bus module profinet - advanced energyethernet bus module profinet order-no. 2000 000 846. 7 1.4...

63
BUS MODULE PROFINET FOR THYRO-S, THYRO-A, THYRO-AX, THYRO-POWER MANAGER, THYRO-STEP CONTROLLER, THYRO-MEASUREMENT UNIT, THYRO-A ...C01, ...C02, ...C03, ...C05 AND ...C07 July 2014 DE/EN - V3

Upload: others

Post on 10-Mar-2020

16 views

Category:

Documents


5 download

TRANSCRIPT

1

BUS MODULE PROFINET FOR ThyRO-S, ThyRO-A, ThyRO-AX, ThyRO-POwER MANAgER,

ThyRO-STEP CONTROLLER, ThyRO-MEASUREMENT UNIT,

ThyRO-A ...C01, ...C02, ...C03, ...C05 AND ...C07

July 2014 DE/EN - V3

2

1. Introduction 6

1.1 general 6

1.2 Special features 6

1.3 Type designation 6

1.4 Abbreviations 6

1.5 warranty 7

2. Safety 8

2.1 Identification in the operating instructions 8

2.2 general danger information 9

2.3 Operator requirements 10

2.4 Personnel requirements 10

2.5 Intended use 10

2.6 Use of the device 11

2.6.1 Operation 11

2.6.2 Prior to installation/commissioning 11

2.6.3 Maintenance, service, faults 11

2.6.4 Transport 12

3. Functions 13

3.1 Processing the setpoint Thyro-S 13

3.2 Processing the setpoint Thyro-A/Thyro-AX 13

3.3 Processing the setpoint Thyro-Step Controller 14

3.4 Freely addressable digital outputs 15

4. Installation 16

4.1 Connection terminals (overview) 16

4.2 Connecting a 24 V power supply 16

4.3 Connecting the power controller to X1-X8 17

4.4 Connecting the Ethernet bus module to the master 17

5. Settings 18

5.1 Setting the protocol 18

CONTENTS

3

5.2 Setting the number of slots 18

5.3 Setting the device name 18

5.4 Operating display of the bus module 20

6. Operation 21

6.1 Start configuration (parameterization) 21

6.2 Cyclical data transmission (configuration) 22

6.3 Input and output data Thyro-S 22

6.4 Input and output data Thyro-A/Thyro-AX 24

6.5 Input and output data Thyro-Power Manager 35

6.6 Input and output data Thyro-Step Controller 36

6.7 Input and output data Thyro Input/Output Unit 37

6.8 Input and output data Thyro- Measurerment Unit 38

6.9 Acyclic data transmission (parameterization) 39

7. External connections 41

7.1 Power supply 41

7.2 Operating elements and terminal blocks 42

8. Interfaces 43

8.1 System interface 43

8.2 Ethernet interface 43

9. Connection diagrams Thyro-A/Thyro-AX 44

10. Connection diagrams Thyro-S 45

11. Connection diagrams Thyro-Step Controller 46

12. Specific notes 47

12.1 Installation 47

12.2 Service 47

13. Technical Data 47

14. Dimension drawings 48

15. Accessories and options 48

16. Approvals and conformity 49

17. Appendix A Acyclic parameter tables 50

4

Fig. 1 Configuration & LED dis plays 19

Fig. 2 Connection diagram Thyro-A/Thyro-AX 44

Fig. 3 Connection diagram Thyro-S 45

Fig. 4 Connection diagram TSC 46

Tab. 1 Connecting terminals (overview) 16

Tab. 2 Operating display of the bus module 20

Tab. 3 Interpretation of the master setpoint for Thyro-S 22

Tab. 4 Cyclic input and output data for Thyro-S…h1 22

Tab. 5 Cyclic input and output data for Thyro-S…hRL1 23

Tab. 5a Thyro-S Faults 23

Tab. 5b Thyro-S Status 24

Tab. 6 Cyclic input and output data for Thyro-A 1A…h1 24

Tab. 7 Cyclic input and output data for Thyro-A 1A...hRL1/Thyro-AX 1A...hRL2 25

Tab. 8 Cyclic input and output data for Thyro-A 1A...hRLP1/Thyro-AX 1A...hRLP2 25

Tab. 9 Cyclic input and output data for Thyro-A 2A…h1 26

Tab. 10 Cyclic input and output data for Thyro-A 2A...hRL1/Thyro-AX 2A...hRL2 26

Tab. 11 Cyclic input and output data for Thyro-A 2A...hRLP1/Thyro-AX 2A...hRLP2 27

Tab. 12 Cyclic input and output data for Thyro-A 3A…h1 27

Tab. 13 Cyclic input and output data for Thyro-A 3A...hRL1/Thyro-AX 3A...hRL2 28

Tab. 14 Cyclic input and output data for Thyro-A 3A...hRLP1/Thyro-AX 3A...hRLP2 29

Tab. 14a Thyro-A/Thyro-AX Fault 30

Tab. 14b Thyro-A/Thyro-AX Status 31

Tab. 15 Cyclic input and output data for Thyro-A 1A…C01 32

Tab. 16 Cyclic input and output data for Thyro-A 1A…C02 32

Tab. 17 Cyclic input and output data for Thyro-A 1A…C03 33

Tab. 18 Cyclic input and output data for Thyro-A 1A…C05 33

Tab. 19 Cyclic input and output data for Thyro-A 1A…C07 34

Tab. 20 Supported operating modes 34

Tab. 21 Cyclic input and output data TPM automatic mode 35

Tab. 22 Cyclic input and output data TPM manual mode 35

Tab. 23 Cyclic input and output data TSC mode 36

Tab. 24 Cyclic input and output data TIO mode 37

Tab. 25 Cyclic input and output data TMU mode 38

Tab. 25a Status TPM, TSC, TIO,TMU 38

Tab. 25b Faults TPM, TSC, TIO,TMU 39

LIST OF FIgURES AND TABLES

5

CONTACT

TEChNICAL qUERIESDo you have any technical queries regarding the subjects dealt with inthese operating instructions?If so, please get in touch with our team for power controllers:Phone +49 (0) 2902 763-520

COMMERCIAL qUERIESDo you have any commercial queries on power controllers?If so, please get in touch with our team for power controllers.Phone +49 (0) 2902 763-558

SERVICEAdvanced Energy Industries gmbhBranch Office warstein-BeleckeEmil-Siepmann-Straße 32D-59581 warsteinPhone +49 (0) 2902 763-0http://www.advanced-energy.com

COPyRIghTNo part of these operating instructions may be transmitted, reproduced and/or copied by any electronic or mechanical means without the express prior written permission of Advanced Energy.© Copyright Advanced Energy Industries gmbh 2014.All rights reserved.

FURThER INFORMATION ON COPyRIghTThyro-™, Thyro-S™, Thyro-A™, Thyro-AX™ are registered trademarks of Advan-ced Energy Industries gmbh. All other company and product names are (registered) trademarks of the respective owners.

6

1. INTRODUCTION

The operating instructions below serve only as an addition to be used in conjunction with the operating instructions of the Advanced Energy Thyro-A and Thyro-AX power controllers, Thyro-S power switch, and Thyro-Power Ma-nager in the versions of the types indicated on the covering page. The safety instructions contained therein are to be observed in particular.

1.1 gENERALThe Ethernet bus module can connect up to 8 power controllers of type Thyro-A, type Thyro-AX and type Thyro-S with a master in any desired order.Several bus modules can be used on one system.The power supply of the bus module comes from an external 24 V DC voltage source (150 mA), which is to be fed in (reverse polarity protected) at X11.1 (+) and X11.2 (ground). Several modules can be operatedfrom one power supply. As short a ground connection as possible is needed at terminal X11.3 for EMC reasons.

1.2 SPECIAL FEATURES· The Ethernet bus module connects the devices with several Ethernet bus systems. By setting the “Protocol” switch to 0, the Ethernet bus module beco-mes a PROFINET IO-device.

· when position 9 „Set all default“ is active the bus module will be reset to factory defaults for settings and address.

· when the bus module is linked to Thyro-AX, please be aware that data trans-fer is the same as for Thyro-A whereas special features or other additional parameters are excluded from this.

· function control via LED· 8 free application outputs X1 to X8 in each case terminal 5· C-rail assembly

1.3 TyPE DESIgNATIONEthernet bus module PROFINET order-no. 2000 000 846

7

1.4 ABBREVIATIONSAdvanced Energy Advanced Energy Industries gmbhTPM Thyro-Power ManagerTSC Thyro-Step ControllerTMU Thyro-Measurment UnitTIO Thyro Input/Output Unit

1.5 wARRANTyIn the event of any claims in connection with the Ethernet bus module, please contact us quoting:· type designation· fabrication number / serial number· reason for the complaint· environmental conditions of the device· operating mode· period of use

goods and services are subject to the general conditions of supply for products of the electrical industry, and our general sales conditions. Claims in connection with supplied goods must be submitted within one week of receipt, along with the delivery note. Advanced Energy will rescind all obli-gations such as warranty agreements, service contracts, etc. entered into by Advanced Energy or its representatives without prior notice if maintenance and repair work is carried out using anything other than original Advanced Energy spare parts or spare parts purchased from Advanced Energy.

8

2. SAFETy

2.1 IDENTIFICATION IN ThE OPERATINg INSTRUCTIONSIn these operating instructions, there are warnings before dangerous actions. These warnings are divided into the following danger categories:

DANgERDangers that can lead to serious injuries or fatal injuries.

wARNINgDangers that can lead to serious injuries or considerable damage to property.

CAUTIONDangers that can lead to injuries and damage to property.

CAUTIONDangers that can lead to minor damage to property.The warnings can also be supplemented with a special danger symbol (e.g. ”Electric current“ or ”hot parts“) , e.g.

risk of electric current or

risk of burns.

9

In addition to the warnings, there is also a general note for useful information.

NOTEContent of note

2.2 gENERAL DANgER INFORMATION

DANgERNot adhering to the safety stipulations in the operating instructions of the power controllers used can lead to danger of injury/danger of damaging the device or system.· Adhere to all safety stipulations in the chapter “Safety” of the operating instructions of the power controllers being used.

DANgERElectric currentRisk of injury from current carrying parts/danger of damaging the bus mo-dule.· Never operate the device without the covering.· Undertake settings and wiring without current being supplied.

CAUTIONDanger of damaging the bus moduleThe current at terminals X1.5 to X8.5 must not exceed 120 mA.· Check the connection information of the preceding relay.

