4500 Series Electric Strike Installation Instructions HES, Inc. Phoenix, AZ 800-626-7590 www.hesinnovations.com 1 Electrical Specifications ELECTRICAL RATINGS FOR SOLENOID MINIMUM WIRE GAUGE REQUIREMENTS SOLENOID VOLTAGE CONTINUOUS DUTY 12 VDC 12VDC 50 .24 24 VDC 24VDC 200 50 200 .12 .24.–.32 .12 12–16 VAC 24 VAC INTERMITTENT DUTY* Resistance in Ohms Amps Solenoids are rated at +/- 10% indicated value. *10% max duty cycle (2 min. max on time) 200 feet or less 200 - 300 feet 300 - 400 feet 18 gauge 16 gauge 14 gauge 20 gauge 18 gauge 16 gauge 4 Cutout Templates Inches [Millimeters] 2 ASSA ABLOY, the global leader in door opening solutions Product Components 1 2 4500 Electric Strike Body Keeper Shims & Screws (#4-40 x 1/8” and #4-40 x 3/16”) 5 7 3 6 Centerlined and Non-handed Faceplate for Cylindrical Locksets 1 7 3 3053006.002 rev C 1-1/8" 2-1/4" Vertical Centerline Cylindrical Lock Lock Strike 4-7/8" 4-1/8" 3-5/8" C L C L Strike Prep C L [57.2] [28.6] [123.8] [104.8] [92.1] Strike Prep Vertical Centerline 8" 4" Mortise Lockset C L 4-7/8" [123.8] 4-1/8" [104.8] 3-5/8" [92.1] 5/8" [15.9] 1-1/4" [31.8] [203.2] [101.6] Strike Lock C L C L Strike Lock Strike Prep C L 3/8" Vertical Centerline 8" 4" C L Mortise Lockset C L 4-7/8" [123.8] 4-1/8" [104.8] 3-5/8" [92.1] 5/8" [15.9] 1-1/4" [31.8] [9.5] 1-1/4" [31.8] 1-3/4" [44.5] [203.2] [101.6] JAMB Cutout Dimensions 4500 with Cylindrical Locksets 4500 with Mortise Locksets Schlage L9000 and YALE 8700 Locks Only 1-1/4" [31.8] 1-3/4" [44.5] 1-1/4" [31.8] 1-3/4" [44.5] 5/8" [15.9] 1-1/4" [31.8] [31.8] 1-1/4” [25.4] 1” [123.8] 4-7/8” [92.1] 3-5/8” 6 4 5 #12-24 x 1/2” Mounting Screws 12 & 24 Volt Plug In Connectors Trim Enhancer & Screws 4 Offset and Non-handed Faceplate for Mortise Locksets © 2015, Hanchett Entry Systems, Inc., an ASSA ABLOY Group company.

Upload: others

Post on 13-Aug-2020

18 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Cutout Templates 4500 Series Electric Strike · 4500 Series Electric Strike Installation Instructions HES, Inc. Phoenix, AZ 800-626-7590 1 Electrical Specifications ELECTRICAL RATINGS

4500 Series Electric StrikeInstallation Instructions

HES, Inc.Phoenix, AZ800-626-7590www.hesinnovations.com

1

Electrical SpecificationsELECTRICAL RATINGS FOR SOLENOID MINIMUM WIRE GAUGE REQUIREMENTS SOLENOID VOLTAGECONTINUOUS DUTY

12 VDC 12VDC

50

.24

24 VDC 24VDC

200 50 200

.12 .24.–.32 .12

12–16 VAC 24 VAC

INTERMITTENT DUTY*

Resistance in Ohms

Amps

Solenoids are rated at +/- 10% indicated value.*10% max duty cycle (2 min. max on time)

200 feet or less

200 - 300 feet

300 - 400 feet

18 gauge

16 gauge

14 gauge

20 gauge

18 gauge

16 gauge

4Cutout TemplatesInches [Millimeters]

2

ASSA ABLOY, the global leaderin door opening solutions

Product Components1

2

4500 Electric Strike BodyKeeper Shims & Screws (#4-40 x 1/8” and #4-40 x 3/16”)

5

73

6

Centerlined and Non-handed Faceplate for Cylindrical Locksets

1

7

3

3053006.002 rev C

1-1/8"

2-1/4"

VerticalCenterline

Cylindrical Lock

Lock

Strike

4-7/8"

4-1/8"

3-5/8"

CL

CL

Strike PrepCL

[57.2]

[28.6]

[123.8]

[104.8]

[92.1]

Strike Prep

Vertical Centerline

8"

4"

MortiseLockset

CL

4-7/8"[123.8]

4-1/8"[104.8]

3-5/8"[92.1]

5/8"[15.9]

1-1/4"[31.8]

[203.2]

[101.6]

Strike

Lock

CL

CL

Strike

Lock

Strike Prep

CL

3/8"

Vertical Centerline

8"

4"CL

MortiseLockset

CL

4-7/8"[123.8]

4-1/8"[104.8]

3-5/8"[92.1]

5/8"[15.9]

1-1/4"[31.8]

[9.5]

1-1/4"[31.8]

1-3/4"[44.5]

[203.2]

[101.6]

JAMB Cutout Dimensions 4500 with Cylindrical Locksets

4500 with Mortise Locksets Schlage L9000 and YALE 8700 Locks Only

1-1/4"[31.8]

1-3/4"[44.5]

1-1/4"[31.8]

1-3/4"[44.5]

5/8"[15.9]

1-1/4"[31.8]

[31.8]1-1/4”

[25.4]1”

[123.8]4-7/8”

[92.1]3-5/8”

6

4

5

#12-24 x 1/2” Mounting Screws 12 & 24 Volt Plug In ConnectorsTrim Enhancer & Screws

4 Offset and Non-handed Faceplate for Mortise Locksets

© 2015, Hanchett Entry Systems, Inc., an ASSA ABLOY Group company.

