/Alarm UnitC50 SS/C50_7
6
Overall Dimensions
Electrical Connections
10(0.39)
110(4.33)
+ 0.6- 0
+ 0.03- 0
48(1.89)
48 (1.89)
Panel cut out45
(1.77 )
+ 0.6- 0
+ 0.03- 0
45
(1.77 )
N/O C N/C
7
8
9
16 17 18
13 14 15
10
11
12
1
2
3
4
5
6
Relay Output 2
L
N96 to 264V AC Mains Supply
N/O
C
N/C
Rel
ayO
utp
ut
1
RTD
–
+
THC
–
+
V/mV
+
–mA
+
–DC
fo
r S
SR
Dimensions in mm (in.)
1/16 DIN Controller/Alarm UnitC50 SS/C50_7
7
Ordering Information
05C 1/ 61 tinUmralA/rellortnoCNID 05C X/ X X X X X X
)ylnoslaunamrof(egaugnaL
hsilgnEhcnerFnamreG
KFD
sepyTtupnI
lasrevinU 2
1tuptuO
cigoL/yaleR 1
2tuptuO
enoNyaleR1
01
serutaeFlaicepS/gnimmargorP
enoN 0 0 0
1/16 DIN Controller/Alarm UnitC50 SS/C50_7
SS
/C50
Issu
e 7
ABB Inc.125 E. County Line RoadWarminsterPA 18974USATel: +1 215 674 6000Fax: +1 215 674 7183
ABB LimitedHoward Road, St NeotsCambridgeshirePE19 8EUUKTel: +44 (0)1480 475321Fax: +44 (0)1480 217948
ABB has Sales & Customer Supportexpertise in over 100 countries worldwide
www.abb.com
The Company’s policy is one of continuous productimprovement and the right is reserved to modify the
information contained herein without notice.
Printed in UK (07.04)
© ABB 2004
ControlIT
1/8 DIN Process Controller
C100
PID controller with 'one shot' auto-tune– single loop, heat/cool and ramp/soak as standard
Quick code, front face or PC configuration– easy commissioning and operation using our
Windows™-based software
Universal process input withtransmitter power supply– direct connection for any process signal
Hoseproof front panel and full noise immunity– reliability in the harshest environments
RS485/Modbus serial communications– SCADA, PLC and open systems integration
C100 –the easy-to use 1/8 DIN controller
with extensive capabilities
Data SheetSS/C100_10
1/8 DIN Process ControllerC100 SS/C100_10
2
C100
The C100 Universal Process controller is a highly versatile,single loop controller designed to be exceptionally easy tooperate and set up.
Universal input and integral transmitter power supply ensurethat the C100 has the capabilities to measure a wide rangeof process signals such as temperature, pressure, flow andlevel.
Analog, logic and relay control outputs are all fitted asstandard, with the option to add further i/o capabilities suchas additional relays, remote set point and digital input, tosuit your application.
The configuration of the C100 is simply achieved by movingthe security switch and entering a simple code from thefront panel keys. No passwords, no input links, nocomplications.
With hoseproof front panel protection and superior RFimmunity as standard the C100 has been designed tocontrol reliably in the harshest of today’s industrialenvironments.
1/8 DIN Process ControllerC100 SS/C100_10
3
PID Control
Alarms
PVRetransmission
AlarmAnnunciator
SCADA Systems (on PC)KEY: Standard Option
Transmitter PowerSupply
Universal Process Input• Thermocouple• RTD• 4 to 20mA• Volts, millivolts
Primary Outputs1 x Analog1 x Logic1 x Relay
Serial CommunicationsRS485 Modbus RTU
Additional Alarm Outputs2 x Relays
Auxiliary Inputs
• Digital• Remote Set Point
1/8 DIN Process ControllerC100 SS/C100_10
4
PID ControlSimple PID control is available using any of the unit’s threebuilt-in outputs.
• 4 to 20mA analog
• Logic 18V time proportioning (to drive solid state relays)
• 5A relay for Time proportioning or On/Off control
SP
t
SP
PV1
PV2 OP
MRA A
OPOP
MRA A
OPOP
SP
Ramp/Soak Set Point ProfilesThe ramp/soak facility available on every C100 provides for asingle program, four-segment profile. This facility also includesguaranteed ramp/soak, repeat program, skip and reset.
