data logging power and energy meter - power meter and
TRANSCRIPT
www.
elec
troin
d.co
m
Revenue Metering
• Certified ANSI C12.20 0.2 Accuracy Class and IEC 62053-22 0.2S Energy Measurement Accuracy
• High Precision Frequency Measurements - 0.007 Hz
• Transformer Line Loss and CT/PT Compensation
• Data Logging, Including three Historical Logs with 64+ Parameters Each
• Designed for High Reliability and Ease of Use
Power Quality Metering
• Programmable Alarm Limits
• THD Monitoring and Harmonics Recording
• Waveform Recording of up to 512 Samples/Cycle, 170 Events
Communication and I/O
• Two Optional, Separately Addressable Ethernet Ports with Email on Alarm, Data Push, Web Servers, IP Whitelisting
• Standard IrDA and RS485 Port
• Modbus ASCII/RTU/TCP, DNP3, and IEC 61850 Protocols
• V-Switch™ Keys Add Functionality in the Field
• Field Upgradable I/O Including Analog Outputs, Status Inputs, Control Relays, and Pulse Outputs
1®200
Data Logging Power and Energy Meter
Shark® 200 Meter/Transducer
Applications
* New York State approved for residential submetering.
Primary Revenue Metering
Certified 0.2% Energy Accuracy
The Shark® 200 meter is certified to ANSI C12.20 0.2 Accuracy Class and IEC 62053-22 0.2S measurement accuracy. It provides highly stable, precise, and reliable measurements that maintain accuracy over time. The meter has a standard energy test pulse for accuracy verification.
Accuracy Chart
Measured Parameters Accuracy % Display Range
Voltage L-N 0.1% 0-9999 Scalable V or kV
Voltage L-L 0.2% 0-9999 V or kV Scalable
Current 0.2% 0-9999 Amps or kAmps
+/- Watts 0.2% 0-9999 Watts, kWatts, MWatts
+/-Wh 0.2% 5 to 8 Digits Programmable
+/-VARs 0.2% 0-9999 VARs, kVARs, MVARs
+/-VARh 0.2% 5 to 8 Digits Programmable
VA 0.2% 0-9999 VA, kVA, MVA
VAh 0.2% 5 to 8 Digits Programmable
PF 0.2% +/- 0.5 to 1.0
Frequency +/- 0.007 Hz (45 to 65) Hz
THD +/- 2.0% 1 to 99.99%
% Load Bar +/- 1 Segment (0.005 to 6) A
Note: Applies to 3 element WYE and 2 element Delta connections.
CT/PT Compensation
To meet stringent accuracy requirements, users need to compensate for inaccuracies of instrument transformers in their system. The Shark® 200 meter has built-in features that provide CT/PT compensation through amplitude and phase angle adjustment.
Transformer/Line Loss Compensation
The Shark® 200 meter's transformer and line loss compensation (TLC)supports correct energy measurements when the meter is placed on the secondary side of the transformer. Compensate energy readings for TLC to perform accurate customer usage billing.
V-Switch™ Key Technology
The Shark® 200 meter has EIG’s V-Switch™ key technology, which allows a user to upgrade features without removing the meter from service.
V-Switch™ Keys
Features V1 V2 V3 V4 V5 V6
Multifunction Measurement with I/O Expansion PP PP PP PP PP PP
2 MB Data Logging PP PP PP
3 MB Data Logging PP
4 MB Data Logging PP
Harmonic Analysis PP PP PP PP
TLC and CT/PT Compensation PP PP PP PP PP PP
Limit and Control Functions PP PP PP
64 Samples per Cycle Waveform Recorder PP
512 Samples per Cycle Waveform Recorder PP
• Utility metering.
• Commercial metering.
• Substation metering.
• Industrial metering.
• Power generation.
• Campus metering.
• Submetering.*
• Analog meter replacement.
• Power quality studies.
• Disturbance recording.
• Load studies.
• Voltage recording.
