cim network modelcimug.ucaiug.org/meetings/na2017/2017 columbus... · single powertransformer...
TRANSCRIPT
![Page 1: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/1.jpg)
Open Grid SystemsOGO
CIM Network Model
1
Alan McMorran B.Eng Ph.D
![Page 2: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/2.jpg)
Open Grid SystemsOGO
Information ModellingA simple introduction to CIM UML
2
![Page 3: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/3.jpg)
Open Grid SystemsOGO www.opengrid.com
CIM UML
• IEC 61970-301 defines the components in the power
system used by the EMS in UML
• The definitions originally reflected how components
are modelled in existing EMS systems
• As the scope of the CIM has grown the model has
changed to reflect its uses outside of transmission
operations
• The majority of CIM classes have IdentifiedObject as
their root classes
3
![Page 4: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/4.jpg)
Open Grid SystemsOGO www.opengrid.com
Inheritance in the CIM
• A Breaker is “a mechanical switching device capable of
making, carrying and breaking currents under normal
circuit conditions and also making, carrying for a
specified time, and breaking current under specified
abnormal circuit condition”
4
Breaker
![Page 5: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/5.jpg)
Open Grid SystemsOGO www.opengrid.com
Inheritance in the CIM
• Breaker is a type of ProtectedSwitch,
with attributes to define the current
rating and transit time
• ProtectedSwitch is a type of Switch that
can be operated by protection equipment
• Switch is a generic class for any piece of
conducting equipment that operates as a
switch in the network and has an
attribute to define whether the switch is
normally open or closed.
5
+ inTransitTime : SecondsBreaker
+ breakingCapacity : CurrentFlowProtectedSwitch
+ normalOpen : Boolean
+ open : Boolean
+ ratedCurrent : CurrentFlow
+ retained : Boolean
+ switchOnCount : Integer
+ switchOnDate : DateTime
Switch
![Page 6: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/6.jpg)
Open Grid SystemsOGO www.opengrid.com
Inheritance in the CIM
• ConductingEquipment is a type of
Equipment that is designed to carry
current or that are conductively
connected to the network and contains
an attribute to denote the phases
• Equipment refers to any resource of the
power system that is a physical device,
whether it be electrical or mechanical
• PowerSystemResource is used to
describe any resource within the power
system
6
+ inTransitTime : SecondsBreaker
+ breakingCapacity : CurrentFlowProtectedSwitch
+ normalOpen : Boolean
+ open : Boolean
+ ratedCurrent : CurrentFlow
+ retained : Boolean
+ switchOnCount : Integer
+ switchOnDate : DateTime
Switch
ConductingEquipment
Equipment
PowerSystemResource
+ mRID : String+ name : String
IdentifiedObject
![Page 7: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/7.jpg)
Open Grid SystemsOGO www.opengrid.com
Defining Connectivity
• IEC 61970-301 uses Connectivity Nodes and Terminals
to define component interconnections
• Electrical Components (e.g. Breakers, Loads, Lines) do
not associate directly with each other
• Instead any piece of Conducting Equipment has 1 or
more Terminals
• The Connectivity Node class represents a zero-
impedance point of connection between Terminals
7
![Page 8: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/8.jpg)
Open Grid SystemsOGO www.opengrid.com
Connectivity
• Everything that inherits from Conducting Equipment
can have Terminals
• A Terminal has an association to a Connectivity Node
• A ConnectivityNode can have multiple Terminal
associations
8
ConductingEquipment Terminal ConnectivityNode
Terminals0..*
ConnectivityNode0..1
Terminals0..*
ConductingEquipment 1
![Page 9: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/9.jpg)
Open Grid SystemsOGO www.opengrid.com
Multiple Terminals
• In this example Breaker 1 has two Terminals
• Measurements on the Breaker concerning electrical
properties can be assigned to either Terminal
Load A
Breaker 1
ACLineSegment Alpha
ConnectivityNode I
Terminals
10
![Page 10: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/10.jpg)
Open Grid SystemsOGO www.opengrid.com
Inheriting Connectivity
11
+ mRID : String
+ name : String
IdentifiedObject
+ normalOpen : Boolean
+ open : Boolean
+ ratedCurrent : CurrentFlow
+ retained : Boolean