Master/Slave and CascadeTwo or more C100s can be used in master/slave, or cascade,configuration with the addition of the remote set point optionto the basic unit.
Heat/CoolHeat/Cool control strategies may be implemented on thestandard C100, using a combination of the analog, logic andrelay outputs.
RS485/ModbusFitted with an optional RS485 serial communication board, theC100 can communicate with PLCs and SCADA systems using
1/8 DIN Process ControllerC100 SS/C100_10
5
Standard FunctionsControl types
Programmable for manual, on/off, time proportioning,current proportioning and heat/cool control.
Set points
Local
Remote
4 selectable fixed value
Ramping set point
Profile controller
Number 4 ramp/soak segments
Features Guaranteed ramp/soak, self seeking set point,program repeat
Controls Run, hold and stop from front panel switcheRun/hold or run/stop from digital input
Alarms
Number Two user-defined
Type High/low processHigh/low deviation
Specification
SummaryP, PI, PID single loop controller
Autotune facility
Fully user configurable
Hoseproof front face
OperationDisplay
High-intensity 7-segment, 2 x 4-digit LED display
Display range –999 to +9999
Display resolution ±1 digit
Display height 10mm (0.39 in.)
Configuration
User defined via front panel or PC Configurator
1/8 DIN Process ControllerC100 SS/C100_10
6
Analog InputsNumber
One as standard
One optional (4 to 20mA remote set point input)
Input sampling rate
250ms per channel
Type
Universally configurable to provide (Channel 1 only):
Thermocouple (THC)
Resistance Thermometer (RTD)
Millivolt
Current
DC voltage
Input impedance
mA 100Ω
mV, V >10MΩ
Linearizer functions
Programmable for standard inputs:
SqRoot, THC types B, E, J, K, N, R, S, T or Pt100
Broken sensor protection
Upscale drive on THC and RTD
Downscale drive on milliamps and voltage
Cold junction compensation
Automatic CJC incorporated as standard
Stability <0.05°C/°C change in ambient temperature
Input protection
Common mode isolation >120dB at 50/60Hz with 300Ωimbalance
Series mode rejection >60dB 50/60Hz
Transmitter power supply
24V, 30mA max. powers one 2-wire transmitter
...Specification
1/8 DIN Process ControllerC100 SS/C100_10
7
elpuocomrehT egnaRmumixaM °C egnaRmumixaM °F )gnidaerfo%(ycaruccA
B 0081ot81– 0723ot0 ro%52.0 ±2° 002evoba(C ° )C
E 009ot001– 0561ot041– ro%52.0 ± 5.0 °CJ 009ot001– 0561ot041– ro%52.0 ± 5.0 °CK 0031ot001– 0532ot041– ro%52.0 ± 5.0 °CN 0031ot002– 0532ot523– ro%52.0 ± 5.0 °CR 0071ot81– 0003ot0 ro%52.0 ± 0.1 ° 003evoba(C ° )C
S 0071ot81– 0003ot0 ro%52.0 ± 5.0 ° 002evoba(C ° )C
T 003ot052– 055ot004– ro%52.0 ± 5.0 °C
DTR egnaRmumixaM °C egnaRmumixaM °F )gnidaerfo%(ycaruccA
001TP 006ot002– 0011ot523– ro%52.0 ± 5.0 °C
stupnIraeniL egnaR )gnidaerfo%(ycaruccA
spmailliM 02ot0 ro%52.0 ±2µA
spmailliM 02ot4 ro%52.0 ±2µA
stloV 5ot0 ro%52.0 ± 002 µV
stloV 5ot1 ro%52.0 ± 002 µV
stlovilliM 05ot0 ro%52.0 ± 02 µV
tupnItooRerauqS egnaR )gnidaerfo%(ycaruccA
spmailliM 02ot4 ro%52.0 ±2µA
.setoN.segnartoor.qsdnaelpuocomrehtfodnewolemertxetadeetnaraugtonsiycaruccaecnamrofreP
001,munitalperiw-3,DTR Ω 004ot0foegnarhtiw,)157CEI(dradnats06734NIDrep Ω.orezwolebnaps.niM
sdradnatsCHTsdradnatsDTR