2
Extensive Data Logging Capability (V2 and Higher)
The Shark® 200 meter has up to 4 MB of data logging memory, used for historical trends, limit alarms, I/O changes, and sequence of events. The unit's real time clock timestamps all data in the instrument when log events are created.
Historical Logs
• Three assignable historical logs.
• 64+ parameters per log.
• Independently programmed trending profiles.
I/O Change Log
• Provides a timestamped log of any relay output.
• Provides a timestamped log of input status changes.
• 2048 events available.
System Events Log
To protect critical billing information, the meter records and logs the following actions with a timestamp:
• Demand resets.
• Password requests.
• System startup.
• Energy resets.
• Log resets.
• Log reads.
• Programmable settings changes.
• Critical data repairs.
Limit/Alarm Log
• Provides magnitude and duration of an event.
• Includes timestamp and alarm value.
• 2048 events available.
• Email on alarm capability with INP100S Ethernet card.
Alarm Limits and Control Capability (V4 and Higher)
• Up to eight limits.
• Set limits on any. measured parameter.
• Voltage unbalance.
• Current unbalance.
• Based on % of full scale settings.
• Trigger relay outputs or emails for control.
Historical Trending
High Performance Power Quality Analysis (V5 and V6)
Simultaneous Voltage and Current Waveform Recorder
The meter records up to 512 samples per cycle for a voltage sag or swell or a current fault event. It provides the pre- and post-event recording capability shown in the table below. Waveform records are programmable to the desired sampling rate.
The meter's advanced DSP design allows power quality triggers to be based on a one cycle updated RMS. Up to 170 events can be stored until the memory is full. The meter stores waveform data in a first-in/first-out circular buffer to ensure data is always recording.
Samples per
Cycle
Pre Event Cycles
Post Event Cycles
Max Waveforms per Event
Number of Stored
Events
V532 16 48 128 85
64 8 24 64 85
V6
128 4 12 32 170
256 2 6 16 170
512 1 3 8 170
Note: Sampling rate based on 60 Hz systems. . . For 50 Hz systems, multiply by 1.2.
Waveform Scope
The unit uniquely offers a waveform scope that lets you view the real time waveform for voltage and current. The waveform scope lets you use the meter as a basic oscilloscope throughout a power system.
Independent CBEMA or SEMI F47 Log Plotting
The meter stores an independent CBEMA or SEMI F47 log for magnitude and duration of voltage events. This lets you quickly view total surges, total sags, and duration, without retrieving waveform data. Timestamps are stored with millisecond accuracy.
Harmonic Recording to the 40th Order
The Shark® 200 meter provides advanced harmonic analysis to the 40th order for each voltage and current channel, in real time. Using the stored waveforms, harmonic analysis is available to the 255th order.
3
Standard Communication Capability
The Shark® 200 meter provides two independent communication ports with advanced features.
Rear Mounted Serial Port with KYZ Pulse
• RS485 - This port allows RS485 communication using Modbus or DNP3 protocols. Baud rates are from 1200 to 57600.
• KYZ Pulse - In addition to the RS485 port, the meter also includes pulse outputs mapped to absolute energy.
Front Mounted IrDA Communication
The meter also has an optical IrDA port, allowing you to program it with an IrDA-enabled laptop.
Field Communication Capability
The Shark® 200 meter's flexible communication architecture integrates directly into most existing software systems. In addition to its standard communication, the meter offers extensive communication and I/O ex-pandability though its two universal option card slots. The meter accepts and auto-detects new I/O cards even after installation. Up to 2 cards of any type can be used per meter.
INP100S: 100BaseT Ethernet Capability
• NTP time server for high accuracy network time synchronization.
• Simultaneous DNP3 over Ethernet and Modbus TCP/IP Communication.
• See page 5 for INP100S card details.
INP300S: IEC 61850 Protocol Ethernet Card
• Multiple logical nodes; configurable .CID file.
• See page 5 for INP300S card details.
1mAOS: Four Channel Bi-directional 0-1 mA Outputs
• Assignable to any parameter.
• 0.1% of full scale.
• Max. load impedance 10 kΩ.
