cables surges
TRANSCRIPT
-
8/9/2019 Cables Surges
1/9
61
1
EEE Transactions on Power Delivery, Vol.
9,
No. 2 A p d
1994
EFFECTS
OF
VOLTAGE SURGES ON EXTRUDED DIELECTRIC CABLE LIFE
PROJECT UPDATE
by
Richard
A.
Hartlein, Member V.
S.
Harper, Member
Georgia Power Company Georgia Power Company Electric Power Research
Harry Ng, Member
AtlanG, Georgia Atlanta, Georgia
KEYWORDS
Cable, Lightning, Water
Tree,
mpulse, Thumper
ABSTRACT
Electric utility engineers have commented
[I], [2]
that
extruded distribution cables frequently fail during or shortly
after a thunder storm. These engineers also comment that
failures often reoccur on cable circuits where previous
failures were located with a thumper. Linemen at Georgia
Power often make similar comments.
To
investigate this observation, crosslinked W P E ) and tree
retardant crosslinked
(TRXLPE)
cable designs were
subjected t accelerated water treeing tests. Samples were
subjected to simulated lightning surges
or
simulated
thumping surges. Crosslinked cables removed after
15 years
of
service operation were also subjected to these surges.
The results show that,
in
some cases, lightning surges do
reduce extruded distribution cable life. Also, high level
thumping surges appear to reduce cable life once cables are
well aged.
INTRODUCTION
The Electric Power Research Institute (EPRI) sponsored the
work
to
investigate the effects of voltage surges on extruded
dielectric cable life under Project
RP2284-01.
Since voltage
surges may affect insulation materials differently, five
commonly used insulation types were initially chosen for this
test program. These include high molecular weight
polyethylene (HMWPE), tree retardant high molecular
weight polyethylene (TRHMWPE) and ethylene propylene
rubber (EPR) aswell as XLPE and TRXLPE.
Preliminary results and a detailed description of the test
93 SM 357-4 PVRD
by the IEEE Insulated Conductors Committee of the IEEE
Power Engineering Society for presentation at the IEEE/
PES 1993 Summer Meeting, Vancouver, B.C., Canada. July
18-22, 1993.
made available for printing April 22, 1993.
PRINTED IN USA
A paper recommended and approved
Manuscript submitted January 4, 1993;
.
Institute
Palo Alto, California
program were published in
[3]
and
[4].
Those results
provide
data
on cables aged in the laboratory and subjected
to 40
kV,
7 0
kV and
120
kV lightning surges. The
data
also
include laboratory aged cables which were subjected
to
a
25
kV thumper surge to simulate surges
use
to locate field
failures.
Aging times of up to 600
days
were reported.
To gather additional information on the effects of surges on
aged cable, a second phase was added to the test program.
In this phase, aging was continued on selected cables beyond
600 days, crosslinked polyethylene cables aged
in
service
(XLPEF) were added to the test program and a 25 kV
lightning surge magnitude was also introduced.
To minimize time and cost, only XLPE, TRXLPE and
XLPEF cables were included
in
the second
phase.
These
compounds were selected because they represent the majority
of cable insulations used by electric utilities.
This paper presents the results gathered to
date
on the cables
tested in phase two.
This
new
data
provides greater insight
into the effects of lightning and thumping
surges
on aged
cables.
A
brief review of the test program is also included.
TEST CABLES
Fifteen kV cables were used because they are very common
and 15 kV cables are easily managed in accelerated
laboratory tests.
Since the ac voltage and surge voltage
stress distribution varies with insulation thickness, cables
with different insulation thicknesses were evaluated.
Table
1
outlines the cables utilized for this program.
The XLPE and TRXLPE cables were made by one
manufacturer specifically for use in this test program.
This
was done to minimize the variations in cable quality that
can
occur between manufacturers.
They were manufactured to
the AEIC CS5-82 specification for crosslinked polyethylene
insulated power cable using a triple extrusion, steam curing
process. The conductor shields were extruded, conventional,
semiconducting XLPE with a nominal thickness of 15 mils.
The nominal insulation thickness was either
175
mils or 220
mils. The insulation shields were extruded, semiconducting
XLPE with a nominal thickness of
30
mils.
Extra smooth
or extra clean shields were not available at the time these
cables were manufactured.
