contactors ct1000, 1, 2 and 3 pole power contactors for ac ......connect - contact - control 3 index...
TRANSCRIPT
Connect - Contact - Control
3
IndexPower contactors for AC and DC CT1115, CT1130 1
Power contactors for AC and DC, Series CT 2
Features 2
Ordering code 2
Applications 2
Standards 2
Specifications 3
CT1115/04 Dimension diagram single pole NO contactor for 1,500 V / 400 A 4
CT1130/04 Dimension diagram single pole NO contactor for 3,000 V / 400 A 4
CT1115/04 Dimension diagram 1 / 2 / 3 pole NO contactor for 1,500 V / 400 A, coil terminal, front view 5
CT1130/04 Dimension diagram 1 / 2 / 3 pole NO contactor for 3,000 V / 400 A, coil terminal, front view 5
Maintenance instructions 6
Safety instructions 6
Spare parts 6
Circuit diagrams 6
Mounting instructions 7
Electrical Components and Systems for Railway Engineering and Industrial Applications 8
Contactors
CT1115/04, CT1130/04 CT1215/04, CT1230/04 CT1315/04, CT1330/04
1, 2 and 3 pole power contactors
for AC and DC
Catalogue C20.en
2
Owing to a new blowout technology, CT Series contactors can be used in almost any AC or DC railway network, even in countries where the normal tolerances are exceeded. The single pole contactor ensures low-wear and reliable switch-ing of both extremely low and very high loads.
● Compact, rugged design
● 2 breaking capacity levels
● Double-break contacts, (normally open)
● 1, 2, and 3 pole versions
● Easy maintenance: ● Easy inspection and replacement of main contact tips ● Easy replacement of arc chute
● Drive system with coil tolerance according to railway standards
● Functional insulation for main circuit
● Basic insulation between main circuit and protective earth
● Reinforced insulation between main circuit and control circuit / auxiliary circuit
● Main contactor for:● traction motors● convertors● inverters for auxiliary equipment
● Contactor for: ● field circuits of motors● conventional resistor based traction units (retrofit)● starters and compressor motors
● Power switch for heating circuits
● Contactor for a host of industrial applications
Double and triple pole styles are being developed. Especially robust and environmentally friendly materials, from plastics featuring low smoke and low content of toxic gases up to cadmium-free contact tips, are used for the CT1000. It has been tested and approved by independent laboratories.
● IEC 60077: Railway applications – Electric equipment for rolling stock
● EN 50124-1: Railway applications – Insulation coordination – Part 1: Basic requirements – Clearances and creepage distances for all electrical and electronic equipment
● IEC 61373: Railway applications - Rolling stock equipment - Shock and vibration tests
Example: CT1130/04 H 110ET-00
Series
CT11 1 pole NO contactor CT12 2 pole NO contactor CT13 3 pole NO contactor
Nominal voltage
15 Un = 1,500 V 30 Un = 3,000 V
Conv. thermal current
02 Ith = 150 A*2
04 Ith = 400 A 08 Ith = 800 A*1
15 Ith = 1,500 A*2
Mounting position
H horizontal (lock bar yellow) V vertical (lock bar red)
Coil voltage
24 / 36 / 72 / 110 V DC
Coil tolerance
E -30 % … +25 %
Coil suppression
T Suppressor diode
Auxiliary switches, number and type
00 1x S870*3 (a1) 1x S870*3 (b0) 2x S826 a L*4
01 1x S870*3 (a1) 1x S870*3 (b0) 2x S826*4
02 4x S826*4
03 4x S826*4
04 2x S870*4
*1 Series in development *3 See also catalogue D70*2 Series planned *4 See also catalogue D26
Features Ordering code CT series
Power contactors for AC and DC, Series CT
Applications
Standards
Note: Presented in this catalogue are only stock items which can be supplied in short delivery time. For some variants minimum quantities apply. Please do not hesitate to ask for the conditions.
Special variant:If you need a special variant of the contactor, please do not hesitate to contact us. Maybe the type of contactor you are looking for is among our many special designs. If not, we can also supply customized designs. In this case, however, minimum order quantities apply.