20mAOS: Four Channel 4-20 mA Outputs
• Assignable to any parameter.
• 0.1% of full scale.
• 850 Ω at 24 V DC.
• Loop powered using up to 24 V DC.
PO1S: Four Pulse Outputs / Four Status Inputs
• Programmable to any energy parameter and pulse value.
• Form A: Normally open contacts.
• Also used for end of interval pulse.
RO1S: Two Relay Outputs / Two Status Inputs*
• 250 V AC / 30 V DC - 0.25 A relays, Form C.
• Trigger on user set alarms.
• Set delays and reset delays.
FOVPS or FOSTS: Fiber Optic Card
• EIG’s exclusive fiber optic daisy chain switchable built-in logic mimics RS485 half duplex bus. This lets you daisy chain meters for lower installation costs; full duplex is also assignable. This feature requires the software to ignore echoes.
• St terminated option (-FOSTS).
• Versatile link terminated option (-FOVPS).
• Modbus and DNP3 protocols available.
Field-Expandable I/O Slots
Note: I/O cards can be ordered separately - see last page.
*The meter must be at V-Switch™ key 4 or higher to use the relay features.
Meter Auto Detects I/O Card Type
Simple Field Upgrade
4
100BaseT Ethernet (INP100S or INP300S)
Simultaneous Data Connections
INP100S - Web Server, Modbus, DNP3, and Email
• Web server with configurable HMI.
• Smartphone compatible.
• 12 Connections Modbus TCP/IP.
• 5 Connections DNP3 over TCP/IP.
• Data push of meter readings to cloud servers.
• Send email on alarm or periodic email notification of meter status and readings.
INP300S - Web Server, Modbus, DNP3, and IEC 61850
• IEC 61850 protocol.
• 5 Modbus connections.
• 5 MMS clients.
• Web server for status and configuration.
• Dual Ethernet port capable.
• Simultaneous Modbus, DNP3 over Ethernet, and IEC 61850.
Both INP100S and INP300S offer enhanced security through the Exclusive Client feature, which provides secure communication for a whitelisted IP/MAC address, to protect from unauthorized programming.
Embedded Web Server with Smartphone Support
EnergyPQA.com® Cloud-based Energy Management System
The EnergyPQA.com® system provides energy analytics and predictions enterprise-wide and deep insights into power quality.
• Increase energy usage efficiency by analyzing load disaggre-gation and usage comparisons.
• Perform cost allocation and submetering by properly billing for actual energy usage versus square footage estimations.
• Analyze enterprise carbon footprint to determine and improve impact on the environment.
Designed for High Reliability and Ease of Use
• Ruggedly designed to withstand harsh electrical environments.
• Industrial grade components.
• Designed to the highest surge withstand and transient standards.
• Detailed circuit board testing and automation to ensure 100% reliability.
• Bright-red, three 0.56” line LED display for easy meter reading in any environment.
• Short-circuit safe current inputs with dual input methods ensure that CT connections will not open in a fault condition.
Shark® 200 Meter ANSI and DIN Mounting for Easy Retrofit
The unit mounts directly in an ANSI C39.1 (4” round form) or an IEC 96 mm DIN square form. This is perfect for new installations and for existing panels. In new installations, simply use DIN or ANSI punches. For existing panels, pull out old analog meters and replace them with the Shark® 200 meter. The meter uses standard voltage and current inputs so that CT and PT wiring does not need to be replaced.
Shark® 200T Transducer
This transducer version of the Shark® 200 meter does not include a display. The unit mounts directly to a DIN rail and provides an RS485 Modbus or DNP3 output and the expandable I/O.
Easy DIN Rail Mounting
5
Typical Substation Solutions
Substation Voltage and Frequency Recording
Traditionally, voltage recording meters were relegated to high cost metering or monitoring solutions. The Shark® 200 meter can be placed throughout an electrical distribution network. The meter provides one of the industry's lowest cost methods of collecting voltage information within a utility power distribution grid.
• Perform voltage reliability analysis to ensure proper voltage to customers.
