#1 #2 Previous in Forum: slipring ethernet test Next in Forum: Perhaps ordinary (primary) batteries can be recharged. I was able to . parimalam Active Contributor Join Date: Feb 2009 Posts: 16 High PD value on 13.8KV, 12,5 MW steam turbine generator 02/14/2009 9:24 AM Hi, Good day. This is my first post on this forum. we have one of our 13.8KV, 12.5 MW, turbine alternator having high PD values, some specili says this alternator needs to be rewinded to avoid failure of winding. presently this generator is running on load about 11MW. my question here is, how exactly the results are PD measurements, it is necessary to do rewinding this alternator to avoid unexpected failure??? is the any way one can prolong the life of this alternator having high PD value. I request specilist in this forum to respond to this query as quickl as possible, so that it will be helpful to take decision on this issue. [email protected] , +65 92326838 thanks and best regards K.Parimalam Interested in this topic? By joining CR4 you can "subscribe" to this discussion and receive notification when new comments are added. Join CR4, The Engineer's Place for News and Discussion! Comments rated to be Good Answers: These comments received enough positive ratings to make them "good answers". #5 " Re: High PD value on 13.8KV, 12,5 MW steam turbine generator " by Siswanto on 02/15/2009 12:24 PM (score 2) Comments rated to be "almost" Good Answers: Check out these comments that don't yet have enough votes to be "official" good answers and, if you agree with them, rate them! #8 " Re: High PD value on 13.8KV, 12,5 MW steam turbine generator " by Siswanto on 02/17/2009 8:35 PM (score 1) CJMcGill Guru Join Date: Jul 2008 Location: SoCal USA Posts: 563 Good Answers: 24 Re: High PD value on 13.8KV, 12,5 MW steam turbine generator 02/15/2009 12:18 AM Hi Parimalam, welcome. It has been a few years since I dealt with large motor assessment and repair, and I am surprised that you have not received any posts so far, but I think you would do well to get input from several sources that offer these services professionally. Partial discharge (PD) when identified at high levels, especially when a continuous monitoring has show a dramatic increase in levels, is a very good indicator of serious degradation in the insulation or cracks in the bars etc. Sometimes errors in placing the wedges or flaws in the metals can begin to produce these discharge patterns, and usually serious consequences are pending. Here are a few quick links I found that may help you. discussion information and definition information and a supplier of equipment and services specific to your need Hope you get what information you need in a timely manner. Regards, CJ __________________ I do not 'know it all', but i will admit that I would like to. CJM myn1996 Commentator Join Date: Jan 2009 Location: Philippines Posts: 60 Re: High PD value on 13.8KV, 12,5 MW steam turbine generator 02/15/2009 2:27 AM Parimalam, A high PD reading does not mean that the generator needs rewinding asap. As with all other methods of testing and diagnostics, PD is not only a science but rather it is also an art. For example, Equipment A might show a higher PD value compared to Equipment B. However, experience does not always show that Equipment A failed sooner than Equipment B. In fact Equipment A lasted to its normal lifespan as if its PD value is within normal range. Additionally, was this equipment tested before with PD? If it was tested, what where the results? Compared to the past PD results, is the Home News & Analysis Products & Suppliers Standards Library Reference Library Engineering Community IHS GlobalSpec is now Search Community Community GO CR4 The Engineer's Place for News and Discussion ® Login | Regist

Upload: unifim1102

Post on 27-Sep-2015

254 views

Category:

Documents


7 download

DESCRIPTION

PD, descargas parciales, betwwen, insulation, tanget of delta, thread, high pd of a generator electric of 250 MW is the generator of hydropower

TRANSCRIPT

  • #1

    #2

    PreviousinForum:slipringethernettest NextinForum:Perhapsordinary(primary)batteriescanberecharged.Iwasableto.

