GENERAL
• These notes shall be read in conjunction with all relevant drawings of the Engineer and
all applicable codes and specifications mentioned below. In the event of any discrepancy between these notes and the codes and specifications, these notes shall take precedence.
• All codes, standards and specifications mentioned below refer to the latest editions
thereof.
• The Engineers drawings shall be read in conjunction with all relevant architect's, consultant's and specialist's drawings. Any discrepancies shall immediately be referred to the Engineer in writing prior to commencing with construction.
• The relevant sections of the SANS 2001 shall apply.• No scaling off of drawings is allowed.
• The superimposed design loads for the suspended slabs are indicated on the engineer's drawings. These design loads may not be exceeded at any stage during construction, unless adequate additional support is provided for the slab. The contractor must obtain the engineers consent regarding any proposed additional support methodology.
• For retaining walls laterally supported by concrete slabs, backfilling to be carried out no sooner than 7 days after casting of slab.
• All work is to be executed in accordance with the latest occupational Health and Safety
Act.
• It is the contractors responsibility to ensure that all sub-contractors and relevant site personnel are in possession of these notes and have familiarised themselves with the content.
FOUNDATIONS
• Foundations have been designed for the following allowable bearing pressure: 100 kPa
• All founding depths and foundation excavations shall be approved by the Engineer on site.
• Design bearing pressure as specified is to BE verified by the Engineer on site.
• Foundation levels shown of the Structural Engineer's drawings are preliminary, and may vary depending on the Engineers findings on site.
• As built levels of all foundations must be forwarded to the Engineer for his records.
• All foundations are located centrally under columns or walls unless shown otherwise.
• Cast 15 MPa blinding under all reinforced foundations and pile caps unless shown otherwise. Minimum thickness of blinding to be 50 mm.
• No excavations shall undermine any existing foundations.
• DCP Ground test results @ 10m c/c along Strip footing excavations to be submitted for approval.
CONCRETE
• All concrete shall conform to the requirements of the latest edition of SANS 2001 CC1.
• Concrete specifications:
• ELEMENT 28 DAY - fcu(Mpa) Aggregate (mm)
• Massconcrete/Blinding 15 19• Foundations 30 19• Columns 40 19• Slabs 30 19• Surface beds 30 19
• Beams 30 19• Walls & Retaining walls 30 19
• The contractor shall submit a mix design and report by a recognised concrete laboratory, to indicate that suitable materials and mix proportions will be used. the mix
design is to be submitted to the engineer for his records prior to commencing with construction.
• Max slump for all concrete to be 75mm unless otherwise approved by the Engineer.
• No pumping of concrete shall be allowed without prior approval from the Engineer.
• All concrete shall be continuously cured for 7 days by an approved method. This method to be submitted to the Engineer for his records.
• The position and method of forming all construction joints shall be submitted to the Engineer for approval prior to construction.
• Refer to Architect, Electrical and Mechanical Engineers drawings to verify positions of downpipes, duct penetrations, recesses ect. as required by them prior to casting. Any discrepancies shall immediately be referred to the Engineer.
• Depth of RC beams (downstand and inverted) is the second dimension and includes the slab thickness.
• No kickers to be cast for columns and walls.
• Concrete Cover:
ELEMENT Min Cover (mm)
• Foundations 75• Columns 40 • Beams 25 • Walls 40• Slabs 25
•
• The contractor is responsible for checking and ensuring that the reinforcement is fixed and maintained in the correct position before and during the casting of concrete.
• Reinforcement allowances for concrete work are as follow for Tender purposes:
Foundations / Slab Edge 65 Kg/m³Concrete Columns 150 Kg/m³Concrete Beams 120 Kg/m³
Concrete Slabs 100 Kg/m³RC Surface Bed Ground Level 100 Kg/m³Concrete Walls 120 Kg/m³
• All reinforcement must be inspected by the Engineer before concrete is cast. The Engineer shall be given 24 hours advance notice of an inspection. Inspections will only be carried out once all the relevant reinforcement has been properly fixed, the spacer blocks have been positioned, the shuttering has been cleaned out and the contractor has checked and approved
the reinforcement. • No alterations may be made to the structure or the reinforcement without prior approval from
the Engineer.
• Bending dimensions and scheduling of steel reinforcement for concrete is to SANS 282. (r) -denotes mild steel bars (fy - 250 Mpa) ; (Y) - denotes high-yield bars (fy - 450 Mpa)
• Mill certificates for reinforcement bars to be submitted to the engineer for his records.
• Welding of high-yield (Y) reinforcement is not allowed. Mild steel (R) reinforcement may be welded only if instructed in writing by the Engineer.
• Concentrations of a large number of sleeves or services to be cast into a concrete element will not be allowed. position and spacing to be agreed with the engineer prior to casting.
• No chasing of services into the concrete structure will be allowed.• No core drilling will be allowed without prior approval from the Engineer.• Any penetrations not shown on the drawings must be brought to the attention of the engineer
prior to casting.
• The standard of concrete finish shall be to the Architect's specification.• All exposed corners of concrete elements to have 20x20 chamfer or as per Architect's
specification.
• Removal of formwork in normal to hot conditions(Refer to SANS 2001:CC1-Table 2)
• TYPE OF STRUCTURAL TIME TO • MEMBER OR FORM WORK REMOVAL
• Beam sides, walls & unloaded columns. 1 day• Slabs with props left underneath. 4 days• Beam soffits & coffer slab soffits with props left underneath. 7 days• Slab props. 10 days
• Beam props, slab cantilever props and beam cantilever props. 14 days
• Extent of back propping and sequence to be discussed with the Engineer before commencement of works.
• The contractor shall be responsible for the design and maintenance of all temporary structures,
including formwork and support work.• One set of concrete test cubes shall be prepared per 50m³ of concrete cast, or any part thereof
daily of every type cast.
1. Generally one concrete cube shall be tested at 7 days and three cubes at 28 days.
2. The 3 cubes tested at 3 days, are to be left on the cast slab to simulate actual curing conditions on site, the sides of these cubes are to be protected to prevent excessive drying out.
• The cube results are to be forwarded to the Engineer immediately after testing. the cube
results should be clearly labeled and referenced, indicating the cast date, which element type and specific elements were cast with the relevant concrete.
• All suspended slabs are to be adequately surveyed at intervals as agreed with the Engineer before and after removal of support work. Results to be forwarded to the engineer for his records.
• Sawn joints in surface beds shall be cut within 48 hours after casting concrete.
MASONRY
• All brickwork or blockwork to be laid to the requirements and tolerances of SANS 10164 Appendix
B.
• Class II mortar shall be used throughout as per SANS 10164.• All structural brickwork or blocks shall have a nominal compressive strength of 14 MPa.
• Water absorption of clay bricks not to exceed 12%.• Clay bricks shall comply with SANS 227 and shall be well saturated 2 hours before being used.
• No clay bricks shall be laid within 6 weeks from removal from kiln.• Calcium silicate bricks shall comply with SANS 285; bricks shall be laid slightly wetted but not
saturated.
• Concrete blocks shall comply with SANS 1215 and shall be laid dry.• For cavities smaller than 75mm galvanized butterfly ties complying with SANS 28 or approved
polypropylene ties shall be built into cavity walls at a rate of 5 ties per m2 minimum.
• For cavities bigger than 75mm galvanised vertical twist type ties shall be used at a rate of 5 ties per m2.
• Adjacent to columns, wall ties to be built into every second layer of brickwork.
• In concrete blockwork brickforce shall be installed continuous throughout in every second course as well as in two courses below and above all windows and above all doors, extending 600mm past such openings.
• In clay brickwork brickforce shall be installed continuously throughout in every third course as well
as in two courses below and above all windows and above all doors, extending at least 600mm past such openings.
• Galvanized hoop iron anchors (min 60 mm2 section) shall be installed every 4th course between RC columns and brickwalls and extend min 600mm into masonry. Use 6mm nail plugs, no shot
fixing will be allowed.
• All brickforce shall be galvanized and comprise of hard drawn steel wire comprising two main diameter wires of diameter not less than 2.8mm spaced a constant distance apart and 2.5mm diameter cross wires spaced at longitudinal intervals of 300mm in ladder type brickforce.
• A slip joint of 2 layers 3-ply malthoid must be provide between all loadbearing brickwork and concrete structure.
• A 10mm soft joint (jointex) must be provided between all non-loadbearing brickwork and concrete
structure.
• Joints to be sealed in accordance with Architect's specification.• All brick walls to be set out according to Architect's drawing.• All brick walls to be built on centrally strip footings unless noted otherwise.