NOTECommunication errorsTo avoid communication errors please note the following points:· Use shielded cables.· Undertake grounding of the bus module (X1.7 to X8.7). Do not ground addi-tionally at the power controller.

10

2.3 OPERATOR REqUIREMENTSThe operator must ensure the following:· The safety regulations of the operating instructions are observed.· The accident prevention regulations valid in the respective country of use and the general safety regulations are observed.

· All safety devices (covers, warning signs etc.) are present, in perfect condi-tion and are used correctly.

· The national and regional safety regulations are observed.· The personnel has access to the operating instructions and safety regulati-ons at all times.

· The operating conditions and restrictions resulting from the technical data are observed.

· Should abnormal voltages, noises, increased temperatures, vibration or similar occur, the device is immediately put out of operation and the mainte-nance personnel is informed.

2.4 PERSONNEL REqUIREMENTSOnly qualified electro-technical personnel who are familiar with the pertinent safety and installation regulations may perform the following:· transport· installation· connection· commissioning· maintenance· testing· operation

These operating instructions must be read carefully by all persons working with or on the equipment prior to installation and initial start-up.

2.5 INTENDED USEThe device may only be used for the purpose for which it was intended, as persons may otherwise be exposed to dangers (e.g. electric shock, burns) and plants also (e. g. overload). The user must therefore observe the following points:· It is not permitted to make any unauthorized modifications to the unit or to use any spare parts or replacement parts not approved by Advanced Energy, or to use the unit for any other purpose.

11

· The warranty obligations of the manufacturer are only applicable if these operating instructions are observed and complied with.

· The device is a component that cannot function alone.· Project planning must account for the proper use of the device.

2.6 USE OF ThE DEVICE

2.6.1 OPERATION· Only switch on the mains voltage at the device when there is no danger to persons, system or load.

· Protect the device against dust and damp.· Ensure that the ventilation openings are not blocked.

2.6.2 PRIOR TO INSTALLATION/COMMISSIONINg· If stored in a cold environment: ensure that the device is absolutely dry. (Allow the device a period of at least two hours to acclimatize before com-missioning).

· Ensure sufficient ventilation of the cabinet if mounted in a cabinet.· Observe minimum spacing.· Ensure that the device cannot be heated up by heat sources below it. (see chapter 13, Technical data).

· ground the device in accordance with local regulations.· Connect the device in accordance with the connection diagrams.

2.6.3 MAINTENANCE, SERVICE, FAULTSIn order to avoid personal and material damages, the user must observe the following:· Before all work:· Disconnect the device from all external voltage sources.· Secure the device against accidentally being switched back on.· Use suitable measuring instruments and check that there is no voltage present.

· ground and short circuit the device.· Provide protection by covers or barriers for any neighboring live parts.· The device may only be serviced and repaired by trained electro-technical personnel.

12

2.6.4 TRANSPORT· Only transport the device in the original packaging.· Protect the device against damage, caused by jolts, knocks and contaminati-on, for instance.

13

3. FUNCTIONS

3.1 PROCESSINg ThE SETPOINT Thyro-SOnly local setpoints, no bus setpointSwitching signal (24DC) at the control terminal X22.1 of the Thyro-S· No wiring of the terminal point X22.4 at the power controller.· The bus module is fully functional. The analog signal from the control termi-nal X22.1 is used as setpoint (on/off).

Setpoint from the bus module (X22.3), no local setpoint· Connect the ground to terminal X22.4 of the power controller.· The master setpoint of the bus module is used. For this purpose the setpoint is interpreted as the operating mode.

Bus setpoint, switching over to „local“ in case of bus faultOnly use the setpoint of the bus module if there is an IO connection.· Connect terminal X22.4 of the power controller to one of the terminals X1.1 to X8.1 of the bus module.

· If there is an IO connection the master set point is used. If not then the analog signal from the control terminal X22.1 is used as setpoint (on/off).

Switching over to bus/local setpoint switchable for each controller in operationIndividual setpoint from the bus module for each power controller.· Connect terminal X22.4 of the power controller to one of the terminals X1.5 to X 8.5 of the bus module.

· The power controllers can be switched over individually (targeted) via the bus between master setpoint and terminal X22.1.

3.2 PROCESSINg ThE SETPOINT Thyro-A/Thyro-AXOnly local set points, no bus set point:Analog input at control terminal X2.4 of Thyro-A/Thyro-AX> Do not connect anything to terminal X22.1 of the power controller.- The bus module is fully functional. The analog signal from the control termi-nal X2.4 is used as set point (on/off).

Set point from the bus module (X22.3), no local set point:> Connect the ground to terminal X22.1 of the power controller.- The master set point of the bus module is used.

14

Bus set point, switching over to “local” in case of bus fault:Only use the set point of the bus module if there is an IO connection.> Connection between X22.1 Thyro-A and bus module X1.1 to X8.1During normal operation, the set point is digital.If an error is detected in the bus module or Ethernet IP communications, then the bus module will automatically float the bus module, X1.1 output.This causes the Thyro-A, X22.1 input to go high and switches to analog set point for Thyro-A (switches to 4-20mA or potentiometer control).For further details: Chapter 17. Connection diagrams Thyro-A / Thyro-AX, Fig.2

- If there is an IO connection the master set point is used. If there is no IOconnection then the analog signal from the control terminal X2.4 is used asset point.

Switching over to bus / local set point reversible for each controller in opera-tion:Individual set point from the bus module for each power controller.> Connection between X22.1 Thyro-A and bus module X1.5 to X8.5 During normal operation, the set point is analog (bit set to 0)If the bit is set to 1 then the Thyro-A set point is switched to digital.If an error is detected in the bus module or Ethernet IP communications, then the bus module will automatically float the bus module, X1.5 output.For further details: Chapter 17. Connection diagrams Thyro-A / Thyro-AX, Fig.2

- The power controllers can be switched over individually (targeted) via thebus between master set point and terminal X2.4.

3.3 PROCESSINg ThE SETPOINT Thyro-Step ControllerOnly local setpoints, no bus setpointAnalog input at control terminal X6.1 or X6.4 (depending on X6.7) of the TSC· Do not connect anything to terminal X2.1 of the power controller.· The bus module is fully functional. The analog signal from the control termi-nal X6.1 or X6.4 is used as setpoint.

Setpoint from the bus module (X22.3), no local setpoint· Connect the ground to terminal X2.1 of the TSC.· The master setpoint of the Ethernet bus module is used.

Bus setpoint, switching over to “local” in case of bus faultOnly use the setpoint of the bus module if there is an IO connection.· Connect terminal X2.1 of the TSC to one of the terminals X1.1 to X8.1 of the bus module.

15

RELAIS CONTROL

· If there is an IO connection the master setpoint is used. If there is no IO connection then the analog setpoint is used.

Switching over to bus/local setpoint value switchable for each controller in operationIndividual setpoint from the bus module for each power controller.· Connect terminal X2.1 of the power controller to one of the terminals X1.5 to X8.5 of the bus module.

· The power controllers can be switched over individually (targeted) via the bus between master setpoint and the analog setpoint.

3.4 FREELy ADDRESSABLE DIgITAL OUTPUTS· As long as the terminals X1.5 to X8.5 of the bus module are not being used for switching over the setpoint, these can be used as switch outputs.

· Connect the relay to a 24 V DC coil voltage for free use. The idle circuit is inte-grated. The actuating current is a maximum 120 mA per output. As a result it is possible to switch over, for example, the room ventilators, anti-condensati-on heating, circuit breakers or control lamps via the bus.

16

4. INSTALLATION

DANgERDangers during InstallationRisk of injury/Risk of damage to the device or plantObserve all safety regulations in the chapter “Safety”.

4.1 CONNECTION TERMINALS (OVERVIEw)

TERMINAL DESCRIPTION

X11 .1 24 V (+)

.2 24 V (ground)

.3 grounding, carry out as short as possible

X1-X8 .1 jointly switchable ground potential

.2 RxD

.3 TxD

.4 ground

.5 separately switchable ground potential

.6 ground

.7 ground potential for shield connection

TAB. 1 CONNECTINg TERMINALS (OVERVIEw)

Connection diagram see page 44.

4.2 CONNECTINg A 24 V POwER SUPPLy· Switch off the main power supply including the external 24 V power source and make sure these cannot be accidentally switched back on again.

· Connect the external 24 V voltage supply (150 mA) to X11.1 (+) and X11.2 (-) (reverse polarity protection).

· ground the X11.3 terminal by as short a route as possible (for EMC reasons).

17

REMARk24 V DC power sourceSeveral bus modules can be operated with one power supply.· In cases of SELV (safety extra low voltages) do not ground the 24 V power source.

4.3 CONNECTINg ThE POwER CONTROLLER TO X1-X8· Switch off the main power supply including the external 24 V power source and make sure these cannot be accidentally switched back on again.

· Connect the interfaces X1 to X8 of the bus module to the system interfaces of the power controller (shielded four-wire cable)

Attention: To control all parameters by PROFINET we recommend closing the Thyro-A/Thyro-AX switches S1.3, S1.4, S1.5 (Thyro-Tool Mode).

4.4 CONNECTINg ThE EThERNET BUS MODULE TO ThE MASTERThe Ethernet bus module has two Ethernet ports which are equipped with a switch functionality which allows a line topology to be constructed.A standard patch cable is required for connecting with a switch. For a direct connection (line topology) a cross-over cable is required.

18

5. SETTINgS

5.1 SETTINg ThE PROTOCOLThe Ethernet bus module supports various real time Ethernet bus systems. The desired system can be selected using the rotary switch “Protocol”. For PROFINET this needs to be set to 0.

5.2 SETTINg ThE NUMBER OF SLOTSThe number of devices which are connected to the Ethernet bus module is set with the rotary switch “Slots”. After switching on, the Ethernet bus module reads all the parameters of the device. Following this it starts communicating.

Attention: To change the number of slots when switched on, the switch “Slots” must first be turned to 0. Communication with the master is then interrupted. Following this the desired number can be set. Afterleaving the position 0 you have about 2 seconds time for this.