• Compare voltage reliability throughout transmission or distribu-tion networks.
• Monitor the output of substation transformers or line regulators.
• Initiate conservation voltage reduction, reducing system demand.
• Monitor highly accurate frequency to regulate frequency stability.
• Replace costly frequency transducers.
Interval Load Profiling
The Shark® 200 meter allows you to log substation data over time for electrical usage, demand, voltage, current, PF, and many other param-eters. This enables a complete analysis of the power system over time.
• Provide revenue accurate load profiling.
• Determine substation usage.
• Analyze feeder capacity and utilization.
• Provide time-based load profile for planning and estimation.
• Data trend PF distribution and imbalances for system efficiency analysis.
Low Cost Substation Telemetry
The Shark® 200 meter's advanced output capability brings back data using many different communication media, such as RS485, Ethernet, and analog outputs. This ensures that one meter can be used for almost every substation application, no matter what communication infrastructure is needed.
• Perfect for new or retrofit applications.
• Multiple communication paths.
• One meter provides outputs for every application.
• Multiple systems and/or users can access data simultaneously.
6
C
C
B
B
A
A
lc
HI
LO
lb
HI
LO
la
HI
LO
Earth Ground
Earth Ground
L(+)
Power SupplyConnection
N(-)
L(+)
GND
N(-)
Vref
Va
VbVc
LINE
LOAD
CT ShortingBlock
FUSES2 x 0.1A
FUSE
3A
C
C
B
B
A
A
N
N
lc
HI
LO
lb
HI
LO
la
HI
LO
Earth Ground
Earth Ground
L(+)
Power SupplyConnection
N(-)
L(+)
GND
N(-)
Vref
Va
VbVc
LINE
LOAD
CT ShortingBlock
FUSES3 x 0.1A
FUSE
3A
C
C
B
B
A
A
Earth Ground
L(+)
Power SupplyConnection
N(-)
L(+)
GND
N(-)
Vref
Va
VbVc
LINE
LOAD
CT ShortingBlock
FUSES3 x 0.1A
FUSE
3Alc
HI
LO
lb
HI
LO
la
HI
LO
C
C
B
B
A
A
N
N
Earth GroundL(+)
GND
N(-)
Vref
Va
VbVc
LINE
LOAD
CT ShortingBlock
FUSES3 x 0.1A
lc
HI
LO
lb
HI
LO
la
HI
LO
L(+)
Power SupplyConnection
N(-)
FUSE
3A
4.85”
4.85
”
[12.32cm]
[12.
32cm
]
[10.41cm]4.10”
5.02
” [1
2.75
cm]
3.25” [8.26cm]
[12.00cm]4.71”
Ic Ib Ia
HI HI HI
LOLOLO
3.25”[8.26cm]
3.56
”[9
.04c
m]
0.62”[1.61cm]
[12.10cm]4.76"
[2.31cm]0.91"
4.14”[10.57cm]
3 Phase 4 Wire WYE Direct
3 Phase 3 Wire Delta Direct
3 Phase 4 Wire WYE with PTs
3 Phase 3 Wire Delta with PTs
Wiring Diagrams
Shark® 200 Meter Front Dimensions
Shark® 200 Meter Side Dimensions
Shark® 200T Side Dimensions
7
Dimensional Drawings
1800 Shames Drive, Westbury, NY 11590 1-877-EIMETER (1-877-346-3837) Tel: 516-334-0870 Fax: 516-338-4741 Email: [email protected] www.electroind.com E149702 081321 V.1.33
Ordering Information - All fields must be filled in to create a valid part number.Model Frequency
RangeCurrent
InputV-Switch™
PackPower Supply
I/O Slot 1*
I/O Slot 2*
Mounting (Shark® 200 Meter)
Option Numbers:
Example: Shark200 60 10 V2 D2 INP100S X X
Shark200 (Meter/Transducer)
60 60 Hz System
10 5 A Nominal
CT Secondary
V1 Multifunction Meter Only
D2 (90-265) V AC @ 50/60 Hz or (100-370) V DC
X None
X None
X ANSI Mounting
Shark200T (Transducer Only)
50 50 Hz System
2 1 A Nominal
CT Secondary
V2 Standard Data Logging
Memory
D (18-60) V DC
RO1S** 2 Relays/2 Status
RO1S** 2 Relays/2 Status
DIN DIN Mounting Brackets
V3 Power Quality Harmonic
PO1S 4 Pulses/4 Status
PO1S 4 Pulses/4 Status
V4 Limits
& Control
1mAOS 4 Channel Analog
