cern safety alarm monitoring presented by luigi scibile st division / mo group

23
CERN CERN Safety Alarm Safety Alarm Monitoring Monitoring Presented by Luigi Scibile ST division / MO group

Upload: brandon-lawrence

Post on 30-Dec-2015

221 views

Category:

Documents


1 download

TRANSCRIPT

CERN CERN Safety Alarm MonitoringSafety Alarm Monitoring

Presented by Luigi Scibile

ST division / MO group

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

2

IntroductionIntroduction

Safety informationAlarm

systemMonitoring system

CERN

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

3

IntroductionIntroduction

CERN Safety Alarm

Monitoring

= CSAM

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

4

Detectionequipment

BackgroundBackground

Hard-wired network

Computer-based network

What’s next ?

Fire CDIN-00052 B104-R-02

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

5

CSAM MandateCSAM Mandate The CSAM will provide CERN with an integrated safety alarm

system covering acquisition, transmission, logging and display for all the CERN sites, the LHC machine, LHC experiments and experimental areas. The system will be incorporated into the safety, technical, accelerator, and experiment control rooms.

The requirements of the system were defined by the AL3S* working group.

The mandate of the project team covers the system specification, prototyping, tendering, installation and integration of the product in the existing monitoring architecture.

* Safety alarms require the immediate intervention of the fire brigade and are defined at CERN as 'Alarms of Level 3' (AL3S)

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

6

CSAM SpecificationCSAM Specification

For the Fire Brigade Safety alarm acquisition from all CERN safety zones Local monitoring from each safety zone Central monitoring, archiving, display, reporting and configuration Non-interruptible 24h/365d system based on redundant networks Specific human computer interfaces and tools for the alarm handling Real-time monitoring of the correct functioning of all sub-systems.

For the Experiments and the other control rooms A safety alarm gateway to external systems A flexible system architecture for the integration of the LHC and LHC

experiments future alarms. A modular acquisition and local monitoring system based on

standard industrial equipment

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

7

CSAM Specification, cont.CSAM Specification, cont. No common mode of failure

Power supply, Location, server, display, acquisition module,etc.

INB compliant system based on redundant transmission paths.

Availability requirements In order to meet the availability requirements of 99.8% set by the

AL3 Working Group, a Safety Integrity Level (SIL) 2 has been fixed. A supervision and monitors the availability of all sub-systems and

generates performance reports.

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

8

CSAM specificationsCSAM specifications, cont., cont.

Transmission System

Technical Data Interface

Safety Alarm Detection Interface

Safety Alarm Transmission

Redundant

Safety & Technical

Alarm Transmission

Central Alarm Display Human Computer Interface

Supervision

Local Alarm Display

Safety Actions

Reference Database

(Configuration)

Data Exchange Protocol

Event Logging System

Functional diagram

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

9

CSAMsupervision & maintenance

manager

TechnicalData Server

(TDS)

Localsafety alarmscontroller

Safety alarm networks

Safety alarmmonitoringcentre

Safety alarmgateway to

externalsystems

(TDS, experiments,

XCR, etc.)

CERN safetyequipment

x33

Hardwired Path 1

Path 2

TCR consoleSCR console

SCRSCADAx2

Central Alarm Display at SCR

Laser printer 1

PLC 1 PLC 2

Local Alarm Synptic PanelZone x

CSAM specificationsCSAM specifications, cont., cont.

PVSS

PVSS

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

10

Safety alarmMonitoringcentre

Remote XCR console

SCRSCADA

ExperimentsDCS

Experiments

LocalXCR console

Safety alarmgateway to

externalsystems(TDS,

experiments, XCR, etc.)

CSAM-experiments interfaceCSAM-experiments interface

How Data exchange protocol JCOP conventions

For the XCR operators Only Safety Alarms and safety-related information

concerning their experiment. Also analogue values of safety equipment. Possible seamless integration in the experiment DCS

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

11

Localsafety alarmscontroller

Safety alarmMonitoringcentre

CERN safetyequipment

Remote XCR console

SCRSCADA

CSAM animation scenarioCSAM animation scenario

ExperimentsDCS

TechnicalData Server

(TDS)

Experiments

LocalXCR console

Safety alarmgateway to

externalsystems(TDS,

experiments, XCR, etc.)

Warning

Warning

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

12

Current systemCurrent system

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

13

Future systemsFuture systems

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

14

Current SystemCurrent System

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

15

Current SystemCurrent System

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

16

Current systemCurrent system

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

17

4 alarms

Future systemFuture system

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

18

B40-5-002

Future systemFuture system

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

19

23:11:15 Fire Detector CDIN-00052 MEY-Z-22-B-0287-R-02 Smoke concentration too high came

23:11:15 Fire Detector CDIN-00052 MEY-Z-22-B-0287-R-02 Smoke concentration too high came

23:11:15 Fire Detector CDIN-00052 PREV-Z-10-B-0112-R-04 Smoke concentration too high came

Fr. 12/05/1999

04:11:15 Fire Detector CDIN-00052 MEY-Z-22-B-0287-R-02 Smoke concentration too high came

05:11:16 Fire Detector CDIN-00052 PREV-Z-10-B-0112-R-04 Smoke concentration too high came

12:12:45 Lift blockage AS-0058 MEY-B-0504-- Lift blocked came

15:14:02 Dead Man HM-Z29 MEY-Z29 Dead Man went

15:16:15 Flooding Det. INOND-863-E-T SPS-B-862-R-05 Flooding Detected came

CERN Safety Alarm System - Messages display

Time Type Identifier Location Description Direction

Comments Old List New List ChronicleSelection Ack All

Fr. 13.05.1999 00:01:20

Ack

SelectedMessage

All Messages

Selection Criteria: Chronicle

15:16:15 Flooding Det. INOND-863-E-T SPS-B-862-R-05 Flooding Detected came15:16:15 Flooding Det. INOND-863-E-T SPS-B-862-R-05 Flooding Detected came

Future systemFuture system

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

20

PrototypePrototype

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

21

What has been done ?What has been done ?

Analysis of technical solutions IEC61508 standards Prototype Technical specifications including:

User requirements Functional and safety requirements Product requirements Interface requirements

Approval of the finance committee

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

22

What’s next?What’s next?

Detailed design and testing during year 2001 Pilot installation planned for APRIL 2002 Deployment of product on the CERN site in

accordance with the LHC and LHC experiments schedule

21 March 2001 JCOP presentation - L. Scibile and the CSAM Team

23

Additional informationAdditional information

Papers S. Grau, P. Ninin, R. Nunes, L. Scibile, C. Soler, CERN

Safety Alarm monitoring Project, 3rd ST workshop Chamonix, February 2000.

L.Scibile, P.Ninin, S.Grau, Functional Safety: a Total Quality Approach, 4st WS Chamonix, 2001.

S. Grau, L. Scibile, F. Balda, A. Chouvelon, Application of risk management for control and monitoring systems, 4rd ST workshop Chamonix, February 2001.

Visit the CSAM Homepage: http://nicewww.cern.ch/st/mo/CSAM/CSAM.htm

Just come and see us!