    parimalamActiveContributor

    JoinDate:Feb2009Posts:16

    HighPDvalueon13.8KV,12,5MWsteamturbinegenerator02/14/20099:24AM

    Hi,Goodday.Thisismyfirstpostonthisforum.wehaveoneofour13.8KV,12.5MW,turbinealternatorhavinghighPDvalues,somespecilistsaysthisalternatorneedstoberewindedtoavoidfailureofwinding.presentlythisgeneratorisrunningonloadabout11MW.myquestionhereis,howexactlytheresultsarePDmeasurements,itisnecessarytodorewindingthisalternatortoavoidunexpectedfailure???isthereanywayonecanprolongthelifeofthisalternatorhavinghighPDvalue.Irequestspecilistinthisforumtorespondtothisqueryasquicklyaspossible,sothatitwillbehelpfultotakedecisiononthisissue.kparimalam@gmail.com,+6592326838

    thanksandbestregardsK.Parimalam

    Interestedinthistopic?ByjoiningCR4youcan"subscribe"tothisdiscussionandreceivenotificationwhennewcommentsareadded.

    JoinCR4,TheEngineer'sPlaceforNewsandDiscussion!

    CommentsratedtobeGoodAnswers:Thesecommentsreceivedenoughpositiveratingstomakethem"goodanswers".

    #5"Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator"bySiswantoon02/15/200912:24PM(score2)

    Commentsratedtobe"almost"GoodAnswers:Checkoutthesecommentsthatdon'tyethaveenoughvotestobe"official"goodanswersand,ifyouagreewiththem,ratethem!

    #8"Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator"bySiswantoon02/17/20098:35PM(score1)

    CJMcGillGuru

    JoinDate:Jul2008Location:SoCalUSAPosts:563GoodAnswers:24

    Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator02/15/200912:18AM

    HiParimalam,welcome.

    IthasbeenafewyearssinceIdealtwithlargemotorassessmentandrepair,andIamsurprisedthatyouhavenotreceivedanypostssofar,butIthinkyouwoulddowelltogetinputfromseveralsourcesthatoffertheseservicesprofessionally.

    Partialdischarge(PD)whenidentifiedathighlevels,especiallywhenacontinuousmonitoringhasshowadramaticincreaseinlevels,isaverygoodindicatorofseriousdegradationintheinsulationorcracksinthebarsetc.Sometimeserrorsinplacingthewedgesorflawsinthemetalscanbegintoproducethesedischargepatterns,andusuallyseriousconsequencesarepending.

    HereareafewquicklinksIfoundthatmayhelpyou.

    discussioninformationanddefinitioninformationanda

    supplierofequipmentandservicesspecifictoyourneed

    Hopeyougetwhatinformationyouneedinatimelymanner.

    Regards,CJ

    __________________Idonot'knowitall',butiwilladmitthatIwouldliketo.CJM

    myn1996Commentator

    JoinDate:Jan2009Location:PhilippinesPosts:60

    Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator02/15/20092:27AM

    Parimalam,

    AhighPDreadingdoesnotmeanthatthegeneratorneedsrewindingasap.Aswithallothermethodsoftestinganddiagnostics,PDisnotonlyasciencebutratheritisalsoanart.

    Forexample,EquipmentAmightshowahigherPDvaluecomparedtoEquipmentB.However,experiencedoesnotalwaysshowthatEquipmentAfailedsoonerthanEquipmentB.InfactEquipmentAlastedtoitsnormallifespanasifitsPDvalueiswithinnormalrange.

    Additionally,wasthisequipmenttestedbeforewithPD?Ifitwastested,whatwheretheresults?ComparedtothepastPDresults,isthe

    Home News&AnalysisProducts&Suppliers

    StandardsLibrary

    ReferenceLibrary

    EngineeringCommunity

    IHSGlobalSpecisnow

    SearchCommunityCommunity GO

    CR4TheEngineer'sPlaceforNewsandDiscussion Login|Register

  • #4Inreplyto#2

    #6Inreplyto#4

    #3

    #5

    GoodAnswers:4 presentPDvaluetoohigh?Istherateofincreaseacauseofalarm?