07TepyT ° 621/C °F501NepyT ° 981/C °F
485CEI01734NID157CEI06734NID
Standard Analog Input Ranges
1/8 DIN Process ControllerC100 SS/C100_10
8
...Specification
OutputsControl output/retransmission
Analog, configurable in the range of 4 to 20mA
Max. load 15V (750Ω at 20mA)
Accuracy ≤0.25% of span
Dielectric 500V DC from I/P (not isolated from logic O/P)
Logic output
18V DC at 20mA
Min. load 400Ω
Dielectric 500V DC from I/P (not isolated from control O/P)
Relay output
One relay as standard (SPDT) (5A @ 115/230V AC)
OptionsOne option board can be installed from:
Type 1 One relay
Type 2 Two relays + one digital input + remote setpoint
Type 3 One relay + one digital input + remote setpoint + Modbus serial communications
Relay output
SPDT 5A @ 115/230V AC
Digital input
Type Volt-free
Minimum pulse 250ms(not isolated form remote set point)
Modbus serial communications
Connections RS422/485, 2 or 4-wire
Speed 2.4k or 9.6k baud rate
Protocol Modbus RTU slave
Remote Set Point Input
4 to 20 mA DC, 100Ω nominal input impedance
Preset to process variable engineering units(not isolated from digital inputs)
PhysicalSize
48 wide x 96 high x 125mm(1.89 in. wide x 3.78 in. high x 4.92 in.)
Weight
250g (0.5lb) approximate
ElectricalVoltage
85 to 265V AC (50/60Hz)
24V DC
Power consumption
< 6VA
EnvironmentalOperating limits
0 to 55°C (32 to 131°F)
5 to 95%RH non-condensing
Temperature stability
< 0.02% of reading or 2µV/°C (1µV/°F)
Front face
IP65 (NEMA3), case rear IP20
EMCEmissions
Meets requirements of EN50081-2
Immunity
Meets requirements of EN50082-2
Design and manufacturing standards
CE Mark
Safety standards
EN61010 – 1
C22.2 No. 1010
UL 310 – 1
FM 3810
1/8 DIN Process ControllerC100 SS/C100_10
9
COMMANDER 100
119 (4.64) 48 (1.89)
96(3.78)
14.7 (0.58)
91(3.58)
Cut out dims. 45 wide x 92 high
(1.77 wide x 3.62 high)
+ 0.6– 0
+ 0.8– 0
+ 0.02– 0
+ 0.03– 0
2.7 (0.11) 44.6 (1.76)
40 (1.57) 79 (3.11)
Dimensions
Dimensions in mm (in,)
1/8 DIN Process ControllerC100 SS/C100_10
10
Electrical Connections
Remote Set Point Input (–)
Remote Set Point Input (+)
Digital Input (–)
Digital Input (+)
Relay 2 Normally Open
Relay 2 Common
Relay 2 Normally Closed
Analog Input (–)
Analog Input (+)
Analog Input (Rtd)
Transmitter PSU (+)
Logic / Analog Output (+)
Analog Output (–)
Logic Output (–)
Relay 1 Normally Open
Relay 1 Common
Relay 1 Normally Closed
Neutral
Live
1
2
3
4
Thermocouple,
Millivolts and Volts
(–)
(+)
2-Lead RTD
and Resistance
1
2
3
4
Milliamps
(100 shunt placed across
Terminals 1 and 2)
(–)
(+)
Milliamps using internal
2-wire transmitter power supply
(100Ω shunt placed across
Terminals 1 and 2)
13
14
15
16
17
18
19
20
21
22
23
24
1
2
3
4
5
6
7
8
9
10
11
12
Seebelow
1
2
3
4
3-Lead RTD
RedRed
White
a.c. power
Relay 3 Normally Open
Relay 3 Common
Relay 3 Normally Closed
1
2
3
5
Tx
–
+4
1
2
3
4
White
Red
+
–
+
–
Common
20
21
22
23
24
Tx
Tx/ Rx RS485
1/8 DIN Process ControllerC100 SS/C100_10
11
Instrument Coding ExampleC100 / 01 0 0/ STD
C100 1/8 DIN Process Controller
One additional relay
85V to 265V AC power supply
Standard build
Configured to factory standard
Ordering Guide
001C 1/8 rellortnoCssecorPNID 001C / X X X X / X X X X