Page 2: Cutout Templates 4500 Series Electric Strike · 4500 Series Electric Strike Installation Instructions HES, Inc. Phoenix, AZ 800-626-7590 1 Electrical Specifications ELECTRICAL RATINGS

2Installation Directions

Preparing the Strike

CAUTION!Before connecting any device at the installation site, verify input voltage using a multimeter.Many power supplies and low voltage transformers operate at higher levels than listed. Any input voltage exceeding10% of the solenoid rating may cause severe damage to the unit and will void the warranty.

Finishing the Installation

3Installation (continued)

LBM WIRING

White

Orange Normally Open

Green Normally Closed

Common

LBSM WIRING

Brown

Blue Normally Open

Yellow Normally Closed

Common

Figure 3: Strike MonitorFigure 2: Latchbolt Monitor

Converting the Operation Mode

Figure 4: Fail Safe Conversion

Figure 6: Horizontal Adjustment

Adding One Shim Adding Two Shims

Figure 5: Faceplate Options

Figure1: 12 VDC to 24 VDC Conversion

RED

RED/GREEN

BLACK

VIOLET

RED

BLACK

VIOLET

RED/GREEN

IF CONNECTOR IS MISSING

(+ 12 VDC)

(-NEG)

(+ 24 VDC)

(-NEG)

ELEC

TRIC

ST

RIKE

ELEC

TRIC

ST

RIKE

CONNECT TOGETHER

CONNECT TOGETHER

CONNECT TOGETHER

Preparing the FrameNOTE: Schlage L9000 and Yale 8700 locksets must use the template labeled “Schlage L9000 & Yale 8700 Locks Only.” All other locksets should use the template labeled “Cylindrical Lockset” or Mortise Lockset.”

5. PREPARE the frame for lockset using appropriate cutout template, as shown on Page 4.

1 2

WhiteOrangeGreen

BrownBlueYellow

Fire Door Safety Screw

Unpowered and inunactuated state

Unpowered and inunactuated state

10. REMOVE the Fire Door Safety Screw as shown in Figure 4.

11. LOOSEN the two #2-56 screws located on the back of the strike, but DO NOT REMOVE them.

12. MOVE screws from the bottom of the hole (Fail Secure mode position) to the top hole (Fail Safe mode position).

13. TIGHTEN the bottom screw first (wire side), and THEN TIGHTEN the top screw.

NOTE 1: For 12 VAC, 12 VDC, or 16 VAC, the pigtail marked “12 VDC” is used.

NOTE 2: For 24VAC or 24 VDC, the pigtail marked “24 VDC” is used.

1. SELECT the appropriate plug in connector that matches system power and electrically CONNECT as shown in Figure 1, “12 VDC to 24 VDC Conversion.”

NOTE: The state of switch is listed for an unpowered strike and LBM in unactuated (door open) position.

2. IF using a Latchbolt Monitor (LBM) or Latchbolt Strike Monitor (LBSM), THEN COMPLETE wiring in accordance with Figures 2, “Latchbolt Monitor,” and Figure 3, “Strike Monitor,” on Page 3.

CAUTIONConverting the 4500 Series Strike to Fail SafeMode negates the unit’s fire rating.

NOTE: This unit ships in Fail Secure mode.

3. VERIFY that the strike is in the correct mode of operation.

4. IF the 4500 Series Electric Strike must be converted to Fail Safe mode, THEN CONVERT in accordance with Figure 4, “Fail Safe Conversion,” on Page 3.

6. CHOOSE the appropriate faceplate for the strike as shown in Figure 5, “Faceplate Options,” on Page 3. 7. CONNECT wires from the power source to the strike.

8. INSTALL the electric strike unit in jamb cutout, using #12-24 x 1/2” Mounting Screws provided.

9. IF horizontal adjustment is needed, THEN GO TO “Adjusting the Horizonal” section on Page 3.

14. VERIFY the strike is now in the Fail Safe operation mode.

15. IF the strike still operates as Fail Secure, THEN ENSURE the screws are fully seated in the top position.

Adjusting the Horizontal

16. IF horizontal adjustment is needed, THEN ADD 1 or 2 keeper shims as shown in Figure 6, “Horizontal Adjustment.”

a. USE the #4-40 x 1/8” keeper shim screws if adding one shim.

b. USE the #4-40 x 3/16” keeper shim screws if adding two shims.

NOTE 1: A Non-handed offset faceplate is provided for use with mortise locksets. The mortise lock deadlatch should be depressed by the faceplate when the door is closed.

NOTE 2: A Non-handed center-lined faceplate is provided for use with cylindrical locksets.