5.3 SETTINg ThE DEVICE NAMEEvery IO device is identified by its device name. The setting of the device name can be undertaken using, for example, the program “Step 7 – hw Config” in the menu “Target system/Ethernet/Edit Ethernet participant…”

19

FIg. 1 CONFIgURATION & LED DISPLAyS

1 Terminal X1 10 Terminal X112 Terminal X2 11 SyS LED3 Terminal X3 12 COM0 (BF) LED4 Terminal X4 13 COM1 (SF) LED5 Terminal X5 14 Fault LED6 Terminal X6 15 Switch Slots7 Terminal X7 16 Switch Protocol8 Terminal X89 Ethernet Port

20

5.4 OPERATINg DISPLAy OF ThE BUS MODULE

LED COLOR STATUS MEANINg

SyS green On Operating system running

Red Flashing with 1 hz Error in boot process

Red On waiting for boot process (check posi-

tion of “Protocol” switch)

Off No supply voltage

COM0 (BF) Red On No physical connection

Red Flashing with 2 hz No data exchange

Off The device is exchanging data with

the PROFINET IO Controller

COM1 (SF) Red On watchdog time out or system error

Off No error

Fault Red On hardware error

TAB. 2 OPERATINg DISPLAy OF ThE BUS MODULE

OPERATINg STATUS OF ThE EThERNET BUS MODULE

LED COLOR STATUS MEANINg

Link green On There is an Ethernet connection

Activity yellow On Data are being exchanged via

Ethernet

STATUS LED OF ThE EThERNET PORTS

21

6. OPERATION

6.1 START CONFIgURATION (PARAMETERIzATION)Via the parameterization (in step 7 – hw Config, double-click on slot 0 of the bus module, parameter tab) the following settings can be undertaken.

No connection (slot 1-8):here you can set what should happen with the output data of the devices if the connection to the master is interrupted.hold last values The output data are not changed.Outputs = 0 The output data are set to 0.

No connection (slot 9):here you can set what should happen with the output data of the bus modu-le if the connection to the master is interrupted.hold last value The digital outputs are not changed.Outputs = 0 The digital outputs are set to 0.

Averaging of the measured values:here you can enter the number of actual values which flow into the ave-raging. A new value is calculated once a second. Values from 0-20 can be entered, whereby 0 or 1 deactivates this function.

Remove device when it is switched off:Not all devices are equipped with a 24 V supply connection. when switching off the Thyro mains supply and the control voltage supply (24 V) the Thyro no longer communicates with the bus modules. A switched off device will normally be displayed as pull. This display can be suppressed here.Deactivate Devices which are no longer accessible (no commu-

nication) will continue to be displayed as plug.Activate Devices which are no longer accessible will be

displayed as pull.

22

Use output data:The suppression of certain output data can be activated here.Always New output data are transferred immediately.Only when Bit is set New output data are only transferred, if the Bit

0 is set in the output “Functions”.ATTENTION If the setting of Thyro-A / Thyro-AX are changed with Thyro-Tool Family, then the new values are not automatically implemented into the bus module. To save the values permanently, the switch „slot“ shoudl be turned very shortly to 0 and back to its original position. Then the values are saved in the bus module.

6.2 CyCLICAL DATA TRANSMISSION (CONFIgURATION)The configuration of the cyclical data traffic is undertaken by adding modu-les.The input and output data depend on the device types. The following tables show the input and output data available for each of the devices.

6.3 INPUT AND OUTPUT DATA Thyro-Swith the Thyro-S the setpoint is interpreted as operating mode.

SETPOINT (MASTER) STATUS (RETURN VALUE) (TOTAL SETPOINT)

0 to 409 = OFF 0 =

410 to 1091 1/5 819

1092 to 1706 = 1/3 1365 =

1707 to 3071 1/2 2047

3072 to 4096 = ON 4096

TAB. 3 INTERPRETATION OF ThE MASTER SETPOINT wITh Thyro-S

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 Load voltage L1 float 4 [V]

4 Mains voltage L1 integer 2 [V]

6 Total setpoint integer 2 4096=100%

8 Fault (see table 5a) integer 2 -

10 Status (see table 5b) integer 2 -

23

OFFSET OUTPUT DATA, SETPOINT

DATA TyPE SIzE UNIT

0 Master Setpoint integer 2 4096=100%

TAB. 4 CyCLIC INPUT AND OUTPUT DATA wITh Thyro-S ..h1

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 Load voltage L1 float 4 [V]

4 Load current L1 float 4 [A]

8 Mains voltage L1 integer 2 [V]

10 Total setpoint integer 2 4096=100%

12 Fault (see table 5a) integer 2 -

14 Status (see table 5b) integer 2 -

OFFSET OUTPUT DATA, SETPOINT

DATA TyPE SIzE UNIT

0 Master setpoint integer 2 4096=100%

TAB. 5 CyCLIC INPUT AND OUTPUT DATA wITh Thyro-S ..hRL1

DESCRIPTION BIT LEDs RELAy

Frequency measurement

outside of 47 hz to 63 hz

Bit 0 TEST LED

flashing slowly

open

SyNC error, no zero-crossing

within the gate

Bit 1 TEST LED

flashing slowly

open

Temperature monitoring

triggered

Bit 2 Load Fault

flashing slowly

open

Load fault Bit 3 Load Fault on open

Flash values invalid Bit 4 Test LED and Load Fault

LED flashing simultane-

ously quickly

open

24

Mains undervoltage (<AD_P_

SPg_MIN)

Bit 5 Load Fault LED and Test

LED on

open

Mains overvoltage

(>AD_P_SPg_MAX)

Bit 6 None closed

TAB. 5A Thyro-S FAULTS

DESCRIPTION BIT LEDs RELAy

Pulse inhib active

(bridge X2.1-X2.2 open)

Bit 0 none open

Mains frequency is 60 hz Bit 2 none open

Relay status

(0=Relais off/1=Relais on)

Bit 8 none open

Device switched off Bit 9 - closed

wrong device Bit 10 - -

Bus module active (0=no bus

module/1=bus module active)

Bit 11 none -

Thyristor short-circuit Bit 14 Test LED and Load Fault

LED flashing alternately

slowly

-

TAB. 5B Thyro-S STATUS

6.4 INPUT AND OUTPUT DATA Thyro-A/Thyro-AX

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 Load voltage L1 float 4 [V]

4 Mains voltage L1 integer 2 [V]

6 Switch-on time TS integer 2 [period]

8 Switch-on angle alpha integer 2 [0.01 °el]

10 Total setpoint integer 2 4096=100%

25

12 Fault (see table 14a) integer 2 -

14 Status (see table 14b) integer 2 -

OFFSET OUTPUT DATA, SETPOINT

DATA TyPE SIzE UNIT

0 Master setpoint integer 2 4096=100%

TAB. 6 CyCLIC INPUT AND OUTPUT DATA wITh Thyro-A 1A...h1

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 Load voltage L1 float 4 [V]

4 Load current L1 float 4 [A]

8 Mains voltage L1 integer 2 [V]

10 Switch-on time TS integer 2 [period]

12 Switch-on angle alpha integer 2 [0.01 °el]

14 Total setpoint integer 2 4096=100%

16 Fault (see table 14a) integer 2 -

18 Status (see table 14b) integer 2 -

OFFSET OUTPUT DATA, SETPOINT

DATA TyPE SIzE UNIT

0 Master setpoint integer 2 4096=100%

TAB. 7 CyCLIC INPUT AND OUTPUT DATA wITh Thyro-A 1A...hRL1/ Thyro-AX 1A..hRL2

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 Load voltage L1 float 4 [V]

4 Load current L1 float 4 [A]

8 Power L1 float 4 [w]

12 Mains voltage L1 integer 2 [V]

14 Switch-on time TS integer 2 [period]

16 Switch-on angle alpha integer 2 [0.01 °el]

18 Total setpoint integer 2 4096=100%

20 Fault (see table 14a) integer 2 -

22 Status (see table 14b) integer 2 -

26

OFFSET OUTPUT DATA, SETPOINT

DATA TyPE SIzE UNIT

0 Master setpoint integer 2 4096=100%

TAB. 8 CyCLIC INPUT AND OUTPUT DATA wITh Thyro-A 1A...hRLP1/Thyro-AX 1A..hRLP2

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 Load voltage L1 float 4 [V]

4 Load voltage L3 float 4 [V]

8 Mains voltage L1 integer 2 [V]

10 Mains voltage L3 integer 2 [V]

12 Switch-on time TS integer 2 [period]

14 Total setpoint integer 2 4096=100%

16 Fault (see table 14a) integer 2 -

18 Status (see table 14b) integer 2 -

OFFSET OUTPUT DATA, SETPOINT

DATA TyPE SIzE UNIT

0 Master setpoint integer 2 4096=100%

TAB. 9 CyCLIC INPUT AND OUTPUT DATA wITh Thyro-A 2A...h1

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 Load voltage L1 float 4 [V]

4 Load voltage L3 float 4 [V]

8 Load current L1 float 4 [A]

12 Load current L2 float 4 [A]

16 Load current L3 float 4 [A]

20 Mains voltage L1 integer 2 [V]

22 Mains voltage L3 integer 2 [V]

24 Switch-on time TS integer 2 [period]

26 Total setpoint integer 2 4096=100%

28 Fault (see table 14a) integer 2 -

30 Status (see table 14b) integer 2 -

OFFSET OUTPUT DATA, SETPOINT

DATA TyPE SIzE UNIT

0 Master setpoint integer 2 4096=100%

TAB. 10 CyCLIC INPUT AND OUTPUT DATA wITh Thyro-A 2A...hRL1/ Thyro-AX 2A..hRL2

27

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 Load voltage L1 float 4 [V]

4 Load voltage L3 float 4 [V]

8 Load current L1 float 4 [A]

12 Load current L2 float 4 [A]

16 Load current L3 float 4 [A]

20 Power L1 float 4 [w]

24 Power L3 float 4 [w]

28 Total power float 4 [w]

32 Mains voltage L1 integer 2 [V]

34 Mains voltage L3 integer 2 [V]

36 Switch-on time TS integer 2 [period]

38 Total setpoint integer 2 4096=100%

40 Fault (see table 14a) integer 2 -

42 Status (see table 14b) integer 2 -

OFFSET OUTPUT DATA, SETPOINT

DATA TyPE SIzE UNIT

0 Master setpoint integer 2 4096=100%

TAB. 11 CyCLIC INPUT AND OUTPUT DATA wITh Thyro-A 2A...hRLP1/Thyro-AX 2A..hRLP2

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 Load voltage L1 float 4 [V]

4 Load voltage L2 float 4 [V]

8 Load voltage L3 float 4 [V]

12 Mains voltage L1 integer 2 [V]

14 Mains voltage L2 integer 2 [V]

16 Mains voltage L3 integer 2 [V]

18 Switch-on time TS integer 2 [period]

20 Switch-on angle alpha integer 2 [0.01 °el]

22 Total setpoint integer 2 4096=100%

24 Fault (see table 14a) integer 2 -

26 Status (see table 14b) integer 2 -

OFFSET OUTPUT DATA, SETPOINT

DATA TyPE SIzE UNIT

0 Master setpoint integer 2 4096=100%

TAB. 12 CyCLIC INPUT AND OUTPUT DATA wITh Thyro-A 3A...h1

28

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 Load voltage L1 float 4 [V]