draoBnoitpO enoN–yalerlanoitiddaenO–
tupnilatigideno+syalerlanoitiddaowT–Am02ot4tnioptesetomer+
tupnilatigideno+yalerlanoitiddaenO–subdoM/584SR+tnioptesetomer+
000
0
012
3
ylppuSrewoP CAV562otV58CDV42
01
dliuB dradnatSynapmoClavorppaASC
lavorppaLUlavorppaMF
0124
serutaeFlaicepS/gnimmagorP dradnatsyrotcafotderugifnoCstnemeriuqerremotsucotderugifnoC
serutaeflaicepS
SCS
TUP
DSX X
1/8 DIN Process ControllerC100 SS/C100_10
ABB Inc.125 E. County Line RoadWarminsterPA 18974USATel: +1 215 674 6000Fax: +1 215 674 7183
ABB LimitedHoward Road, St. NeotsCambridgeshirePE19 8EUUKTel: +44 (0)1480 475321Fax: +44 (0)1480 217948
ABB has Sales & Customer Supportexpertise in over 100 countries worldwide
www.abb.com
The Company’s policy is one of continuous productimprovement and the right is reserved to modify the
information contained herein without notice.
Printed in UK (10.04)
© ABB 2004
SS
/C10
0Is
sue
10
Wall-/Pipe-mount Universal Process Controller
COMMANDER 310
IP66/NEMA 4X wall/pipe-mount housing– no need for an instrument panel
Single output, Heat/Cool or Motorized Valvecontrol– one controller for every PID control application
9 program, 30 segment Ramp/Soak– comprehensive set point profiling capabilities
Analog, relay and logic outputs as standard– extensive control output requirements
built-in
Universal process input with 0.1% accuracy– direct connection of any process signal, simple
installation without recalibration
RS485 Modbus serial communications– SCADA, PLC and open systems integration
COMMANDER 310 – gives you thecontrol that you need wherever
you need it
Data SheetSS/C310_6
Wall-/Pipe-mount Universal Process ControllerCOMMANDER 310 SS/C310_6
2
COMMANDER 310
The COMMANDER 310 Wall/pipe-mount UniversalProcess Controller is a highly versatile single-loop controllerpackaged in a robust field-mounting housing.
No need to fit an expensive instrument panel when installingor upgrading process equipment. The COMMANDER 310can be rapidly commissioned by simply fixing it to any flatsurface or pipe and making the electrical connections viathe cable entry glands on the underside of the unit.
The instrument has extensive control and i/o capabilitiesfitted as standard, allowing it to be rapidly configured foralmost any application.
With IP66/NEMA4X water/dust protection theCOMMANDER 310 can be mounted right next to yourprocess, no matter how harsh the environment.
Valve positioner
Solid state relay
Contactor
Alarmannunciator
Chart recorderSlave controller
SCADA systems (on PC)KEY: Standard Option
Transmitter PowerSupply
Auxiliary Inputs
• Digital (x 2)• Remote Set Point• Valve position feedback
Universal Process Input• Thermocouple• RTD• 4 to 20mA• Volts, millivolts
Control Outputs• Analog (4 to 20mA)• Logic• Relay x 2
Additional Alarm Outputs1 x Relay
Auxiliary OutputProcess ValueRetransmission
Serial CommunicationsRS485 Modbus RTU
Wall-/Pipe-mount Universal Process ControllerCOMMANDER 310 SS/C310_6
3
PID ControlThe COMMANDER 310’s isolated analog output provides thestandard control output to I/P converters, thyristors etc.Alternatively, built-in relays can be used to generate a time-proportioning control output.