M3 screw type terminals
M3 screw type terminals
M3 screw type terminalsFlat tabs 6.3 x 0.8M3 screw type terminals
Flat tabs 6.3 x 0.8
3
Series CT1115/04 / CT1215/04 / CT1315/04 CT1130/04 / CT1230/04 / CT1330/04Kind of voltage DC (bidirectional), AC (f < 60 Hz)Main contacts, Number of, configuration CT11xx/04: 1x SPST-NO / CT12xx/04: 2x SPST-NO / CT13xx/04: 3x SPST-NONominal voltage Un 1,500 V 3,000 VRated operating voltage Ue 1,800 V 3,600 VRated insulation voltage Ui 3,000 V 4,800 VRated impulse withstand voltage Uimp 15 kV 25 kVPollution degree / Overvoltage category PD3 / OV3Switching overvoltages at Ue = 1,800 V Ue = 3,600 V
< 9 kV (<11 kV at T2 = 40 ms) ---
--- < 14.4 kV
Conventional thermal current Ith 400 A *1 400 A *1
Component category (IEC 60077-2) A2 A2Short-circuit making capacity 3.5 kA (new contacts) / 5 kA (used contacts)Rated operating current Ie (at operational frequency C2) DC, Ue = 1,800 V (T2 = 15 ms) DC, Ue = 3,600 V (T2 = 15 ms)
300 A ---
200 A
Rated operating current Ie (at operational frequency C2) AC, Ue = 1,800 V (f = 16.7 Hz; cosφ = 0.8) AC, Ue = 3,600 V (f = 16.7 Hz; cosφ = 0.8)
400 A ---
350 A
Rated operating current Ie (at operational frequency C2) AC, Ue = 1,800 V (f = 50 Hz; cosφ = 0.8) AC, Ue = 3,600 V (f = 50 Hz; cosφ = 0.8)
300 A ---
280 A
Breaking capacity (T2 = 15 ms) DC, Ue = 1,200 V DC, Ue = 1,800 V DC, Ue = 3,600 V
700 A 400 A
---
900 A 700 A 400 A
Breaking capacity (T2 = 1 ms) DC, Ue = 1,200 V DC, Ue = 1,800 V DC, Ue = 3,600 V
1,300 A 900 A
---
2,000 A 1,600 A 800 A
Breaking capacity (cosφ = 0.8) AC, Ue = 1,200 V (f = 16.7 / 50 Hz) AC, Ue = 1,800 V (f = 16.7 / 50 Hz) AC, Ue = 3,600 V (f = 16.7 / 50 Hz)
1,000 A / 700 A 800 A / 500 A
--- / ---
2,000 A / 1,200 A 1,600 A / 900 A 900 A / 500 A
Breaking capacity (cosφ = 1) AC, Ue = 1,200 V (f = 16.7 / 50 Hz) AC, Ue = 1,800 V (f = 16.7 / 50 Hz) AC, Ue = 3,600 V (f = 16.7 / 50 Hz)
1,300 A / 1,000 A 1,000 A / 700 A
--- / ---
2,500 A / 1,500 A 2,100 A / 1,200 A 1,300 A / 800 A
Rated short-time withstand current Icw (T < 100 ms) 6 kA 6 kACritical current range none noneMain contacts Contact material Terminals Torque
AgSnO2M10
20 Nm max.Auxiliary contacts Number and type Contact material S826 switching capacity (T = 5 ms) Terminals, Flat tabs
1x S870 (a1), 1x S870 (b0), 2x S826 or optional 4x S826) *2
Silver 16 A at 24 V DC; 13.5 A at 80 V DC; 7 A at 110 V DC
Screws M3 / Flat tabs 6.3 x 0.8 mmMagnetic drive Pollution degree / Overvoltage category Coil voltage Us Coil tolerance Coil power dissipation at Us and Ta = 20 °C Typical pull-in voltage at Ta = 20 °C Typical pull-in time at Ta = 20 °C Typical drop-off voltage at Ta = 20 °C Typical drop-off time at Ta = 20 °C Coil suppression Coil terminal
PD3 / OV224 / 36 / 72 / 110 V DC
-30 % ... +25 % Uscold coil: 55 W / warm coil: 40 W - per pole
0.6 x Us120 ms 0.1 x Us60 ms
Suppressor diode Cage clamp
Degree of protection IP00Mechanical endurance > 2 million cyclesVibration / shock (IEC 61373) Category 1, class BMounting position horizontal / verticalTemperature Operating temperature / Storage temperature Altitude / humidity (EN 50125-1)
-40 °C … +70 °C / -40 °C … +85 °C< 2,000 m above sea level / < 75 % yearly average
Weight 11 kg / 22 kg / 33 kg 13 kg / 26 kg / 39 kg *1 with multipole contactors or frequent switching under load the conventional thermal current must be limited to 350 A*2 a1 and b0 according to IEC60077
Specifications CT series
4
Caution:
Device contains unprotectedactive pieceparts.
