Page 1: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Commercial Deep Energy Retrofit: Castle Square Case StudyAugust 8, 2019

Page 2: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square

Page 3: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise RetrofitProject Overview:

– Occupied rehabilitation– 1960’s era, brick and

concrete public housing structure

– Majority owned by residents association

Page 4: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Project Objective:– Leverage tax incentive

financing, grants, incentives, technical support, etc. to include Deep Energy Retrofit in rehabilitation scope

– Rehabilitation of otherwise limited scope

Castle Square Mid-Rise Retrofit

Page 5: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Project Overview:

– Owner:

– Location:– Buildings:

– Units:

Castle Square Tenants Organization, Winn DevelopmentBoston, MA4 Buildings, 7 stories (6 Residential over Ground Floor Commercial) 192 Units, 48 Units/Building,600-900 sq. ft./Unit

Castle Square Mid-Rise Retrofit

Page 6: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Circumstances of the Project• 51% Tenant Owned

ØCSTO in chargeØInterests of tenant group protectedØDriving factors for the “energy” measures: Comfort,

IEQ concerns

Page 7: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Circumstances of the Project• Originally built as subsidized housing

– Small, compact apartments– Economy of layout– Structure affords no opportunity to run services in

interstitial spaces,– Structure and aesthetic expression poses challenge

to thermal performance

Page 8: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Circumstances of the Project• 100% occupied renovation (!)

– Severe constraints on scope within apartments• Completed over 2-3 days• Tenants return to functioning kitchen first day• Belongings in bedrooms, living room not moved

Page 9: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Resident Surveys & Charrettes

Top Resident Concerns:

1. Poor Ventilation

2. Comfort (Too Hot or Cold)

Page 10: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Property Management Concerns:– IAQ– Comfort– Energy costs– Water leakage– Façade maintenance and repair issues

Castle Square Mid-Rise Retrofit

Page 11: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise RetrofitProject Overview:

• Ambitious energy performance goals– Estimated Heating and Water Heating Energy

Savings: >70%– Combined Gas & Elec. Savings: >50%

October,• Construction Start: 2010

• Construction Schedule: 18 Months

Page 12: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

!(52)$*678(%$*A'9B1'5$ 1$2%"3'2

!##" K#HC#"'

!(52)$*678(%$*A'9 1'5$ 1$2%"3'2

)1#";

3%;'2%'+&;

Q+"((M/35+'@

F6%">@ &#;';aL0355+6>&#6&"%'%

)/' 13'%1((=+'&2%6;

Page 13: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise RetrofitWhat do we have to work with?Understanding the building through:

– Testing/measurement– Investigation of construction– Simple analysis

Page 14: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Testing

Page 15: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Testing

Page 16: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Testing

Page 17: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Testing

Page 18: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Testing

Page 19: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Testing

Page 20: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Testing

Page 21: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Testing

Page 22: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Testing

Page 23: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: TestingTesting and Measurement:▪ Leakage to outside (guarded testing)

Ø~2.5 ACH50Ø~0.7 cfm50 / sf exterior enclosure

▪ Total leakage for apartment units (unguarded)Ø~10-17 ACH50Ø~0.5-0.8 cfm50 / sf total enclosure

Page 24: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Existing Enclosure:

▪ ~R-20 Roof Insulation▪ Exposed concrete frame withuninsulated brick cavity wallinfill

▪ Aluminum Frame Windows (assumed no thermal break in frame, no Low-E)

Image courtesy of Elton + Hampton Architects

Castle Square Mid-Rise: Investigation

Page 25: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Investigation

Page 26: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Investigation

Page 27: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Investigation

Page 28: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Investigation

Page 29: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Investigation

Page 30: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Investigation

Page 31: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Investigation

Page 32: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

!(52)$*678(%$*A'9B1'5$4 K.G$52'/(2'".

Page 33: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Investigation

Page 34: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Analysis

Simple Analysis• UA analysis• Estimates of ventilation, infiltration

Page 35: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise: Analysis

Page 36: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise Retrofit

Testing, investigation, analysis:• Building is moderately (but not abnormally)

air leaky• Apartment units are not well contained• Any significant improvement to energy

performance will require adding insulation to walls

Page 37: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise Retrofit

Testing, evaluation, analysis:• High performance will require1. adding insulation to walls,2. controlling infiltration and ventilation,3. improving windows

Page 38: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise Retrofit

Performance Targets:–R-40 Walls–R-5 Windows–R-40 Roof–Improve compartmenting as much as

possible

Page 39: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

R-40Wall

R-5Wind

R-3Wall

R-1.7Windo

R-40Roof

20Roo

f

Page 40: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise Retrofit

Image credit: www.CastleDeepEnergy.com

Page 41: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Mid-Rise Retrofit

Image credit: www.CastleDeepEnergy.com

Page 42: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Airflow Control/Ventilation

• Avoid cross-contamination• Provide effective ventilation with minimal

energy inputs• Reduce drivers of infiltration• Compartmenting of apartments is critical to

ventilation performance

Page 43: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Ventilation

Page 44: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

VentilationContext:• Odor complaints a major motivation for

residents• Exhaust ventilation a part of existing

infrastructure• Project aspiring to LEED-NC recognition

(ventilation distribution requirements)

Page 45: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Challenges:• Building does not afford interstitial space for

distribution• Hazardous materials (asbestos)• Coordination of façade penetrations

– Coring– Clearances– Time and disruption toresidents

Ventilation

8’-3” floor-to-floor

Page 46: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Ventilation

Options investigated:ØHRV per apartment

• Ceiling too low for dropped soffit in circulation areas• Asbestos made penetration of partitions impractical

ØCentral supply and Hx• Would need to refit or reconfigure riser• Distribution within apartment

Page 47: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Ventilation

Selected approach:ØUse existing ventilation shafts, exhaust

– Controlled rate at unit – CAR– Seal exhaust riser from roof– Passive inlet vent (PIV)

Page 48: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Ventilation

Whither the ventilation supply:• Passive Inlet Vents (PIV)

– Concern about effectiveness of passive vents– Act as intake only when apartment negative WRT

exterior– Could exhaust ventilation act to depressurize

enough – depends on how tight apartment is– Is source controlled?