Solid State Relay SSRA 12V time-proportioning logic output on the standard C310 canbe used to drive solid state relays (SSRs).
SP
t
Valve PositionThe COMMANDER 310 is fitted with twin relays and a valve-position input for closed-loop control of a motorized valve.'Boundless' control (without position feedback) and analogcontrol (using 4 to 20mA output) are also available in thestandard unit.
Heat/CoolHeat/cool control strategies may be implemented on thestandard COMMANDER 310, using a combination of theanalog control output and one relay.
Ramp/Soak Set Point ProfilesThe standard ramp/soak facility provides 30 segments, freelyassignable amongst 9 programs. A Segment Event functionenables relays to be switched on or off at predetermined pointswithin the program.
Serial CommunicationsNot only does the COMMANDER 310 provide clear processinformation in the field, it can also communicate plant data tocontrol rooms via an RS485 link, using Modbus protocol.
Wall-/Pipe-mount Universal Process ControllerCOMMANDER 310 SS/C310_6
4
Specification
Summary
epytDTR/CHT&521SBNreP
485CEI
C F
.nim .xam.nimnaps
.nim .xam.nimnaps
BepyT 81– 0081 017 0 2723 8721
EepyT 001– 009 54 841– 2561 18
JepyT 001– 009 05 841– 2561 09
KepyT 001– 0031 56 841– 2732 711
LepyT 001– 009 05 841– 2561 09
NepyT 002– 0031 09 823– 2732 261
S&RepyT 81– 0071 023 0 2903 675
TepyT 052– 003 06 814 275 801
06734NIDrepDTR157CEI& 002– 006 52 823– 2111 54
.setoN
004wolebdeetnaraugtonsiycaruccaecnamrofreP 257(C rof)FselpuocomrehtSdnaR,Bsepyt
001,munitalperiw-3,DTR 004ot0foegnarhtiw, orezwolebnaps.niM 07TepyT 621(C )F
501NepyT 981(C )F
epyttupnI eulav.niM eulav.xaM naps.niM
stlovilliM 0002– 0002 5.2
stloV 02– 02 52.0
spmailliM 001– 001 52.0
ecnatsiseR 0 0008 01
Temperature limits
Electrical limits
Input noise rejection
Common mode rejection >140dB at 50/60Hz with 500imbalance
Series mode rejection >60dB at 50/60Hz
Accuracy
Measurement error <0.1% of reading or 5V
Linearizer Typically 0.1C (0.2F)
Display range –9999 to +9999
CJC accuracy <0.05C/C change in ambient
Transmitter power supply
24V 30mA max. powers one loop, fitted as standard
COMMANDER 310 Wall-/Pipe-mount Universal Controller
P, PI, PID single loop controller
Autotune facility
Fully user configurable
IP66 (NEMA 4X) front face and housing
OperationDisplay
High-intensity 7-segment, 0.56 in. (14mm), 2 x 6 red LED display
Configuration
User defined via front panel
Analog InputsNumber
Three universal process inputs
Type
Universally configurable for:
Channels 1 & 2 – Thermocouple (THC)
(Process Variable & Resistance thermometer
Remote Set Point) (RTD)
Millivolt
Current
DC voltage
Resistance
Channel 3 – DC voltage
(Actuator PositionFeedback) Current Resistance
Input sampling rate
160ms per channel
Millivolts/THC >10M
Voltage 500k
Current 10
Linearizer functions
Programmable for input channels 1 and 2
Sqrt, X3/2, X5/2 THC types B, E, J, K, R, S, T, L, N or Pt100
Broken sensor protection
Programmable Up/Downscale or None
Cold junction compensation
Automatic CJC incorporated as standard
Wall-/Pipe-mount Universal Process ControllerCOMMANDER 310 SS/C310_6
5
OutputsControl output
Configurable as either:
Analog in the range of 0 to 20mA
Max. load 15V (750 at 20mA)
Accuracy 0.1% of span
Isolation 1kV AC
Logic 12V DC (SSR drive)
Max. load 400
Isolation 1kV AC
Retransmission
0 to 20mA configurable for process variable, set point or positionfeedback values
Max. load 15V (750 at 20mA)
Accuracy 0.1% of span
Relay outputs
Three relays, configurable for time proportioning control, valvedrive or alarms.
