control strategy for a distributed dc power system with renewable energy
TRANSCRIPT
8/7/2019 Control strategy for a distributed DC power system with renewable energy
http://slidepdf.com/reader/full/control-strategy-for-a-distributed-dc-power-system-with-renewable-energy 1/8
Control strategy for a distributed DC power system with renewable energy
Kyohei Kurohane a,*, Akie Uehara a,1, Tomonobu Senjyu a,1, Atsushi Yona a,1, Naomitsu Urasaki a,1,Toshihisa Funabashi b, Chul-Hwan Kim c
a University of the Ryukyus, 1 Senbaru, Nishihara-cho, Nakagami, Okinawa 903-0213, Japanb Meidensha Corporation, 36-2 Nihonbashi-Hakozakicho, Chuo-ku, Tokyo 103-8513, Japanc Sungkyunkwan University and NPT Center, Suwon City 440-746, South Korea
a r t i c l e i n f o
Article history:
Received 31 March 2009
Accepted 25 May 2010
Available online 18 June 2010
Keywords:
DC distribution
Micro-grid
Permanent magnet synchronous generator
Pitch angle control
Fault ride-through (FRT)
a b s t r a c t
This paper deals with a DC-micro-grid with renewable energy. The proposed method is composed of
a gearless wind power generation system, a battery, and DC loads in a DC distribution system. The battery
helps to avoid the DC over-voltages by absorbing the power of the permanent magnet synchronous
generator (PMSG) during line-fault. In addition, the control schemes presented in this paper including
the maximum power point tracking (MPPT) control and a pitch angle control for the gearless wind
turbine generator. By means of the proposed method, high-reliable power can be supplied to the DC
distribution system during the line-fault and stable power supply from the PMSG can be achieved after
line-fault clearing. The effectiveness of the proposed method is examined in a MATLAB/SimulinkÒ
environment.
Ó 2010 Elsevier Ltd. All rights reserved.
1. Introduction
Currently, for the greenhouse gas reduction, introduction of the
renewable energies such as photovoltaics and wind energy is
gaining popularity [1e3]. When these renewable Distributed
Generators (DGs) are connected to the power system, there is
a concern about their harmful effects as most of their power uc-
tuate with weather conditions. Therefore, researchers have been
working on practical application of micro-grids. Micro-grid is
a small-scale power grid that has sources in certain areas and can
supply power to a particular consumer. In the future, not only
hospitals, banks and semiconductor factories [4], but also of ces,
shops and residential houses need high quality power. So, DC
distribution systems are attracting attention in the world.
The DC distribution system has the following advantages over
the AC distribution system: (1) Each power generator connected tothe DC distribution system can easily be operated in coordination
because it controls only the DC bus voltage. (2) When the AC-grid
system has fault conditions, the DC distribution system is discon-
nected from the AC grid, and then it is switched to the stand-alone
operation in which the generated power is supplied to the loads
connected to the DC distribution system. (3) The system cost and
loss can be reduced because only a single AC grid-side inverter unit
is needed.
Usually, a permanent magnet synchronous generator (PMSG) is
used as the wind turbine generator (WTG) in the DC distribution
system. Because PMSG has simple structure and high ef ciency.
For a particular wind speed, there is a specic turbine rotational
speed which generates the maximum power. The maximum power
point tracking (MPPT) for each wind speed increases the energy
generation [5e8]. However, the MPPT control for each wind speed
generates the output power uctuations. The voltage and
frequency uctuations of the power system caused by the output
uctuations of the WTG affect the quality of the supplied electrical
power. Therefore, the introduction of fuel cell and ywheel has
been increasing. They have been proposed to reduce the frequency
and voltage uctuations. However, fuel cells are expensive andywheels have noise and vibration problems.
With the rapid growth of the WTG systems, it is dif cult to
stabilize the operation of the powersystem by disconnecting WTGs
when line-faults. Under the line-fault the dispersed power sources
are disconnected from the power system and it needs much more
time and energy compensating for the power supplyedemand
balance. In addition, with the recovery of the power system,
disconnected WTGs need restart. Thus, the frequency of the power
system rises as many WTGs return to the system. As a counter-
measure, in Europe, the large WTGs are required to remain
connected to the power system under line-fault and supply power
* Corresponding author. Tel.: þ81 98 895 8686; fax: þ81 98 895 8708.