4 Load voltage L2 float 4 [V]

8 Load voltage L3 float 4 [V]

12 Load current L1 float 4 [A]

16 Load current L2 float 4 [A]

20 Load current L3 float 4 [A]

24 Mains voltage L1 integer 2 [V]

26 Mains voltage L2 integer 2 [V]

28 Mains voltage L3 integer 2 [V]

30 Switch-on time TS integer 2 [period]

32 Switch-on angle alpha integer 2 [0.01 °el]

34 Total setpoint integer 2 4096=100%

36 Fault (see table 14a) integer 2 -

38 Status (see table 14b) integer 2 -

OFFSET OUTPUT DATA, SETPOINT

DATA TyPE SIzE UNIT

0 Master setpoint integer 2 4096=100%

TAB. 13 CyCLIC INPUT AND OUTPUT DATA wITh Thyro-A 3A...hRL1/Thyro-AX 3A..hRL2

29

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 Load voltage L1 float 4 [V]

4 Load voltage L2 float 4 [V]

8 Load voltage L3 float 4 [V]

12 Load current L1 float 4 [A]

16 Load current L2 float 4 [A]

20 Load current L3 float 4 [A]

24 Power L1 float 4 [w]

28 Power L2 float 4 [w]

32 Power L3 float 4 [w]

36 Total power float 4 [w]

40 Mains voltage L1 integer 2 [V]

42 Mains voltage L2 integer 2 [V]

44 Mains voltage L3 integer 2 [V]

46 Switch-on time TS integer 2 [period]

48 Switch-on angle alpha integer 2 [0.01 °el]

50 Total setpoint integer 2 4096=100%

52 Fault (see table 14a) integer 2 -

54 Status (see table 14b) integer 2 -

OFFSET OUTPUT DATA, SETPOINT

DATA TyPE SIzE UNIT

0 Master setpoint integer 2 4096=100%

TAB. 14 CyCLIC INPUT AND OUTPUT DATA wITh Thyro-A 3A...hRLP1/Thyro-AX 3A..hRLP2

30

DESCRIPTION BIT LEDs RELAy

Frequency measurement

outside of 47hz to 63 hz

Bit 0 Pulse Inhibit LED

flashing slowly

open

SyNC error, no cero

crossing within the gate

Bit 1 Pulse Inhibit LED

flashing slowly

open

Temperature monitoring

triggered

Bit 2 Load Fault LED

flashing slowly

open

Load fault Bit 3 Load fault LED on open

Flash values invalid Bit 4 Pulse Inhibit LED and Load

Fault LED flashing simulta-

neously qickly

open

Mains undervoltage

(<AD_P_SPg_MIN)

Bit 5 Pulse Inhibit LED, Load Fault

LED and test LED on

open

Mains overvoltage (>AD_P_

SPg_MAX)

Bit 6 none open

Master/slave fault

(only with Thyro-A 2A/

Thyro-AX 2A)

Bit 8 none closed

Umin Bit 9 none closed

Umax Bit 10 none closed

Imin Bit 11 none closed

Imax Bit 12 none closed

Pmin Bit 13 none closed

Pmax Bit 14 none closed

TAB. 14A Thyro-A/Thyro-AX FAULT

31

DESCRIPTION BIT LEDs RELAy

Pulse inhib active

(bridge X2.1-X2.2 open)

Bit 0 Pulse Inhibit LED on closed

Mains frequency is 60 hz Bit 2 none closed

U-limiting Bit 4 Pulse Inhibit LED and

Load Fault LED flashing

alternately slowly

closed

I-limiting Bit 5

Pulse Inhibit LED and Load

Fault LED flashing alterna-

tely slowly

closed

P-limiting Bit 6 Pulse Inhibit LED and Load

Fault LED flashing alterna-

tely slowly

closed

Relay status (0=Relais

off/1=Relais on)

Bit 8 none on/off

Device switched off Bit 9 - -

wrong device Bit 10 - -

Bus module active

(0=no bus module/

1=bus module active)

Bit 11 none closed

Thyristor short-circuit Bit 14 only with Thyro-S -

Failure rotating field/ phase

(only Thyro-A 2A or 3A/

Thyro-AX 2A or 3A)

Bit 15 Pulse Inhibit LED and Test

LED flashing

simultaneously slowly

closed

Imax (Internal) Bit 12 none closed

Pmin (Internal) Bit 13 none closed

Pmax (Internal) Bit 14 only with Thyro-A/Thyro-AX closed

TAB. 14B Thyro-A/Thyro-AX STATUS

32

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 Load voltage L1 float 4 [V]

4 Load current L1 float 4 [A]

8 Power L1 float 4 [w]

12 Mains voltage L1 integer 2 [V]

14 Switch-on time TS integer 2 [period]

16 Switch-on angle alpha integer 2 [0.01 °el]

18 Total setpoint integer 2 4096=100%

20 Fault (see table 14a) integer 2 -

22 Status (see table 14b) integer 2 -

OFFSET OUTPUT DATA, SETPOINT

DATA TyPE SIzE UNIT

0 Master setpoint integer 2 4096=100%

TAB. 15 CyCLIC INPUT AND OUTPUT DATA wITh Thyro-A 1A...C01

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 Load voltage phase 1 float 4 [V]

4 Load current phase 1 float 4 [A]

8 Load current phase 2 float 4 [A]

12 Total load current float 4 [A]

16 Mains voltage L1 integer 2 [V]

18 Switch-on angle alpha phase 1 integer 2 [0.01 °el]

20 Total setpoint integer 2 4096=100%

22 Fault (see table 14a) integer 2 -

24 Status (see table 14b) integer 2 -

OFFSET OUTPUT DATA, SETPOINT

DATA TyPE SIzE UNIT

0 Master setpoint integer 2 4096=100%

TAB. 16 CyCLIC INPUT AND OUTPUT DATA wITh Thyro-A 1A...C02

33

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 Load voltage L1 float 4 [V]

4 Load current L1 float 4 [A]

8 Power L1 float 4 [w]

12 Mains voltage L1 integer 2 [V]

14 Switch-on time TS integer 2 [period]

16 Switch-on angle alpha integer 2 [0.01 °el]

18 Total setpoint integer 2 4096=100%

20 Fault (see table 14a) integer 2 -

22 Status (see table 14b) integer 2 -

OFFSET OUTPUT DATA, SETPOINT

DATA TyPE SIzE UNIT

0 Master setpoint integer 2 4096=100%

TAB. 17 CyCLIC INPUT AND OUTPUT DATA wITh Thyro-A 1A...C03

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 Load voltage phase 1 float 4 [V]

4 Load current phase 1 float 4 [A]

8 Load current phase 2 float 4 [A]

12 Total load current float 4 [A]

16 Power phase 1 float 4 [w]

20 Power phase 2 float 4 [w]

24 Total power float 4 [w]

28 Mains voltage L1 integer 2 [V]

30 Switch-on angle alpha phase 1 integer 2 [0.01 °el]

32 Total setpoint integer 2 4096=100%

34 Fault (see table 14a) integer 2 -

36 Status (see table 14b) integer 2 -

OFFSET OUTPUT DATA, SETPOINT

DATA TyPE SIzE UNIT

0 Master setpoint integer 2 4096=100%

TAB. 18 CyCLIC INPUT AND OUTPUT DATA wITh Thyro-A 1A...C05

34

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 Load voltage L1 float 4 [V]

4 Load current L1 float 4 [A]

8 Power L1 float 4 [w]

12 Mains voltage L1 integer 2 [V]

14 Load temperature integer 2 [°C]

16 Switch-on angle alpha integer 2 [0.01 °el]

18 Total setpoint integer 2 4096=100%

20 Fault (see table 14a) integer 2 -

22 Status (see table 14b) integer 2 -

OFFSET OUTPUT DATA, SETPOINT

DATA TyPE SIzE UNIT

0 Master setpoint integer 2 4096=100%

TAB. 19 CyCLIC INPUT AND OUTPUT DATA wITh Thyro-A 1A...C07

Supported operating modes TPM; TSC; TMUwith the Thyro-Power Manager, Thyro-Step Controller and Thyro-Measure-ment Unit the input and output data are depend on the operating mode. The following table shows which operating mode the devices support.

TPM TSC TIO TMU

automatic manual

Thyro-Power Manager x x x x x

Thyro-Step Controller - - x x x

Thyro-Measurement Unit - - - x x

TAB. 20 SUPPORTED OPERATINg MODES

35

6.5 INPUT AND OUTPUT DATA Thyro-Power Manager

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 AC input 1 float 4 [A], [V]

4 AC input 2 float 4 [A], [V]

8 AC input 3 float 4 [A], [V]

12 Power float 4 [w]

16 Energy float 4 [kwh]

20 DC input 1 integer 2 4096=100%

22 DC input 2 integer 2 4096=100%

24 DC input 3 integer 2 4096=100%

26 Mains voltage integer 2 [V]

28 Period duration integer 2 [μs]

30 Temperature integer 2 [°C]

32 Fault (see table 25b) integer 2 -

34 Status (see table 25a) integer 2 -

TAB. 21 CyCLIC INPUT AND OUTPUT DATA TPM AUTOMATIC MODE

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 AC input 1 float 4 [A], [V]

4 AC input 2 float 4 [A], [V]

8 AC input 3 float 4 [A], [V]

12 Power float 4 [w]

16 Energy float 4 [kwh]

20 DC input 1 integer 2 4096=100%

22 DC input 2 integer 2 4096=100%

24 DC input 3 integer 2 4096=100%

26 Mains voltage integer 2 [V]

28 Period duration integer 2 [μs]

30 Temperature integer 2 [°C]

32 Fault (see table 25b) integer 2 -

34 Status (see table 25a) integer 2 -

TAB. 22 CyCLIC INPUT AND OUTPUT DATA TPM MANUAL MODE

36

6.6 INPUT AND OUTPUT DATA Thyro-Step Controller

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 AC input 1 float 4 [A], [V]