+ switchOnCount : Integer
+ switchOnDate : DateTime
Switch
PowerSystemResource
Equipment
ConductingEquipment
+ breakingCapacity : CurrentFlow
ProtectedSwitch
+ inTransitTime : Seconds
BreakerLoadBreakSwitch
Terminal
ConnectivityNode
Terminals
0..*
ConnectivityNode
0..1
Terminals
0..*
ConductingEquipment
1
EnergyConsumer Conductor PowerTransformer
ACLineSegment
![Page 11: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/11.jpg)
Open Grid SystemsOGO
Modelling a SubstationTranslating a Substation schematic into CIM components
12
![Page 12: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/12.jpg)
Open Grid SystemsOGO www.opengrid.com
Simple Substation in CIM
• This is a simple single
line diagram for a
substation stored in an
EMS
• These electrical
components can be
mapped to components
from IEC 61970-301
17KV
132KV33KV
Generator Alpha
Breaker 17KV
CT 17KV
Transformer 17-132Transformer 17-33
Breaker 33KVBreaker 132KV
Load ALine I
13
![Page 13: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/13.jpg)
Open Grid SystemsOGO www.opengrid.com
Simple Substation in CIM
• These main components
map directly to one piece of
Conducting Equipment
• Generator Alpha also has a
an instance of
GeneratingUnit
• This class represents “a
single or set of synchronous
machines for converting
mechanical power into
alternating-current”
BusbarSection
ACLineSegmentEnergyConsumer
Breaker Breaker
Breaker
SynchronousMachine
17KV
132KV33KV
Generator Alpha
Breaker 17KV
CT 17KV
Transformer 17-132Transformer 17-33
Breaker33KV Breaker 132KV
Load A Line I
Busbar 17KV
GeneratingUnit
14
![Page 14: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/14.jpg)
Open Grid SystemsOGO www.opengrid.com
Transformers
• A transformer is not mapped to a single CIM class
• It is split down into a number of components with a
single PowerTransformer container class
• A two-winding power transformer becomes two
PowerTransformerEnd objects within a
PowerTransformer container
• If a tap changer is present to control one of the
windings then an instance of a PhaseTapChanger or
RatioTapChanger class is associated with that
particular winding
15
![Page 15: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/15.jpg)
Open Grid SystemsOGO www.opengrid.com
Transformer Classes
16
ConductingEquipment
PowerTransformer
TransformerEnd
PowerTransformer0..1
TransformerTankEnd1..*
PowerTransformerEnd0..*
TerminalTerminals0..*
ConductingEquipment1
Terminal1
TransformerEnd0..*
PowerTransformerEnd
PowerTransformer1
TransformerTank
TransformerTankEnd
TransformerTanks0..*
TransformerTanks0..1
TransformerStarImpedance
TransformerCoreAdmittance
TransformerMeshImpedance
TransformerEnd0..*
TransformerEnd0..* FromTransformerEnd
1 ToTransformerEnd1..*
FromMeshImpedance0..* ToMeshImpedance
0..*
StarImpedance0..1
CoreAdmittance0..1
![Page 16: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/16.jpg)
Open Grid SystemsOGO www.opengrid.com
Tap Changers
17
TransformerEnd
PhaseTapChanger
TransformerEnd1
TapChanger
RatioTapChanger
PhaseTapChangerNonLinear
PhaseTapChangerLinear
PhaseTapChangerSymmetrical
PhaseTapChangerAsymmetrical
TransformerEnd1
PhaseTapChanger0..1
RatioTapChanger0..1
![Page 17: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/17.jpg)
Open Grid SystemsOGO www.opengrid.com
Transformer Mapping
• In the example SLD each transformer
results in six CIM objects
• The impedance can be modelled as
Mesh or Star in a separate object
• The core admittance is similarly
modelled as a separate object
• A transformer with a tertiary or
quartiary winding can be represented
as a single PowerTransformer
containing three or four instances of
the PowerTransformerEnd class
18
PowerTransformerEnd
PowerTransformerEnd
PowerTransformer
RatioTapChanger
TransformerMeshImpedance
TransformerCoreAdmittance
Terminal
Terminal
![Page 18: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/18.jpg)
Open Grid SystemsOGO www.opengrid.com
Current Transformer
• For transmission models a current transformer (CT)
does not map directly to a piece of conducting
equipment in the CIM hierarchy for Transmission
• In an EMS the CT does not affect the network
behaviour and is represented as a point of
measurement
• As such a CT is represented as an instance of
Measurement assigned to a particular Terminal
• To support IEC 61850 interoperability there is a
