    OPERATION MANUAL

    THREE-PHASE MULTI TARIFF-DEMANDMETER

    ACTIVE

    ELECTRONIC ELECTRICITY METER

    MODEL : VEM-T5100DB0

    MODEL : VEM-T5100DB2

  • 7/27/2019 Contor Viko Multi Phase

    2/16

    2

    CONTENTS

    GENERAL INFORMATION AND WARNINGS ...3

    TYPE CODE TABLE............3

    GENERAL FEATURES...................................... .....4

    TABLE OF PRODUCT SPECIFICATIONS............ 5

    FUNCTIONS..........5

    INSTALLATION INSTRUCTIONS.........6CONNECTION DIAGRAMS............7

    RS485 CONNECTION INFORMATION.............7

    DISPLAY SYMBOLS.......8

    DISPLAY INFORMATION..9

    SUB-MENU INFORMATION.......................10-11

    SECOND SUB-MENU INFORMATION..............13-15

    ERROR WARNING DISPLAYS.........14

    COMPANY AND TECHNICAL SERVICE INFORMATION...15

    GENERAL INFORMATION AND WARNINGS

  • 7/27/2019 Contor Viko Multi Phase

    3/16

    3

    This manual provides information regarding the specifications, installation and operation of the VIKO BRAND,

    VEM-T series Electronic Electricity Meters.

    PLEASE READ THIS MANUAL CAREFULLY BEFORE ATTEMPTING TO INSTALL OROPERATE THE METER!

    THE INSTALLATION OF THE METER MUST BE PERFORMED BY QUALIFIED PERSONNEL,IN ACCORDANCE WITH THE METERS OPERATIONAL INFORMATION.

    POWER LINES MUST BE DISCONNECTED DURING THE INSTALLATION AND

    DISASSEMBLY OF THE METER. COMING INTO CONTACT WITH PARTS THAT ARE CHARGED WITH VOLTAGES POSE

    LETHAL RISK.

    THE METER MUST BE OPERATED IN ENVIRONMENTS HAVING TEMPERATURESBETWEEN THE VALUES SPECIFIED WITHIN THIS MANUAL.

    THE EXTERIOR SURFACE OF THE METER SHOLD NOT BE CLEANED USING ABRASIVEMATERIALS.

    THE CALIBRATION AND PROGRAMMING OF THE METER IS CARRIED OUT DURING THEPRODUCTION PHASE AND EACH METER IS OFFERED AFTER CONDUCTING QUALITY

    CONTROLS. THERE ARE NO MAINTENANCE OR PROGRAMMING ACTIVITIES THAT MAY

    BE CONDUCTED BY THE USERS.

    This manual is the property of Viko, and it may not be copied, reproduced, or lent to third parties.

    All information contained herein is current information at the time of printing. VIKO reserves the right to make

    changes without prior notification.

    Scope of the Guarantee

    Our meters are guaranteed against production flaws for a period of five (5) years. The damages that may arise

    due to installation and operation of the meters that are not in accordance with the information stated in this

    manual are excluded from the scope of the guarantee.

    Servicing or maintenance may only be performed by VIKOs authorized technical service personnel or other

    persons or organizations that are authorized by VIKO. The damages that may arise due to the servicing or

    maintenance performed by unauthorized persons renders the guarantee void.

    VIKO BRAND, VEM-T series Electronic Electricity Meters are designed and produced in accordance with the

    most current international standards applicable in Turkey. The meters are designed to provide precise readings,

    with the help of high-tech components for flawless operation over long periods of time in accordance with themost current international standards to provide ease of use while possessing physical qualities that are able to

    satisfy site requirements.

    The meter satisfies the following standards:

    TS EN 50470-1

    TS EN 50470-3

    TS EN 62054-21

    TS EN 62056-21

    METER TYPE CODE TABLE

  • 7/27/2019 Contor Viko Multi Phase

    4/16

    4

    PRODUCTCODE

    TYPE OFMEASUREMENT CURRENT TYPE OF CONNECTION

    MEASUREMENTCLASS

    COMMUNICATIONOUTPUT TYPE

    VEM - X XXXXX X X X X

    VIKO ENERGYMETERING M = MONOPHASE 1080 D = DIRECT CONNECTION A = CLASS A 0= NOT

    NULLCHARACTERNORMAL

    T = THREEPHASE 10100C = WITH CURRENTTRANSFORMER B = CLASS B 1= RS232

    P= WITHADVANCEPAYMENT

    C = COMBI x5V = WITH CURRENT/VOLTAGETRANSFORMER C = CLASS C 2= RS485

    1060 3= PLC5(80)

    5(100)

    General Features

    Active energy measurement

    Active demand measurement

    Has a timer and calendar that may operate during power outages.