E-mail addresses: [email protected] (K. Kurohane), [email protected]
ryukyu.ac.jp (T. Senjyu), [email protected] (C.-H. Funabashi),
[email protected] (C.-H. Kim).1 Tel.: þ81 98 895 8686; fax: þ81 98 895 8708.
Contents lists available at ScienceDirect
Renewable Energy
j o u r n a l h o m e p a g e : w w w . e l s e v i e r . c o m / l o c a t e / r e n e n e
0960-1481/$ e see front matter Ó 2010 Elsevier Ltd. All rights reserved.
doi:10.1016/j.renene.2010.05.017
Renewable Energy 36 (2011) 42e49
8/7/2019 Control strategy for a distributed DC power system with renewable energy
http://slidepdf.com/reader/full/control-strategy-for-a-distributed-dc-power-system-with-renewable-energy 2/8
to the power system after fault clearing. This requirement is called
fault ride-through (FRT). Moreover, under the line-fault, DC bus
voltage in the DC distribution system experiences the over-voltage.
Therefore, unstable power supply from DC distribution system and
an over-voltage problem of semiconductor devices of the power
converter occur. It is important to solve these problems of the stable
operation for DC distribution system. However, no paper or article
has been presented or published on a micro-grid (or DC-micro-
grid) which solves these problems simultaneously [9e12].
In this paper, stable power supply strategies for DC distribution
system and stable control strategies for PMSG under the line-fault
are proposed. The proposed method uses a battery for the DC
distribution system. Under the line-fault, a chopper circuit is used
to avoid DC bus over-voltage by absorbing energy from the PMSG
and by supplying to the battery. By means of the proposed method,
stable operation of the DC power system under the line-fault
becomes possible, and high-reliable power supply from the grid-
side inverter to the AC grid after the line-fault clearing can
be achieved. The effectiveness of the proposed method is veried
by simulation results under three-line to ground-fault using
MATLAB/SimulinkÒ.
2. DC distribution system conguration
2.1. System conguration
The DC power system used in this paper is shown in Fig. 1. The
wind power generator is a gearless 2 MW permanent magnet
synchronous generator (PMSG). The PMSG has a simple structure
and high ef ciency. In addition, the DC distribution system consists
of a gearless 2 MW PMSG, a grid-side inverter, a 576 Ah battery and
100 kW DC loads. The DC system is connected to a 10 MVA diesel
generator and 5 MW AC loads through the grid-side inverter. Wind
power energy obtained from the windmill is sent to the PMSG. In
order to generate maximum power, rotational speed of the PMSG is
controlled by the PWM converter and the generated power is
leveled by a pitch angle control. Then these power is supplied to the
DC load. The rest of the power is supplied to the AC load through
the grid-side inverter.
Fig. 1. DC power system.
Fig. 2. Windmill output power characteristics. Fig. 3. Pitch angle control system for PMSG.
K. Kurohane et al. / Renewable Energy 36 (2011) 42e49 43
8/7/2019 Control strategy for a distributed DC power system with renewable energy
http://slidepdf.com/reader/full/control-strategy-for-a-distributed-dc-power-system-with-renewable-energy 3/8
2.2. Windmill model
The windmill output power P w and the windmill torque T w are
given by the following equations:
P w ¼1
2C pðl; bÞrpR2V 3w; (1)
T w ¼
1
2lC pðl; bÞrpR3
V 2w; (2)
where V w is thewind speed, r is the air density, R is the radius of the
windmill, C p is the windmill powercoef cient, l¼uwR/V w isthe tip
speed ratio, uw is the angular rotor speed for the windmill and b is
the pitch angle. C p is given by the following equation [13]:
C p ¼ 0:22
116
GÀ 0:4b À 5
expÀ12:5
G ; (3)
where
G ¼1
1lþ0:08b
À 0:035b
3þ1
: (4)
From (1) and (3), the windmill output power characteristics are
depicted in Fig. 2, from which it can be seen that, for any particular
wind speed, there is a rotational speed uopt, which is called the
optimum rotational speed, which generates the maximum power
P max. In this way, the MPPT for each wind speed increases the
energy generation. uopt is calculated by differentiating C p with
respect to uw. Therefore, uopt is approximated by
uopt ¼ 0:2V w À 0:2: (5)
MPPTcontrol is applied when the wind speed V w is less than the
rated wind speed V w, ref ¼ 12 m/s, and then the output uctuations
of PMSG are smoothed by the pitch angle system. The pitch angle is
operated in the following cases. When the wind speed is within
0 V w < 5 m/s, the pitch angle is xed at b¼ 90. When the wind
speed is within 5 V w < 12 m/s (rated wind speed), the pitch angle
is operated so that the power uctuations are reduced. When thewind speed is within 12 V w < 24 m/s, the pitch angle is operated
so that the output power of PMSG becomes the rated power 2 MW.