Device contains unprotected non-activepieceparts, which may interact with activepieceparts.Touch only after adhering tocorresponding safety regulations!
Arc chute
Aux. contact block(incl. cover)
Latching lever
Release slider to unlock arc chute
Main terminal screw M10
Lock bar with indicator (arc chute open/locked)
yellow: mounting pos. Hred: mounting pos. V
Coil terminal WAGO 264(incl. cover)
Insulating plate.2 and 3 pole version only
Mounting rail: 2 and 3 pole version only
340
385 ±3
202
137
258 27
2
285
(1 p
ole
vers
ion:
with
out m
ontin
g ra
ils)
297
(2 a
nd 3
pol
e ve
rsio
n: w
ith m
ontin
g ra
ils)
163
318274
340
410
12
Caution:
Device contains unprotected
active pieceparts.
Device contains unprotected non-active
pieceparts, which may interact with active
pieceparts.
Touch only after adhering to
corresponding safety regulations!
Arc chute
Aux. contact block(incl. cover)
Latching lever
Release slider to unlock arc chute
Main terminal screw M10
Lock bar with indicator (arc chute open/locked)
yellow: mounting pos. Hred: mounting pos. V
Coil terminal WAGO 264(incl. cover)
Insulating plate.2 and 3 pole version only
Mounting rail: 2 and 3 pole version only
369320
198
340
385 ±3
202
137
319
305.
5
340
(1 p
ole
vers
ion:
with
out m
ontin
g ra
ils)
352
(2 a
nd 3
pol
e ve
rsio
n: w
ith m
ontin
g ra
ils)
410
12
Reduced scale diagrams / dimensions in mm
CT1x15/04 Dimension diagram single pole NO contactor for 1,500 V / 400 A CT series
CT1x30/04 Dimension diagram single pole NO contactor for 3,000 V / 400 A CT series
5
max. 20 Nm max. 20 Nm max. 20 Nm max. 20 Nm max. 20 Nm max. 20 Nm
Mounting rails (2 and 3 pole version)
Mounting plate (1 pole version)
79
79
7979
164
21393.5
79 79
249
65 min.
60 m
in.*
60 m
in.*
65 min.65 min. 65 min. 65 min. 65 min.
65 min. 65 min.65 min. 65 min. 65 min. 65 min.
179 264
306
max. 20 Nm max. 20 Nm max. 20 Nm max. 20 Nm max. 20 Nm max. 20 Nm
Mounting rails (2 and 3 pole version)
Mounting plate (1 pole version)
164
213
79 79
179
79
79
93.5
249
79 79
65 min.
60 m
in.*
60 m
in.*
65 min.65 min. 65 min. 65 min. 65 min.
306
264
Reduced scale diagrams / dimensions in mm
CT1x15/04 Dimension diagram 1 / 2 / 3 pole NO contactor for 1,500 V / 400 A, coil terminal, front view CT series
CT1x30/04 Dimension diagram 1 / 2 / 3 pole NO contactor for 3,000 V / 400 A, coil terminal, front view CT series
* Interrupting at maximum capacity could require larger clearance! Feel free to contact us, we will be happy to assist you with dimensioning.
* Interrupting at maximum capacity could require larger clearance! Feel free to contact us, we will be happy to assist you with dimensioning.
6
● Except for the main contacts and the arc chute, CT1000 Series contactors are maintenance free.
● The design allows easy access to all parts which require mainte-nance. So when installing the contactor, make sure that there is enough space to remove and replace the arc chute with ease and that the main contacts become accessible for inspection.
● The switching device meets the requirements of basic insulation. In addition to that, the bar onto which the drive of the contactor is mounted should be earthed in a vibration resistant way.