    Now,thisiswheretheexperienceofthetestingengineercomesin.HistoricalPDdatawouldgreatlyhelpinanalyzingthepresentone.Awisetestingengineerwouldnotdependononlyjustonetestingmethod.Weretheretestsperformedonthisgeneratorbyyourspecialist?Whatarethesetests?Whatdidtheresultsimply?

    AdditionaltestishighlyrecommendedtoconfirmthePDfindings.AnFDS(frequencydomainspectroscopy)orDFR(dielectricfrequencyresponse)ifyouwanttheotherterminology,isstronglyrecommendedforthissituation.

    __________________Patriotismisthelastrefugeofscoundrels

    parimalamActiveContributor

    JoinDate:Feb2009Posts:16

    Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator02/15/20099:44AM

    DearCJMcGillPoweruser,myn1996Associate,InstruformParticipant,

    Ithankallofyoufortakingtimeandprovidingguideline,andIamveryhappytoheartheresponsesandnowIwillfurtherexploreasperyourrecommendationsandalsotolookforthetestsuchasFDS(frequencydomainspectroscopy)orDFR(dielectricfrequencyresponse).canyoupleaseadvicemethebestmethodforPDmeasurement,asofnowwehavemeasuredwithonlinePDmeasurementonlyonceusingtoshibaequipmentandusedinternalsinglewindingtemperatureresistorasasensingelementforthistest.AlsowefoundlotsofwhitepowderonrunningturbinegeneratorandthiswhitepowderbecauseofPDactivityisitnot??.willCO2cleaningonrunninggeneratortoremovethesewhitepowderisnecessary,supposeweuseCO2cleaningisthereanychancethatwemaydamageinsulationfurtherleadingtoPD???advicerequired.

    Thanksandbestregards

    K.Parimalam

    CJMcGillGuru

    JoinDate:Jul2008Location:SoCalUSAPosts:563GoodAnswers:24

    Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator02/15/20091:34PM

    BynowyouhavereadtheexcellentinformationfromSiswanto,withgreatdetailedphotos.(GA)

    Inoticedthementionofwhitepowderspecificallyinconnectionwithgreasewhenloosetiesontheleadswerefound.

    MyinstinctsleadmetorecognizethatthispowderwillhelpintheidentificationoflocationsaffectedbythePD,andcleaningmayerasetheevidence.Asfarascleaning,thatwoulddependonthepowderpropertiesandwhetherthepowderitselfwillcausefurtherproblems.

    Iwillleavethefurtherdiscussionaboutthepowdertomoreexperiencedindividualswithspecificknowledge

    __________________Idonot'knowitall',butiwilladmitthatIwouldliketo.CJM

    InstruformAssociate

    JoinDate:Feb2009Posts:35

    Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator02/15/20096:53AM

    Ihaveover40yearsofPDtestingexperienceandwouldsupportwhatMyn1996&CJMcGillrecommend.PDlimitvaluestandardsaresetfornewmachinesandhaveonlybeensetinthelast5yearsaftersome20yearsoftrial.Forlifeexpectancyyouneedtoascertainthechangefrompreviousresults/reportstoevaluateyoursituation.Thatiswhywhentestingforservicelifeexpectancytheinception,extinctionvoltagesandthedischargeshapeareimportantreadings&observationsandtogetsomeconsistencythesameprofessional&experiencedtestershouldbeusedonaregularbasisifpossible.UnfortunatelyPDtestingisstillbothascience&aseatofthepantsfeel.Makepreparationsbyallmeans,havecoilsavailabletolimityouroutagetime,butdon'tpanicyoucouldstillhaveyearsofservicefromthemachine.

    SiswantoCommentator

    JoinDate:Mar2008Location:JAKARTA.INDONESIAPosts:73GoodAnswers:15

    Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator02/15/200912:24PM

    Dearparimalam:

    Welcometothisforum

    ourcolleagueCJMcGillandmynhasgiveagoodsharing,IwouldliketotryoffersolutionbasedonmyexperiencesduringrepairofGeneratorsinINDONESIA.