Since the XLPEF cable was obtained from the field, the
0885-8977/94/$04.00
Q 1993 IEEE
-
8/9/2019 Cables Surges
2/9
-
8/9/2019 Cables Surges
3/9
613
applied, the voltage was lowered
to
1X the operating voltage
to ground
(8.6
kV). This was also done to represent field
conditions.
Thumuer Surne Auulication
To apply the thumping surge, a thumper was connected to
each cable rack individually using a dummy cable length
which contained a simulated fault
to
ground. A Biddle
Model
No. 652025
humper with a
12
pf capacitor was used
open end of the test cable is shown in
Figure
2.
r
to apply the thumping surge. A typical waveform at the
Figure 2. Typical waveform as seen at the open (far)
end of the cable subjected to a 25 kV
thumping surge.
Aging of Cables Removed From the Field
The XLPEF cables aged for 15 years in service at 7.6 kV.
An examination of the insulation revealed numerous, large
bowtie and vented water trees. The vented trees were
as
long
as 170 mils
and the bowtie trees were as long
as 60
mils.
A C
breakdown tests were conducted according
to
AEIC CS5-82 starting at 100 V/mil. The resulting
breakdown strength of five, 30 foot long samples was 220,
220,220,220
and
260
V/mil. Since cables with this type
of
watertreeing
and
dielectric strength are considered to be well
aged, the aging voltage used in the laboratory was the same
magnitude as the service voltage (7.6 kV).
Initially, the XLPEF cables were aged in conduits filled with
tap water but with no water in the conductor. The conductor
of this cable was
sealed
immediately after receipt at the
laboratory. This was done to preserve field conditions as
much as possible. However, since no failures occurred after
aging in the laboratory for 200 days, deionized water was
added
to the conductors. Deionized water wasuse to avoid
adding ions which may not have been present in service.
Aging Temuerature
ACCELERATED AGING PROCEDURE
Aeinn of New Cables
The cable aging test was designed
to
simulate and accelerate
field aging and was pattemed after the AEIC CS5-82,
B.5
accelerated water treeing test which
was
in force when this
project was initiated. In accordance with the AEIC
accelerated water treeing test procedure, the XLPE and
TRXLPE cables were thermally preconditioned. This is
done to reduce the high concentration of volatiles contained
in the newly manufactured cable insulations.
Preconditioning was conducted after the cables were placed
in the aging conduits but before they were filled with water.
AEIC specifies a preconditioning conductor temperature of
130 C for
10 days
using current in the conductor.
However, 110
C
was
used
in
this
test to avoid the
possibility of overheating the insulation. All temperature
tolerances were 5
C .
After preconditioning, the
conductors and conduits were filled with tap water.
To
accelerate aging, 3X rated voltage
to
ground
(26
kV,
60
Hz ac) was applied to both the XLPE and TRXLPE
175-mil-wall and 220-mil-wall cables. Thus, the aging stress
was
149
V/mil on the thin wall cables and
118
V/mil on the
thick wall cables.
This
procedure was followed to represent
the different stresses that thick and
thin
wall cables
experience
in
the field. When the lightning surge was
Normally, the AEIC accelerated water treeing test is
performed with sufficient current to achieve a
90°C
conductor temperature in air. However,
in
phase one, the
75°C
rated HMWPE cables were connected
in series
with
the
90°C
rated XLPE, TRXLPE and EPR cables. To
prevent overheating
of
the HMWPE cable and to maintain
the same aging conditions on all cables, a maximum
conductor temperature of 75 C was chosen for all test
cables in phase one. For consistency, this temperature was
also used in the second phase of the test program.
This
temperature was achieved with
260
amperes in the
conductor using a lZhour-on, 12-hour-off load cycle.
Aging With ImDulses
The lightning surges were applied an average of
2.3
times a
week. They were always applied at the end of the
12-hour-on period while the cables were still warm.
Approximately 5 to 10 minutes before the lightning impulse
was applied, the aging voltage was reduced from 26 kV to
8.7
kV.
Thumping surges were applied in a manner that represents
field conditions. Cables used for the thumping test condition
were removed from the aging test and connected to the
thumper. Nine hundred thumping impulses were applied to
each test cable rack individually. The cables were then
placed back in the aging test. Thumping was performed
-
8/9/2019 Cables Surges
4/9
614
every
60 days
after the first
120
days of aging.
175 MI1 ConlMl
............................. *...................... *..x
...............