    Automatic daylight saving adjustments in accordance with the EU norms in force Technical hardware that allows for canceling the application of daylight savings or makes it possible to

    alter the times.

    Storage of the data belonging to the previous year.

    8 time zones and 4 tariffs, the tariffs may be altered without having to remove the meter from where it isplaced.

    Communication through an optical port

    Large LCD display for ease of reading

    Availability of information from the optical port and LCD display even if there is a power outage.

    Ability to view the electric terminal cover and top covers (open/closed) positions on the LCD display

    Critical battery level warning

    Timer error warning

    60 day demand profile

    Ability to set the index information displayed on the LCD display in 5 integers and 3 decimals, 6integers and 2 decimals or 7 integers and 1 decimal.

    Displaying of the active operational direction for all phases on the LCD display

    Phase sequence error warnings

    Demand definition and displaying of warnings in the event of exceeding demand

    THE FOLLLOWING INFORMATION ARE DISPLAYED IN THE SUB-MENU THAT CAN BE

    ACCESSED BY PRESSING AND HOLDING DOWN THE METER READING BUTTON.

    Displaying of the index information of the previous month on the LCD display Displaying of the voltage levels for each phase on the LCD display

    Displaying of the voltage levels between phases on the LCD display

    Displaying of the current values for each phase on the LCD display

    Displaying of the power factor values for each phase on the LCD display

    Displaying of the network frequency for each phase on the LCD display

    Displaying of the power values for each phase on the LCD display

    Displaying of the total power passing through the meter on the LCD display

    TABLE OF PRODUCT SPECIFICATIONS

  • 7/27/2019 Contor Viko Multi Phase

    5/16

    5

    MODELT5100DB2T5100DB0

    T10100DB2T10100DB0

    TYPE OFCONNECTION

    THREEPHASE,3 PHASE4 WIRES

    THREEPHASE,3 PHASE4 WIRES

    CURRENT CIRCUITPOWER CONSUMPTION

    < 2 W 10 VA

    OPERATING VOLTAGE 230/400 V 230/400 VVOLTAGE CIRCUITPOWER CONSUMPTION

  • 7/27/2019 Contor Viko Multi Phase

    6/16

    6

    HOLDING PART : They are used during the installation of the meter. The position of the part of the meter

    can be adjusted vertically with the help of the adjustment screws found on the back of the meter.

    LCD DISPLAY : It displays the information gathered by the meter.

    OPTICAL PORT : It is a communication unit that enables communication between the meter and a handheld terminal or computer for the programming of permitted parameters or for the reading of the information

    gathered by the meter.

    READING BUTTON : It is the button that successively updates the informaton gathered by the meter on the

    LCD display. If the meter button is not pressed, the display information will be updated automatically every 5

    seconds and displayed on the screen. The automatic screen will start to operate 30 seconds after a reading has

    been conducted using the button.

    TOP COVER SEAL: It is a seal affixed after the production, quality control and calibration procedures of the

    meter have been conducted. Due to the fact that legal action may be taken against unauthorized persons

    that tamper with these seals, the seals shall not be removed or damaged.

    TERMINAL COVER SEAL: It is an area where the distribution company must affix their seals in order to

    prevent unauthorized access to the electric terminal block where the meter connections are made. Due to the

    fact that legal action may be taken against persons that have not been authorized by the distribution

    company but tamper with the electric terminal seals, the seals shall not be removed or damaged

    TERMINAL COVER : It is the part which covers the area where the meters connections are made. In the

    event that the covers are opened, the information at the time of opening of the covers are recorded in the

    devices memory. After installation, power is supplied after the covers have been closed. There is a part

    underneath that may be broken off for the cables to be inserted.

    Fi ure 1 Fi ure 2

  • 7/27/2019 Contor Viko Multi Phase

    7/16

    7

    INSTALLATION OF THE METER AND ITS SEALS

    The meter is installed by the help of the installation part located on the top of the device and the three

    installation holes found on either bottom side of the device. The dimensions of the device are shown in

    figure 1, and the installation holes are shown in figure 2.

    The VEM-T series electronic electricity meters are protected against unauthorized use with the help of atotal of 3 seals of which 2 are calibration seals and 1 is an electric terminalcover seal.

    INSTALLATION INSTRUCTIONS

    1- Install the meter using the installation holes as shown in figure 2.2- Make the phase and neutral connections in accordance with the connection diagram.

    (While the connections are being made, make sure that the tips of the cables are properly stripped,

    that the connection screws in the electric terminal are tightened in a way that does not damage the

    conductor, and that no faulty connections are made.)

    3- Before applying voltage, make sure that the electric terminal cover and the electric terminal coverbutton are closed.

