currentratings currentratings *attention* sure 49s are no
TRANSCRIPT
Model Output Torque Electrical Speed of Spring Speed Duty Cycle Rating Duty Cycle RatingInch Pounds (N.m) Operation — 60 Hz. (50 Hz.) of Operation 115 VAC 220 VAC
Sure 25-5 300 (34) 5 seconds/90° 2 seconds/90° 50% 50%)1()1()°09/sdnoces 6(
Sure 25-10 300 (34) 10 seconds/90° 2 seconds/90° 50% 50%)2()2()°09/sdnoces 21(
Sure 24-10 300 (34) 10 seconds/90° 2 seconds/90° 25% 25%)1()1()°09/sdnoces 21(
Sure 49-5 600 (68) 5 seconds/90° 2 seconds/90° 25% 25%)1()1()°09/sdnoces 6(
Sure 49-15 600 (68) 15 seconds/90° 2 seconds/90° 25% 25%)1()1()°09/sdnoces 81(
Sure 49-30 600 (68) 30 seconds/90° 2 seconds/90° 50% 50%)2()2()°09/sdnoces 53(
Sure 100-10 1,200 (136) 10 seconds/90° 5 seconds/90° 25% 25%)1()1()°09/sdnoces 21(
Sure 100-30 1,200 (136) 30 seconds/90° 7 seconds/90° 50% 50%)2()2()°09/sdnoces 53(
115 & 230 VAC, 1 Phase, 50/60 Hz.
SUR
EPO
WR
Current Ratings Current Ratings115 VAC 220 VAC
N.L.A.* L.R.A.* N.L.A.* L.R.A.*
1.40 2.15 CF** CF**
1.00 1.55 CF** CF**
.70 1.05 .45 .65
1.10 1.80 1.00 1.20
.55 1.55 .35 .90
.65 .70 .30 .35
1.90 2.90 .90 1.35
.65 .95 .35 .45
* (N.L.A.) — No Load Ampere (L.R.A.) — Locked Rotor Ampere (1) — Open/Close Service (2) — Open/Close or Modulating Service** (CF) — Consult Factory
Mounting Geometry — Bottom View
SURE 24/25
SURE 49
SURE 100
* (N.L.A.) — No Load Ampere (L.R.A.) — Locked Rotor Ampere (1) — Open/Close Service (2) — Open/Close or Modulating Service** (CF) — Consult Factory + — Approximate, Based on Load
Model Output Torque Electrical Speed of Spring Speed Duty Cycle Rating Duty Cycle RatingInch Pounds (N.m) Operation — 60 Hz. (50 Hz.) of Operation 115 VAC 220 VAC
Sure 150-15 1,800 (204) 15 seconds/90° 5 seconds/90° 25% 25%(18 seconds/90°) (max) + (1), (2) (1), (2)
Current Ratings Current Ratings115 VAC 220 VAC
N.L.A.* L.R.A.* N.L.A.* L.R.A.*
1.90 2.90 .90 1.35
yrtnE tiudnoCyrtnE tiudnoC3/8 - 16 UNC x .625” DeepTyp. 4 places located on a 2.756 D.B.C.
1.102 Dia. x 1.38 DP.
1.240
0.315 x 0.276 [8mm x 7mm] Key Typ. 3 places
nruteR gnirpS WCnruteR gnirpS WCC
4.00 Dia.
4
Bore Depth – 1.50"
2.75"
.135"
Notes
1. Direction of rotation is based on viewing actuator from top.
2. Actuator shown in power fail position.
3. Two keys are recommended for driving device.
4. Actuator suitable for mounting in any orientation.
SURE 150
Class I, Group C and D, Class II, Group E, F and G, Class III
Ex d IIB Gb, Ex tb IIIC T85 Db IP 66/67;
Class I, Zone 1, AEx d IIB. Zone 21, AEx tD, T85
Enclosure Types 4/4X & 6; Ambient Rating: -40°C to +65°C
Model
Input Volt-age 1-Phase,
50/60 Hz.
Output Torque Electrical Speed of
Operation 90° Revolution
Spring Speed of Operation 90° Revolution~
Duty Cycle Rating ** (22.5° C)
Current Rating
N.L.A. F.L.A. L.R.A.
Sure 65-10 120 VAC 780 lb. in (88 N-m) 10 Seconds 3 Seconds 45% 1.10 A 1.60 A 1.90 A
Sure 65-10 240 VAC 780 lb. in (88 N-m) 10 Seconds 3 Seconds 45% 0.80 A 0.85 A 0.98 A
Sure 65-30 120 VAC 780 lb. in (88 N-m) 30 Seconds 7 Seconds 75% 0.52 A 0.64 A 0.89 A
Sure 65-30 240 VAC 780 lb. in (88 N-m) 30 Seconds 7 Seconds 75% 0.27 A 0.32 A 0.44 A
(F.L.A.) – Full Load Ampere (N.L.A.) - No Load Ampere (L.R.A.) - Locked Rotor Ampere ~ Approximate, Based on Load -
Weight Without Manual Override [Lb / Kg] - 75/34
A
VIEWSCALE 1 : 16
4X 3/8-16 UNC - 2B .60[15.2]ON 4.016 [102] B.C.
2.84072.12
2X .8722.06
2.25057.15
1.94949.50
CONDUIT ENTRY
SURE 65 OUTPUT DRIVE F10INCH[MM]
HOLES MARKED "X" FOR F10 MOUNTHOLES MARKED "Y" FOR F07 MOUNT
HOLES MARKED "Z" FOR SURE 49 MOUNTING
Z
Z
Z
Z
X
XX
X
Y
Y
Y
Y
4X 5/16-18 UNC-2B .63[16.0]ON 2.76 [70.1] B.C
4X 5/16-18 UNC - 2B .63[16.0]ON 3.18 [80.8] B.C
SURE 65