4 AC input 2 float 4 [A], [V]

8 AC input 3 float 4 [A], [V]

12 Power float 4 [w]

16 Energy float 4 [kwh]

20 DC input 1 integer 2 4096=100%

22 DC input 2 integer 2 4096=100%

24 DC input 3 integer 2 4096=100%

26 Mains voltage integer 2 [V]

28 Period duration integer 2 [μs]

30 Temperature integer 2 [°C]

32 Fault (see table 25b) integer 2 -

34 Status (see table 25a) integer 2 -

36 Analog output 4 integer 2 4096=100%

38 Steps integer 2 -

40 Total setpoint integer 2 4096=100%

OFFSET OUTPUT DATA, SETPOINT

DATA TyPE SIzE UNIT

0 Master setpoint integer 2 4096=100%

TAB. 23 CyCLIC INPUT AND OUTPUT DATA TSC MODE

37

6.7 INPUT AND OUTPUT DATA Thyro Input/Output Unit

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 AC input 1 float 4 [A], [V]

4 AC input 2 float 4 [A], [V]

8 AC input 3 float 4 [A], [V]

12 Power float 4 [w]

16 Energy float 4 [kwh]

20 DC input 1 integer 2 4096=100%

22 DC input 2 integer 2 4096=100%

24 DC input 3 integer 2 4096=100%

26 Mains voltage integer 2 [V]

28 Period duration integer 2 [μs]

30 Temperature integer 2 [°C]

32 Fault (see table 25b) integer 2 -

34 Status (see table 25a) integer 2 -

OFFSET OUTPUT DATA, SETPOINT

DATA TyPE SIzE UNIT

0 Digital output integer 2 -

2 Analog output 1 integer 2 4096=100%

4 Analog output 2 integer 2 4096=100%

6 Analog output 3 integer 2 4096=100%

8 Analog output 4 integer 2 4096=100%

10 Analog output 5 integer 2 4096=100%

12 Analog output 6 integer 2 4096=100%

TAB. 24 CyCLIC INPUT AND OUTPUT DATA TIO MODE

38

6.8 INPUT AND OUTPUT DATA Thyro-Measurement Unit

OFFSET INPUT DATA, ACTUAL VALUES

DATA TyPE SIzE UNIT

0 AC input 1 float 4 [A], [V]

4 AC input 2 float 4 [A], [V]

8 AC input 3 float 4 [A], [V]

12 Power float 4 [w]

16 Energy float 4 [kwh]

20 DC input 1 integer 2 4096=100%

22 DC input 2 integer 2 4096=100%

24 DC input 3 integer 2 4096=100%

26 Mains voltage integer 2 [V]

28 Period duration integer 2 [μs]

30 Temperature integer 2 [°C]

32 Fault (see table 25b) integer 2 -

34 Status (see table 25a) integer 2 -

TAB. 25 CyCLIC INPUT AND OUTPUT DATA TMU MODE

DESCRIPTION BIT FAULT LED, FAULT OUTPUT*

Frequency measurement outside of

47 hz to 63 hz

Bit 0 on

SyNC error, no cero crossing within the gate Bit 1 on

Temperature max. limit has been exceeded Bit 2 on

Temperature min. limit has been exceeded Bit 3 on

One or more parameters outside the limits Bit 4 on

Mains voltage lower than lower voltage limit Bit 5 on

TAB. 25A STATUS TPM, TSC, TIO, TMU

39

DESCRIPTION BIT ALARM LED, ALARM OUTPUT*

Mains frequency is 60 hz Bit 2 off

Transformer 1 fallen below min. limit Bit 3 on

Transformer 1 exceeded max. limit Bit 4 on

Transformer 2 fallen below min. limit Bit 5 on

Transformer 2 exceeded max. limit Bit 6 on

Transformer 3 fallen below min. limit Bit 7 on

Transformer 3 exceeded max. limit Bit 8 on

Device switched off Bit 9 -

wrong device Bit 10 -

Bus module active (0=no bus module/

1=bus module active)

Bit 11 off

TAB. 25B FAULT TPM, TSC, TIO, TMU

* Default setting can be parameterized.

6.9 ACyCLIC DATA TRANSMISSION (PARAMETERIzATION)Via the acyclic parameter data transmission, parameters of the devices can be changed or selected. Cyclical and acyclical services can be used in the network simultaneously.

Read data record “RDREC”:For reading access to a data record, the slot, index and length of the data record must be entered. At step 7 and when using the SFB 52 the Logical Address of the slot is to be entered instead of the slot. As suchthe device at slot X1 is to be activated as the device at slot 1.

ERROR CODE MEANINg

DE80B000 The unit does not recognize the parameter (invalid index)

DE80B100 The length entry of the parameter is incorrect

DE80B200 The actual unit type does not match the set unit type

DE80B300 The projected slot is not occupied

write data record “wRREC”:For writing access to a data record, the slot, index, length of the data record and the new value must be entered. At step 7 and when using the SFB 53 the Logical Address of the slot is to be entered instead of the slot.

40

ERROR CODE MEANINg

DF80B000 The unit does not recognize the parameter (invalid index)

DF80B100 The length entry of the parameter is incorrect

DF80B200 The projected slot is not occupied

DF80B300 The actual unit type does not match the set unit type

DF80B600 The parameter cannot be changed

DF80B700 Invalid range of values of a parameter

you will find the parameter tables (acyclic) of each of the device types in Appendix 17 (A).

41

7. EXTERNAL CONNECTIONS

7.1 POwER SUPPLy+24 V to X11, current consumption approx. 150 mA

The foregoing circuit diagram shows the connection of the bus module.

bridge (contact)Thyro-S: see chapter 3.1Thyro-A: see chapter 3.2TPM: see chapter 3.3

X1 - X8 to the power controllers

supply24 V DC (approx. 150 mA)

Thyro-A…h1…h RL1…h RLP1

Thyro-AX...h RL2...h RLP2

42

7.2 OPERATINg ELEMENTS AND TERMINAL BLOCkSThis chapter describes the available terminal blocks, plug connectors and operating elements.Configuration of the 7 pin connector of slots X1 to X8:1 Switched ground potential. All pins 1 of slots X1 – X8 are connec-

ted.2 RxD3 TxD4 ground5 Switchable ground potential. The slots X1 – X8 can be

switched as desired.6 ground7 ground potential for shield connection

Configuration of the 3 pin connector X11:X11: +24VX11: 24V - groundX11: grounding, cable should be as short as possible for EMC reasons

43

8. INTERFACES

8.1 SySTEM INTERFACEThe bus module is connected with the relevant system interfaces of the pow-er controllers via X1 to X8 (four-wire, 2x2 twisted, shared shielding).The transmission rate is 38,400 Bd.The asynchronous characters are transferred with 8bit, no parity, one stop bit. The protocol begins with STX, followed by an identifier, the data, and is concluded with a check sum. Defective protocols are ignored.

8.2 EThERNET INTERFACESCommunication medium CAT 5eNetwork topology tree, star and lineMaximum cable length 100 mPROFINET-participants restricted to the maximum supported num-

ber of devices by the controller usedPNO identification number 0x0188Device ID 0x0001Transmission rate 100 Mbit/s

44

9. CONNECTION DIAgRAMS Thyro-A/Thyro-AX

FIg. 2 CONNECTION DIAgRAM Thyro-A/Thyro-AX

45

10. CONNECTION DIAgRAMS Thyro-S

FIg. 3 CONNECTION DIAgRAM Thyro-S

46

11. CONNECTION DIAgRAMS TSC

FIg. 4 CONNECTION DIAgRAM ThyRO-STEP CONTROLLER

47

12. SPECIFIC NOTES

13. TEChNICAL DATA

12.1 INSTALLATIONThe Ethernet bus module PROFINET can be installed in any desired order.

12.2 SERVICEThe devices supplied have been produced in accordance with the quality standard ISO 9001. Should there be faults in spite of this, please contact our Advanced Energy team for assistance (see chapter CONTACT INFORMATION)..

Power supply 24 VDC (+/-20 %) 150 mAConnection options for up to 8 Advanced Energy power control-

lers of series Thyro-S, Thyro-A, Thyro-AX and the Thyro-Power Manager series

Function control LEDAssembly DIN railAmbient temperature maximum 55 °CDimensions (wxDxh): 150 x 60 x 95 mmweight circa: 0.35 kg

48

14. DIMENSION DRAwINgS

15. ACCESSORIES AND OPTIONS

Ready-made bus module-side shielded cable.A set of cable consists of 4 connection cables for connecting 4 power controllers.Order number 2000 000 848 Bus module connection cable for

4 controllers, 2.5 m longOrder number 2000 000 849 Bus module connection cable for

4 controllers, 1.5 m long

55 mm heightincl. cover

49

16. APPROVALS AND CONFORMITy

- quality standard in acc. with EN ISO 9001- CE conformity- PROFINET conformity- RohS compliant 5/6

DIRECTIVESThe CE mark on the device confirms compliance with the EC directives 2006/95/EEC for low voltage and 2004/108/EEC for electromagnetic compati-bility if the instructions on installation and commissioningdescribed in the operating instructions are followed.

In detail:

DEVICE APPLICATION CONDITIONS

PROFINET IEC 61158 IEC 61784Built-in device (VDE0160) EN 50 178Storage temperature (D) -25 °C - +55 °CTransport temperature -25 °C - +70 °COperating temperature (better B) -10 °C - +55 °Chumidity class B EN 50 178 tab. 7 (EN 60 721)Degree of contamination 2 EN 50 178 tab. 2Air pressure 900 mbar * 1000 m above sea levelDegree of protection IP00 EN 69 529EMC-testing EN 61000-6-2 (-4)Emitted interference CISPR 16Radiated immunity EN/IEC 61000-4-3Conducted immunity EN/IEC 61000-4-6ESD 8 kV (A) EN/IEC 61000-4-2Burst control lines 1 kV (A) EN 61000-4-4

5017

. APP

END

IX A

1. A

cycl

ic p

aram

eter

tabl

e Th

yro-

S; T

hyro

-A; T

hyro

-A C

01; T

hyro

-A C

02; T

hyro

-A C

03; T

hyro

-A C

05; T

hyro

-AX

CONT

ROLL

ER PA

RAM

ETER

1S1A

2A3A

1A

INDEX

SyM

BOL

NAM

EDA

TA

TyPE

VALU

E RAN

gECO

MBO

-OPT

UNIT

R/w

h1hRL1h1h RL1/h RL2h RLP1/h RLP2h1h RL1/h RL2h RLP1/h RLP2h1h RL1/h RL2h RLP1/h RLP2C01C02C03C05