    Since10yearsagoIjustfound2casesofPDFailureonGenerators,duetoitsnotdetectedandsettledatearlierstage.

    HaveyoutestPDbefore?ifyes,plscomparedtheresulthowfastthePDlevelacceleration,andyouknowwhereisthePDactivitieslocation?

    Attheendwinding?

    intheslot?

    attheoverhang?

    intheinternalwindinginsulation?

    IfPDactivitieshasfoundattheendwinding,slotandoverhang,itslittlebiteasytorepair,butiffoundwithinintheinsulationduetovoidsitsverydifficultandalmostimpossibletorepairexceptrewinding.

    CanyoutoldmethePDlevelandlocation?whichbarsthathavehighPDlevel?

    Followingarticlemaycanhelpyoutomadeadecision.Plsforgivemeifitsnotsufficientinformationforyou..

    PARTIALDISCHARGEphenomenononElectricmachine

    2

  • Coronaactivity

    Coronaisdefineastheionizationofgaswhenexposedtoanintenseelectricfield,thedischargehaveawiderangeoffrequencies[40kHzto100MHz].

    PartialDischarge(PD)inthelargegeneratorapplication,isusuallyassociatedwiththehighvoltagestatorconductorbars.

    Coronaactivityintherotatingmachine:

    SurfacedischargeduetoCoronaatendwinding(EndwindingDischarge)

    InternaldischargeduetoCoronaatinsideoftheinsulation(voidsordelamination)

    SlotdischargeCoronaatgroundwallinsulationresultingfromlosscontactbetweenbarandcore.(damagedonthesemiconductivecoatingonthestatorbar)

    SurfacedischargeduetoCoronaatoverhangofwindingresultingfrombarvibration

    Aproblemcommontomachineswiththermoplasticinsulationisthatthenormalthermalcyclingiscausescoilmovementintheslot,tendtogeneratecrackwithinthegroundwallinsulation.

    Atapeseparationisaseparationoftapecoveringthewallinsulationofthecoilduetoaxialexpansionandcontractionoftheconductorsandtheopposingforcesoftheslotappliedtothewallinsulation.

    Insomecasesonlythearmortapeisseparated,inothercasesthemicatapecomprisingthegroundwallinsulationisalsoaffected,whenthisoccurafewlayermaybeaffectedandthewholetapewillmovecreating"aneck"inthecoil.

    FollowingaretypicalinsulationfailureduetoPDactivitiesbasedonoursiterepairexperiencesonGeneratorsinINDONESIA.basedonourexperiencessince10yearsago,wefound2caseswindingbreakdownduetoundetectedPDactivitiesonstatorwindinggenerators,wedomuchtorepairofsemiconductivecoatingandstressgradingtominimizeandpreventthePDonthewinding

    A.PDInspection,

  • PDinspectiononAlstom87.5MVAafter18topbarscompletedremovedfromslot

    Coronaprobemeasurements

    Coronaprobetestingcanpinpointpartialdischargelocationineachslot.Itsupplementsonline/offlinepartialdischargetestsbypreciselylocatingpartialdischargetoaparticularcoiloraspot.ThecoronaprobecanalsobeusedasatestingtooltomeasurelevelsofPDactivity.Coronaprobetestingcanbeperformedeitherwiththerotorinoroutofthemachine

    EndoscopicPDVisualinspectiononAlstom87.5MVA

    PDVisualinspectionbyUVcameraon6.6KVMotors(figtakenfromOfil)

    WindingInspection

    FollowingaretypicalrootcauseofPDactivities

  • StatorwedgelooseonGEgenerator49,5MVA

    WhenStatorwedgehasloose,followingpartsmayaffectedloosetoduetomovement.

  • FillerslipoutonMitsubishiGenerator125MVA.

    Endwindingmovementduetostatorwedgesloose(notsufficienttokeepstatorcoilstayinplace)onGEGenerator237MVA

  • Loosesupportduetovibration

  • Typicalwindinginstallmentintheslot

    Whenties,wedge,supporthasloose,statorbarswillmovementanddamaged.