- ?5,M 4??Pu?eA
.....................
A. A .A. ..A........
.........................................
y ...
y
...
A.A*.A
...A y A n
....... .............
.........
y ......
. nMMkx ......................
175
HII
70kv Pulse
.......................................
.......A...) .
.....................................................
175 MI1
l 2 U V
PUIS0
175 MI1 Thumper
.....................................................
Control samples were exposed to the same aging conditions
as
the surged samples but with no surges applied. All
samples were en er g id , deenergized and filled with water
at the same time. Every effort was taken
to
ensure that the
only difference between the control and surged samples was
the application of the voltage surges.
.....................................................................................
.................................................... ......
.... ...... .x ...........................
Each surge test condition was applied
to
a separate set of
cable samples.
No
cables were subjected
to
both thumping
and lightning impulses.
This
would have been an interest ing
condition to evaluate because it represents the kind of surge
combinations that can occur in service. However, individual
surge effects were considered the most important variables
to
investigate first.
220 MI1 7WV Pula8
_....
.....................
.........
.....
y
.....
.......... .... ....
A u . X
..........................
Redicates
Two, 180-foot-long coils of cable were subjected
to
each test
condition. Each coil was a continuous length which
contained six, 30-foot-long samples. Thus there were 12
samples or replicates for each test condition.
Summarv of Test Variables Investigated
Table 2 shows a matrix of the test conditions examined in
phase
2
A
Cy
indicates that a test covering this condition
was performed.
n (N)
indicates that a test
to
evaluate this
condition was not performed due to time or space
limitations.
Table
2
Matrix showing all of the test conditions
reported in this paper.
175
mil wall
thickness
surge
condition
CNTRL
25kV 4OkV 70kV 12OkV
XLPE
Y N Y Y Y
TRXLPE
Y N N Y Y
XLPEF
Y Y N Y N
220
mil wall
thickness
surge condition
CNTRL 25kV 40kV 70kV 120kV
XLPE
Y N N Y N
TRXLPE
N N N N N
XLPEF
N N N N N
RESULTS
In
phase one, four traditional methods of evaluating the
integrity of an extruded power cable were
used
to determine
the effects of surges on each cable
tested
in the project.
They included ac breakdown tests, impulse breakdown tests,
time
to
failure and visual analysis. After a thorough
investigation, time to failure analysis was the only method
which revealed differences between control and surges
samples. Therefore, only time to failure data is presented
for the cables tested in phase two.
Aging Failures
To simplify the discussion, an abbreviation is
used to
describe the test conditions. The insulation material and
wall thicknesses in mils is followed by the surge or control
test variable. For example, the XLPE, 175-mil-wall cable
subjected to a 70
kV
surge is referred to
as
XLPE, 175/70.
As mentioned earlier, at the start of this project ac
breakdown tests were considered an important diagnostic
tool for evaluating surge effects. Therefore, during the first
360
days of aging in the initial tests, numerous samples were
removed from the test and subjected to
an
ac breakdown
test. By the end of
360
days, almost
no
samples remained.
Thus, the 175/control and 175/70 surged samples of XLPE
and TRXLPE cables were unavailable for further aging
beyond
360
days.
Other conditions examined for these cables
as
well
as
the
XLPEF test cables
started
the test program after the
data
showed that aging time is more important than breakdown
strength. Therefore, data are available for longer than
360.
Also, since unaged TRXLPE cable was still available, the
TRXLPE 175/control condition was repeated.
To compare the time to failure data for all cables, line
graphs are employed which show when each failure
occurred. The data presented in this manner provide a
visual method of observing early failures or clusters of
failures.
n X
at the end
of
a line means either the test
condition was discontinued to perform breakdown tests or
most of the samples failed at the time the X s shown.
No
X at the end of the line means the cable is still under test.
Except for the XLPEF cable, failures during the surge
application are rare. The failures
as
a
function of time are
shown in Figures
3-5.
~
0
100
200 300
400
500
600 700
Oays of Aging
Figure
3.
XLPE failures
as
a function of time in the aging
test. Each failure is represented by a triangle.
-
8/9/2019 Cables Surges
5/9
1
175 Mil Cnnlmi
.........................................................................................................................
175 MI1
25 kv Pulse
............................................... f ................2 .............
* ..... ..& ................
. .....................................................
.i .
.. 2
...
.ai.
...............................