• Brick- or blockwork built on suspended slabs to be built only once the concrete slab has reach its required design strength and all the props have been removed.
• Brick- or blockwork built on suspended slabs to have no brick- or blockwork above internal door openings.
• Precast lintols to be propped during brickwork over, and to remain propped for a minimum period of 7 days.
STRUCTURAL STEEL
• All Structural steelwork shall comply with SANS 2001-CS1: 2005• All structural steelwork shall be fabricated and erected in accordance with the latest edition of
SANS 1200 H excluding clause 8.• The steel structure shall be manufactured and erected according to SANS 1200 H degree of
accuracy II.
• The contractor shall at the commencement of the project acquaint himself with the availability and delivery time of the products and steel profiles specified on the drawings so that such material can be ordered ahead of time.
• All hot roll sections to be grade S355 JR.• All cold-formed steel sections - Min yield stress of 200 MPa• All bolts to be Grade 8.8• All cold-formed steel sections and bolts to be hot-dipped galvanized unless noted otherwise.
• Steelwork shall comply with the requirements of SANS 1431 for weldable structural steel. • A certificate from the steel manufacturer verifying the grade of the structural steel shall be
submitted to the engineer for his records.• The sequence of the erection of the structure is the responsibility of the contractor. The contractor
shall ensure the stability of the structure during erection. Where temporary bracing or propping is
necessary, the contractor shall be responsible for the design, erection, maintenance and removal (where necessary) of such supports.
• The contractor to submit in writing his proposed erection method statement for the comment of the engineer. it remains the contractors responsibility to produce the final product in accordance with the engineers design drawings.
• All drawings are design drawings. Workshop drawings are to be prepared by the contractor and submitted to the engineer for approval prior to commencing with fabrication. The contractor must also prepare drawings showing all positions, levels and orientation of cast in plates and bolts.
• Contractor to allow a minimum of 2 weeks for checking and approval of the workshop drawings by the Engineer, the contractor should also allow for possible changes to workshop drawings.
• All dimensions and levels to be checked on site by the contractor before commencing with workshop drawings and manufacture. Any discrepancies shall be brought to the attention of the engineer in writing.
• For structural steel fixed to concrete allow 20mm tolerance for lining up.
• Approved non-shrink structural grout shall be provided under all steel supported on concrete.
• All design shall be accordance with SANS 10160 and SANS 10162.• All connections to be adequate to develop the full tensile capacity of the members.
• All truss and girder members to be welded all round both sides. Allow for gusset plates if necessary to ensure adequate welding length to develop full tensile capacity of the members.
• Centroids of all members to intersect, no eccentricities except for those shown on the Engineers design drawings shall be allowed.
• All connection details to be approved by the engineer in writing prior to fabrication.
• Use Class E70XX electrodes for all welding.• All welding shall be done in accordance with AWS D1.1 Structural Welding Code-Steel.
• Minimum weld size to be 6mm continuous fillet welds. Throat thickness not to be less than 0.7 x the thinner material thickness welded to.
• All butt welds to be full penetration butt welds of full strength.• All welders shall be coded welders.• The contractor shall produce evidence acceptable to the engineer that welding procedures
and welders have been tested in accordance with the requirements of SANS 044, parts III
and IV
• Post-fixing using mechanical or chemical anchors to be approved by the Engineer prior to commencing with installation. All fixings to be strictly in accordance with the manufacturer's specifications.
• Penetrations and holes required in galvanized steel shall be pre-drilled before the steel is galvanized. No drilling is allowed on site in any galvanised steel members.
• No holes may be made in any structural members without the prior consent of the Engineer.• No site cutting or welding will be allowed unless approved or specified by the Engineer.
• Allow 10% of light and medium steelwork (excluding purlins and girts) for connections, splices, column cap and base plates, plus 1% for Grade 8.8 bolts and 0,5% for Grade 4.8 bolts.
CORROSION PROTECTION SPECIFICATION
Pre-fabrication preparation:Commercial blast steel to remove rust and mill scale Duplex system: Post-fabrication & trial assembly: hot dipped galvanized to SANS 121:2000 (heavy duty) -
un-passivated. Micro-blast with garnet slag to achieve a water break free
Surface & rough profile:Apply one coat of epoxy primer to a dft of 60 microns. Apply one coat of re-coatable polyurethane finishing to a dft of 30 microns (colour to
architect's specification).
• Cladding to be done in accordance with SANS 1200 HB• All roof and side cladding to be as per architect's specification.• Cladding to only commence once all bracing is installed, inspected and approved by the
Engineer.• Cladding contractor to ensure purlins and girts remain straight during installation of cladding
and insulation material.• Fixing of services to the roof structure - fixing to purlins to be done by screwing or bolting
through the vertical leg (web) of the purlin. purlin clamps shall not be allowed anywhere. No hanging off the purlins until the roof sheeting has been installed.
• No fixing of services to longitudinal ties at truss bottom chords will be allowed.
• Main pipe runs and other heavy items are to be suspended from trusses and girders only and never further than 100mm from a node point. approved flange clamps may be used.
• Feeder pipes and other lightweight elements:Running perpendicular to the purlins are to be suspended from every purlin it crosses.Running parallel to the purlins have to be suspended from two adjacent purlins and at
1250mm c/c max.
CONSULTING ENGINEERS
A1
REVISION:DRAWING NO:
SCALE:
NWE RESPONSIBLE PERSON
APPROVED
CLIENT:
RESPONSIBLE PERSON
ISSUED FOR:
DRAWN
DESIGN
SHEET SIZE:DATE:
SIGNATURE + ECSA DETAILS DATE
PROJECT NAME:
DRAWING TITLE:
1st FLOOR PLATTEKLOOF HOUSE I TYGERBERG OFFICE PARK163 UYS KRIGE DRIVE I PLATTEKLOOF I SOUTH AFRICA
P.O. BOX 5263 I TYGER VALLEY I 7536TEL. (+27) 21 914 2264
E-MAIL: [email protected] I WEB: www.nweng.co.za
SPECIAL NOTES
COPYRIGHT RESERVED
THE COPYRIGHT OF THIS DRAWING IS VESTED IN NWE AND IT MAY NOT BE
REPRODUCED IN WHOLE OR PART, ISSUED OR USED FOR ANY PURPOSE OTHER
THAN WHAT IT WAS ORIGINALLY INTENDED FOR WITHOUT THE EXPRESS
PERMISSION OF THE COPYRIGHT HOLDERS.
CONFIRMATION OF DIMENSIONS
WORK TO FIGURED DIMENSIONS ONLY. ALL DIMENSIONS , LEVELS AND CO-
ORDINATES TO BE CHECKED AND CONFIRMED ON SITE WITH THE ENGINEER
BEFORE CONSTRUCTION COMMENCES. DIMENSIONS ARE NOT TO BE SCALED FROM
THIS DRAWING. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL
RELEVANT ARCHITECT's AND NWE DRAWINGS AND SPECIFICATIONS.