    4- Apply voltage and current. In the event that the directions of the current and voltage connections aremade in reverse, the phase that has been connected in reverse will be displayed on the screen as phase

    P. In the event that the phase sequence has been connected in reverse, the R-S-T symbols flash on the

    meter display. When this happens, control the meters connections after you have disconnected the

    power. In the event that the meter is properly connected and the three phases are energized, the R-S-T

    symbols will light up constantly. In the event that the current polarities are properly connected a + P

    symbol will be displayed on all phases.

    CONNECTION DIAGRAM OF A THREE-PHASE METER

    RS 485 CONNECTI ON

  • 7/27/2019 Contor Viko Multi Phase

    8/16

    8

    VEM-T10100DB2MODEL: The RS485 outputs are supplied as standard components in our VEM-T5100DB2

    Three-phase meters. It is possible to obtain a read-out from the meters thanks to these outputs. It is possible to

    access numerous meters by connecting these outputs in parallel. The protocol structure for communicating with

    the meters is as follows: Communicating structure is in accordance with the TS EN 62056-21 standard.

    Communication established!

    Baud Rate 300

    --> /?00012835![CRLF]

    [ACK]051

    --> [ACK]051

    Baud Rate 9600

    --> [SOH]R2[STX]0.0.0()[ETX]P

    [SOH]B0[STX]0.0.0()[ETX]P

    --> [SOH]B0[STX]0.0.0()[ETX]P

    Communication shut down!

    DISPLAY SYMBOLS

    Timer error warning

    Lights up when information related to date is displayed on the LCD screen.

    Lights up when information related to time is displayed on the LCD screen.

    Battery warning

    The section where OBIS codes of the information displayed on the meter screen is shown.

    The numerator where the information contained in the meter is displayed.

    The section that indicates which tariff information belongs to the tariffs

    Indicates the tariff that the meter keeps records in.

    The symbols indicating the direction of the current passing through the meter. When thesymbol +P is displayed on screen, it means that the connections of the meter have beenproperly made. When the symbol +P is displayed on screen, it means that the meters current

  • 7/27/2019 Contor Viko Multi Phase

    9/16

    9

    connections have been made in reverse.

    It is displayed on the screen in the event that voltage is applied on the phase connections, it lights upconstantly when the connections have been made properly, and it flashes when there is an error in thephase sequence.

    Indicates that the information displayed on the screen is related to demand.

    Indicates the measurement units of the information displayed.

    Terminal cover opening warning.

    Top cover opening warning.

    Displayed when information regarding reactive consumption is displayed on screen.

    DISPLAY INFORMATION

    DATE

    TIME

    TOTAL ACTIVE ENERGY

    TARIFF 1

    ACTIVE ENERGY

    TARIFF 2

    ACTIVE ENERGY

    TARIFF 3ACTIVE ENERGY

  • 7/27/2019 Contor Viko Multi Phase

    10/16

    10

    TARIFF 4

    ACTIVE ENERGY

    CURRENT PERIOD (MONTH) ACTIVE ENERGY

    P-MAX VALUE

    DATE OF INFORMATION OF

    ACTIVE ENERGY PMAX

    TIME OF INFORMATION OF

    ACTIVE ENERGY PMAX

    Can be read in sequence by pressing the display information reading button. The automatic screen that operates 30 seconds after the

    display button is pressed, indicates the information on screen at 5 second intervals.

    SUB-MENU INFORMATIONThe sub-menu can be accessed by pressing and holding down the meter reading button for 3 seconds. The latest

    demand reset information for the meter is displayed in the sub-menu. To exit the sub-menu, the reading button

    must be pressed and held down for 3 seconds. If the meter is left in the sub-menu, it will return to the main

    menu automatically after 30 seconds.

    SERIAL NUMBER

    PREVIOUS PERIOD TOTAL

    ACTIVE ENERGY

    PREVIOUS PERIOD TARIFF 1 TOTAL

    ACTIVE ENERGY

    PREVIOUS PERIOD TARIFF 2 TOTAL

    ACTIVE ENERGY

    PREVIOUS PERIOD TARIFF 3 TOTAL

    ACTIVE ENERGY

  • 7/27/2019 Contor Viko Multi Phase

    11/16

    11

    PREVIOUS PERIOD TARIFF 4 TOTAL

    ACTIVE ENERGY

    PREVIOUS PERIOD (MONTH) ACTIVE ENERGY

    P-MAX VALUE

    PREVIOUS PERIOD

    DATE OF INFORMATION OF

    ACTIVE ENERGY PMAX

    PREVIOUS PERIOD

    TIME OF INFORMATION OF

    ACTIVE ENERGY PMAX

    DATE OF THE OPENING

    TERMINAL COVER

    TIME OF THE OPENING

    TERMINAL COVER

    NUMBER OF TIMES TERMINAL

    COVER HAS BEEN OPENED

  • 7/27/2019 Contor Viko Multi Phase

    12/16

    12

    2. SUB-MENU INFORMATION (OPERATIONAL INFORMATION)The following information may be accessed in the meters 2nd sub-menu. To display the menu on the screen,

    the reading button must be pressed and held down for 6 seconds. The first sub-menu is displayed 3 seconds

    after the menu button is pressed, and if the button is kept held down for 6 seconds, the second sub-menu is

    displayed. The menu button must be pressed for a long period of time to exit the sub-menu in question. If the

    meter is left in the second sub-menu, it will return to the main menu automatically after 30 seconds.