  • HVCoil

    Preventiveaction

    WhenwedgewasfoundlooseandtheaccelerationofPDactivitiesInthewindinghasincreasewithcomparedtotheprevioustestorthePDtesthasoverorclosetothemaxthreshold,followinginspectionmustbedonetomadeadecisiontorepairorreplace.

    1Checkthewedgetightness'foundloosemorethan30%mustbereplaced,concerntoreplacealsoforradialsprings,improvethematerials

    2Checkthecoilblocking,ties,foundloose,break,toodry,missing,mustberepaired

    3Checkthewindingsupport,surgerings,boltsetc,foundloosemustberepairedorretight

    4PDwasfoundhighonthewinding/

    IfPDactivitiescausedbyloosecontactbetweencoilbarstoslotwalls,dorepairthesemiconductivebycoatingorsemicondpainting

    IfPDactivitiescausedbylooseorstressgradingdeteriorationatendwindingportion,dorepairstressgradingbycoating

  • IfPDactivitiescausedbyinternalinsulationvoid,wecan'tdonothingexceptrewinding

    Followingarerepairreferenceswhenwerepaironlargegeneratorupto250MVA(basedonourexperiences).

    Replaceofstatorwedgeandradialspring

    TakenfromIRISEngineering

    Repairblockingcoil,ties,support,etciffoundloose,defect

  • Injectthesideripplebysemiconductivepainting

    Suggestionsolutionforyourproblems

    Followingmysuggestion

    1. IdentifiedthePDsources,trytorepairofsemiconductivecoatingintheslot,beforetorepairallstatorwedges,ripple(topifany),fillersmustberemovedfirst.

    2. DoretestPDbyofflinemethod,andprovidewithbartobarscanningorbyprobetoidentifiedwhichcoilsarehavehighPDlevelwithvoltageUn/1.73(linevoltagetoground)

    3. Inspectallwindingregion,insideslot,endwindingetc,useendoscopic(borescope)toinspectwindingintheslot4. Dotestinsulationtangentdelta,withvoltagetestsameforoflinePDtest.5. Replaceallstatorwedges,toprippleIfprovide)andflatfillers,iftheexistingarenotprovidebytopripple,andifthespaceis

    possibleenoughtoaccommodateoftopspring,providethethespring,andimprovethematerialfromclassBtoclassF,NEMAG11isrecommended

    6. Retightallwindingsupportandreplacethewindingtiesiffoundloose,missing,broken,etc7. Repairtheendwindingregioniffoundstressgradingdefectorreinsulatetheendwindingiffounddelaminationontheseareaand

    applieditbystressgradingpaintafterreinsulation.8. Cleanupallwindingareas,9. DryoutthestatorwindingbyusingDCsupply,keepthetemperatureround8090degreecelround24hrsormoreifmoistureis

    stillpresence10. Recoatingbyvarnishpainting11. Whengeneratorrunning,ifequipmentavailable,dotestPDonline.12. Recordallthetestresultasbasedline

    GoodLuck

    __________________LOVEFORUMANDDISCUSSION

    NomoreGoodAnswers. Gotofirst"Almost"GoodAnswer

  • #7Inreplyto#5

    #8Inreplyto#7

    parimalamActiveContributor

    JoinDate:Feb2009Posts:16

    Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator02/17/200910:59AM

    HitoAll,

    ItissimplygreatandInevergetsuchvaluableinformationanywerebutinthisforumitisamazingandIverymuchthankfultoallofyou.Iamgoingthroughalltheinformationandsuggestionandwilltaketimeformetounderstandfully.inthemeantimeIwillreplyfewanswerstothequestionspostedhere.

    thisplant2x12.5MW,13.8KVsteammachines(FSO)runningcontinuouslyforthepast10yearsandnowonealreadyfailedandalsothefailuredamagedthecorelaminationsandendupwiththebigjob,rewindingandlaminationrepairsandthejobisongoingatpresent.Myquestionhereisthereyanywaywecouldhavepreventedcoredamageduetocoilgrounding???intermsoffastswitchingprotectionrelayetc..????