Page 49: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Compartmenting

Page 50: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Compartmenting

Page 51: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Compartmenting

Page 52: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Context:• Odor complaints a major motivation for

residents• Project aspiring to LEED-NC recognition

(apartment air tightness requirement)

Compartmenting

Page 53: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Challenges:ØOccupied renovation severely limits opportunities

• 2 – 3 days total for interior work• Belongings not moved from living and bedrooms

ØInterstitial interconnected• Openings into shafts• Hollow walls

ØLimited disruption beyond kitchen and bath

Compartmenting

Page 54: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

How to identify effective and important measures?

ØHave a look at building(may have to get destructive)– Understand/confirm construction– Assess significance of holes– Devise approaches to seal holes– Test implementation of measures.

Compartmenting

Page 55: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Compartmenting

Page 56: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Compartmenting

Page 57: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Compartmenting

Page 58: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Context– Buildings are un-insulated– Significant air leakage comfort complaints (papers

blowing off of desks)– Exterior rain infiltration issues– Façade maintenance issues– R-40 performance goal

Castle Square Wall Insulation Strategy

Page 59: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Challenges:– Occupied Retrofit– Significant Thermal Bridging of Concrete Structure– Existing Building Construction Tolerances

Castle Square Wall Insulation Strategy

Page 60: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Options pursued:– Exterior air barrier, insulation and cladding– Exterior insulation and finish system (EIFS)– Insulated metal panels (IMP)

Castle Square Wall Insulation Strategy

Page 61: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

• Exterior air barrier, insulation, and claddingCastle Square Wall Insulation Strategy

Page 62: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

• Exterior air barrier, insulation, and cladding:– Large range of options

• Insulation types• Air barrier materials• Cladding options

Castle Square Wall Insulation Strategy

Page 63: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

• Exterior air barrier, insulation, and cladding:– Fire concerns

• Lack of UL rated assemblies– Insulation thickness needed to achieve desired R-

Value could be significant

Castle Square Wall Insulation Strategy

Page 64: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

• Exterior insulation and finish system (EIFS)

Castle Square Wall Insulation Strategy

Page 65: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

• Exterior insulation and finish system (EIFS)– Lower cost option– No need for design of cladding attachment system

Castle Square Wall Insulation Strategy

Page 66: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

• Exterior insulation and finish system (EIFS)– Thick layers of insulation needed to achieve design

goals– Insurance concerns (Fire, water, durability)

Castle Square Wall Insulation Strategy

Page 67: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

• Insulated metal panels (IMP)Castle Square Wall Insulation Strategy

Page 68: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

• Insulated metal panels (IMP)– High R-Value – thinner overall thickness– Fire rated– Durable

Castle Square Wall Insulation Strategy

Page 69: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

• Insulated metal panels (IMP)– Attachment due to building variances– Water and Air control approach:

• Use panels as the complete enclosure? (air barrier, insulation, water management)

• Use the panels as an insulated cladding with another air barrier and water management layer behind?

Castle Square Wall Insulation Strategy

Page 70: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Insulated metal panels (IMP) as complete enclosure:

Castle Square Wall Insulation Strategy

Page 71: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Wall Insulation StrategyInsulated metal panels (IMP) as complete enclosure:

Page 72: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Wall Insulation StrategyInsulated metal panels (IMP) with separate water/air control:

Page 73: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Castle Square Wall Insulation StrategyInsulated metal panels (IMP) with separate water/air control:

Page 74: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

▪ Wall System Approaches for Super Insulation (R40) Retrofit2. Field-constructed system

separate components: applied air barrier and drainage plane, cladding attachment, exterior insulation, and cladding;judged to costly and complicated

2. EIFS (Exterior Insulation and Finish System) required thickness not approved by insurance

3. Insulated metal panel system

Castle Square Wall Insulation Strategy

Page 75: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

• Insulated metal panels (IMP)– Compartmentalization of the livingunits

Castle Square Wall Insulation Strategy

Page 76: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Building Enclosure

Page 77: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Building Enclosure

Page 78: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Building Enclosure

Page 79: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

• Insulated metal panels (IMP)– Integration of windows and other enclosure

elements made at the air barrier/water resistive barrier location

Building Enclosure

Page 80: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Building Enclosure

Page 81: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 82: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 83: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 84: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 85: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 86: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 87: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 88: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 89: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 90: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 91: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 92: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 93: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 94: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 95: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Phot

o cr

edit:

Elto

n +

Ham

pton

Arch

itect

s

Page 96: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Phot

o cr

edit:

Elto

n +

Ham

pton

Arch

itect

s

Page 97: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)

Phot

o cr

edit:

Elto

n +

Ham

pton

Arch

itect

s

Page 98: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 99: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 100: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 101: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 102: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 103: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)
Page 104: Commercial Deep Energy Retrofit: Castle Square Case Study · 8/8/2019  · Castle Square Mid-Rise Retrofit Testing, investigation, analysis: • Building is moderately (but not abnormally)