1 : 1
A
M.STEYN
C.NORTJE
C.DE JAGER 2020.10.16
2020.10.16
2020.10.16
M.STEYN 2020.10.16
20005-SANSA-S- 000
SANSASPACE WEATHER CENTRE
GENERAL SPECIFICATIONS
FOR INFORMATION
REV DESCRIPTION BY DATE
A FOR INFORMATION CN 2020.10.16
![Page 2: C:UsersCharlDesktopIssue FolderSANSASWC - Sheet - 000 - … · 2020. 11. 13. · • Beam sides, walls & unloaded columns. 1 day ... • The contractor to submit in writing his proposed](https://reader033.vdocuments.site/reader033/viewer/2022060816/60949a7859caf93fc420eac2/html5/thumbnails/2.jpg)
750x250mm RC STRIP FOOTING
750x250mm RC STRIP FOOTING
750x250mm RC STRIP FOOTING
750x250mm RC STRIP FOOTING
750x250mm RC STRIP FOOTING
750x250mm RC STRIP FOOTING
750x250mm RC STRIP FOOTING
750x250mm RC STRIP FOOTING 750x250mm RC STRIP FOOTING
750
x250
mm
RC
ST
RIP
FO
OT
ING
750
x250
mm
RC
ST
RIP
FO
OT
ING
750
x250
mm
RC
ST
RIP
FO
OT
ING
750
x250
mm
RC
ST
RIP
FO
OT
ING
750
x250
mm
RC
ST
RIP
FO
OT
ING
750
x250
mm
RC
ST
RIP
FO
OT
ING
750
x250
mm
RC
ST
RIP
FO
OT
ING
750x
250
mm
RC
ST
RIP
FO
OT
ING
750x
250
mm
RC
ST
RIP
FO
OT
ING
750x
250
mm
RC
ST
RIP
FO
OT
ING
750x
250
mm
RC
ST
RIP
FO
OT
ING
750x
250
mm
RC
ST
RIP
FO
OT
ING
750x
250
mm
RC
ST
RIP
FO
OT
ING
750x
250
mm
RC
ST
RIP
FO
OT
ING
750x
250
mm
RC
ST
RIP
FO
OT
ING
750
x250
mm
RC
ST
RIP
FO
OT
ING
750x
250
mm
RC
ST
RIP
FO
OT
ING
750
x250
mm
RC
ST
RIP
FO
OT
ING
750
x250
mm
RC
ST
RIP
FO
OT
ING
750 1947 750 1922 750 1922 750 1898 750 8980 750 1755 750 1780 750 1780 750 1805 750
1000
855
750
3526
750
679
750
981
750
3524
750
681
750
4056
750
1710
750
3573
750
1929
750
414
1186 750 3505 750 545
750 8430 750
1530
750
4530
750
530
451
750
3664
515 750 3538
1125
750 1005 1365 750 1390 750 2760
750
3573
750
1929
750
2144
750 2346 750
750
3400
750
1009
750
750
3530
750
7648
750
750 1260 750 1495 750
750
420
750
3526
750
1980
A
004
A
004
H
005
H
005
G
005
G
005
1300x300mm RC
STRIP FOOTING
130
0x30
0mm
RC
ST
RIP
FO
OT
ING
130
0x30
0mm
RC
ST
RIP
FO
OT
ING
160x340 RC
COLUMN160x340 RC
COLUMN
160x340 RC
COLUMN 160x340 RC
COLUMN
160x340 RC
COLUMN
160x340 RC
COLUMN
160x340 RC
COLUMN
160x340 RC
COLUMN
160x340 RC
COLUMN
280x280 BRICK
1000x1000x250mm
RC BASE
1000 6837
345
mm
thk
RC
WA
LL
345
mm
thk
RC
WA
LL
E.J E.J
E.J E.J
E.J
E.JE.J
1000x1000x250mm
RC BASE1000x1000x250mm RC BASE
1300 8915 130013
0015
800
SCALE: 1 : 100
FOUNDATION LAYOUT
CONSULTING ENGINEERS
A1
REVISION:DRAWING NO:
SCALE:
NWE RESPONSIBLE PERSON
APPROVED
CLIENT:
RESPONSIBLE PERSON
ISSUED FOR:
DRAWN
DESIGN
SHEET SIZE:DATE:
SIGNATURE + ECSA DETAILS DATE
PROJECT NAME:
DRAWING TITLE:
1st FLOOR PLATTEKLOOF HOUSE I TYGERBERG OFFICE PARK163 UYS KRIGE DRIVE I PLATTEKLOOF I SOUTH AFRICA
P.O. BOX 5263 I TYGER VALLEY I 7536TEL. (+27) 21 914 2264
E-MAIL: [email protected] I WEB: www.nweng.co.za
SPECIAL NOTES
COPYRIGHT RESERVED
THE COPYRIGHT OF THIS DRAWING IS VESTED IN NWE AND IT MAY NOT BE
REPRODUCED IN WHOLE OR PART, ISSUED OR USED FOR ANY PURPOSE OTHER
THAN WHAT IT WAS ORIGINALLY INTENDED FOR WITHOUT THE EXPRESS
PERMISSION OF THE COPYRIGHT HOLDERS.
CONFIRMATION OF DIMENSIONS
WORK TO FIGURED DIMENSIONS ONLY. ALL DIMENSIONS , LEVELS AND CO-
ORDINATES TO BE CHECKED AND CONFIRMED ON SITE WITH THE ENGINEER
BEFORE CONSTRUCTION COMMENCES. DIMENSIONS ARE NOT TO BE SCALED FROM
THIS DRAWING. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL
RELEVANT ARCHITECT's AND NWE DRAWINGS AND SPECIFICATIONS.
1 : 100
A
M.STEYN
C.NORTJE
C.DE JAGER 2020.10.16
2020.10.16
2020.10.16
M.STEYN 2020.10.16
20005-SANSA-S- 001
SANSA
SPACE WEATHER CENTRE
SPACE WEATHER CENTRE
FOUNDATION LAYOUT
FOR INFORMATION
REV DESCRIPTION BY DATE
A FOR INFORMATION CN 2020.10.16
![Page 3: C:UsersCharlDesktopIssue FolderSANSASWC - Sheet - 000 - … · 2020. 11. 13. · • Beam sides, walls & unloaded columns. 1 day ... • The contractor to submit in writing his proposed](https://reader033.vdocuments.site/reader033/viewer/2022060816/60949a7859caf93fc420eac2/html5/thumbnails/3.jpg)
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
I.J I.J I.J I.J
I.J I.J
I.J I.J I.J I.J
I.J I.J I.J I.J I.J I.J I.J I.J I.J I.J I.J I.J I.J I.J I.J I.J I.J I.J
I.J
I.J
I.J I.J
I.J
I.J
I.J
I.J
I.J I.J I.JI.J
I.J
I.J I.J
I.J I.J
I.J I.J
I.J I.J
I.J I.J
I.J I.JI.J
I.J
I.J
I.J
I.J I.J I.J
I.J
I.J
I.J
I.J
I.J
I.J
I.JI.J
I.J I.J I.J I.J
I.J
I.J
I.J
I.J
I.J
I.JI.J I.J I.J
I.J
I.J
I.J
I.J
I.JI.J
I.J
I.JI.J
I.J
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
S.J
S.J
S.J
S.J
S.J
S.J
S.J
S.J
S.J
S.J
S.J
S.J
S.J
S.J
S.J
S.J
S.J
S.J
S.J
S.J
S.J
S.J S.J
S.J
S.J
S.J
S.J
S.J S.J
S.J S.J
S.J
S.J
S.J
S.J
S.J
S.J
S.J
S.J
250
x250
mm
ED
GE
TH
ICK
EN
ING
250
x250
mm
ED
GE
TH
ICK
EN
ING
A
004
A
004
B
004
B
004
C
005
C
005
D
005
D
005
S.J
H
005
H
005
E
005
E
005
F
005
F
005
E.J E.J
E.J E.J
E.J
75x75x3.0 SHS
COLUMN75x75x3.0 SHS
COLUMN
G
005
G
005
160x340 RC
COLUMN160x340 RC
COLUMN
160x340 RC
COLUMN160x340 RC
COLUMN
160x340 RC
COLUMN
160x340 RC
COLUMN
160x340 RC
COLUMN
160x340 RC
COLUMN
160x340 RC
COLUMN
125
mm
thk
SU
RF
AC
E B
ED
SLA
B
WIT
H M
ES
H R
EF
. 24
5
125
mm
thk
SU
RF
AC
E B
ED
SLA
B
WIT
H M
ES
H R
EF
. 24
5
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
150
mm
thk
EX
PO
SE
D
AG
GR
EG
AT
E S
LA
B W
ITH
ME
SH
RE
F. 2
45
-O
VE
RC
AS
T 3
mm
AN
D
GR
IND
DO
WN
TO
AR
CH
ITE
CT
'S
SE
C.
150mm thk
EXPOSED
AGGREGATE SLAB
WITH MESH REF.
245 - OVERCAST
3mm AND GRIND
DOWN TO
ARCHITECT'S SEC.
125mm thk
SURFACE BED
SLAB WITH MESH
REF. 245
250
x250
mm
ED
GE
TH
ICK
EN
ING
150mm thk EXPOSED
AGGREGATE SLAB WITH MESH
REF. 245 - OVERCAST 3mm AND
GRIND DOWN TO ARCHITECT'S
SEC.
250x250mm EDGE THICKENING
250x250mm EDGE THICKENING
150mm thk EXPOSED
AGGREGATE SLAB WITH MESH
REF. 245 - OVERCAST 3mm AND
GRIND DOWN TO ARCHITECT'S
SEC.
280x280 BRICK
E.J E.J
E.J
E.JE.J
S.J
S.J
S.JS.JS.JS.J
S.J
S.J
S.J
S.J
S.J
S.J
150mm thk RC LECTURE SEATING
300 10 300
27
0
10x10mm GREY POLISULPHIDE
JOINT SEALANT ON
BOTH SIDES OF JOINT.
1.2mm THK CONCERTINA TIE
(GALVANISED HOOP IRON TIE)
600mm LONG BEND 25mm DOWN
AT THE JOINT TO ALLOW FORMOVEMENT.