● Do not use contactor without properly mounted arc chute.
● The contactor has unprotected live parts and carries a label that warns of the hazard. This caution must be observed and the label must not be removed in any way.
● The required clearance to other live parts and earth is also to be ob-served as well as the safety regulations of the applicable standards.
● Do not use without protective covers (for coil terminals and auxiliary switches)
● Coil suppression for reducing surges when the coil is switched off is optimally attuned to the contactor’s switching behaviour. Caution: The existing opening characteristic must not be negatively influenced by parallel connection with an external diode.
Maintenance instructions Safety instructions CT series
Spare parts Circuit diagrams CT series
1 pole version: CT1115/04, CT1130/04
Standard version with auxiliary switches S1, S2, S3, S4: 4 x S826
2A2
1A1 33 31+
34+S3S1 S2
2A2
1A1 13 11+
14+ 12 44+ 42
43 41+
24+ 22
23 21+
34+ 32
33 31+
S1 S2 S3 S4
S432 44+ 42
43 41+
22
21
14
13b0a1
A2
A1 33 31+
34+S3S1 S2
A2
4
3
4
3
2
1
2
1A1 13 11+
14+ 12 44+ 42
43 41+
24+ 22
23 21+
34+ 32
33 31+
S1 S2 S3 S4
S432 44+ 42
43 41+
22
21
14
13b0a1
4A2
3A1 33 31+
34+S3S1 S2
4A2
3
6
5
6
5
2
1
2
1A1 13 11+
14+ 12 44+ 42
43 41+
24+ 22
23 21+
34+ 32
33 31+
S1 S2 S3 S4
S432 44+ 42
43 41+
22
21
14
13b0a1
Version acc. to rail way standard IEC 60077 with auxiliary switches S1, S2: 2 x S870 (a1, b0) S3, S4: 2 x S826 2A2
1A1 33 31+
34+S3S1 S2
2A2
1A1 13 11+
14+ 12 44+ 42
43 41+
24+ 22
23 21+
34+ 32
33 31+
S1 S2 S3 S4
S432 44+ 42
43 41+
22
21
14
13b0a1
A2
A1 33 31+
34+S3S1 S2
A2
4
3
4
3
2
1
2
1A1 13 11+
14+ 12 44+ 42
43 41+
24+ 22
23 21+
34+ 32
33 31+
S1 S2 S3 S4
S432 44+ 42
43 41+
22
21
14
13b0a1
4A2
3A1 33 31+
34+S3S1 S2
4A2
3
6
5
6
5
2
1
2
1A1 13 11+
14+ 12 44+ 42
43 41+
24+ 22
23 21+
34+ 32
33 31+
S1 S2 S3 S4
S432 44+ 42
43 41+
22
21
14
13b0a1
2 pole version: CT1215/04, CT1230/04
Standard version with auxiliary switches S1, S2, S3, S4: 4 x S826
2A2
1A1 33 31+
34+S3S1 S2
2A2
1A1 13 11+
14+ 12 44+ 42
43 41+
24+ 22
23 21+
34+ 32
33 31+
S1 S2 S3 S4
S432 44+ 42
43 41+
22
21
14
13b0a1
A2
A1 33 31+
34+S3S1 S2
A2
4
3
4
3
2
1
2
1A1 13 11+
14+ 12 44+ 42
43 41+
24+ 22
23 21+
34+ 32
33 31+
S1 S2 S3 S4
S432 44+ 42
43 41+
22
21
14
13b0a1
4A2
3A1 33 31+
34+S3S1 S2
4A2
3
6
5
6
5
2
1
2
1A1 13 11+
14+ 12 44+ 42
43 41+
24+ 22
23 21+
34+ 32
33 31+
S1 S2 S3 S4
S432 44+ 42
43 41+
22
21
14
13b0a1
Version acc. to rail way standard IEC 60077 with auxiliary switches S1, S2: 2 x S870 (a1, b0) S3, S4: 2 x S826
2A2
1A1 33 31+
34+S3S1 S2
2A2
1A1 13 11+
14+ 12 44+ 42
43 41+
24+ 22