75
Mil
70kv Pulse
175 Mil
Thumper
-. ............................................................................... .........A............................
I
1
I75
Mil Cantmi
.............................. ... ........ ..............A........ ..............................
175
Mil
70kv
ulse
.........................................
K.
..........................................................................
175 Mli
IZWv Pulse
...........................................
..A.......
.A..
& ...... A...A.
X
.............
.75 Mi l Thumper
........... .....................................
.......................................................................................................................
0 200
400
600
800
1000
Days of Aging
Figure4. TRXLPE failures as a function of time in the
Each failure is represented by a
ging test.
triangle.
Figure 5 . XLPEF failures as a function of time in the
Each failure is represented by a
ging test.
triangle.
Discussion of Time to Failure Data
Examination of the time to failure
data
begins to provide
interesting insight on surge effects. For the 175 wall XLPE
cables, it is difficult to compare the control condition to the
surge conditions because the control test was terminated
so
early in the test program. Therefore, it is unclear how
strongly the lightning surges influenced cable life. There is
also no clear difference between the 40 kV and 70 kV
lightning surge conditions. However, comparing the 40 kV
and
70
kV lightning surge conditions to the thumper test
condition is useful.
The samples subjected to the lightning surges failed fairly
regularly throughout the test after the first
150
days of
aging. On the other hand, once the samples subjected to the
thumping surge started to experience a few failures, they
failed very rapidly.
In
fact, the thumper failure points on
the graph were artificially spread out to distinguish
individual failures. Thus, the thumping surge did not appear
~
615
to have a significant effect on the cable until approximately
450
days of aging. At that point, the cable failed rapidly
until all the samples were consumed.
For the 220 wall XLPE cables, the only apparent difference
between the control condition and the
70
kV lightning surge
condition is that failures occurred earlier on the samples
subjected to the lightning surge. Interestingly, the
observation made for the 175 wall XLPE cable subjected to
the thumping surge also applies to the 220 wall XLPE cables
subjected to the thumping surge.
The control and
120
kV lightning surge TRXLPE cables
appear to experience similar failure rates. However,
as
before, the samples subjected to the thumping surge fail
rapidly after they have aged for 450 days.
The effect of the 25 kV and 70 kV lightning surges on the
XLPEF cable is very pronounced. Multiple failures
occurred on the samples subjected to lightning surges while
no control samples failed. Once again, there are no clear
differences between the 25 kV and
70
kV surge levels.
Interestingly, the thumper has not had a significant effect on
the cable life.
Unlike the XLPE and TRXLPE cables, the XLPEF cables
often failed when the lightning surge was applied. This
phenomena will be discussed in more detail later.
Statistical Analysis of Time to Failure Data
To provide a more in depth analysis of the time to failure
data, Weibull probability statistics were employed. The
estimated failure rates for the XLPE, TRXLPE and XLPEF
cables using the Weibull model are presented in Figures
6 -
9. The test conditions are noted on the graphs following the
insulation material description. The abbreviations used are
similar to those employed for the aging failure graphs except
that a 0 represents the control condition.
The characteristic life for each test condition is the point at
which 63.2% of the samples have already failed. For
convenience, the 63.2% level is shown with a dotted line on
each graph. If fewer than three failures occurred for a given
test condition, a failure model could not be calculated.
.
--
TIME
DAYS
Figure
6.
Weibull life model for 175 wall XLPE cable.
-
8/9/2019 Cables Surges
6/9
616
w
50
1 , , , ' k
1 1
TIME. DAYS
Figure
7.
Weibull life model for
220
wall XLPE cable.
TIME,
DAYS
Figure 8. Weibull life model for TRXLPE cable.
TIME, DAYS
Figure 9. Weibull life model for XLPEF cable.
Confidence Intervals
To gain further insight from the Weibull statistical mdel,
the values for characteristic life (indicated as I* ) ith
corresponding
90%
confidence intervals are shown for each
test condition in Figure
10.
The values for the Weibull,
shape parameter (also indicated as I* )ith corresponding
90% confidence intervals are shown in Figure 11. %e
shape parameter gives an indication of
bow
the probability
distribution function changes with aging time.
Discussion of Statistical Model
F6r the XLPE and TRXLPE cable designs, there are slight
differences in characteristic life between test conditions.
However,
in
all cases, the confidence intervals overlap,
Figure
10.