INSTALLED EVERY 3rd BRICK COURSE
ON BOTH SKINS.
280 WIDE 14MPa
MASONRY WALL
GALVANISED BUTTERFLY TIES IN
EVERY 2nd LAYER OF BRICKWORK,
BOTH SIDES OF RC COLUMN
10mm JOINT CONSISTING
OF 10mm JOINTEX SEALED
WITH 10x10 POLYURETHANE
SEALANT
BRICK WALL TO BE FIXED WITH GALVANISED HOOP IRONS
(60 sq mm SECTION) EXTENDING MIN. 600mm INTO
BRICKWORK EVERY 3 COURSES. HOOP IRONS TO BE FIXED
WITH 8mm NAIL PLUGS. NO SHOT FIXING - ALL HOLES
TO BE PRE-DRILLED.
600
SURFACE BED NOTE:
125mm THK 30MPa SURFACE BED SLAB
MESH Ref. 245 ON 375 MICRON DPM
ON 200mm CLEAN SAND COMPACTED
TO 100% MOD AASHTO
ON COMPACTED IN-SITU MATERIAL
REINFORCEMENT ESTIMATE
FOOTINGS = 65 kg/m³
RC WALLS = 120 kg/m³
RC COLUMNS = 150 kg/m³
RC BEAMS = 120 kg/m³
RC SLABS = 100 kg/m³
LEGEND
ISOLATION JOINT = I.J
SAW-CUT JOINT = S.J
EXPANSION JOINT = E.J
CONSTRUCTION JOINT = C.J
ABBREVIATIONS:
TOS = TOP OF STEEL
TOC = TOP OF CONCRETE
TOW = TOP OF WALL
U/S = UNDERSIDE
COL = STEEL COLUMN
NGL = NEAR GROUND LEVEL
MESH REF. 245
NOT CONTINUOUS
6wd x 35dp JOINT MUST BE CUT WITHIN 48
HOURS OF CASTING CONCRETE & INSERT
FLEXIBLE JOINT FILLER+SEALANT.
55 55
125
7550
35
CLEAN IMPORTED SAND LAYER
COMPACTED TO 100% AASHTO.
DPC & WEEP HOLES
TO ARCHITECT'S DETAILS
ALL FOUNDATION PLINTH WALLS
TO BE 14MPa LOAD BEARING MASONRY
WITH BRICK FORCE EVERY COURSE & WALL TIES
@400mm c/c EVERY SECOND COURSE
UP TO GROUND FLOOR SLAB LEVEL
10 x 10mm POLYURETHANE
SEALANT + 10mm JOINTEX
375 MICRON DPM
CLASS 15/19 CONCRETE
CONTINUOUS BRICK FORCE EVERY
COURSE WITH 400mm LAPS
CLEAN IMPORTED SAND LAYER
COMPACTED TO 100% AASHTO.
IN-SITU SAND MATERIAL
COMPACTED TO
MIN. 95% MOD AASHTO.
270
270mm WIDE 14MPa
MASONRY WALL
NOTE:
ALLOWANCE SHOULD BE MADE FOR
DEWATERING OF THE TRENCHES
DURING CONSTRUCTION
IMPORTED G5 MATERIAL
COMPACTED TO 95% MOD AASTHO
IN 150mm LAYERS
500
1000
WALL / COLUMN
NGL
RC FOOTING / BASE
WIDTH
1.5 x WIDTH
35°
110mm WIDE 14MPa
NON-LOAD BEARING MASONRY
WALL
MESH REF
200
700
125 450 125
50
CONSULTING ENGINEERS
A1
REVISION:DRAWING NO:
SCALE:
NWE RESPONSIBLE PERSON
APPROVED
CLIENT:
RESPONSIBLE PERSON
ISSUED FOR:
DRAWN
DESIGN
SHEET SIZE:DATE:
SIGNATURE + ECSA DETAILS DATE
PROJECT NAME:
DRAWING TITLE:
1st FLOOR PLATTEKLOOF HOUSE I TYGERBERG OFFICE PARK163 UYS KRIGE DRIVE I PLATTEKLOOF I SOUTH AFRICA
P.O. BOX 5263 I TYGER VALLEY I 7536TEL. (+27) 21 914 2264
E-MAIL: [email protected] I WEB: www.nweng.co.za
SPECIAL NOTES
COPYRIGHT RESERVED
THE COPYRIGHT OF THIS DRAWING IS VESTED IN NWE AND IT MAY NOT BE
REPRODUCED IN WHOLE OR PART, ISSUED OR USED FOR ANY PURPOSE OTHER
THAN WHAT IT WAS ORIGINALLY INTENDED FOR WITHOUT THE EXPRESS
PERMISSION OF THE COPYRIGHT HOLDERS.
CONFIRMATION OF DIMENSIONS
WORK TO FIGURED DIMENSIONS ONLY. ALL DIMENSIONS , LEVELS AND CO-
ORDINATES TO BE CHECKED AND CONFIRMED ON SITE WITH THE ENGINEER
BEFORE CONSTRUCTION COMMENCES. DIMENSIONS ARE NOT TO BE SCALED FROM
THIS DRAWING. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL
RELEVANT ARCHITECT's AND NWE DRAWINGS AND SPECIFICATIONS.
As indicated
A
M.STEYN
C.NORTJE
C.DE JAGER 2020.10.16
2020.10.16
2020.10.16
M.STEYN 2020.10.16
20005-SANSA-S- 002
SANSASPACE WEATHER CENTRE
SPACE WEATHER CENTRESURFACE BED LAYOUT + SECTIONS &
DETAILS
FOR INFORMATION
REV DESCRIPTION BY DATE
A FOR INFORMATION CN 2020.10.16
SCALE: 1 : 100
SURFACE BED LAYOUT
SCALE: 1 : 10
TYPICL EXPANSION JOINT (E.J) DETAIL
SCALE: 1 : 10
MOVEMENT JOINT BETWEEN
RC COLUMN AND MASONRY WALL
SCALE: 1 : 5
TYPICAL SAW-CUT JOINT (S.C.J.)
SCALE: 1 : 10
TYPICAL FLOOR ISOLATION JOINT DETAIL (I.J)
SCALE: 1 : 25
TYPICAL GROUND WORKS BELOW ALL FOOTINGSSCALE: 1 : 10
TYPICAL SURFACE BED THICKENING
![Page 4: C:UsersCharlDesktopIssue FolderSANSASWC - Sheet - 000 - … · 2020. 11. 13. · • Beam sides, walls & unloaded columns. 1 day ... • The contractor to submit in writing his proposed](https://reader033.vdocuments.site/reader033/viewer/2022060816/60949a7859caf93fc420eac2/html5/thumbnails/4.jpg)
A
004
A
004
H
005
H
005
G
005
G
005
280x340 RC BEAM
280x850 RC BEAM
280x650 RC BEAM
280
x650
RC
BE
AM
160x340 RC
COLUMN
160x340 RC
COLUMN
160x340 RC
COLUMN
160x340 RC
COLUMN
230x850 RC BEAM
280x850 RC BEAM
160
x340
RC
BE
AM
230x230 RC
COLUMN
230x230 RC
COLUMN
230x230 RC
COLUMN
230x230 RC
COLUMN
230x230 RC
COLUMN
230x230 RC
COLUMN
160x340 RC
COLUMN
160x340 RC
COLUMN
160x340 RC
COLUMN
160x340 RC
COLUMN
230x425 RC BEAM
230x425 RC BEAM
230x425 RC BEAM
230x425 RC BEAM
230
x425
RC
BE
AM
230
x425
RC
BE
AM
CONSULTING ENGINEERS
A1
REVISION:DRAWING NO:
SCALE:
NWE RESPONSIBLE PERSON
APPROVED
CLIENT:
RESPONSIBLE PERSON
ISSUED FOR:
DRAWN
DESIGN
SHEET SIZE:DATE:
SIGNATURE + ECSA DETAILS DATE
PROJECT NAME:
DRAWING TITLE:
1st FLOOR PLATTEKLOOF HOUSE I TYGERBERG OFFICE PARK163 UYS KRIGE DRIVE I PLATTEKLOOF I SOUTH AFRICA
P.O. BOX 5263 I TYGER VALLEY I 7536TEL. (+27) 21 914 2264
E-MAIL: [email protected] I WEB: www.nweng.co.za
SPECIAL NOTES
COPYRIGHT RESERVED
THE COPYRIGHT OF THIS DRAWING IS VESTED IN NWE AND IT MAY NOT BE
REPRODUCED IN WHOLE OR PART, ISSUED OR USED FOR ANY PURPOSE OTHER
THAN WHAT IT WAS ORIGINALLY INTENDED FOR WITHOUT THE EXPRESS
PERMISSION OF THE COPYRIGHT HOLDERS.