Fig. 3 shows the pitch angle control system that determines the
pitch angleb, where the output power error e isused asinputof the
PI controller. Actually, the pitch angle control system includes
a hydraulic servo system. The system has nonlinear characteristics,
but can be modeled as rst-order lag system [14]. Therefore, in this
paper, the rst-order lag system is used where the time constant is
1 s. Moreover, the pitch angleb islimited bya limiter within 2e90
and the maximum rate of change is 10/s.
2.3. PMSG model
The mathematical model of PMSG is same as the permanent
magnet synchronous motor (PMSM). The voltage and torqueequations of PMSM in the synchronous reference frame are given
by the following equations:
vd ¼ ðRa þ PLdÞid À ueLqiq; (6)
vq ¼ ueLdid þÀ
Ra þ PLq
Áiq þ ueK ; (7)
T e ¼ pÈ
Kiq þÀ
Ld À Lq
Áidiq
É; (8)
where vd and vq are the dq axis voltages, id and iq are the dq axis
currents, Ra is the stator resistance, Ld and Lq are the dq axis
inductances, ue is the electrical rotational speed, K is the perma-
nent magnetic ux, P is the differential operator, and p is the
number of pole pairs. Power generation starts when the electro-
magnetic torque T e is negative. In addition, the equation of the
motion of PMSG is given by the following equation:
Fig. 4. Model of drive train for wind generator PMSG.
Fig. 5. Model of PMSG.
Table 1
Parameter of PMSG and windmill.
Rated power P ref 2 MW
Rated wind speed V w, ref 12 m/s
Resistance Ra 0.1U
Inductance L 2.0 mH
Number of pole pairs p 80
Field ux K 10.68 V s/rad
Equivalent inertia J eq 8000 kg m2
Rotational damping D 0
Fig. 6. Wind generator-side converter control system.
Fig. 7. AC grid-side inverter control system.
K. Kurohane et al. / Renewable Energy 36 (2011) 42e4944
8/7/2019 Control strategy for a distributed DC power system with renewable energy
http://slidepdf.com/reader/full/control-strategy-for-a-distributed-dc-power-system-with-renewable-energy 4/8
T e ¼ J eqdug
dt þ Dug þ T l; (9)
where D is the rotational damping, J eq (J eq ¼ J g þ J w) is the equivalent
inertia, T l is the loadtorque,andug is themechanicalrotational speed.
The models of the drive train and the PMSG are given in Figs. 4
and 5, respectively. The parameters of the PMSG and the windmill
are shown in Table 1 [8,14].
2.4. Diesel generator and battery model
The diesel generator model consists of a synchronous generator
model with AVR control and GOV control, and the battery model is
designed in MATLAB/SimulinkÒ [15]. The battery model is consid-
ered for battery’s discharge and charge characteristics. In this
paper, we consider a Lithiumeion battery. The state of charge (SOC)
is calculated by the integration of the discharge and charge power
of the battery.
3. Conguration of DC distribution control system
3.1. Control system of power converters
The power converter control systems are shown in Figs. 6 and 7.
Generator-side converter achieves variable speed operation by
controlling rotational speed of the PMSG. On the other hand, grid-
side inverter supplies electrical power and its frequency is
synchronized with the frequency of the power system. Each of the
powerconverters is a standard 3-phase two-level unit, is composed
of six IGBTs and is controlled by the triangle-wave PWM law. In
addition, DC distribution system includes a battery, in order toavoid DC bus over-voltages under line-fault. The control systems
are described below.