    ThesemachinesnevercheckedforPDandnowonlyafterfailurewehavecheckedtherunningTAandfoundPDvalueisveryhigh(therewasnoearlierreadingforcomparisson).presneltywearerunningthisTAonlywith10%stationload,duetofear.Myquestionhere,runninglessloadwillhavelessPD???,eventhoughvoltageissame??curioustoknowsomesaynochangeinPDasthevoltageisthecreteriaforPDIamthinkinginotherwaybyhavinglowload,IreducethetemperatureandalsovibrationofcoilsomeextendreducedcanrunlongerperiodtocaterthestationloadtillwerepairanotherfailedTA.needadvice.

    CananyonecansuggestonlindPDmetereconomicalmodelbrandforpurchaseinordertokeepitatsiteforfrequentmonitoring

    restinnextpost.

    SiswantoCommentator

    JoinDate:Mar2008Location:JAKARTA.INDONESIAPosts:73GoodAnswers:15

    Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator02/17/20098:35PM

    Dearparimalam

    Asyouknow,PDisassociatedwiththehighvoltagestatorconductorbars,PDwouldbestillproducedwhengeneratorisenergizeevennoload,ofcourseyes,reducedloadwouldbereducedalsotheaccelerationofPD,becauseyouhavereducedalsothevibrationandthermal.

    Mysuggestion,whenyouscheduledtoshutdown,doinspectonyourwinding,

    InspectthePDbyofflinemethod(probetestisrecommended,itsdesignedtocheckandidentifywhichcoilbarsarehavehighPDlevel,soyoucanrepaired,inmyopinionthehighPDlevelinyourwindingiscausedbysemiconductivedeterioration).YoucanalsocheckthePDactivitybyusingendoscopic(borescope),checkthePDviaventholes(airduct)ofwinding

    ProvidealsoTangentDeltatest,isusefultoanalysisofyourwinding

    Statorwedgetightens,looseonthispartswillcreatebigproblemsonyourwinding,suchas:

    oDeteriorationonsemiconductivelayer,duetothestatorbarcoilswillmovemententireslot

    oLooseendwindingblockingandties,itscancreateendwindingdeteriorationoninsulation,electricfieldconcentrationonendofcorecanoccurringwhenstressgradingfailure,mayalsocancreatedelaminationonscarfjoin,scarfjoinisinsulationtapejoinbetweenoverhangtoendwindingarea,thisistheweaknessinsulationjoin.

    oWhenloosewedgeswasfound,itscanalsocreateinsulationvoidsacceleration,whenPDiscausedbythewindingvoids,youcan'tdoanythingtorepair,exceptrewinding

    Note:torepairsemiconductivelayer,usematerialsasbellow:

    Entireslot,use:"coronapainting",i.e.VonRollIsolaproducttypeP8003orequivalent.

    Endwinding,use:"coronapainting",i.e.vonrollisolaproduct,typeP8001orequivalent

    Cleanfirstanddryoutbeforeappliedthesematerials

    oWhenyoufoundstatorwedgesloose,replaceandimprovethematerials,providewithradialspringsifthespaceispossibletoaccommodateit,forwedgematerialyoucanimprovebyNEMAG11materialorequivalent,andforradialspringimprovetoclassF

    RetightorreplacetheendwindingandblockingcoiltiesbyusingbendingtapeclassF,alsoreplaceifyoufoundlooseormissingofblockingcoils,thefunctionofBlockingcoilsareusedtodeterminetheclearancebetweenthecoilsideattheendregion,toeliminate

  • mechanicalstressesarisingcoilmovement,thatwillberesultingcoiltouchingeachotherattheendwinding,Blockingcoilsarealmostmadefromsolidinsulationmaterials(suchastextolite,felt,etc)whichissoakedinresin.Blockingcoilisalwaysheldinplacewithties.Oftensolidseparatortendtolooseafterlongperiodofoperation,inseverecasesitwillfallfromthewinding.