CONFIRMATION OF DIMENSIONS
WORK TO FIGURED DIMENSIONS ONLY. ALL DIMENSIONS , LEVELS AND CO-
ORDINATES TO BE CHECKED AND CONFIRMED ON SITE WITH THE ENGINEER
BEFORE CONSTRUCTION COMMENCES. DIMENSIONS ARE NOT TO BE SCALED FROM
THIS DRAWING. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL
RELEVANT ARCHITECT's AND NWE DRAWINGS AND SPECIFICATIONS.
1 : 100
Designer
Author
Approver 10/15/20
2020.10.16
2020.10.16
M.STEYN 10/15/20
20005-SANSA-S- 003
SANSA
SPACE WEATHER CENTRE
RING BEAM LAYOUT
FOR INFORMATION
REV DESCRIPTION BY DATE
SCALE: 1 : 100
RING BEAMS
![Page 5: C:UsersCharlDesktopIssue FolderSANSASWC - Sheet - 000 - … · 2020. 11. 13. · • Beam sides, walls & unloaded columns. 1 day ... • The contractor to submit in writing his proposed](https://reader033.vdocuments.site/reader033/viewer/2022060816/60949a7859caf93fc420eac2/html5/thumbnails/5.jpg)
0
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
280 WIDE 14MPa
MASONRY WALL
IN-SITU FOUNDING MATERIAL
TO BE INSPECTED AND APPROVED
BY STRUCTURAL ENGINEER
I.J
I.J I.J
750
6875
345mm thk RC WALL
230x425 RC BEAMTIMBER ROOF AND WATER PROOFING
TO ARCHITECT'S DESIGN & SPECIFICATION
K.C.J
K.C.J
999 1070 1070 1070 1070 1070 1070 1070 1070
210
210
210
210
210
210
220
220
240
200
300300 300 2610300 1469 300 300 3680
11
°
11
°
11
°
125mm thk SURFACE BED SLAB WITH
MESH REF. 245
150mm thk RC LECTURE SEATING
K.C.J
150
0
3500
IN-SITU FOUNDING MATERIAL
TO BE INSPECTED AND APPROVED
BY STRUCTURAL ENGINEER
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
250x250mm
EDGE THICKENING
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
280 WIDE 14MPa
MASONRY WALL
230 WIDE 14MPa
MASONRY WALL
1680
280x650 RC BEAM
TIMBER ROOF AND WATER PROOFING
TO ARCHITECT'S DESIGN & SPECIFICATION
280x650 RC BEAM
650
3000
7503505750100575010215750
280 WIDE 14MPa
MASONRY WALL
280x650 RC BEAM
280x650 RC BEAM
Y10 BARS (400mm LONG)
CAST INTO RC BEAM
@ 250mm c/c
GALVANIZED STEEL BUTTERFLY WALL TIES
EVERY SECOND COURSE
AT MIN. 400mm HORIZONTAL SPACING
2xY12 BARS IN CONCRETE CAVITYFILL CAVITY WITH
CLASS 20/19 CONCRETE
CONTINUOUS
BRICK FORCE
EVERY COURSE
WITH 400mm LAPS
JOINT MUST BE CUT WITHIN 48 HOURS
OF CASTING & INSERT FLEXIBLE JOINT FILLER
BEFORE THE SCREED IS PLACED
30
15
CONSULTING ENGINEERS
A1
REVISION:DRAWING NO:
SCALE:
NWE RESPONSIBLE PERSON
APPROVED
CLIENT:
RESPONSIBLE PERSON
ISSUED FOR:
DRAWN
DESIGN
SHEET SIZE:DATE:
SIGNATURE + ECSA DETAILS DATE
PROJECT NAME:
DRAWING TITLE:
1st FLOOR PLATTEKLOOF HOUSE I TYGERBERG OFFICE PARK163 UYS KRIGE DRIVE I PLATTEKLOOF I SOUTH AFRICA
P.O. BOX 5263 I TYGER VALLEY I 7536TEL. (+27) 21 914 2264
E-MAIL: [email protected] I WEB: www.nweng.co.za
SPECIAL NOTES
COPYRIGHT RESERVED
THE COPYRIGHT OF THIS DRAWING IS VESTED IN NWE AND IT MAY NOT BE
REPRODUCED IN WHOLE OR PART, ISSUED OR USED FOR ANY PURPOSE OTHER
THAN WHAT IT WAS ORIGINALLY INTENDED FOR WITHOUT THE EXPRESS
PERMISSION OF THE COPYRIGHT HOLDERS.
CONFIRMATION OF DIMENSIONS
WORK TO FIGURED DIMENSIONS ONLY. ALL DIMENSIONS , LEVELS AND CO-
ORDINATES TO BE CHECKED AND CONFIRMED ON SITE WITH THE ENGINEER
BEFORE CONSTRUCTION COMMENCES. DIMENSIONS ARE NOT TO BE SCALED FROM
THIS DRAWING. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL
RELEVANT ARCHITECT's AND NWE DRAWINGS AND SPECIFICATIONS.
As indicated
A
M.STEYN
C.NORTJE
C.DE JAGER 2020.10.16
2020.10.16
2020.10.16
M.STEYN 2020.10.16
20005-SANSA-S- 004
SANSA
SPACE WEATHER CENTRE
SECTIONS & DETAILS
FOR INFORMATION
REV DESCRIPTION BY DATE
A FOR INFORMATION CN 2020.10.16
SCALE: 1 : 50
SECTION A
SCALE: 1 : 50
SECTION B
SCALE: 1 : 20
PARAPATE WALL STABILISING DETAIL
SCALE: 1 : 20
KEYED CONSTRUCTION JOINT
![Page 6: C:UsersCharlDesktopIssue FolderSANSASWC - Sheet - 000 - … · 2020. 11. 13. · • Beam sides, walls & unloaded columns. 1 day ... • The contractor to submit in writing his proposed](https://reader033.vdocuments.site/reader033/viewer/2022060816/60949a7859caf93fc420eac2/html5/thumbnails/6.jpg)
0
3500
280x850 RC BEAM
433 9577 434
850
100
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
750 9974 750 IN-SITU FOUNDING MATERIAL
TO BE INSPECTED AND APPROVED
BY STRUCTURAL ENGINEER
0
75x75x3.0 SHS
COLUMN
75x75x3.0 SHS
COLUMN
280x340 RC BEAM
340
1500
170
430
750 8980 750 IN-SITU FOUNDING MATERIAL
TO BE INSPECTED AND APPROVED
BY STRUCTURAL ENGINEER
2809450280
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
280x280x170mm
15MPa CONCRETE
PAD FOOTING
280x280x170mm
15MPa CONCRETE
PAD FOOTING
200x200x8mm THK BASE PLATE
WITH 4 x M 12 G.r. 8.8
CHEMICAL ANCHOR BOLTS
200x200x8mm TOP PLATE
WITH 4 x R8 LUGS WELDED TO THE PLATE.
TOP PLATE TO BE CAST INTO RC BEAM
3500
280x850 RC BEAM
230 9450 230
390
460
3500230x850 RC BEAM
250
600
6657671664
0
6550 6550160x340 RC BEAM 160x340 RC BEAM
160x340 RC
COLUMN160x340 RC
COLUMN
160x340 RC BEAM 160x340 RC BEAM
2140
0
3500
6550
160x340 RC
COLUMN
160x340 RC
COLUMN
160x340 RC BEAM
160x340 RC BEAM
160x340 RC
COLUMN160x340 RC
COLUMN
150mm thk EXPOSED
AGGREGATE SLAB WITH MESH
REF. 245 - OVERCAST 3mm AND
GRIND DOWN TO ARCHITECT'S
SEC.
CONSULTING ENGINEERS
A1
REVISION:DRAWING NO:
SCALE:
NWE RESPONSIBLE PERSON
APPROVED
CLIENT:
RESPONSIBLE PERSON
ISSUED FOR:
DRAWN
DESIGN
SHEET SIZE:DATE:
SIGNATURE + ECSA DETAILS DATE
PROJECT NAME:
DRAWING TITLE:
1st FLOOR PLATTEKLOOF HOUSE I TYGERBERG OFFICE PARK163 UYS KRIGE DRIVE I PLATTEKLOOF I SOUTH AFRICA
P.O. BOX 5263 I TYGER VALLEY I 7536TEL. (+27) 21 914 2264
E-MAIL: [email protected] I WEB: www.nweng.co.za
SPECIAL NOTES
COPYRIGHT RESERVED
THE COPYRIGHT OF THIS DRAWING IS VESTED IN NWE AND IT MAY NOT BE
REPRODUCED IN WHOLE OR PART, ISSUED OR USED FOR ANY PURPOSE OTHER
THAN WHAT IT WAS ORIGINALLY INTENDED FOR WITHOUT THE EXPRESS
PERMISSION OF THE COPYRIGHT HOLDERS.