DEFA

ULT

NOTE

INDE

X1

I_TyP

Cont

rolle

r typ

e cur

rent

u16

0…A

rx

xx

xx

xx

xx

xx

xx

xx

type

12

U_Ty

PCo

ntro

ller s

uppl

y vol

tage

u16

0…10

00V

rx

xx

xx

xx

xx

xx

xx

xx

type

23

P_Ty

PCo

ntro

ller t

ype o

utpu

t pow

eru3

20…

wr

xx

xx

xx

type

h RLP1

/h RLP2

36

BETR

Oper

atin

g mod

eu1

60…

3res

erved

, TAkT

, VA

R, qT

Mr/w

*x

xx

xx

xx

xx

xx

xx

TAkT

S1.1-

26

7AN

1Ph

ase a

ngle

of 1s

t half

wav

eu1

60…

180

˚el

r/w*

xx

xx

xx

xx

xx

x60

˚el

R201

78

Soft

start

dura

tion (

give

n)9

SDN

Soft

stop

dura

tion (

give

n)u1

60…

1000

perio

dr/w

xx

xx

xx

xx

xx

xx

x6 p

erio

d9

10T0

Cycle

per

iod

dura

tion

u16

0…10

00pe

riod

r/w*

xx

xx

xx

xx

xx

x50

per

iod

R201

1011

MP

Min

imum

inte

rval

u16

0…10

perio

dr/w

*x

xx

xx

xx

xx

xx

3 per

iod

R201

1112

TSM

AXM

axim

um cy

cle tu

rn on

time

u16

1…T0

perio

dr/w

xx

xx

xx

xx

xx

x50

per

iod

1213

TSM

INM

inim

um cy

cle tu

rn on

time

u16

0…T0

perio

dr/w

xx

xx

xx

xx

xx

x0 p

erio

d13

14V_

IEFr

ont p

ulse

stop

u16

0…18

0˚e

lr/w

xx

xx

xx

xx

xx

180˚

el14

15h_

IEBa

ck p

ulse

stop

u16

0…18

0˚e

lr/w

xx

xx

xx

xx

xx

0˚el

1516

RECo

ntro

l (ana

log o

utpu

t valu

e)u1

60…

8U loa

d2, U loa

d eff,

I load2,

I load eff

, res

erved

, real

powe

r, rese

rved,

reserv

ed, w

ith-ou

t reg

ulatio

n

r/w*

xx

xx

xx

xx

xx

xx

xUl

oad2

S1.3-

5 po

wer

only

with

h

RLP1

/ h

RLP2

16

17TI_

1PI

cont

rolle

r, I p

art

u16

0= off

0…65

535

r/wx

xx

xx

xx

xx

xx

xx

2017

18kP

_1PI

cont

rolle

r, P p

art

u16

0= off

0…65

535

r/wx

xx

xx

xx

xx

xx

xx

6018

19kR

_1PI

cont

rolle

r, cou

nter

P pa

rtu1

60…

6553

5r/w

xx

xx

xx

xx

xx

xx

x10

1920

V_IE_

2Fr

ont p

ulse

stop

pha

se 2

u16

0…18

0pe

riod

r/wx

x20

21UE

MA

Effec

tive v

oltag

e setp

oint m

axim

umu1

60…

0.1 V

r/w*

xx

xx

xx

xx

xx

xx

x44

0 VR 2

02 **

2122

IEMA

Effec

tive c

urren

t setp

oint m

axim

umu1

60…

0.1 A

r/w*

xx

xx

xx

xx

xx

110 A

R 203

2223

PMA

Powe

r set

poin

t max

imum

u32

0…w

r/w*

xx

xx

xx

0R 2

02 **

2324

Sw_E

NABL

ESe

tpoi

nt ac

tivat

ion

u16

0…3

Bit0=

1 setp

oint

x2.4

activ

e, Bit

1=1 s

etpoin

t ma

ster a

ctive

rx

xx

xx

xx

xx

xx

xx

xx

024

27Sw

_REg

LER

Setp

oint

x2.4

u16

0…40

96409

6=100

%r

xx

xx

xx

xx

xx

xx

xx

x27

28OF

_1Ac

tual

valu

e out

put o

ffset

1u1

60…

4096

20/409

6 mA

r/w*

xx

xx

xx

xx

xx

0 mA

S1.9

28

51

29FA

_1Sc

ale en

d valu

e actu

al valu

e outp

ut 1

u16

0…40

961/

819

r/w*

xx

xx

xx

xx

xx

1R 2

0429

30SP

g_M

INM

ains v

olta

ge m

onito

ring m

in.

u16

0…10

00V

r/wx

xx

xx

xx

xx

xx

xx

xx

type

3031

SPg_

MAX

Main

s vol

tage

mon

itorin

g max

.u1

60…

1000

Vr/w

x

xx

xx

xx

xx

xx

xx

xx

type

3132

UN_S

Unde

rcurre

nt m

onito

ring

u16

0…1

off, o

nr/w

*x

xx

xx

xx

xx

xx

offR 2

0532

33REL

AIS_CT

RL_2

Relay

confi

gura

tion 2

u16

0…65

535

bit c

oded

r/wx

xx

xx

xx

xx

x0

3334

LASTB

RUCh

_MI

N_AB

SLo

ad fa

ult, m

inim

um va

lue

u16

0…45

05100

/4096%

r/w*

xx

xx

xx

xx

xx

x0%

R 205

34

36Sy

NC_A

DRSy

nchr

o cyc

le ad

dres

su1

60…

6553

5pe

riod/

2r/w

xx

xx

xx

xx

xx

x10

036

37IM

ABPu

lse sw

itch-

off in

case

of fa

ilure

u16

0…65

535

bit c

oded

r/wx

xx

xx

xx

xx

xx

xx

037

38ST

A_RE

Contr

ol sta

rt con

troller

analo

g setp

oint

u16

0…65

535

20/409

6 mA

r/w*

xx

xx

xx

xx

xx

xx

x0 m

AS1

.638

39ST

E_RE

Contr

ol en

d con

trolle

r ana

log se

tpoint

u16

0…65

535

20/409

6 mA

r/wx

xx

xx

xx

xx

xx

xx

20 m

A39

40Co

nfigu

ratio

n 3A

u16

bit c

oded

r/wx

xx

4041

MOS

I_FA

Peak

curre

nt va

lue l

imit

u16

0…40

96r/w

xx

xx

xx

xx

xx

xx

xty

pe41

42DA

C_1_C

TRL

Analo

g out

put c

onfig

urat

ion 1

u16

0…10

r/wx

xx

xx

xx

xx

x6

4244

VERS

_TVe

rsion

day

u16

1…31

rx

xx

xx

xx

xx

xx

xx

xx

4445

VERS

_MVe

rsion

mon

thu1

61…

12r

xx

xx

xx

xx

xx

xx

xx

x45

46VE

RS_J

Versi

on ye

aru1

60…

9999

rx

xx

xx

xx

xx

xx

xx

xx

4648

Cont

rolle

r inhi

bit

u16

0…1

off, o

nr/w

xx

xx

xx

xx

xx

xx

xx

xoff

4849

RELA

IS_CT

RLRe

lay co

nfigu

ratio

n 1u1

60…

6553

5bi

t cod

edr/w

xx

xx

xx

xx

xx

447

4950

Save

u16

0…1

off, s

ave

r/wx

xx

xx

xx

xx

xx

xx

xx

off50

56M

ITTE

LAv

erag

ing a

nalo

g out

put 1

u16

0…65

535

r/wx

xx

xx

xx

xx

x10

056

84TE

MP

Tem

pera

ture

u16

-50…

150

°Cr

xx

xx

xx

xx

xx

xx

xx

x84

109

MIT

TEL_

2Av

erag

ing a

nalo

g out

put 2

u16

0…65

535

r/wx

x10

010

911

0OF

_2Ac

tual

valu

e out

put o

ffset

2u1

60…

4096

20/409

6 mA

r/wx

x0 m

AS1

.911

011

1FA

_2Sc

ale en

d valu

e actu

al va

lue ou

tput 2

u16

0…40

961/

819

r/wx

x1

R 204

111

112

DAC_

2_CTR

LAn

alog o

utpu

t con

figur

ation

2u1

60…

10r/w

xx

611

211

5M

ITTE

L_3

Avera

ging a

nalog

outp

ut 3

u16

0…65

535

r/wx

x10

011

511

6OF

_3Ac

tual

valu

e out

put o

ffset

3u1

60…

4096

20/409

6 mA

r/wx

x0 m

AS1

.911

611

7FA

_3Sc

ale en

d valu

e actu

al va

lue ou

tput 3

u16

0…40

961/

819

r/wx

x1

R 204

117

118

DAC_

3_CTR

LAn

alog o

utpu

t con

figur

ation

3u1

60…

10r/w

xx

611

811

9U_

MIN

Volta

ge lim

it min

imum

u16

0…65

535

0.1 V

r/wx

xx

xx

xx

xx

xx

119

120

U_M

AXVo

ltage

limit m

axim

umu1

60…

6553

50.1

Vr/w

xx

xx

xx

xx

xx

x12

012

1I_M

INCu

rrent

limit m

inim

umu1

60…

6553

50.1

Ar/w

xx

xx

xx

xx

121

122

I_MAX

Curre

nt lim

it max

imum

u16

0…65

535

0.1 A

r/wx

xx

xx

xx

x12

212

3P_

MIN

Powe

r lim

it min

imum

u32

0…w

r/wx

xx

xx

123

124

P_M

AXPo

wer li

mit m

axim

umu3

20…

wr/w

xx

xx

x12

4

TABL

E A:

Thy

ro-S

; Thy

ro-A

; Thy

ro-A

C01

; Thy

ro-A

C02

; Thy

ro-A

C03

; Thy

ro-A

C05

; Th

yRO

-AX

POw

ER C

ON

TRO

LLER

PA

RAM

ETER

S SL

OT

1-8

522.