proposal to add a two-terminal CT but this is still in
discussion
19
![Page 19: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/19.jpg)
Open Grid SystemsOGO www.opengrid.com
Containment
• CIM has an EquipmentContainer class that provides a
means of grouping pieces of Equipment together to
represent both electrical and non-electrical
containment
• Subclasses of EquipmentContainer include:
• VoltageLevel
• Bay
• Substation
• Line
20
![Page 20: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/20.jpg)
Open Grid SystemsOGO www.opengrid.com
Substation Containment
• Within Substations there is
a containment hierarchy for
the subclasses of
EquipmentContainer
• A Bay can contain
equipment
• A VoltageLevel can contain
equipment and Bays
• A Substation can contain
equipment, VoltageLevels
and Bays
21
ConductingEquipment
Equipment EquipmentContainer
Substation
VoltageLevel
Bay
![Page 21: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/21.jpg)
Open Grid SystemsOGO www.opengrid.com
Containment
• Substations (and Lines) are contained
by SubGeographicalRegions
• Which in turn are within a
GeographicalRegion
22
ConductingEquipment
Equipment EquipmentContainer
Substation
VoltageLevel
Bay
Line
SubGeographicalRegion
GeographicalRegion
![Page 22: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/22.jpg)
Open Grid SystemsOGO www.opengrid.com
Circuit as CIM Objects
17KV
132KV33KV
Generator Alpha
Breaker 17KV
CT 17KV
Transformer 17-132Transformer 17-33
Breaker 33KVBreaker 132KV
Load ALine I
ConnectivityNode
Terminal
• Load and Breaker in a
33kV VoltageLevel
• Breaker in a 132kV
VoltageLevel
• ACLineSegment in a
Line
• Busbar, Breaker and
SynchronousMachine
in 17kV VoltageLevel
23
EnergyConsumer
Breaker33KV
Load A
Breaker
VoltageLevel
BaseVoltage33KV
Breaker132KVBreaker
VoltageLevel
BaseVoltage132KV
Line IACLineSegment
VoltageLevel
BusbarSectionMeasurement
SynchronousMachineGenerator Alpha
Breaker 17KV
GeneratingUnit
Breaker
BaseVoltage17KV
![Page 23: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/23.jpg)
Open Grid SystemsOGO www.opengrid.com
Substation
Circuit as CIM Objects
• 33kV->17kV
Transformer as a
PowerTransformer
with 2 Windings and a
TapChanger
• Same with 132Kv-
>17kV Transformer
• VoltageLevels and
PowerTransformers
contained in a
Substation
ConnectivityNode
Terminal
24
EnergyConsumer
Breaker33KV
Load A
Breaker
VoltageLevel
BaseVoltage33KV
Breaker132KVBreaker
VoltageLevel
BaseVoltage132KV
Line IACLineSegment
VoltageLevel
BusbarSectionMeasurement
SynchronousMachineGenerator Alpha
Breaker 17KV
GeneratingUnit
Breaker
BaseVoltage17KV
PowerTransformerEnd
PowerTransformerEndRatioTapChanger
TransformerMeshImpedance
TransformerCore
Admittance
PowerTransformerEnd
PowerTransformerEndRatioTapChanger
TransformerMeshImpedance
TransformerCore
Admittance
![Page 24: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/24.jpg)
25
Substation
EnergyConsumer
Breaker33KV
Load A
Breaker
VoltageLevel
BaseVoltage33KV
Breaker132KVBreaker
VoltageLevel
BaseVoltage132KV
Line IACLineSegment
VoltageLevel
BusbarSectionMeasurement
SynchronousMachineGenerator Alpha
Breaker 17KV
GeneratingUnit
Breaker
BaseVoltage17KV
PowerTransformerEnd
PowerTransformerEndRatioTapChanger
TransformerMeshImpedance
TransformerCore
Admittance
PowerTransformerEnd
PowerTransformerEndRatioTapChanger
TransformerMeshImpedance
TransformerCore
Admittance
17KV
132KV33KV
Generator Alpha
Breaker 17KV
CT 17KV
Transformer 17-132Transformer 17-33
Breaker 33KVBreaker 132KV
Load ALine I
![Page 25: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/25.jpg)
Open Grid SystemsOGO
SummaryNode Breaker/Bus Branch modelling in the CIM
26
![Page 26: CIM Network Modelcimug.ucaiug.org/Meetings/NA2017/2017 Columbus... · single PowerTransformer container class • A two-winding power transformer becomes two PowerTransformerEnd objects](https://reader033.vdocuments.site/reader033/viewer/2022060500/5f1a54c33e0043469b3cf66b/html5/thumbnails/26.jpg)
Open Grid SystemsOGO www.opengrid.com
Summary
• The CIM Equipment Profile defines the components in
the network model and the connectivity
• This is the core of the electrical network model
defining a model that represents the state of the
network at a single point in time
• To this static model Steady State Hypothesis and
Measurement data can be applied to alter the
characteristics of components for a given scenario
27