    Inspectalltiesonthesurgeringsupport,ndwindingandsurgeringsaresecuredwithties,aswiththeblockingcoilsties,whenexposedoveralongtimeoperation,tiestendto"dry",becomelooseduetolosevolume,brittle,broken,etcretightorreplaceitbyusingbendingtypeandsoakedwithresin

    Inspecttightensofsupportstructures,foundsludgeorgreasingorwhitepowderisindicateloose,retight.

    Inspectthedustunderwindingclosetocore,extractitandcheckit,foundmetaldustonit,indicatestatorcoreloose,checkthecorelooseness,retighttheboltssupportbasedonmanufacturerspecification,foundbent,brokencoreteeth,repairitandappliedepoxy/resinorRTVonitstopreventorminimizethecorevibration.

    InspectthecorebyusingDigitalELCIDmethod,foundhotspot,repairedassoon,itsmustbedonewhenyouperformrewinding,recordedtheresultasbasedline,doregularlyin5years.

    Corerepairandtest,seethefollowinglink.

    http://cr4.globalspec.com/thread/32530/HowtoRepairaPartialCoreStatorGenerator

    PDInstruments.

    Youcanbrowsingintheinternet,itsmanysuppliercanprovide,orourcolleaguesheremaycanhelpyoutoprovidethetechnicalspecificationandsupplierfortheinstruments.

    PDinstrumentforofflinetest,PDProbemaythecheapest,anditsusefultoquickidentifiedofPDlocation,

    GoodLuck.

    __________________LOVEFORUMANDDISCUSSION

    Nomore"Almost"GoodAnswers.

    RegistertoReply 8commentsBacktotop

    Interestedinthistopic?ByjoiningCR4youcan"subscribe"tothisdiscussionandreceivenotificationwhennewcommentsareadded.

    JoinCR4,TheEngineer'sPlaceforNewsandDiscussion!

    CommentsratedtobeGoodAnswers:Thesecommentsreceivedenoughpositiveratingstomakethem"goodanswers".

    #5"Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator"bySiswantoon02/15/200912:24PM(score2)

    Commentsratedtobe"almost"GoodAnswers:Checkoutthesecommentsthatdon'tyethaveenoughvotestobe"official"goodanswersand,ifyouagreewiththem,ratethem!

    #8"Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator"bySiswantoon02/17/20098:35PM(score1)

  • CopytoClipboardUserswhopostedcomments:CJMcGill(2)Instruform(1)myn1996(1)parimalam(2)Siswanto(2)

    PreviousinForum:slipringethernettest NextinForum:Perhapsordinary(primary)batteriescanberecharged.Iwasableto.Youmightbeinterestedin:ElectricalWindingServices,BevelandMiterGears,WormsandWormGears

    Advertisement

    "Twentyyearsfromnowyouwillbemoredisappointedbythethingsthatyoudidn'tdothanbytheonesyoudiddo.Sothrowoffthebowlines.Sailawayfromthesafeharbor.Catchthetradewindsinyoursails.Explore.Dream.Discover."MarkTwain

    AlltimesaredisplayedinUS/Eastern(EDT)(Registertochangetimezone)

    2015IHS.Allrightsreserved.Reproductioninwholeorinpartwithoutpermissionisprohibited.Theinformationcontainedonthissiteisbyusersforusersandisprovidedforinformationpurposesonlyanddoesnotconstituteadvice.AnyviewsoropinionsexpressedbyusersarepersonaltothemanddonotrepresenttheviewsoropinionsofIHS.Youshouldcheckanyinformationanduseyourownjudgmentorseekexpertadvicebeforedoingornotdoinganythingonthebasisofwhatyoureadhere.IHSdoesnotverifyorwarranttheaccuracyorcompletenessofanyinformationonthissiteand,totheextentpermittedbylaw,IHSshallnotbeliableforanyloss,damageorexpenseincurredbyrelianceonitorforanydealingsyouhavewithusersorotherthirdpartiesthattakeplaceusingorfacilitatedbythissite.