CONFIRMATION OF DIMENSIONS
WORK TO FIGURED DIMENSIONS ONLY. ALL DIMENSIONS , LEVELS AND CO-
ORDINATES TO BE CHECKED AND CONFIRMED ON SITE WITH THE ENGINEER
BEFORE CONSTRUCTION COMMENCES. DIMENSIONS ARE NOT TO BE SCALED FROM
THIS DRAWING. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL
RELEVANT ARCHITECT's AND NWE DRAWINGS AND SPECIFICATIONS.
As indicated
A
M.STEYN
C.NORTJE
C.DE JAGER 2020.10.16
2020.10.16
2020.10.16
M.STEYN 2020.10.16
20005-SANSA-S- 005
SANSA
SPACE WEATHER CENTRE
SECTIONS & DETAILS
FOR INFORMATION
REV DESCRIPTION BY DATE
A FOR INFORMATION CN 2020.10.16
SCALE: 1 : 50
SECTION C
SCALE: 1 : 50
SECTION D
SCALE: 1 : 75
SECTION E
SCALE: 1 : 75
SECTION F
SCALE: 1 : 50
SECTION G
SCALE: 1 : 50
SECTION H
![Page 7: C:UsersCharlDesktopIssue FolderSANSASWC - Sheet - 000 - … · 2020. 11. 13. · • Beam sides, walls & unloaded columns. 1 day ... • The contractor to submit in writing his proposed](https://reader033.vdocuments.site/reader033/viewer/2022060816/60949a7859caf93fc420eac2/html5/thumbnails/7.jpg)
A
S-002
A
S-002
B
S-002
B
S-002
750x250mm RC STRIP FOOTING
750x250mm RC STRIP FOOTING
750x250mm RC STRIP FOOTING
750
x250
mm
RC
ST
RIP
FO
OT
ING
750
x250
mm
RC
ST
RIP
FO
OT
ING
750x250mm RC STRIP FOOTING75
0x2
50m
m R
C S
TR
IP F
OO
TIN
G
750
x250
mm
RC
ST
RIP
FO
OT
ING
750
x250
mm
RC
ST
RIP
FO
OT
ING
750
x250
mm
RC
ST
RIP
FO
OT
ING
750
x250
mm
RC
ST
RIP
FO
OT
ING
750x250mm RC STRIP FOOTING
750 10370 750
730
750
2050
750
410 750 1465
750
630
750
2050
750
730
750
505
750
4620
750 3372 750 3372 750
6298 750 967
1526 750
750
3365
165
750
750 4030 750 7493 750 3243 750
22652
265
A
S-002
A
S-002
B
S-002
B
S-002
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
150mm thk EXPOSED
AGGREGATE SLAB WITH MESH
REF. 193 - OVERCAST 3mm AND
GRIND DOWN TO ARCHITECT'S
SEC.
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
150mm thk EXPOSED
AGGREGATE SLAB WITH MESH
REF. 193 - OVERCAST 3mm AND
GRIND DOWN TO ARCHITECT'S
SEC.
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
2000
2613 6161 2625
I.J
I.J I.J
I.J
I.J
I.J
I.J
I.J
I.J
I.J
I.J
I.J
I.J I.J I.J I.J I.J I.J
I.J
I.JI.J
I.J
I.J
I.J
I.J I.J
I.J
I.JI.J
I.J I.J
250x250mm EDGE THICKENING
S.J
250x250mm EDGE THICKENING
S.J S.J S.J S.J
S.J
S.J
S.J
S.J
S.J
MESH REF. 245
NOT CONTINUOUS
6wd x 35dp JOINT MUST BE CUT WITHIN 48
HOURS OF CASTING CONCRETE & INSERT
FLEXIBLE JOINT FILLER+SEALANT.
55 55
125
7550
35
CLEAN IMPORTED SAND LAYER
COMPACTED TO 100% AASHTO.
DPC & WEEP HOLES
TO ARCHITECT'S DETAILS
ALL FOUNDATION PLINTH WALLS
TO BE 14MPa LOAD BEARING MASONRY
WITH BRICK FORCE EVERY COURSE & WALL TIES
@400mm c/c EVERY SECOND COURSE
UP TO GROUND FLOOR SLAB LEVEL
10 x 10mm POLYURETHANE
SEALANT + 10mm JOINTEX
375 MICRON DPM
CLASS 15/19 CONCRETE
CONTINUOUS BRICK FORCE EVERY
COURSE WITH 400mm LAPS
IMPORTED CLEAN SAND LAYER
COMPACTED TO 100% AASHTO.
IN-SITU SAND MATERIAL
COMPACTED TO
MIN. 95% MOD AASHTO.
280mm WIDE 14MPa
MASONRY WALL
110mm WIDE 14MPa
NON-LOAD BEARING
MASONRY WALL
MESH REF
200
700
125 450 125
50
SURFACE BED NOTE:
125mm THK 30MPa SURFACE BED SLAB
MESH Ref. 245 ON 375 MICRON DPM
ON 200mm CLEAN SAND COMPACTED
TO 100% MOD AASHTO
ON COMPACTED IN-SITU MATERIAL
REINFORCEMENT ESTIMATE
FOOTINGS = 65 kg/m³
RC WALLS = 120 kg/m³
RC COLUMNS = 150 kg/m³
RC BEAMS = 120 kg/m³
RC SLABS = 100 kg/m³
LEGEND
ISOLATION JOINT = I.J
SAW-CUT JOINT = S.J
EXPANSION JOINT = E.J
CONSTRUCTION JOINT = C.J
ABBREVIATIONS:
TOS = TOP OF STEEL
TOC = TOP OF CONCRETE
TOW = TOP OF WALL
U/S = UNDERSIDE
COL = STEEL COLUMN
NGL = NEAR GROUND LEVEL
NOTE:
ALLOWANCE SHOULD BE MADE FOR
DEWATERING OF THE TRENCHES
DURING CONSTRUCTION
IMPORTED G5 MATERIAL
COMPACTED TO 95% MOD AASTHO
IN 150mm LAYERS
500
1000
WALL / COLUMN
NGL
RC FOOTING / BASE
WIDTH
1.5 x WIDTH
35°
CONSULTING ENGINEERS
A1
REVISION:DRAWING NO:
SCALE:
NWE RESPONSIBLE PERSON
APPROVED
CLIENT:
RESPONSIBLE PERSON
ISSUED FOR:
DRAWN
DESIGN
SHEET SIZE:DATE:
SIGNATURE + ECSA DETAILS DATE
PROJECT NAME:
DRAWING TITLE:
1st FLOOR PLATTEKLOOF HOUSE I TYGERBERG OFFICE PARK163 UYS KRIGE DRIVE I PLATTEKLOOF I SOUTH AFRICA
P.O. BOX 5263 I TYGER VALLEY I 7536TEL. (+27) 21 914 2264
E-MAIL: [email protected] I WEB: www.nweng.co.za
SPECIAL NOTES
COPYRIGHT RESERVED
THE COPYRIGHT OF THIS DRAWING IS VESTED IN NWE AND IT MAY NOT BE
REPRODUCED IN WHOLE OR PART, ISSUED OR USED FOR ANY PURPOSE OTHER
THAN WHAT IT WAS ORIGINALLY INTENDED FOR WITHOUT THE EXPRESS
PERMISSION OF THE COPYRIGHT HOLDERS.
CONFIRMATION OF DIMENSIONS
WORK TO FIGURED DIMENSIONS ONLY. ALL DIMENSIONS , LEVELS AND CO-
ORDINATES TO BE CHECKED AND CONFIRMED ON SITE WITH THE ENGINEER
BEFORE CONSTRUCTION COMMENCES. DIMENSIONS ARE NOT TO BE SCALED FROM
THIS DRAWING. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL
RELEVANT ARCHITECT's AND NWE DRAWINGS AND SPECIFICATIONS.
As indicated
A
M.STEYN
C. NORTJE
C. DE JAGER 2020.10.16
2020.10.16
2020.10.16
M.STEYN 2020.10.16
20005-SANSA- S-001
SANSASPACE WEATHER CENTRE
GUEST ACCOMMODATIONFOUNDATION & SURFACE BED LAYOUT
INFORMATION
SCALE: 1 : 65
FOUNDATION LAYOUT
REV DESCRIPTION BY DATE
A ISSUED FOR INFORMATION CN 2020.10.16
SCALE: 1 : 65
SURFACE BED LAYOUT
SCALE: 1 : 5
TYPICAL SAW-CUT JOINT (S.C.J.)