Weibull life model parameters. 90%
confidence intervals on characteristic life.
The calculated characteristic life values are
shown
as
a *'
Figure 11. Weibull life model parameters.
90%
confidence intervals on shape factor. The
calculated shape factor values are shown as a
* U .
making distinctions between the characteristic lives of each
sample statistically inconclusive.
h e XLPEF cable design does show a noticeable difference
in characteristic life between samples subjected to the
25
kV
lightning surge and those subjected to the
70
kV lightning
surge. Although there is a slight overlap in the confidence
intervals of the
two
test conditions, the amount is very
small. Thus the observation that the two test conditions
differ is statistically valid, indicating that lowering the surge
-
8/9/2019 Cables Surges
7/9
level from 70 kV to 25 kV increases cable life.
There is a distinct difference in the slope for the 220 wall
XLPE cable between the control and the 70 kV lightning
surge condition.
This
verifies the observation made on the
time
to
failure
data
that the samples subjected
to
the 70 kV
surge failed earlier than the control samples.
Another interesting observation for the XLPE and TRXLPE
Weibull curves is that the slope for the thumper test
condition is consistently higher than the slope for other test
conditions. Although there is
some
overlap in the
confidence intervals, this trend indicates that the samples
subjected to the thumper surge very likely experience a wear
out phase. That is, after a period of occasional failures,
they start to fail rapidly,
as
if the cable reached the end of
its reliable service life.
FAILURE MECHANISMS
Several possible
reasons
for differences between control and
surged sample failure rates
as
well
as
differences in lightning
surge and thumping surge failure rates were discussed in [4].
However, failures of the XLPEF cables during the lightning
surge application is a newly observed phenomena. Almost
all of the other cable designs failed sometime after the surge
was applied. The different failure
mode
for the XLPEF
cable can
be
explained by the degree of water treeing in the
insulation.
The XLPEF cables age at 1X ra td voltage which allows the
dielectric to experience greater deterioration before they fail
than the other cables which were aged at 3X rated voltage.
Thus the ratio of the surging voltage to aging voltage (degree
of deterioration) is larger for the cables operated at 1X than
for the cables operated at 3X rated voltage.
This phenomena
is
demonstrated by the very large bowtie
and vented water trees which formed while the XLPEF cable
was in service. Many of the trees found in the insulation of
this cable extend through
as
much
as
97 9 of the insulation
wall. They continued to grow slowly in the aging test where
the applied voltage magnitude is 1X the operating voltage.
However, they easily become a failure path in the presence
of a large magnitude lightning surge.
The XLPE and TRXLPE cables started the test new, with no
water
trees
present. Since the aging voltage on these cables
was 3X the operating voltage, failures occurred in the aging
test long before the water trees reached the length observed
in the XLPEF cables. Since extremely long water trees are
not present in these cables, they are not nearly
as
susceptible
to failure during voltage surges.
617
CONCLUSIONS
Phase 2
The results of EPRI Project RP2284-01 have provided some
interesting insight into the effects of voltage impulses on
extruded cables aged in the laboratory. Several conclusions
drawn during the first phase of the project are presented in
[3] and [4]. Only new conclusions developed during
phase 2 are
stated
in
this
paper. They apply only to the
cables evaluated in the test program described in this paper.
They may
or
may not
be
applicable to cables operating in
service. Obviously, many questions remain unanswered.
1.
2.
3.
1.
2.
3 .
Lightning Voltage Impulses Can Reduce Cable Life.
This observation was made in phase one and reinforced
in phase 2. The 175 mil and 220
mil
XLPE cables, the
175 mil TRXLPE cables and the 175 mil XLPEF cables
which were surged often failed more than the same
cables that were aged without the voltage impulses.
Thumping Voltage Surges Can Reduce Cable Life.
This is a new observation. After 400 days of aging in
the laboratory, the XLPE and TRXLPE cables subjected
to a thumping surge failed more rapidly than the same
cables subjected the control
or
lightning surge condition.
This implies that once cables have been in service long
enough to develop water tree growth similar to that
obtained after 400 days of aging under the conditions
described in this paper, they may fail prematurely if
subjected to thumping surges.
Lighting Surge Magnitude Does Not Strongly Affect
Cable Failure Rates.
Only the XLPEF cables demonstrated a change in failure
rate
as
a function of surge magnitude. However, the
effect was not observed in the characteristic life, but in
the slope
of
the Weibull model curve.