Acy

clic

par

amet

er ta

ble

Thyr

o-A

C07

CONT

ROLL

ER PA

RAM

ETER

INDEX

SyM

BOL

NAM

EDA

TA Ty

PEVA

LUE R

ANgE

COM

BO-O

PTUN

ITR/

wDE

FAUL

TNO

TEIN

DEX

1I_T

yPCo

ntro

ller t

ype c

urre

ntu1

60…

Ar

type

12

U_Ty

PCo

ntro

ller s

uppl

y vol

tage

u16

0…10

00V

rty

pe2

3P_

TyP

Cont

rolle

r typ

e out

put p

ower

u32

0…w

rty

peh

RLP1

36

BETR

Oper

atin

g mod

eu1

60…

3re

serv

ed, T

AkT,

VAR,

qTM

r/w*

TAkT

S1.1-

26

7AN

1Ph

ase a

ngle

of 1s

t half

wav

eu1

60…

180

˚el

r/w*

60˚e

lR2

017

9SD

NSo

ft sto

p du

ratio

n (gi

ven)

u16

0…10

00pe

riod

r/w6 p

erio

d9

10T0

Cycle

per

iod

dura

tion

u16

0…10

00pe

riod

r/w*

50 p

erio

dR2

0110

11M

PM

inim

um in

terv

alu1

60…

10pe

riod

r/w*

3 per

iod

R201

1112

TSM

AXM

axim

um cy

cle tu

rn on

time

u16

1…T0

perio

dr/w

50 p

erio

d12

13TS

MIN

Min

imum

cycle

turn

on tim

eu1

60…

T0pe

riod

r/w0 p

erio

d13

14V_

IEFr

ont p

ulse

stop

u16

0…18

0˚e

lr/w

180˚

el14

15h_

IEBa

ck p

ulse

stop

u16

0…18

0˚e

lr/w

0˚el

1516

RECo

ntro

l (ana

log o

utpu

t valu

e)u1

60…

9Ul

oad2

, Uloa

d eff,

Iload

2, Ilo

ad eff

, rese

rved

, real

powe

r, res

erve

d, res

erve

d, wi

thou

t reg

ulatio

n, te

mpe

ratur

e

r/w*

Uloa

d2S1

.3-5 p

ower

only

with

h RL

P116

17TI_

1PI

cont

rolle

r, I p

art

u16

0= off

0…65

535

r/w20

1718

kP_1

PI co

ntro

ller, P

par

tu1

60=

off 0…

6553

5r/w

6018

19kR

_1PI

cont

rolle

r, cou

nter

P pa

rtu1

60…

6553

5r/w

1019

20Te

mpe

ratur

e coe

fficien

t of th

e hea

ting t

ape

u16

0…65

535

r/w20

21UE

MA

Effec

tive v

olta

ge se

tpoi

nt m

axim

umu1

60…

0.1 V

r/w*

440 V

R 202

**21

22IEM

AEff

ectiv

e cur

rent

setp

oint

max

imum

u16

0…0.1

Ar/w

*11

0 AR 2

0322

23PM

APo

wer s

etpo

int m

axim

umu3

20…

wr/w

*0

R 202

**23

24Sw

_ENA

BLE

Setp

oint

activ

atio

nu1

60…

3Bi

t0=1

setp

oint

x2.4

activ

e, Bi

t1=1

setp

oint

mas

ter

activ

e

r0

24

27Sw

_REg

LER

Setp

oint

x2.4

u16

0…40

9640

96=1

00%

r27

28OF

_1Ac

tual

valu

e out

put o

ffset

1u1

60…

4096

20/4

096m

Ar/w

*0 m

AS1

.928

29FA

_1Sc

ale en

d va

lue a

ctua

l valu

e out

put 1

u16

0…40

961/

819

r/w*

1R 2

0429

30SP

g_M

INM

ains v

olta

ge m

onito

ring m

in.

u16

0…10

00V

r/wty

pe30

53

31SP

g_M

AXM

ains v

olta

ge m

onito

ring m

ax.

u16

0…10

00V

r/w

type

3132

UN_S

Unde

rcurre

nt m

onito

ring

u16

0…1

off, o

nr/w

*off

R 205

3233

RELA

IS_CT

RL_2

Relay

confi

gura

tion 2

u16

0…65

535

bit c

oded

r/w0

3334

LAST

BRUC

h_M

IN_A

BSLo

ad fa

ult, m

inim

um va

lue

u16

0…45

0510

0/40

96%

r/w*

0%R 2

0534

36Sy

NC_A

DRSy

nchr

o cyc

le ad

dres

su1

60…

6553

5pe

riod/

2r/w

100

3637

IMAB

Pulse

switc

h-off

in ca

se of

failu

reu1

60…

6553

5bi

t cod

edr/w

037

38ST

A_RE

Cont

rol s

tart

cont

rolle

r ana

log s

etpo

int

u16

0…65

535

20/4

096 m

Ar/w

*0 m

AS1

.638

39ST

E_RE

Cont

rol e

nd co

ntro

ller a

nalo

g set

poin

tu1

60…

6553

520

/409

6 mA

r/w20

mA

3941

MOS

I_FA

Peak

curre

nt va

lue l

imit

u16

0…40

96r/w

type

4142

DAC_

1_CT

RLAn

alog o

utpu

t con

figur

atio

n 1u1

60…

11r/w

642

44VE

RS_T

Versi

on d

ayu1

61…

31r

4445

VERS

_MVe

rsion

mon

thu1

61…

12r

4546

VERS

_JVe

rsion

year

u16

0…99

99r

4648

Cont

rolle

r inhi

bit

u16

0…1

off, o

nr/w

off48

49RE

LAIS_

CTRL

Relay

confi

gura

tion 1

u16

0…65

535

bit c

oded

r/w44

749

50Sa

veu1

60…

1off

, sav

er/w

off50

56M

ITTE

LAv

erag

ing a

nalo

g out

put 1

u16

0…65

535

r/w10

056

84TE

MP

Tem

pera

ture

u16

-50…

150

°Cr

8410

9M

ITTE

L_2

Aver

agin

g ana

log o

utpu

t 2u1

60…

6553

5r/w

100

109

110

OF_2

Actu

al va

lue o

utpu

t offs

et 2

u16

0…40

9620

/409

6 mA

r/w0 m

AS1

.911

011

1FA

_2Sc

ale en

d va

lue a

ctua

l valu

e out

put 2

u16

0…40

961/

819

r/w1

R 204

111

112

DAC_

2_CT

RLAn

alog o

utpu

t con

figur

atio

n 2u1

60…

11r/w

611

211

5M

ITTE

L_3

Aver

agin

g ana

log o

utpu

t 3u1

60…

6553

5r/w

100

115

116

OF_3

Actu

al va

lue o

utpu

t offs

et 3

u16

0…40

9620

/409

6 mA

r/w0 m

AS1

.911

611

7FA

_3Sc

ale en

d va

lue a

ctua

l valu

e out

put 3

u16

0…40

961/

819

r/w1

R 204

117

118

DAC_

3_CT

RLAn

alog o

utpu

t con

figur

atio

n 3u1

60…

11r/w

611

811

9U_

MIN

Volta

ge lim

it min

imum

u16

0…65

535

0.1 V

r/w11

912

0U_

MAX

Volta

ge lim

it max

imum

u16

0…65

535

0.1 V

r/w12

012

1I_M

INCu

rrent

limit m

inim

umu1

60…

6553

50.1

Ar/w

121

122

I_MAX

Curre

nt lim

it max

imum

u16

0…65

535

0.1 A

r/w12

212

3P_

MIN

Powe

r lim

it min

imum

u32

0…w

r/w12

312

4P_

MAX

Powe

r lim

it max

imum

u32

0…w

r/w12

4

TABL

E B:

Thy

ro-A

C07

PO

wER

CO

NTR

OLL

ER P

ARA

MET

ERS

SLO

T 1-

8

543.

Acy

clic

par

amet

er ta

ble

Thyr

o-Po

wer

Man

ager

CONT

ROLL

ER PA

RAM

ETER

INDEX

SyM

BOL

NAM

EDA

TA Ty

PEVA

LUE R

ANgE

COM

BO-O

PTUN

ITR/

wDE

FAUL

TNO

TEIN

DEX

1w

1_Ty

PTy

pe va

lue t

rans

form

er 1

u16

1...65

535

r/w10

01

2w

2_Ty

PTy

pe va

lue t

rans

form

er 2

u16

1...65

535

r/w10

02

3w

3_Ty

PTy

pe va

lue t

rans

form

er 3

u16

1...65

535

r/w10

03

4w

_CTR

LTr

ansfo

rmer

setti

ngu1

60..

.6553

5bi

t cod

edr/w

84

5U_

TyP

Type

valu

e U m

ains

u16

1…26

0r/w

230

5

8AN

zNu

mbe

ru1

62…

10r/w

*10

S28

9T0

11s

t tim

e / p

hase

1u1

60…

T0r/w

09

10T0

22n

d tim

e / p

hase

2u1

60…

T0r/w

510

11T0

33r

d tim

e / p

hase

3u1

60…

T0r/w

1011

12T0

44t

h tim

e / p

hase

4u1

60…

T0r/w

1512

13T0

55t

h tim

e / p

hase

5u1

60…

T0r/w

2013

14T0

66t

h tim

e / p

hase

6u1

60…

T0r/w

2514

15T0

77t

h tim

e / p

hase

7u1

60…

T0r/w

3015

16T0

88t

h tim

e / p

hase

8u1

60…

T0r/w

3516

17T0

99t

h tim

e / p

hase

9u1

60…

T0r/w

4017

18T1

010

th tim

e / p

hase

10u1

60…

T0r/w

4518

39DA

C1_O

FOff

set 1

u16

0…40

9540

96 =

10 V

r/w0

3940

DAC1

_FA

Scale

end

valu

e 1u1

60…

4096

1 / 81

9r/w

819

4041

DAC1

_CTR

LOu

tput

valu

e 1u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

141

42DA

C2_O

FOff

set 2

u16

0…40

9540

96 =

10 V

r/w0

4243

DAC2

_FA

Scale

end

valu

e 2u1

60…

4096

1 / 81

9r/w

819

4344

DAC2

_CTR

LOu

tput

valu

e 2u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

244

45DA

C3_O

FOff

set 3

u16

0…40

9540

96 =

10 V

r/w0

4546

DAC3

_FA

Scale

end

valu

e 3u1

60…

4096

1 / 81

9r/w

819

4647

DAC3

_CTR

LOu

tput

valu

e 3u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

347

48DA

C4_O

FOff

set 4

u16

0…40

9540

96 =

10 V

r/w0

4849

DAC4

_FA

Scale

end

valu

e 4u1

60…

4096

1 / 81

9r/w

819

4950

DAC4

_CTR

LOu

tput

valu

e 4u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

450

55

51DA

C5_O

FOff

set 5

u16

0…40

9540

96 =

10 V

r/w0

5152

DAC5

_FA

Scale

end

valu

e 5u1

60…

4096

1 / 81

9r/w

819

5253

DAC5

_CTR

LOu

tput

valu

e 5u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

953

54DA

C6_O

FOff

set 6

u16

0…40

9540

96 =

10 V

r/w0

5455

DAC6

_FA

Scale

end

valu

e 6u1

60…

4096

1 / 81

9r/w

819

5556

DAC6

_CTR

LOu

tput

valu

e 6u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

1656

57DA

C_M

ITTE

LAv

erag

eu1

61…

6553

5r/w

100

5758

SPg_

MIN

Lowe

r lim

it main

s vol

tage

u16

0…51

20r/w

3473

5859

SPg_

MAX

Uppe

r lim

it main

s vol

tage

u16

0…51

20r/w

4541

5960

w1_

MAX

Limit t

rans

form

er 1

u16

0…81

92r/w

*51

18R3

1060

61w

2_M

AXLim

it tra

nsfo

rmer

2u1

60…

8192

r/w*

5118

R310

6162

w3_

MAX

Limit t

rans

form

er 3

u16

0…81

92r/w

*51

18R3

1062

63w

A_CT

RLMo

nitor

ing m

ode t

ransfo

rmer

u16

0...65

535

bit c

oded

r/w16

399

6364

Faul

t out

put

u16

0...65

535

bit c

oded

r/w12

764

66Al

arm

outp

utu1

60..

