clchslb006en_r1

Upload: erick-sc

Post on 03-Jun-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/12/2019 clchslb006en_r1

    1/2

    Packaged Climate Changer

    General Unit Data

    Size 3 6 8 10 12 14 17 21 25 30

    Coil Face Area 2.8 5.63 7.45 9.74 12.4 14.34 16.88 20.63 24.20 28.83

    Airflow Range1 1050-1800 2100-3600 2800-4800 3500-6000 4200-7200 4900-8400 5950-10200 7350-12600 8750-15000 10500-18000

    Fan RPM Range2 650-1900 650-1500 650-1600 650-1400 650-1200 650-1200 650-1000 650-1000 650-1300 650-1200

    Motor Hp (max - min) 1/2- 2 1/2- 3 3/4- 5 1 - 5 1 - 7 1/2 1 - 7 1/2 1 - 10 2 - 15 3-20 3-20

    DX Circuits3 1 1 1 or 2 1 or 2 2 2 2 2 2 or 4 2 or 4

    2" & 4" Flat Filter (1) 20x25 (2) 20x25 (2) 20x25 (1) 16x25 (2) 16x20 (2) 16x20 (2) 16x20 (2) 16x20 (2) 16x25 (6) 16x25

    (2) 20x25 (1) 16x25 (1) 16x25 (2) 16x25 (2) 16x25 (6) 20x25 (4) 20x25

    (2) 20x20 (2) 20x20 (2) 20x20 (2) 20x20

    (1) 20x25 (1) 20x25 (2) 20x25 (2) 20x25

    2" Angle Filter (2) 16x25 (4) 20x20 (4) 20x20 (4) 20x20

    (2) 16x20 (9) 20x20 (9) 20x20 (6) 16x25 (6) 16x25 (4) 16x20 (12) 16x20

    (6) 20x25 (6) 20x25 (12) 20x20 (8) 20x20

    Notes:1

    Minimum cfm limit applies to units with hot water, steam, or electric heat. There is no airflow limit for cooling only units. Max cfm due to moisture carryover limits.2 Fan rpm max is based on 60 hz motor.3 DX coils are 4 or 6 rows with 9, 12, or 14 fpi.

    2002AmericanStandard,Inc.

    Electric Heat Minimum/Maximum kW by Voltage

    Size 3 6 8 10 12 14 17 21 25 30

    208/60/1 6/9 6/18 7/18 8/28 - - - -

    230/60/1 6/11 6/20 7/20 8/30 - - - -

    277/60/1 6/13 6/24 7/24 8/38 - - - -

    208/60/3 6/13 6/26 7/28 8/41 10/50 12/50 14/50 17/50 20/47 20/41

    230/60/3 6/13 6/26 7/32 8/41 10/53 12/59 14/59 17/59 20/56 20/50

    460/60/3 6/13 6/24 7/32 8/44 10/53 12/63 14/75 17/95 20/95 20/120

    575/60/3 6/13 6/26 7/34 8/44 10/53 12/63 14/75 17/95 20/95 20/120

    380/50/3 6/13 6/26 7/32 8/44 10/53 12/63 14/75 17/95 20/95 20/95

    415/50/3 6/13 6/26 7/32 8/44 10/53 12/63 14/75 17/95 20/95 20/95

    Min cfm 1050 2100 2800 3500 4200 4900 5950 7350 8750 10500

    Note: Refer to catalog CLCH-PRC007-EN for specific electric heat features.