    R PHASE VOLTAGE VALUE

    S PHASE VOLTAGE VALUE

    T PHASE VOLTAGE VALUE

    VOLTAGE VALUE BETWEEN R-S PHASES

    VOLTAGE VALUE BETWEEN R-T PHASES

    VOLTAGE VALUE BETWEEN S-T PHASES

    R PHASE CURRENT

    S PHASE CURRENT

  • 7/27/2019 Contor Viko Multi Phase

    13/16

    13

    T PHASE CURRENT

    R PHASE ACTIVE POWER

    S PHASE ACTIVE POWER

    T PHASE ACTIVE POWER

    R PHASE REACTIVE POWER

    S PHASE REACTIVE POWER

    T PHASE REACTIVE POWER

    R PHASE APPARENT POWER

    S PHASE APPARENT POWER

    T PHASE APPARENT POWER

  • 7/27/2019 Contor Viko Multi Phase

    14/16

    14

    R PHASE COS VALUE

    S PHASE COS VALUE

    T PHASE COS VALUE

    R PHASE FREQUENCY

    S PHASE FREQUENCY

    T PHASE FREQUENCY

    ERROR WARNING DISPLAYS

    Terminal cover opening warning.

    The meter is designed to detect and record instances when the cover used for covering the terminal section that

    the connections are made is opened. For the meter not to keep records of any opening of the covers during the

    initial installation of the meter, the cover opening records are not kept until the meter records indexes. However,

    a warning flashes to indicate the opening of the electric terminal covers. If the index that is required for

    keeping record has not passed through the meter, the warning on the screen disappears after the covers are

    closed. In order for records to be kept after the meter is installed, the terminal covers must be closed, and the

    necessary index must be passed through the meter. If the recording of the opening of covers is activated, themeter, records the date and time of the first opening of the covers in each month and counts, records, and stores

    the number of times they have been opened during the month. This information may b e accessed in the meters

  • 7/27/2019 Contor Viko Multi Phase

    15/16

    15

    sub-menus. During the passage to the next month, it stores the current information in its memory as the

    previous months information and resets the information for the next month. It keeps recording the openings of

    the covers in the next month as described above. If a month passes with the cover of the device open, it records

    the date of the passing of the month as the initial opening of the covers, but indicates the number of openings as

    0.

    It is possible to delete the electric terminal cover opening warning through conducting optical readings from the

    meter. Optical readings only delete the warning on the device display, the stored memory regarding the

    openings are not erased. .

    Top cover opening warning:

    The device is designed to detect, record and store the date and time of the opening of the cover that covers the

    section where the measurement section is located. The top cover should not be tampered with, as the opening

    of the top cover which has been sealed will be regarded as attempting illegal use. When the cover is opened, a

    flashing warning for the opening of the top cover will be displayed on the screen. The date and time of theopening of the top cover will be recorded and stored in memory. Only the first opening of the covers will be

    recorded, and subsequent openings will be ignored. It is only possible to reset the warning for the opening of

    the top cover by authorized personnel in the factory environment.

    Battery warning:

    Appears on the screen when the battery supplying power to the meters timer is at a critical level. Due to thefact that the battery is place underneath the top cover, it must be replaced by authorized service personnel.

    Contact our technical service in the event that a warning is displayed.

    Timer error warning:

    Appears on the screen when there is an error associated with the timer. In this case, the meters tariff function is

    disabled and it records the whole index as a T1 tariff. Please contact our technical service in the event that a

    timer error warning is displayed.

  • 7/27/2019 Contor Viko Multi Phase

    16/16

    16

    COMPANY DETAILS

    COMPANY TITLE: VIKO Elektrik ve Elektronik Endustrisi San.ve Tic. A.S.

    ADDRESS: Abdurrahmangazi Mah. Ebubekir Cad. No:44

    34887 Sancaktepe-Samandira / Istanbul

    Tel : 0 216 564 55 55

    Fax: 0 216 564 55 05

    Web:www.vikosayac.com

    TECHNICAL SERVICE ADDRESS

    Abdurrahmangazi Mah. Ebubekir Cad. No:44

    34887 Sancaktepe-Samandira / Istanbul

    Tel : 0 216 564 55 55

    Fax: 0 216 564 55 66

    http://www.vikosayac.com/http://www.vikosayac.com/