SCALE: 1 : 10
TYPICAL FLOOR ISOLATION JOINT DETAIL (I.J)
SCALE: 1 : 10
TYPICAL SURFACE BED THICKENING
SCALE: 1 : 25
TYPICAL GROUND WORKS BELOW ALL FOOTINGS
![Page 8: C:UsersCharlDesktopIssue FolderSANSASWC - Sheet - 000 - … · 2020. 11. 13. · • Beam sides, walls & unloaded columns. 1 day ... • The contractor to submit in writing his proposed](https://reader033.vdocuments.site/reader033/viewer/2022060816/60949a7859caf93fc420eac2/html5/thumbnails/8.jpg)
0
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
IN-SITU FOUNDING MATERIAL
TO BE INSPECTED AND APPROVED
BY STRUCTURAL ENGINEER
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
I.J I.J I.J I.J I.J I.J I.J I.J
7503242750337275033727504030750
280 WIDE 14MPa
MASONRY WALL230 WIDE 14MPa
MASONRY WALL
280 WIDE 14MPa
MASONRY WALL230 WIDE 14MPa
MASONRY WALL
230 WIDE 14MPa
MASONRY WALL
TIMBER ROOF AND WATER PROOFING
TO ARCHITECT'S DESIGN & SPECIFICATION
TIMBER ROOF AND WATER PROOFING
TO ARCHITECT'S DESIGN & SPECIFICATION
TIMBER ROOF AND WATER PROOFING
TO ARCHITECT'S DESIGN & SPECIFICATION
0
125mm thk SURFACE BED SLAB
WITH MESH REF. 245
IN-SITU FOUNDING MATERIAL
TO BE INSPECTED AND APPROVED
BY STRUCTURAL ENGINEER
750 4620 750 505 750 3530 750
150mm thk EXPOSED
AGGREGATE SLAB WITH MESH
REF. 193 - OVERCAST 3mm AND
GRIND DOWN TO ARCHITECT'S
SEC.
250x250mm
EDGE THICKENING
125mm thk SURFACE BED SLAB
WITH MESH REF. 245250x250mm
EDGE THICKENING
280 WIDE 14MPa
MASONRY WALL
I.JI.J I.J I.J I.J I.J I.J I.J
230 WIDE 14MPa
MASONRY WALL
TIMBER ROOF AND WATER PROOFING
TO ARCHITECT'S DESIGN & SPECIFICATION
TIMBER ROOF AND WATER PROOFING
TO ARCHITECT'S DESIGN & SPECIFICATION
CONSULTING ENGINEERS
A1
REVISION:DRAWING NO:
SCALE:
NWE RESPONSIBLE PERSON
APPROVED
CLIENT:
RESPONSIBLE PERSON
ISSUED FOR:
DRAWN
DESIGN
SHEET SIZE:DATE:
SIGNATURE + ECSA DETAILS DATE
PROJECT NAME:
DRAWING TITLE:
1st FLOOR PLATTEKLOOF HOUSE I TYGERBERG OFFICE PARK163 UYS KRIGE DRIVE I PLATTEKLOOF I SOUTH AFRICA
P.O. BOX 5263 I TYGER VALLEY I 7536TEL. (+27) 21 914 2264
E-MAIL: [email protected] I WEB: www.nweng.co.za
SPECIAL NOTES
COPYRIGHT RESERVED
THE COPYRIGHT OF THIS DRAWING IS VESTED IN NWE AND IT MAY NOT BE
REPRODUCED IN WHOLE OR PART, ISSUED OR USED FOR ANY PURPOSE OTHER
THAN WHAT IT WAS ORIGINALLY INTENDED FOR WITHOUT THE EXPRESS
PERMISSION OF THE COPYRIGHT HOLDERS.
CONFIRMATION OF DIMENSIONS
WORK TO FIGURED DIMENSIONS ONLY. ALL DIMENSIONS , LEVELS AND CO-
ORDINATES TO BE CHECKED AND CONFIRMED ON SITE WITH THE ENGINEER
BEFORE CONSTRUCTION COMMENCES. DIMENSIONS ARE NOT TO BE SCALED FROM
THIS DRAWING. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL
RELEVANT ARCHITECT's AND NWE DRAWINGS AND SPECIFICATIONS.
1 : 50
M.STEYN
C. NORTJE
C. DE JAGER 2020.10.16
2020.10.16
2020.10.16
M.STEYN 2020.10.16
20005-SANSA- S-002
SANSA
SPACE WEATHER CENTRE
GUEST ACCOMMODATION
SECTIONS & DETAILS
INFORMATION
REV DESCRIPTION BY DATE
SCALE: 1 : 50
SECTION A
SCALE: 1 : 50
SECTION B
![Page 9: C:UsersCharlDesktopIssue FolderSANSASWC - Sheet - 000 - … · 2020. 11. 13. · • Beam sides, walls & unloaded columns. 1 day ... • The contractor to submit in writing his proposed](https://reader033.vdocuments.site/reader033/viewer/2022060816/60949a7859caf93fc420eac2/html5/thumbnails/9.jpg)
A
S-002
A
S-002
750 18351 750
4280
750
1440
4005
750x250mm RC FOOTING
750x250mm RC FOOTING
750x250mm RC FOOTING
750x250mm RC FOOTING
750x250mm RC FOOTING
750
x250
mm
RC
FO
OT
ING
750
x250
mm
RC
FO
OT
ING
750
x250
mm
RC
FO
OT
ING
750
x250
mm
RC
FO
OT
ING
6540
750
2435
750
690
750
3530
899
899
750
675
2900 1631 4430 1536
2411 4040 636
898
2189
3530
A
S-002
A
S-002
125mm thk SURFACE BED SLAB
WITH MESH REF. 193
I.J
M.J
M.J
M.JM.JM.J
I.J
I.J I.J
I.J
I.J
I.J
I.J
I.J
I.J
I.J
I.J
S.J S.J S.J S.J S.J
S.JS.JS.JS.J
S.JS.J S.J S.J
S.JS.J S.J S.J
C.J
BUTTRESS RECESSES
TO EXTEND THE FULL LENGTH
OF THE GABE ENDS
BUTTRESS RECESSES
TO EXTEND THE FULL LENGTH
OF THE GABE ENDS
SURFACE BED NOTE:
125mm THK 30MPa SURFACE BED SLAB
MESH Ref. 245 ON 375 MICRON DPM
ON 200mm CLEAN SAND COMPACTED
TO 100% MOD AASHTO
ON COMPACTED IN-SITU MATERIAL
REINFORCEMENT ESTIMATE
FOOTINGS = 65 kg/m³
RC WALLS = 120 kg/m³
RC COLUMNS = 150 kg/m³
RC BEAMS = 120 kg/m³
RC SLABS = 100 kg/m³
LEGEND
ISOLATION JOINT = I.J
SAW-CUT JOINT = S.J
EXPANSION JOINT = E.J
CONSTRUCTION JOINT = C.J
ABBREVIATIONS:
TOS = TOP OF STEEL
TOC = TOP OF CONCRETE
TOW = TOP OF WALL
U/S = UNDERSIDE
COL = STEEL COLUMN
NGL = NEAR GROUND LEVEL
CONSULTING ENGINEERS
A1
REVISION:DRAWING NO:
SCALE:
NWE RESPONSIBLE PERSON
APPROVED
CLIENT:
RESPONSIBLE PERSON
ISSUED FOR:
DRAWN
DESIGN
SHEET SIZE:DATE:
SIGNATURE + ECSA DETAILS DATE
PROJECT NAME:
DRAWING TITLE:
1st FLOOR PLATTEKLOOF HOUSE I TYGERBERG OFFICE PARK163 UYS KRIGE DRIVE I PLATTEKLOOF I SOUTH AFRICA
P.O. BOX 5263 I TYGER VALLEY I 7536TEL. (+27) 21 914 2264
E-MAIL: [email protected] I WEB: www.nweng.co.za
SPECIAL NOTES
COPYRIGHT RESERVED
THE COPYRIGHT OF THIS DRAWING IS VESTED IN NWE AND IT MAY NOT BE
REPRODUCED IN WHOLE OR PART, ISSUED OR USED FOR ANY PURPOSE OTHER
THAN WHAT IT WAS ORIGINALLY INTENDED FOR WITHOUT THE EXPRESS
PERMISSION OF THE COPYRIGHT HOLDERS.