    Dimensions and Weights

    Size 3 6 8 10 12 14 17 21 25 30

    Horizontal Unit1 Height 24.5 30.5 34.5 34.5 42 42 52 52 59.5 59.5

    Width 31.22 44.22 48.22 60.22 68.22 68.22 76.22 76.22 78.22 91.22

    Length 54 57 48 52 56 56 62 62 64 65

    Weight2 164 232 240 277 462 473 594 636 771 967

    Vertical Unit1 Height 47 59 66.5 66.5 82 82 102.5 102.5 - -

    Width 31.22 44.22 48.22 60.22 68.22 68.22 76.22 76.22 - -

    Length 40 46 34 38 42 42 45 45 - -

    Weight2 189 275 286 316 526 539 709 750 - -

    Angle Filter Length 21.5 24 27.25 25.5 27.25 27.25 29.25 34 35 35

    Section Weight 50 68 82 89 126 126 179 179 200 217

    4" Filter Length 21.5 24 27.25 25.5 27.25 27.25 29.25 34 35 35

    Section Weight 46 64 78 83 112 112 164 164 184 201

    Damper Section Length 21.5 24 27.25 25.5 27.25 27.25 29.25 34 35 35

    Weight 80 119 135 168 186 199 274 301 318 355

    Coil Access Length 24 24 24 24 24 24 24 24 28 28

    Section Weight 69 100 106 119 162 157 204 196 248 271

    Notes: 1Basic unit includes: fan, drives, reheat coil, main coil, 2" flat filter.2 Weight of basic unit includes: cabinet, fan, average drive, wiring, and average filter.3Add 9 lbs. to basic weight for control box if applicable.

    Selection Procedure1 Size = coil ft2= design cfm max face

    velocity.

    Example: 6,600 cfm 500 fpm = 13.2

    size 14

    2 Consider your system and choose

    the appropriate sections.

    3 Determine overall dimensions and

    weight. Note that for a given unit size,

    the height and width are the same for

    all sections.

    4 Finalize fan/coil selections using the

    fan curves in catalog, CLCH-PRC001-

    EN, or use the Trane Official Product

    Selection System, TOPSS.

    Electric Heat Section

    Quick Select

    Optional SectionMain Unit Section Configurations

    Vertical Unit, Front Top Discharge Horizontal Unit, Front Top Discharge

    OR

    Top Front

    Horizontal Unit Fan

    Discharge Option

    Top Front Top Back Back Top

    Vertical Unit Fan Discharge Options

    Face & Bypass

    Section

    Optional Sections

    Flat Filter Section

    Angle Filter Section

    OR

    Coil Access SectionMixing Section

  • 8/12/2019 clchslb006en_r1

    2/2

    An American Standard Company

    www.trane.com

    For more information, contact your

    local Trane office or email us at

    comfort trane com

    Literature Order Number

    File Number

    Supersedes

    Stocking Location

    Trane has a policy of continuous product improvement and reserves the right to change design and specifications without

    notice

    Model LPC Vertical Configuration, Front Top Fan Discharge

    CLCH-SLB006-EN

    PL-AH-CLCH-SLB006-0302

    CLCH-SLB006-1200

    La Crosse

    Added Features Without Added Cost

    The Packaged Climate ChangerThe Packaged Climate Changer model LPChas many of the same standard features asmore elaborate air handlers but withoutthe added cost. Features like singlepointpower, factory mounted controls, cleanableunit interiors, and sloped drain pans willhelp save installation and service time!

    Easy to Install

    singlepoint power to reduce jobsite

    installation time and labor

    installation doesnt require additional

    fieldsupplied accessories

    factory mounted controls and variable

    frequency drive

    Easy to Clean

    double-wall wet section and access

    panels

    optional foilfaced insulation

    easily removable coils mount above the

    drain pan to aid cleaning doublesloped drain pans help prevent

    standing water

    Easy to Service

    easily removable doublewall access

    panels on both sides of the unit

    only the drive side of the unit needs

    access to service the motor

    Galvanized steel cabinet

    foilface insulation

    mattfaced insulation

    2inch flat filter option on main section

    Belt driven motor

    1/2to 20 horsepower

    650 to 1900 rpm

    Control box

    control interface with transformer,

    fan contactor, disconnect, and

    customer connection terminal strip

    optional factory-installed and wired

    DDC controller, Tracer AH540

    Forward-curved fan

    fixed pitch orvariable pitchsheaves

    Other Options

    electric heat with singlepoint power connections

    variable frequency drive factory mounted and wired

    Access section option

    1 or 2 row hydronic heat or

    1-row steam preheat

    Mixing section option

    with lowleak dampers

    Filter section option

    2inch angle filters

    4-inch flat filters Up to 8 rows of coil

    4 or 6 row DX coils

    4, 6, or 8 row chilled water coils

    1 row steam pre-heat or reheat

    3 different coil fin series

    Easy Installation and Service

    Packaged Climate Changer