REFERENCES
Minutes of the 78 ' Meeting of the Institute of Electrical
and Electronics Engineers Insulated Conductors
Committee Meeting, April 21-23, 1986. pp. V-C.
Minutes of the
80
Meeting of the Institute of Electrical
and Electronics Engineers Insulated Conductors
Committee Meeting, April 27-29, 1987. pp. V-E2.
R.
A. Hartlein, V. S. Harper and H. Ng. Effects of
Voltage Surges on Extruded Dielectric Cable Life,
IEEE Transactions on Power Delivery, April, 1989
Volume 4, Number 2, pp. 829-841.
-
8/9/2019 Cables Surges
8/9
618
4.
Electric Power Research Institute, Effects of Voltage
Surges on Solid-Dielectric Cable Life , Report EL-
6902,
Interim Report, September,
1990.
ANOWLEDGEMENTS
The authors would like to thank the Electric Power Research
Institute for funding
this
research project. It addresses an
area that has concerned electric utility engineers for many
years.
The authors would also like to thank the following Georgia
Power Research Center personnel for their hard work and
dedication to accomplish the project goals.
- Mr.
Larry
Coffeen who designed and constructed the
lightning surge test equipment.
- Mr. Boyd Pettitt who processed the large volume of data
generated and developed many of the graphs and
maintained the surge test equipment.
In addition, the authors would like to thank Dr. Russell G.
Heikes of the Georgia Institute of Technology for providing
the statistical data analysis and the project advisor,
Mr.
P.
Pate1 for his suggestions and guidance.
BIOGRAPHIES
Richard A. Hartlein (M 80) was born in Atlanta, Georgia
on March 20, 1952. He received a Bachelor and Master of
Mechanical Engineering degrees in 1976and 1982 from the
Georgia Institute of Technology in Atlanta, GA. He
has
been employed at the Georgia Power Research Center since
1970 where he is currently manager of the mechanical
section. He has conducted test programs on extruded, thin
wall, 230 kV transmission cable, water tree resistance of
extruded cable designs, and power cable ampacity inside
riser shields. He has also managed EPRI projects on the
short-circuit characteristics of cable metallic shields.
He is a member of the IEEE Insulated Conductors
Committee. He is chairman of ICC Task Group
10-27
which writes the IEEE
404
splice testing standard. He is
also a past chairman of the Cable Engineering Section of the
Association of Edison IlluminatingCompanies and chairman
of the task group which writes the S I C CS5 specification
for XLPE insulated distribution cables.
V.
S. Ha mr (M 74) was born
in
Marietta, Georgia on
October 3,
1943.
He received a Bachelor of Electrical
Engineering degree in 1966 from the Georgia Institute
of
Technology in Atlanta, Georgia. He has been employed
with the Georgia Power Company since
1966 and
is
presently a Research Manager. Previous fields of work
include substation control, power line relaying, fault current
calculations and project engineering for customer
substations.
Mr. Harper is a member of the IEEE Power Engineering
Society, Insulated Conductors Committee and has served on
several EPRI task forces and committees.
H a m W.
Hg
(SM
74)
received his B.S. degree in
Electrical Engineering in
1971
from the University of
Arizona, Tucson, Arizona. From 1971
to
1983 he was with
Tucson Electric Power Co. in Tucson, Arizona in various
distribution engineering positions, starting
as
a Distribution
Engineer. In
1976,
he was appointed Supervisor of
Distribution Engineering.
In 1983 he joined the Electric Power Research Institute in
Palo Alto, California where he is presently Manager,
Distribution System Design and Operations, in the Electrical
Systems Division. His work has been
in
a broad area
related to the distribution of power by electric utilities.
Some of his responsibilities include distribution cables,
electrical fault location, wood pole management, distribution
design and analysis software, energy conservation and
amorphous steel core distribution transformers. He has
authored many papers related to power distribution.
Mr. Ng is a member of the IEEE Power Engineering
Society, the IEEE Insulated Conductors Committee, and the
American
Wood
Preservers Association. He serves
on
the
Wood
Pole
Working
Group of the Distribution Committee of
IEEE, the research committee of the American Wood
Preservers Association and
as
advisor to the Forest Products
Laboratory, Mississippi State University. He is also a
Registered Professional Engineer (Electrical) in the states of
Arizona and California.