CONFIRMATION OF DIMENSIONS
WORK TO FIGURED DIMENSIONS ONLY. ALL DIMENSIONS , LEVELS AND CO-
ORDINATES TO BE CHECKED AND CONFIRMED ON SITE WITH THE ENGINEER
BEFORE CONSTRUCTION COMMENCES. DIMENSIONS ARE NOT TO BE SCALED FROM
THIS DRAWING. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL
RELEVANT ARCHITECT's AND NWE DRAWINGS AND SPECIFICATIONS.
As indicated
A
M.STEYN
C.NORTJE
C.DE JAGER 2020.10.16
2020.10.16
2020.10.16
M.STEYN 2020.10.16
20005-SANSA- S-001
SANSA
SPACE WEATHER CENTRE
STUDENT ACCOMMODATION
FOUNDATION & SURFACE BED LAYOUT
INFORMATION
REV DESCRIPTION BY DATE
A ISSUED FOR INFORMATION CN 2020.10.16
SCALE: 1 : 50
FOUNDATION LAYOUT
SCALE: 1 : 50
SURFACE BED LAYOUT
![Page 10: C:UsersCharlDesktopIssue FolderSANSASWC - Sheet - 000 - … · 2020. 11. 13. · • Beam sides, walls & unloaded columns. 1 day ... • The contractor to submit in writing his proposed](https://reader033.vdocuments.site/reader033/viewer/2022060816/60949a7859caf93fc420eac2/html5/thumbnails/10.jpg)
0
2814
125mm thk SURFACE BED SLAB
WITH MESH REF. 193
IN-SITU FOUNDING MATERIAL
TO BE INSPECTED AND APPROVED
BY STRUCTURAL ENGINEER
I.J I.J I.J I.J
750 5710 750 3030 750
280 WIDE 14MPa
MASONRY WALL
125mm thk SURFACE BED SLAB
WITH MESH REF. 193
230 WIDE 14MPa
MASONRY WALL
110 WIDE 15MPa
MASONRY WALL
TIMBER ROOF AND WATER
PROOFING
TO ARCHITECT'S DESIGN &
SPECIFICATION
5294
2480
2814
25°
10
10mm JOINTEX WITH
10x10mm GREY POLISULPHIDE
JOINT SEALANT ON
BOTH SIDES OF JOINT.
600
NEW WALL
FASTEN STRIPS WITH MINIMUM
8mm NAIL PLUGS. NO SHOT FIXING.
ALL HOLES TO BE PRE-DRILLED TO
NEATLY FINISHED VERTICAL FACE
OF EXISTING WALLS.
TWO GALVANISED HOOP IRON STRIPS
(ONE FOR 110mm WALLS)
600mm LONG BEND IN L SHAPE
EVERY 4TH BRICK COURSE
BUILT IN THROUGH THE JOINT.
GALVANISED BUTTERFLY TIES
IN EVERY 2nd LAYER OF
BRICKWORK
EXISTING WALL
MESH REF. 245
NOT CONTINUOUS
6wd x 35dp JOINT MUST BE CUT WITHIN 48
HOURS OF CASTING CONCRETE & INSERT
FLEXIBLE JOINT FILLER+SEALANT.
55 55
125
7550
35
CLEAN IMPORTED SAND LAYER
COMPACTED TO 100% AASHTO.
DPC & WEEP HOLES
TO ARCHITECT'S DETAILS
ALL FOUNDATION PLINTH WALLS
TO BE 14MPa LOAD BEARING MASONRY
WITH BRICK FORCE EVERY COURSE & WALL TIES
@400mm c/c EVERY SECOND COURSE
UP TO GROUND FLOOR SLAB LEVEL
10 x 10mm POLYURETHANE
SEALANT + 10mm JOINTEX
375 MICRON DPM
CLASS 15/19 CONCRETE
CONTINUOUS BRICK FORCE EVERY
COURSE WITH 400mm LAPS
IMPORTED CLEAN SAND LAYER
COMPACTED TO 100% AASHTO.
IN-SITU SAND MATERIAL
COMPACTED TO
MIN. 95% MOD AASHTO.
270
270mm WIDE 14MPa
MASONRY WALL
110mm WIDE 14MPa
NON-LOAD BEARING MASONRY
WALL
MESH REF
200
700
125 450 125
50
CHIP AND ROUGHEN EXISTING FACE OF
STRIP FOOTING/BASE
Y12 BARS 400mm LONG DOWELED
EVERY 200mm c/c 200mm DEEP INTO
EXISTING STRIP FOOTING USING ABE
EPIDERMIX 396 OR SIMILAR APPROVED
EQ
EQ
200 200
45°
NEW STRIP FOOTING
APPLY GREASE AND WRAP
WITH ROOFING FELT TO ACT
AS BOND BREAKER
COAT SIDE OF EXISTING RC
SLAB WITH BITUMEN PAINT TO
ACT AS A BOND BREAKER
200 500
NEW RC SLAB
REINFORCEMENT
AS PER SCHEDULE
EXISTING RC SLAB
Y12 DOWELS 700mm LONG IN 12mm ∅
HOLES
@ 200 c/c 200mm DEEP INTO EXISTING
RC SLAB USING ABE EPIDERMIX 396
OR SIMILAR APPROVED
NOTE:
ALLOWANCE SHOULD BE MADE FOR
DEWATERING OF THE TRENCHES
DURING CONSTRUCTION
IMPORTED G5 MATERIAL
COMPACTED TO 95% MOD AASTHO
IN 150mm LAYERS
500
1000
WALL / COLUMN
NGL
RC FOOTING / BASE
WIDTH
1.5 x WIDTH
35°
CONSULTING ENGINEERS
A1
REVISION:DRAWING NO:
SCALE:
NWE RESPONSIBLE PERSON
APPROVED
CLIENT:
RESPONSIBLE PERSON
ISSUED FOR:
DRAWN
DESIGN
SHEET SIZE:DATE:
SIGNATURE + ECSA DETAILS DATE
PROJECT NAME:
DRAWING TITLE:
1st FLOOR PLATTEKLOOF HOUSE I TYGERBERG OFFICE PARK163 UYS KRIGE DRIVE I PLATTEKLOOF I SOUTH AFRICA
P.O. BOX 5263 I TYGER VALLEY I 7536TEL. (+27) 21 914 2264
E-MAIL: [email protected] I WEB: www.nweng.co.za
SPECIAL NOTES
COPYRIGHT RESERVED
THE COPYRIGHT OF THIS DRAWING IS VESTED IN NWE AND IT MAY NOT BE
REPRODUCED IN WHOLE OR PART, ISSUED OR USED FOR ANY PURPOSE OTHER
THAN WHAT IT WAS ORIGINALLY INTENDED FOR WITHOUT THE EXPRESS
PERMISSION OF THE COPYRIGHT HOLDERS.
CONFIRMATION OF DIMENSIONS
WORK TO FIGURED DIMENSIONS ONLY. ALL DIMENSIONS , LEVELS AND CO-
ORDINATES TO BE CHECKED AND CONFIRMED ON SITE WITH THE ENGINEER
BEFORE CONSTRUCTION COMMENCES. DIMENSIONS ARE NOT TO BE SCALED FROM
THIS DRAWING. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL
RELEVANT ARCHITECT's AND NWE DRAWINGS AND SPECIFICATIONS.
As indicated
A
M.STEYN
C.NORTJE
C.DE JAGER 2020.10.16
2020.10.16
2020.10.16
M.STEYN 2020.10.16
20005-SANSA- S-002
SANSASPACE WEATHER CENTRE
STUDENT ACCOMMODATIONSECTIONS AND DETAILS
INFORMATION
REV DESCRIPTION BY DATE
A ISSUED FOR INFORMATION CN 2020.10.16
SCALE: 1 : 50
SECTION A
SCALE: 1 : 10
MOVEMENT JOINT (M.J) BETWEEN
NEW AND EXISTING WALL
SCALE: 1 : 5
TYPICAL SAW-CUT JOINT (S.C.J.)
SCALE: 1 : 10
TYPICAL FLOOR ISOLATION JOINT DETAIL (I.J)SCALE: 1 : 10
TYPICAL SURFACE BED THICKENING
SCALE: 1 : 10
CONNECTION DETAIL
BETWEEN NEW & EXISTING STRIP FOOTINGS
SCALE: 1 : 10
TYPICAL
CONSTRUCTION JOINT (C.J)
SCALE: 1 : 25
TYPICAL GROUND WORKS BELOW ALL FOOTINGS