3.2. Generator-side converter
The generator-side converter controls the rotational speed of
the PMSG in order to achieve the variable speed operation with the
MPPT control. The vector control scheme is used and is shown in
Fig. 6. The speed control of PMSG is realized on a rotating frame,
where the rotational speed error is used as the input of the speed
controller which produces the q-axis stator current command i1q* .
Generally, the cylindrical pole type synchronous machine is
considered to control the d-axis stator current and i1d
is set to zero.
Therefore, in this paper, the d-axis stator current command i1d* , is
set to zero. The errors between the dq axis current commands, i1d*
Fig. 8. Output power reference system of PMSG.
Fig. 10. DC bus constant voltage control system for fault.
Fig. 9. Battery control system.
K. Kurohane et al. / Renewable Energy 36 (2011) 42e49 45
8/7/2019 Control strategy for a distributed DC power system with renewable energy
http://slidepdf.com/reader/full/control-strategy-for-a-distributed-dc-power-system-with-renewable-energy 5/8
and i1q* , and the actual dq axis currents are used as the inputs of
current controllers. The current controller outputs produce the dq
axis voltage commands v1d* and v1q
* after decoupling. The rotor
position qe, is used the transformation from abc to dq variables and
is calculated from the rotational speed of the PMSG.
3.3. Grid-side inverter
The grid-side inverter is aimed at the constant control of the
DC bus voltage V dc and unity power factor operation. The control
system for the grid-side inverter is shown in Fig. 7. The d-axis
Fig. 11. Simulation results during three-line to ground-fault. (a) Wind speed; (b) Active power of PMSG; (c) Reactive power of PMSG; (d) DC bus voltage; (e) DC load; (f) Terminal
voltage of DC load; (g) Terminal voltage of battery; (h) Output power of battery; (i) State of charge; (j) Active power of AC grid-side inverter; (k) Reactive power of AC grid-side
inverter; (l) Active power of diesel generator; (m) Reactive power of diesel generator; (n) AC load; (o) Terminal voltage of AC load; (p) Pitch angle.
K. Kurohane et al. / Renewable Energy 36 (2011) 42e4946
8/7/2019 Control strategy for a distributed DC power system with renewable energy
http://slidepdf.com/reader/full/control-strategy-for-a-distributed-dc-power-system-with-renewable-energy 6/8
current can control the DC bus voltage V dc, and the q-axis
current can control the reactive power Q i. The DC bus voltage
reference V dc* is set to 3500 V while the reactive power command
Q i* is set to zero for unity power factor operation. The phase
angle qs, for the transformation between abc and dq frame, is
detected from the three phase voltages at the low voltage side of
the grid-side transformer by using the phase-locked loop (PLL).
The angular position of the dq reference frame is controlled by
a feedback loop which regulates the q-axis component to be
zero, where the d-axis component depicts the voltage vector
amplitude and its phase is determined by the output of the
feedback loop.
4. The proposed power leveling control and DC bus voltage
control system
4.1. PMSG output power reference system
The PMSG output power reference P ref in Fig. 3 is determined by
control system as shown in Fig. 8. The operating point to obtain
maximum power for each wind speed is set (wind speed V w (m/s),
rotational speed um (pu)) and expressed as a rst-order function. In
this paper, the rated PMSG power is 2 MWand is set to 1 pu and the
operating points are set to 11 m/s, 0.9 pu and 12 m/s, 1 pu. Conse-
quently, the
rst-order function determines the reference vary
Fig. 11. (continued).
K. Kurohane et al. / Renewable Energy 36 (2011) 42e49 47
8/7/2019 Control strategy for a distributed DC power system with renewable energy
http://slidepdf.com/reader/full/control-strategy-for-a-distributed-dc-power-system-with-renewable-energy 7/8
according to the wind speed. The output of comparator 1 depends
on the comparison of the wind speed V w and the rated wind speed
(12 m/s). The output of comparator 1 is 1 when the wind speed V wis greater than the rated wind speed and is 0 when the wind speed
V w is less than the rated wind speed.Therefore, P ref is obtained from
(10). Here, the rising rate for P ref is restricted by the rate limiter in
order to vary P ref for the wind speed uctuation at the low wind
speed. Consequently, it is possible to reduce the PMSG output
uctuation when wind speed is less than the rated wind speed.