23 21+
34+ 32
33 31+
S1 S2 S3 S4
S432 44+ 42
43 41+
22
21
14
13b0a1
A2
A1 33 31+
34+S3S1 S2
A2
4
3
4
3
2
1
2
1A1 13 11+
14+ 12 44+ 42
43 41+
24+ 22
23 21+
34+ 32
33 31+
S1 S2 S3 S4
S432 44+ 42
43 41+
22
21
14
13b0a1
4A2
3A1 33 31+
34+S3S1 S2
4A2
3
6
5
6
5
2
1
2
1A1 13 11+
14+ 12 44+ 42
43 41+
24+ 22
23 21+
34+ 32
33 31+
S1 S2 S3 S4
S432 44+ 42
43 41+
22
21
14
13b0a1
3 pole version: CT1315/04, CT1330/04
Standard version with auxiliary switches S1, S2, S3, S4: 4 x S826
2A2
1A1 33 31+
34+S3S1 S2
2A2
1A1 13 11+
14+ 12 44+ 42
43 41+
24+ 22
23 21+
34+ 32
33 31+
S1 S2 S3 S4
S432 44+ 42
43 41+
22
21
14
13b0a1
A2
A1 33 31+
34+S3S1 S2
A2
4
3
4
3
2
1
2
1A1 13 11+
14+ 12 44+ 42
43 41+
24+ 22
23 21+
34+ 32
33 31+
S1 S2 S3 S4
S432 44+ 42
43 41+
22
21
14
13b0a1
4A2
3A1 33 31+
34+S3S1 S2
4A2
3
6
5
6
5
2
1
2
1A1 13 11+
14+ 12 44+ 42
43 41+
24+ 22
23 21+
34+ 32
33 31+
S1 S2 S3 S4
S432 44+ 42
43 41+
22
21
14
13b0a1
Version acc. to rail way standard IEC 60077 with auxiliary switches S1, S2: 2 x S870 (a1, b0) S3, S4: 2 x S826
2A2
1A1 33 31+
34+S3S1 S2
2A2
1A1 13 11+
14+ 12 44+ 42
43 41+
24+ 22
23 21+
34+ 32
33 31+
S1 S2 S3 S4
S432 44+ 42
43 41+
22
21
14
13b0a1
A2
A1 33 31+
34+S3S1 S2
A2
4
3
4
3
2
1
2
1A1 13 11+
14+ 12 44+ 42
43 41+
24+ 22
23 21+
34+ 32
33 31+
S1 S2 S3 S4
S432 44+ 42
43 41+
22
21
14
13b0a1
4A2
3A1 33 31+
34+S3S1 S2
4A2
3
6
5
6
5
2
1
2
1A1 13 11+
14+ 12 44+ 42
43 41+
24+ 22
23 21+
34+ 32
33 31+
S1 S2 S3 S4
S432 44+ 42
43 41+
22
21
14
13b0a1
Ordering code Description
MC CT1015/04 Fixed contact, right / left for CT1115/04 - CT1215/04 - CT1315/04
MC CT1030/04 Fixed contact, right / left for CT1130/04 - CT1230/04 - CT1330/04
CB CT1030/04Contact bridge, movable
for CT1115/04 - CT1215/04 - CT1315/04 and CT1130/04 - CT1230/04 - CT1330/04
CC CT1030/04 Cover for coil terminal
CA CT1030/04 Cover for auxiliary switches
S826 a L Snap-action switch (SPDT)
AS S870 Switch group with 2x S870 (momentary)
IP CT1015/04 Insulating plate for 2 and 3 pole versions CT1215/04, CT1315/04
IP CT1030/04 Insulating plate for 2 and 3 pole versions CT1230/04, CT1330/04
For detailed maintenance, safety and mounting instructions please refer to our operating manual!
7
ED : 100% Umax : 138VIth : 400A UNenn : 110VBj. : xxWyy Umin : 77V
UNI : 25kVUNM: 4800V
Class C2 (n. IEC60077) Ue: 3600V / Ie: 200A / T=15msType: CT1130/04 V 110ET-00 Art.: 1-xxxx-xxxxxx
vertik
alm
ounti
ngpo
stion coil
Important:
Make sure arc chamberis latched properlyin final position
Caution:
Device contains unprotected
active pieceparts.
Device contains unprotected non-active
pieceparts, which may interact with active
pieceparts.