Output 0-1 mA (bidirectional)
1mAOS 4 Channel Analog
Output 0-1 mA (bidirectional)
V5 64 Samples/Cycle
Waveform Recording
20mAOS 4 Channel Analog Output 4-20 mA
20mAOS 4 Channel Analog Output 4-20 mA
V6 512 Samples/Cycle Waveform Recording
FOSTS Fiber Optic Output
ST terminated
FOSTS Fiber Optic Output
ST terminated
FOVPS Fiber Optic Output VPIN terminated
FOVPS Fiber Optic Output VPIN terminated
INP100S 100BaseT Ethernet
INP100S 100BaseT Ethernet
INP300S IEC 61850 Protocol
Ethernet
INP300S IEC 61850 Protocol
Ethernet
Specifications
* I/O cards can be ordered separately using the part numbers shown in the ordering information.
** The meter must be at V-Switch™ key 4 or higher to use the relay features.
Shark® 200 web page
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Voltage Inputs:
• Absolute Range: (20-576) Volts Line to Neutral, (0-721) Volts Line to Line
• Universal Voltage Input
• Input Withstand Capability – Meets IEEE C37.90.1 (Surge Withstand Capability)
• Programmable Voltage Range to Any PT Ratio
• Supports: 3 Element WYE, 2.5 Element WYE, 2 Element Delta, 4 Wire Delta Systems
• Input Impedance 1 MΩ/Phase
• Burden: 0.36 VA/Phase at 600V; 0.014 VA at 120 Volts
• Input Wire Gauge: AWG#12 -26/(0.129 -3.31) mm2
Current Inputs:
• Class 10: (0.005 to 10) A, 5 A Nominal CT Secondary
• Class 2: (0.001 to 2) A, 1 A Nominal CT Secondary
• Fault Current Withstand (at 23 °C): 100 A for 10 Seconds, 300 A for 3 Seconds, 500 A for 1 Second
• Continuous Current Withstand: 20 A for Screw Terminated or Pass Through Connections
• Programmable Current to Any CT Ratio
• Burden 0.005 VA per Phase Max at 11 A
• Pickup Current: 0.1% of Nominal (Class 10: 5 mA; Class 2: 1 mA)
• Pass Through Wire Diameter: 0.177” / 4.5 mm
Isolation:
• All Inputs and Outputs are Galvanically Isolated to 2500 Volts
Environmental Rating:
• Storage: (-20 to +70) °C
• Operating: (-20 to +70) °C
• Humidity: to 95% RH Non-Condensing
• Faceplate Rating: NEMA 12
• Mounting Gasket Included
• Protection: IP30 - Meter Front/Back, Optional DIN Rail Mounting, Optional Plug-in I/O Modules
Sensing Method:
• True RMS
• Sampling at Over 400 Samples/Cycle on all Channels of Measured Readings Simultaneously
• Harmonics Resolution to 40th Order
• Waveform up to 512 Samples/Cycle
Update Rate:
• Watts, VARs, and VA - Every 6 Cycles
• All Other Parameters - Every 60 Cycles
Power Supply:
• Option D2: (90-265) V AC @ 50/60 Hz or (100-370) V DC/ 10 VA Max
• Option D: (18-60) V DC (24 to 48 V DC Systems) / 7 W Max
Standard Communication Format:
• 2 Com Ports (Back and Faceplate)
• RS485 Port through Backplate
• IrDA through Faceplate
• Com Port Baud Rate: (1200 - 57600)
• Com Port Address: 1-247
• 8-Bit, Parity Setting: Odd, Even, None
• Modbus RTU, ASCII, or DNP3 Protocols
KYZ Pulse:
• Type Form C Contact
• On Resistance: 35 Ohms Max
• Peak Voltage: 350 V DC
• Continuous Load Current: 120 mA
• Peak Load Current: 350 mA (10 ms)
• Off State Leakage Current @350 V DC: 1uA
Dimensions and Shipping:
• Weight: 2 lbs /.91 kg
• Basic Unit: H4.85" x W4.85" x L4.25"
• Shark® 200 Meter Mounts in 96 mm DIN & ANSI C39.1 4" Round Cutouts
• Shark® 200T Transducer: DIN Rail Mounted Using Attached DIN Rail Clips
• Shipping Container Dimensions: 6” Cube
Meter Accuracy:
• See Page 2
• Note: For 2.5 element programmed units, degrade accuracy by an additional 0.5% of reading.