-
8/9/2019 Cables Surges
9/9
619
surge had
a
very noticeable effect on cable performance. In
Figure
3,
the
175
mil and
220
mil cables clearly had more
failures earlier
in
the test when the
40
kV and
70
kV surges
were applied. In the case of the field aged XLPE cables, the
surged samples failed and the samples which were not
surged experienced no failures.
Diecussion
MARC AUDET, KILBORN INC. TORONTO, CANADA :
The authors have reeented data on impulee
testing of XLPE RND EPR insulation under
laboratory conditione, and thie data seems
to indicate little difference in erformance
between the control samplee a n 8 the test
samples, although th e teet eamples were
eub ected t o impulee waves to simula te
ligitni n surges. It appeare from thi e that
any furtxer teeting of similar cables under
labor atory co nd iti on s with bar e eam 1,s
immersed in water is not liable to resul t in
much usef ul information.
The teat data presented by the authore on1
reinforces reviouely ubliehed data tha z
XLPE E%R ine ulat ea cables and cablee
ineulatnedd with similar compounds fail when
subjected to moieture, generally from water
treeing.
Various pap ers have been presented, which
provide information or teat data concerning
the performance of such cablee of varioue
CO fi U atione and compounds. Some of thie
in?or#afion wae preeented as etatietical
data on cablee installed in th e field. The
data indicates that all similar compounde,
whether TRXLPE or EPR provide good life if
the cablee are sealed against moieture at
the shield. and at the conductor
termination.
It appears that futu re efforte in regard to
cab1 m r v ent s uld be dire ed tow
provfdt n8 %ez?er cakne conf guraelone
w l l g
filled conductors, sealed condinuoue
ehielding tapes or eimilar barriers againet
moisture if long cable life is to be
realized.
Some really useful information could have
been obtained if t he teat eamplee had been
made up in such a manner ae to reflect
actual field conditions. with am ro ve d
terminations etrees -relief debices
rounded shielde, and impervious jackete:
8uch teete would yield really useful data
for cable suppliere, s ecifiere, and
installere. Perhape t he facifitiee available
to th e authore did not permit thi e manner of
testing.
It would have been intereeting to know where
the test cablee failed. whether they f led
at or near th e termina'tione due t o vo?tage
streae, or somewh ere in the middle of the
cables, or randomly. Also, were th e
compou nde teated in any ray after failure,
to eee if any chemical change had occurred?
In
many
cases,
Weibull statistics do show that the
characteristic life of a specific cable design may be similar
for control and surged conditions (Figures
6
-
9).
However,
the slope of the Weibull curves in Figures
6
and
7
is very
different for control samples and surged samples. This is
direct evidence that there is indeed a difference between
control and surged samples.
This
is
demonstrated again in Figure
11
where the
confidence intervals are plotted for the Weibull shape factor.
For example, the there is a significant difference in the
calculated shape factor and the corresponding confidence
interval for the XLPE
220
control samples and the XLPE
220
samples subjected to the
70
kV lightning surge.
Test Cables
Since
the scope of our work was to evaluate the effect
of
lightning surges on
aged
underground cable, we used a very
common procedure of aging cables in an accelerated water
treeing test. They had unfilled, stranded conductors and no
jackets to allow for maximum accelerated aging. Water
impervious jackets and/or blocked conductors would have
significantly increased the time to achieve significant aging.
Other tests are currently underway in
our
laboratory to judge
the effects of jackets and moisture barriers on cable aging.
These results will
be
presented sometime in the future.
It
is important to note that there
is
a considerable amount of
cable in service which is very similar to the cable in our
test. The results obtained in this test program should be
applicable to those cables.
Manuscript
received
August 9,
1993.
Test Procedure
RICHARD A. HARTLEIN,
V. S.
HARPER AND HARRY
NG: The authors would like to thank the discussor for the
opportunity to clarify and provide comments on several
aspects
of the paper.
Suree Effects
Although there were some test conditions where the surge
appeared to have no effect, there were others where the
All test samples were constructed with standard terminations
as used in the field. All cable neutrals were grounded. All
reported test sample failures occurred in the cable within the
water filled tube.
Termination failures were repaired and
not considered cable failures. These procedures are
commonly used throughout the cable industry in accelerated
aging tests on extruded dielectric cables.
Manuscript received October 5, 1993.