clchslb006en_r1
TRANSCRIPT
-
8/12/2019 clchslb006en_r1
1/2
Packaged Climate Changer
General Unit Data
Size 3 6 8 10 12 14 17 21 25 30
Coil Face Area 2.8 5.63 7.45 9.74 12.4 14.34 16.88 20.63 24.20 28.83
Airflow Range1 1050-1800 2100-3600 2800-4800 3500-6000 4200-7200 4900-8400 5950-10200 7350-12600 8750-15000 10500-18000
Fan RPM Range2 650-1900 650-1500 650-1600 650-1400 650-1200 650-1200 650-1000 650-1000 650-1300 650-1200
Motor Hp (max - min) 1/2- 2 1/2- 3 3/4- 5 1 - 5 1 - 7 1/2 1 - 7 1/2 1 - 10 2 - 15 3-20 3-20
DX Circuits3 1 1 1 or 2 1 or 2 2 2 2 2 2 or 4 2 or 4
2" & 4" Flat Filter (1) 20x25 (2) 20x25 (2) 20x25 (1) 16x25 (2) 16x20 (2) 16x20 (2) 16x20 (2) 16x20 (2) 16x25 (6) 16x25
(2) 20x25 (1) 16x25 (1) 16x25 (2) 16x25 (2) 16x25 (6) 20x25 (4) 20x25
(2) 20x20 (2) 20x20 (2) 20x20 (2) 20x20
(1) 20x25 (1) 20x25 (2) 20x25 (2) 20x25
2" Angle Filter (2) 16x25 (4) 20x20 (4) 20x20 (4) 20x20
(2) 16x20 (9) 20x20 (9) 20x20 (6) 16x25 (6) 16x25 (4) 16x20 (12) 16x20
(6) 20x25 (6) 20x25 (12) 20x20 (8) 20x20
Notes:1
Minimum cfm limit applies to units with hot water, steam, or electric heat. There is no airflow limit for cooling only units. Max cfm due to moisture carryover limits.2 Fan rpm max is based on 60 hz motor.3 DX coils are 4 or 6 rows with 9, 12, or 14 fpi.
2002AmericanStandard,Inc.
Electric Heat Minimum/Maximum kW by Voltage
Size 3 6 8 10 12 14 17 21 25 30
208/60/1 6/9 6/18 7/18 8/28 - - - -
230/60/1 6/11 6/20 7/20 8/30 - - - -
277/60/1 6/13 6/24 7/24 8/38 - - - -
208/60/3 6/13 6/26 7/28 8/41 10/50 12/50 14/50 17/50 20/47 20/41
230/60/3 6/13 6/26 7/32 8/41 10/53 12/59 14/59 17/59 20/56 20/50
460/60/3 6/13 6/24 7/32 8/44 10/53 12/63 14/75 17/95 20/95 20/120
575/60/3 6/13 6/26 7/34 8/44 10/53 12/63 14/75 17/95 20/95 20/120
380/50/3 6/13 6/26 7/32 8/44 10/53 12/63 14/75 17/95 20/95 20/95
415/50/3 6/13 6/26 7/32 8/44 10/53 12/63 14/75 17/95 20/95 20/95
Min cfm 1050 2100 2800 3500 4200 4900 5950 7350 8750 10500
Note: Refer to catalog CLCH-PRC007-EN for specific electric heat features.