• Note: For 1A (Class 2) Nominal, degrade accuracy to 0.5% of reading for watts and energy; all other values 2 times rated accuracy.
Compliance:
• ANSI C12.20-2015, 0.2 Accuracy Class and C12.1 (MET Labs Certified)*
• ANSI C62.41 (Burst)*
• FCC, Part 15, Subpart B, Class A (Radi-ated and Conducted Emissions)*
• IEC 62053-22 Accuracy, 0.2S (KEMA Laboratories Certified) *
• IEC 62053-23 Edition 1, Class 2
• EN 61000-6-2 – Immunity for Industrial Environments: 2005
• EN 61000-6-4 – Emission Standards for Industrial Environments: 2007
• CE (EN 61326-1*, EN 61000-6-2, EN 61000-6-4)
• EN 61000-3-2, Class A (Harmonic Current)*
• EN 61000-3-3 (Voltage Fluctuation and Flicker)*
• IEC 61000-4-2, Ed.1.2, Class A (Electrostatic Discharge)*
• IEC 61000-4-3, Class A (Radiated EM Immunity)*
• IEC 61000-4-4, Second Ed., Class A (EFT)*
• IEC 61000-4-5, Ed. 1.1, Class A (Surge Immunity)*
• IEC 61000-4-6 (Conducted Im-munity)*
• IEC 61000-4-8, Class A (Magnetic Immunity)*
• IEC 61000-4-11, Class A (Voltage Variations Immunity)*
• IEC/CISPR11, Ed.4.1 (Radiated Emissions)*
• CISPR22, Class A, Fifth Ed.*
• IEC 61850 (KEMA Laboratories Certified)*
• IEEE C37.90.1 (Surge Withstand Capability)
• Certified to UL/IEC 61010-1 and CSA C22.2 No. 61010-1, UL File: E250818*
• REACH/RoHS 3 Directive 2011/65/EU
• New York State approved for residential metering
*Third party lab certified
Accessories
Communication Converters
9PINC RS485 to USB Adapter
CAB6490 USB to IrDA Adapter
Unicom 2500 RS485 to RS232 Converter
Unicom 2500-F RS485 to RS232 to Fiber Optic Converter
Compliance Documents
Certificate of Calibration, Part#: CCal
This provides Certificate of Calibration with NIST traceable Test Data.
Software
COMPQA5P1Y CommunicatorPQA® 5.0 Software for Windows Single-Computer License (One Year)
ENERGYPQA-1Year Cloud-based Energy Management Solution
Current Transformer Kits
CT200K 200/5 Ratio, 1.00" Window, 3 CTs
CT400K 400/5 Ratio, 1.25" Window, 3 CTs
CT800K 800/5 Ratio, 2.5" Window, 3 CTs
CT2000K 2000/5 Ratio, 3.00" Window, 3 CTs
CT Specifications
Frequency (50 to 400) Hz; Insulation: 600 Volts, 10 kV BIL Consult factory application engineer for additional transformer ratios, types, or window sizes.Flexible Leads UL 1015, 105 °C, CSA Approved, 24" Long, AWG#16