P ref ¼ 0:1848V w À 1:129 ½pu�: (10)
4.2. DC bus constant voltage control system
The proposed constant DC bus voltage control is achieved by
using a bi-directional DC chopper in connection with a battery. The
control systems are shown in Figs. 9 and 10. The bi-directional DC
chopper controls the duty-ratio for normal operation (SWnormal) or
line-fault (SWfault). The switching determinations for SWnormal and
SWfault are performed by considering the AC-grid voltage vt . When
the AC-grid voltage is vt ! 0.8 pu, the bi-directional DC chopper
performs the normal operation. If the AC-grid voltage is vt < 0.8 pu,the bi-directional DC chopper performs under the fault operation.
Under the line-fault, this chopper circuit helps to avoid the DC
bus over-voltage by absorbing energy from PMSG and supplying to
battery, and keeps the DC bus voltage constant. Because the
rapidly rising DC bus voltage is dif cult to keep constant by using
the only PI controller of the AC grid-side inverter. The control
system under the line-fault is shown in Fig. 10. In this system, the
PWM reference signal 2 is determined by the output of PI11
controller. The output of the comparator 4 depends on the
comparison of PWM reference signal 2 and carrier wave signal.
Carrier wave signal is 1 when the carrier wave signal is greater
than the reference signal, and is 0 when the carrier wave is less
than the reference signal. IGBTs are used as switching devices for
the DC chopper circuit.
5. Simulation results
In this paper, the effectiveness of the proposed method is
examined by a switching simulation with the system model shown
in Fig. 1. This simulation considers that the three-line to ground-
fault occursat the middle of transmission lineof Fig.1 and electrical
power supply to the load is shut-down. The sequence of simulation
is described below:
(1) At t ¼ 5.0 s: The three-line to ground-fault occurs at the middle
of transmission line.
(2) When the AC-grid voltage is within vt < 0.8 pu, the gate signals
for grid-side inverter are stopped.(3) At t ¼ 5.1 s: The line-fault is cleared.
(4) When the AC-grid voltage is within vt ! 0.8 pu, the gate signals
for grid-side inverter are re-started.
The simulation results are shown in Fig. 9(a)e(p).
5.1. Normal operation
As can be seen from Fig. 11(b) and (c), when the wind speed
becomes less than the rated wind speed at t ¼ 4.0e6.5 s, the PMSG
output uctuation is smoothed by the pitch angle control system.
Moreover, when the wind speed V w is above the rated speed at
t ¼ 6.5e8.0 s, the pitch angle b, as shown in Fig. 11(p), is well
operated by the pitch angle control system. Besides, the active and
reactive power of PMSG, as shown in Fig. 11(b) and (c), are kept
constant within the rated output power by the pitch angle control
system. Here, the output power does not match with the rated
power, because the rate limiter in Fig. 8 restricts the rising rate of
the PMSG output reference, P ref . As can be seen from Fig. 11(d)e(f)
and (m), stable DC power is supplied to DC loads and rest of the
power is supplied to AC loads with unity power factor through the
grid-side inverter. From Fig. 11(h) and (i), it is found that the battery
does not discharge, because the initialvalue of the SOC is set to50%.
5.2. Line-fault operation
Under the line-fault, the current owing to the battery is
controlled by the switching as shown in Fig. 11(h) and (i). As
a result, it is found that the DC bus voltage V dc follows the command
V dc* . As can be seen in the simulation results, the stable power
supply to DC loads is achieved by the constant control of the DC bus
voltage V dc under the line-fault and stable operation for the PMSG
is possible. In addition, it is also found that the output power
uctuation after the line-fault clearing is reduced and electrical
power supply from the PMSG to the power system can be achieved.
6. Conclusion
This paper presents stable power supply strategies for a DC
distribution system and stable operation strategies for the PMSG
under the line-fault. In normal operation, the proposed system
presents a control strategy based on the MPPT control to generate
the maximum power for the variable wind speed and a pitch angle
control to smooth the output uctuation at low wind speed.
