Installation 285
Foundation 6CCT2-01C
4.3 Foundation
200mm or more
200mm700mm 1280mm or more
200mm
Anti vibration pad10mm
Service panel
Knockout hole(For the control wiring,the power supply, refrigerant connecting pipe)
100mmor more
550mm 360mm or more
L8UC100BFA3L8UH100BFA2L8UC150BFA1<Basic intensity>
Bolt Factor M10-J typeConcrete height 200mm or more
Bolt inserted depth 70mm or more
A4UC602FA2A4UH602FA2<Basic intensity>
Bolt Factor M10-J typeConcrete height 100mm or more
Bolt inserted depth 70mm or more
290 Installation
6CCT2-01CClearance space
A : 750 mm or moreB : 250 mm or more
When inlet air enters from right and left sides of unit
Rear
Front
A : 750 mm or moreB : 250 mm or moreC : 150 mm or more
<Top View> <Side View>
When unit is surrounded by walls
When there is an obstructure above the unit
A : 45 ˚ or moreB : 200 mm or moreC : 250 mm or more
D : 1000 mm or moreE : Air outlet guide (procured at the site)F : 250 mm or more
C
A
B
C
A B
A
B
B B
A
B
C E
D
F
Models : L8UC100BFA3 / L8UH100BFA2 / L8UC150BFA1
Outdoor unit 181
Field wiring diagram6CCT2-01C
2.1.12 Field wiring diagram• L4UC-/L4UH- models
L N
L N
Outdoor unit
5(D)5(C)4(N)3(L)5(B)5(A)4(N)3(L)2(N)1(L)
G Terminal Block Outdoor
Terminal Block Indoor
32(N)1(L)
Terminal Block Indoor
32(N)1(L)
Terminal Block Indoor
32(N)1(L)
Terminal Block Indoor
32(N)1(L)
Circuit breaker
Power supply
Main switch
Power cable3 core*5.5mm2
(including earth)
Transmission line(Separate from power line)
Interunit cable3 core*0.75mm2
(including earth)
Power supply cableTransmission line (shielded cable)
*Note: This configuration of field wiring is applied only for L4UC(H)602FA2.
182 Outdoor unit
Field wiring diagram 6CCT2-01C
Power supply
Main switch
G
Outdoor unit
Inter-unit power
1(L) 2(N) 1(L) 2(N)3(A) 3(B)
Terminal Block Indoor
1(L) 2(N) 3
1(L) 2(N) 1(L) 2(N) 1(L) 2(N) 1(L) 2(N)
1(L) 2(N)
1(L)2(N) 1(L)2(N) 1(L)2(N) 1(L)2(N)
1(L) 2(N) S
SSSSSSSS
S
POWER SUPPLY CABLE
TRANSMISSION LINE(Sheilded cable)
Distributorbox
Distributorbox
Power cable4 core * A mm2
(including earth)
Interunit cable3 core* A mm2
(including earth)
Transmission line(Separate from powerline)
R S T
switch
fuse
R S T Outdoor power
R S T N
* Note: All other model of this series will follow same field wiring procedure'A': - Dimensions are mentioned in specification table.
Terminal Block Indoor
1(L) 2(N) 3
Terminal Block Indoor
1(L) 2(N) 3
Terminal Block Indoor
1(L) 2(N) 3
Terminal Block Indoor
1(L) 2(N) 3Terminal Block Indoor
1(L) 2(N) 3
Terminal Block Indoor
1(L) 2(N) 3
Terminal Block Indoor
1(L) 2(N) 3
• L8UC-/L8UH- models
1) Electrical Wiring Method
� L4UC(H)602FA2
310 Installation
Outdoor unit installation requirments 6CCT2-01C
OD UNIT PCB
1(L) 2(N) 3(L) 4(N) 5(A) 5(B) 3(L) 4(N) 5(C) 5(D)
ID PCB_A
1(L) 2(N) 3
�
�
�
MAIN POWER1Ø, 220V, 60Hz
Installation 311
Outdoor unit installation requirments6CCT2-01C
� L8UC150BFA1
• Using Short Tube
R S T 3(L) 4(N) 5(A) 3(L) 4(N) 5(B)
OD UNIT PCB
Main Power3Ø, 220V, 60Hz
BD UNIT1 PCB
S N L S N L S N L S N L S N LCN_ROOM_A CN_ROOM_B CN_ROOM_C CN_ROOM_D CN_PWR
BD UNIT2 PCB
S N L S N L S N L S N L S N LCN_ROOM_A CN_ROOM_B CN_ROOM_C CN_ROOM_D CN_PWR
ID PCB_A
1(L) 2(N) 3
3(L) 4(N) 5(A) 3(L) 4(N) 5(B)
OD UNIT PCB
Main Power3Ø, 220V, 60Hz
ID PCB_A
1(L) 2(N)
1(L) 2(N)
3
ID PCB_B
3
R S T
R S T 3(L) 4(N) 5(A) 3(L) 4(N) 5(B)
OD UNIT PCB
Main Power3Ø, 220V, 60Hz
BD UNIT1 PCB
S N L S N L S N L S N L S N LCN_ROOM_A CN_ROOM_B CN_ROOM_C CN_ROOM_D CN_PWR
BD UNIT2 PCB
S N L S N L S N L S N L S N LCN_ROOM_A CN_ROOM_B CN_ROOM_C CN_ROOM_D CN_PWR
ID PCB_A
1(L) 2(N) 3
� L8UC100BFA3 / L8UH100BFA2• Using BD Unit