SPDT 5A 120/240V AC normally open or normally closed
OptionSerial communications
Connections – RS485, 4-wire, 1.2k to 9.6k baud rate
Protocol – Modbus RTU
ElectricalVoltage
115V 15% or 230V 15% 50/60Hz (link selectable)
Power consumption
<10VA
Power interruption protection
<60ms/<3 cycles, no effect
>60ms/>3 cycles, controlled reset
Line interference
Meets IEC 801 Pt IV level 3 (>2kV spikes)
EnvironmentalOperating limits
–10 to 55C (14 to 131F), 0 to 95%RH non-condensing
Temperature stability
<0.02% of reading or 1V/C (0.5V/F)
Housing dust/water protection
IP66 (NEMA 4X)
RF protection
Meets IEC 801 Pt. III level 3
EMCEmissions
Meets requirements of EN50081-2
Immunity
Meets requirements of EN50082-2
Design and Manufacturing Standards
CE
CSA
CSA/FM Class 1 Div.2 Hazardous Area
Wall-/Pipe-mount Universal Process ControllerCOMMANDER 310 SS/C310_6
6
Dimensions
Electrical Connections
Weight 4.5lb (2kg)
2.68 (68)
8.43(214)
9.13(232)
Fixi
ng C
entr
es
2.68 (68)
8.43(214)
9.13(232)
Fixi
ng C
entr
es
1.65(42)
2.375 (61) O.D.Vertical or Horizontal Post(Mounting Kit Pt. No. 4600/0138)
Allowance forCable Bends
6.3 (160)
9.84(250)
2.72 (69)FixingCentres
7.9 (200)
3 Fixing Holes0.25 (6.5) Dia
PowerSupply
Relay 1
Relay 2
Relay 3 Process Variable InputRemote SetPoint Input
Tx– 0V Rx+ Rx– + – + – 3rd 3+ 3– 1 2 CTx+
Modbus (RTU)(if option fitted)
LogicInput
ControlOutput
Position FeedbackInput
Retransmission Output
N/O C N/C N/O C N/C N/O C N/C 3rd 1+ 1– 3rd 2+ 2–
18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
12 13 14 15
1 2
16 17
L N
3 4 5 6 7 8 9 10 11
Dimensions in ins. (mm)
Wall-/Pipe-mount Universal Process ControllerCOMMANDER 310 SS/C310_6
7
Ordering Information
rellortnoCssecorPlasrevinUtnuom-epiP/-llaW013REDNAMMOC X/013C X X /X XXXX
draoBnoitpOenoN
snoitacinummoCsubdoM584SR00
01
ylppuSrewoP)sgulpgniknalbhtiwdettifTPN(CAV511
)sdnalgelbachtiwdettif02M(CAV032)sdnalgelbachtiwdettif02M(CAV511
)sgulpgniknalbhtiwdettifTPN(CAV032
1245
dliuB
dradnatS)gnidnep(devorppaASC
2.viD1.lCMF/ASC
013
serutaeFlaicepS/gnimmargorP
dradnatsyrotcafotderugifnoCliatedremotsucotderugifnoC
serutaeflaicepsdeergA
DTSSUCXXPS
Instrument Coding Example C310 / 01 1 1 / STD
COMMANDER 310 Controller
RS485 Modbus Communications
115V AC
CSA approved
Factory standard configuration
Wall-/Pipe-mount Universal Process ControllerCOMMANDER 310 SS/C310_6
SS
/C31
0Is
sue
6
ABB Inc.125 E. County Line RoadWarminsterPA 18974USATel: +1 215 674 6000Fax: +1 215 674 7183
ABB LimitedHoward Road, St NeotsCambridgeshirePE19 8EUUKTel: +44 (0)1480 475321Fax: +44 (0)1480 217948
ABB has Sales & Customer Supportexpertise in over 100 countries worldwide
www.abb.com
The Company’s policy is one of continuous productimprovement and the right is reserved to modify the
information contained herein without notice.