Besides, at high wind speeds, it is possible to control the output
power of the PMSG by the pitch angle control system. In addition to
these control strategies, the DC bus voltage is controlled by using
a bi-directional chopper and battery under the line-fault. From the
simulation results, it is conrmed that the DC distribution system
with the proposed method can stabilize power system operation
under the line-fault and can supply stable power from the grid-side
inverter to the power system after the line-fault clearing.
References
[1] Duic N, Carvalho MG. Increasing renewable energy sources in island energysupply: case study Porto Santo. Renewable and Sustainable Energy 2004;8:383e99.
[2] Katsprakakis DA, Paradakis N, Kozirakis G, Minadakis Y, Christakis D,Kondaxakis K. Electricity supply on the island of Dia based on renewableenergy sources (R.E. S). Applied Energy 2009;86:516e27.
[3] Ishigaki Y, Oyama T. Survey & research on multiple power quality distributionsystem. In: The 2007 annual meeting record IEE Japan; 2007. p. 6e23 (inJapanese).
[4] Senjyu Tomonobu, Ochi Yasutaka, Kikunaga Yasuaki, Tokudome Motoki,Yona Atsushi, Muhando Endusa B, et al. Sensor-less maximum power pointtracking control for wind generation system with squirrel cage induction
generator. Renewable Energy 2009;34(4):994e9.[5] Morimoto S, Nakamura T, Takeda Y. Power maximization control of variable
speed wind generation system using permanent magnet synchronousgenerator. Transactions on IEE Japan 2003;123-B(12):1573e9 (in Japanese).
[6] Senjyu Tomonobu, Tamakia Satoshi, Muhando Endusa B, Urasakia Naomitsu,Kinjo Tatsuto, Funabashi Toshihisa, et al. Wind velocity and rotor positionsensorless maximum power point tracking control for wind generationsystem. Renewable Energy 2006;31(11):1764e75.
[7] Veerachary Mummadi, Senjyu Tomonobu, Uezato Katsumi. Neural-network-based maximum-power-point tracking of coupled-inductor interleaved-boost-converter-supplied PV system using fuzzy controller. IEEE Transactionson Industrial Electronics 2003;50(4):749e58.
[8] Li Xiangjun, Song Yu-Jin, Han Soo-Bin. Frequency control in micro-grid powersystem combined with electrolyzer system and fuzzy PI controller. Journal of Power Sources 2008;180(1):468e75.
[9] Green TC, Prodanovic M. Control of inverter-based micro-grids. Electric PowerSystems Research 2007;77(9):1204e13.
[10] Paska Jozef, BinczelPiotr,Klos Mariusz. Hybridpower systemsean effective way
of utilizing primary energy sources. Renewable Energy 2009;34(11):2414e
21.
K. Kurohane et al. / Renewable Energy 36 (2011) 42e4948
8/7/2019 Control strategy for a distributed DC power system with renewable energy
http://slidepdf.com/reader/full/control-strategy-for-a-distributed-dc-power-system-with-renewable-energy 8/8
[11] Jiayi Huang, Chuanwen Jiang, Rong Xu. A review on distributed energyresources and MicroGrid. Renewable and Sustainable Energy Reviews2008;12(9):2472e83.
[12] Yin Ming, Li Gengyin, Zhou Ming. Modeling of the wind turbine witha permanent magnet synchronous generator for integration. IEEE Trans-actions on Power Electronics 2007;6(25):903e11.
[13] Senjyu Tomonobu, Sakamoto Ryosei, Urasaki Naomitsu, Funabashi Toshihisa,Fujita Hideki, Sekine Hideomi. Output power leveling of wind turbine
generator for all operating regions by pitch angle control. IEEE Transactionson Energy Conversion 2006;21(2):467e75.
[14] Hu Weihao, Chen Zhe, Wang Yue, Wang Zhaoan. Wind power uctuationsmitigation by DC-link voltage control of variable speed wind turbines. IEEETransactions on Power Electronics 2008;10(4):108e16.
[15] Tremblay O, Dessaint LA, Dekkiche AI. A generic battery model for thedynamic simulation of hybrid electric vehicles. IEEE Vehicle Power and Pro-pulsion Conference Sep. 2007;2007:284e9.
K. Kurohane et al. / Renewable Energy 36 (2011) 42e49 49