Dimensions and Weights
Size 3 6 8 10 12 14 17 21 25 30
Horizontal Unit1 Height 24.5 30.5 34.5 34.5 42 42 52 52 59.5 59.5
Width 31.22 44.22 48.22 60.22 68.22 68.22 76.22 76.22 78.22 91.22
Length 54 57 48 52 56 56 62 62 64 65
Weight2 164 232 240 277 462 473 594 636 771 967
Vertical Unit1 Height 47 59 66.5 66.5 82 82 102.5 102.5 - -
Width 31.22 44.22 48.22 60.22 68.22 68.22 76.22 76.22 - -
Length 40 46 34 38 42 42 45 45 - -
Weight2 189 275 286 316 526 539 709 750 - -
Angle Filter Length 21.5 24 27.25 25.5 27.25 27.25 29.25 34 35 35
Section Weight 50 68 82 89 126 126 179 179 200 217
4" Filter Length 21.5 24 27.25 25.5 27.25 27.25 29.25 34 35 35
Section Weight 46 64 78 83 112 112 164 164 184 201
Damper Section Length 21.5 24 27.25 25.5 27.25 27.25 29.25 34 35 35
Weight 80 119 135 168 186 199 274 301 318 355
Coil Access Length 24 24 24 24 24 24 24 24 28 28
Section Weight 69 100 106 119 162 157 204 196 248 271
Notes: 1Basic unit includes: fan, drives, reheat coil, main coil, 2" flat filter.2 Weight of basic unit includes: cabinet, fan, average drive, wiring, and average filter.3Add 9 lbs. to basic weight for control box if applicable.
Selection Procedure1 Size = coil ft2= design cfm max face
velocity.
Example: 6,600 cfm 500 fpm = 13.2
size 14
2 Consider your system and choose
the appropriate sections.
3 Determine overall dimensions and
weight. Note that for a given unit size,
the height and width are the same for
all sections.
4 Finalize fan/coil selections using the
fan curves in catalog, CLCH-PRC001-
EN, or use the Trane Official Product
Selection System, TOPSS.
Electric Heat Section
Quick Select
Optional SectionMain Unit Section Configurations
Vertical Unit, Front Top Discharge Horizontal Unit, Front Top Discharge
OR
Top Front
Horizontal Unit Fan
Discharge Option
Top Front Top Back Back Top
Vertical Unit Fan Discharge Options
Face & Bypass
Section
Optional Sections
Flat Filter Section
Angle Filter Section
OR
Coil Access SectionMixing Section
-
8/12/2019 clchslb006en_r1
2/2
An American Standard Company
www.trane.com
For more information, contact your
local Trane office or email us at
comfort trane com
Literature Order Number
File Number
Supersedes
Stocking Location
Trane has a policy of continuous product improvement and reserves the right to change design and specifications without
notice
Model LPC Vertical Configuration, Front Top Fan Discharge
CLCH-SLB006-EN
PL-AH-CLCH-SLB006-0302
CLCH-SLB006-1200
La Crosse
Added Features Without Added Cost
The Packaged Climate ChangerThe Packaged Climate Changer model LPChas many of the same standard features asmore elaborate air handlers but withoutthe added cost. Features like singlepointpower, factory mounted controls, cleanableunit interiors, and sloped drain pans willhelp save installation and service time!
Easy to Install
singlepoint power to reduce jobsite
installation time and labor
installation doesnt require additional
fieldsupplied accessories
factory mounted controls and variable
frequency drive
Easy to Clean
double-wall wet section and access
panels
optional foilfaced insulation
easily removable coils mount above the
drain pan to aid cleaning doublesloped drain pans help prevent
standing water
Easy to Service
easily removable doublewall access
panels on both sides of the unit
only the drive side of the unit needs
access to service the motor
Galvanized steel cabinet
foilface insulation
mattfaced insulation
2inch flat filter option on main section
Belt driven motor
1/2to 20 horsepower
650 to 1900 rpm
Control box
control interface with transformer,
fan contactor, disconnect, and
customer connection terminal strip
optional factory-installed and wired
DDC controller, Tracer AH540
Forward-curved fan
fixed pitch orvariable pitchsheaves
Other Options
electric heat with singlepoint power connections
variable frequency drive factory mounted and wired
Access section option
1 or 2 row hydronic heat or
1-row steam preheat
Mixing section option
with lowleak dampers
Filter section option
2inch angle filters
4-inch flat filters Up to 8 rows of coil
4 or 6 row DX coils
4, 6, or 8 row chilled water coils
1 row steam pre-heat or reheat
3 different coil fin series
Easy Installation and Service
Packaged Climate Changer