Touch only after adhering to
corresponding safety regulations!
Arc chute
Aux. contact block(incl. cover)
Latching lever
Main terminal
Lock bar with indicatorleft: open position,
right: locked positionColour coding:
Yellow: mount. pos. »H«Red: mount. pos. »V«
Coil terminalWAGO 264(incl. cover)
Release sliderto unlock arc chute
334.5 ±0.5
362.5
334.5 ±0.5
364
188
±0.1
5
213
4660
28Mounting holes 4x Ø11 ±0.1
Mounting holes 4x Ø6.6 ±0.1
334.5 ±0.5
362.5
280
±0.1
5
306
28Mounting holes 4x Ø11 ±0.1
(Bottom view)
334.5 ±0.5
362.5
334.5 ±0.5
364
188
±0.1
5
213
4660
28Mounting holes 4x Ø11 ±0.1
Mounting holes 4x Ø6.6 ±0.1
334.5 ±0.5
362.5
280
±0.1
5
306
28Mounting holes 4x Ø11 ±0.1
(Bottom view)
334.5 ±0.5
362.5
334.5 ±0.5
364
188
±0.1
5
213
4660
28Mounting holes 4x Ø11 ±0.1
Mounting holes 4x Ø6.6 ±0.1
334.5 ±0.5
362.5
280
±0.1
5
306
28Mounting holes 4x Ø11 ±0.1
(Bottom view)
Reduced scale diagrams / dimensions in mm
Mounting instructions CT series
Lock barsYELLOW
Lock barsRED
Lock barsYELLOW
Lock barsRED
»H« horizontal (lock bars yellow) »V« vertical (lock bars red)
Start upBefore initial start up make sure that:
● the arc chute is mounted properly and the red levers are in locked position
● the covers are mounted properly
● the contactor is earthed (PE terminal on mounting plate)
Permissible mounting positionsPlease observe the mounting position as shown on the nameplate. The colour of the lock bars is an indication of the correct mounting position:
● yellow lock bars: horizontal
● red lock bars: vertical
Mounting holes1 pole NO contactor, series CT1115/04, CT1130/04
2 pole NO contactor, series CT2115/04, CT2130/04
3 pole NO contactor, series CT1315/04, CT1330/04
with compliments:Schaltbau GmbHFor detailed information on our products and services visit - or give us a call!
Schaltbau GmbH Hollerithstrasse 5 81829 Munich Germany
Phone +49 89 9 30 05-0 Fax +49 89 9 30 05-350 Internet www.schaltbau.com e-Mail [email protected]
Connectors manufactured to industry standards
Connectors to suit the special requirements ofcommunications engineering (MIL connectors)
Charging connectors for battery-poweredmachines and systems
Connectors for railway engineering,including UIC connectors
Special connectors to suit customer requirementsConnectors
Snap-action switches with positive opening operation
Snap-action switches with self-cleaning contacts
Enabling switches
Special switches to suit customer requirements
Snap-action switches
Single and multi-pole DC contactors
High-voltage AC/DC contactors
Contactors for battery powered vehicles and power supplies
Contactors for railway applications
Terminal bolts and fuse holders
DC emergency disconnect switches
Special contactors to suit customer requirementsContactors
Equipment for driver's cab
Equipment for passenger use
High-voltage switchgear
High-voltage heaters
High-voltage roof equipment
Equipment for electric brakes
Design and engineering of train electrics to customer requirements
Electrics for rolling stock
Electrical Components and Systems for Railway Engineering and Industrial Applications
RoHS2002/95/EC
Schaltbau GmbH manufactures in
compliance with RoHS.
Schaltbau GmbH has an environment
management system that has been certified
since 2002.
Schaltbau GmbH has a quality manage-ment system that has been certified since
1994.
RoHS2002/95/EC
Schaltbau GmbH manufactures in
compliance with RoHS.
Schaltbau GmbH has an environment
management system that has been certified
since 2002.
Schaltbau GmbH has a quality manage-ment system that has been certified since
1994.
We reserve the right to make technical alterations without prior notice.
For updated product information visit www.schaltbau-gmbh.com. Issued 07-2010C1909/1003/1.0 Printed in Germany
Electrical Components and Systems for Railway Engineering and Industrial Applications