.6553

5bi

t cod

edr/w

504

6668

Vers_

DFir

mwa

re ve

rsion

day

u16

1…31

r68

69Ve

rs_M

Firm

ware

versi

on m

onth

u16

1…12

r69

70Ve

rs_y

Firm

ware

versi

on ye

aru1

60…

9999

r70

72Sa

veu1

60…

1off

, sav

er/w

072

74Op

erat

ing h

ours

f32

0…h

r74

76TE

MP_

MAX

Limiti

ng va

lue t

empe

ratu

reu1

60…

255

°Cr/w

8076

99En

ergy

f32

0…kw

hr

9910

5An

alog o

utpu

t 1u1

60…

4096

r10

510

6An

alog o

utpu

t 2u1

60…

4096

r10

610

7An

alog o

utpu

t 3u1

60…

4096

r10

710

8An

alog o

utpu

t 4u1

60…

4096

r10

810

9An

alog o

utpu

t 5u1

60…

4096

r10

911

0An

alog o

utpu

t 6u1

60…

4096

r11

012

1De

vice n

umbe

ru3

20…

r12

112

3Se

rial n

umbe

ru1

60…

r12

312

4PC

B num

ber

u32

0…r

124

126

F_M

IN_M

AXFr

eque

ncy l

imit

u16

100…

2500

r/w17

0912

612

7F_

TOL

Freq

uenc

y tol

eran

ceu1

61…

25%

r/w9

127

TABL

E C:

TPM

PA

RAM

ETER

S SL

OT

1-8

564.

Acy

clic

par

amet

er ta

ble

Thyr

o-St

ep C

ontr

olle

r

CONT

ROLL

ER PA

RAM

ETER

INDEX

SyM

BOL

NAM

EDA

TA Ty

PEVA

LUE R

ANgE

COM

BO-O

PTUN

ITR/

wDE

FAUL

TNO

TEIN

DEX

1w

1_Ty

PTy

pe va

lue t

rans

form

er 1

u16

1...65

535

r/w10

01

2w

2_Ty

PTy

pe va

lue t

rans

form

er 2

u16

1...65

535

r/w10

02

3w

3_Ty

PTy

pe va

lue t

rans

form

er 3

u16

1...65

535

r/w10

03

4w

_CTR

LTr

ansfo

rmer

setti

ngu1

60..

.6553

5r/w

84

5U_

TyP

Type

valu

e U ne

twor

ku1

61…

260

bit c

oded

r/w23

05

8AN

zNu

mbe

ru1

61…

11r/w

*11

S28

9S0

11s

t pha

seu1

61…

3276

8r/w

*29

789

10S0

22n

d ph

ase

u16

1…32

768

r/w*

5956

1011

S03

3rd

phas

eu1

61…

3276

8r/w

*89

3411

12S0

44t

h pha

seu1

61…

3276

8r/w

*11

912

1213

S05

5th p

hase

u16

1…32

768

r/w*

1489

013

14S0

66t

h pha

seu1

61…

3276

8r/w

*17

868

1415

S07

7th p

hase

u16

1…32

768

r/w*

2084

615

16S0

88t

h pha

seu1

61…

3276

8r/w

*23

824

1617

S09

9th p

hase

u16

1…32

768

r/w*

2680

217

18S1

010

th p

hase

u16

1…32

768

r/w*

2978

018

27Se

tpoi

nt ac

tivat

ion 1

u16

0…3

bit0=

1 setp

oint x

6.1 ac

tive,

bit1=

1 setp

oint m

aster

activ

er

2731

Cont

rol s

tart

setp

oint

1u1

60…

4096

20/4

096 m

Ar/w

031

32Co

ntro

l sto

p se

tpoi

nt 1

u16

0…40

9620

/409

6 mA

r/w40

9632

37Co

ntro

l sta

rt se

tpoi

nt 2

u16

0…40

9620

/409

6 mA

r/w0

3738

Cont

rol s

top

setp

oint

2u1

60…

4096

20/4

096 m

Ar/w

4096

3839

DAC1

_OF

Offse

t 1u1

60…

4095

4096

= 10

Vr/w

039

40DA

C1_F

ASc

ale en

d va

lue 1

u16

0…40

961 /

819

r/w81

940

41DA

C1_C

TRL

Outp

ut va

lue 1

u16

1…16

trans

forme

r1, tra

nsfor

mer2,

trans

forme

r3, U

mains

, setpo

int1,

setpo

int2,

R309

, R31

0, tem

p., re

s., co

ntroll

er1,…

, contr

oller6

r/w1

41

42DA

C2_O

FOff

set 2

u16

0…40

9540

96 =

10 V

r/w0

4243

DAC2

_FA

Scale

end

valu

e 2u1

60…

4096

1 / 81

9r/w

819

4344

DAC2

_CTR

LOu

tput

valu

e 2u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

244

45DA

C3_O

FOff

set 3

u16

0…40

9540

96 =

10 V

r/w0

4546

DAC3

_FA

Scale

end

valu

e 3u1

60…

4096

1 / 81

9r/w

819

4647

DAC3

_CTR

LOu

tput

valu

e 3u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

347

48DA

C4_O

FOff

set 4

u16

0…40

9540

96 =

10 V

r/w0

48

57

49DA

C4_F

ASc

ale en

d va

lue 4

u16

0…40

961 /

819

r/w81

949

50DA

C4_C

TRL

Outp

ut va

lue 4

u16

1…16

trans

forme

r1, tra

nsfor

mer2,

trans

forme

r3, U

mains

, setpo

int1,

setpo

int2,

R309

, R31

0, tem

p., re

s., co

ntroll

er1,…

, contr

oller6

r4

50

51DA

C5_O

FOff

set 5

u16

0…40

9540

96 =

10 V

r/w0

5152

DAC5

_FA

Scale

end

valu

e 5u1

60…

4096

1 / 81

9r/w

819

5253

DAC5

_CTR

LOu

tput

valu

e 5u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

953

54DA

C6_O

FOff

set 6

u16

0…40

9540

96 =

10 V

r/w0

5455

DAC6

_FA

Scale

end

valu

e 6u1

60…

4096

1 / 81

9r/w

819

5556

DAC6

_CTR

LOu

tput

valu

e 6u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

1656

57DA

C_M

ITTE

LAv

erag

eu1

61…

6553

5r/w

100

5758

SPg_

MIN

Lowe

r lim

it main

s vol

tage

u16

0…51

20r/w

3473

5859

SPg_

MAX

Uppe

r lim

it main

s vol

tage

u16

0…51

20r/w

4541

5960

w1_

MAX

Limit t

rans

form

er 1

u16

0…81

92r/w

*51

18R3

1060

61w

2_M

AXLim

it tra

nsfo

rmer

2u1

60…

8192

r/w*

5118

R310

6162

w3_

MAX

Limit t

rans

form

er 3

u16

0…81

92r/w

*51

18R3

1062

63w

A_CT

RLMo

nitor

ing m

ode t

ransfo

rmer

u16

0...65

535

bit c

oded

r/w16

399

6364

Faul

t out

put

u16

0...65

535

bit c

oded

r/w12

764

66Al

arm

outp

utu1

60..

.6553

5bi

t cod

edr/w

504

6668

Vers_

DFir

mwa

re ve

rsion

day

u16

1…31

r68

69Ve

rs_M

Firm

ware

versi

on m

onth

u16

1…12

r69

70Ve

rs_y

Firm

ware

versi

on ye

aru1

60…

9999

r70

72Sa

veu1

60…

1off

, sav

er/w

072

74Op

erat

ing h

ours

f32

0…h

r74

76TE

MP_

MAX

Limiti

ng va

lue t

empe

ratu

reu1

60…

255

°Cr/w

8076

99En

ergy

f32

0…kw

hr

9910

5An

alog o

utpu

t 1u1

60…

4096

r10

510

6An

alog o

utpu

t 2u1

60…

4096

r10

610

7An

alog o

utpu

t 3u1

60…

4096

r10

710

8An

alog o

utpu

t 4u1

60…

4096

r10

810

9An

alog o

utpu

t 5u1

60…

4096

r10

911

0An

alog o

utpu

t 6u1

60…

4096

r11

011

9DC

inpu

t 3 (x

5.10)

u16

0…40

9640

96=1

00%

r11

912

1De

vice n

umbe

ru3

20…

r12

112

3Se

rial n

umbe

ru1

60…

r12

312

4PC

B num

ber

u32

0…r

124

126

F_M

IN_M

AXFr

eque

ncy l

imit

u16

100…

2500

r/w17

0912

612

7F_

TOL

Freq

uenc

y tol

eran

ceu1

61…

25%

r/w9

127

TABL

E D

: TSC

PA

RAM

ETER

S SL

OT

1-8

585.

Acy

clic

par

amet

er ta

ble

Thyr

o-M

easu

rem

ent U

nit

CONT

ROLL

ER PA

RAM

ETER

INDEX

SyM

BOL

NAM

EDA

TA Ty

PEVA

LUE R

ANgE

COM

BO-O

PTUN

ITR/

wDE

FAUL

TNO

TEIN

DEX

1w

1_Ty

PTy

pe va

lue t

rans

form

er 1

u16

1...65

535

r/w10

01

2w

2_Ty

PTy

pe va

lue t

rans

form

er 2

u16

1...65

535

r/w10

02

3w

3_Ty

PTy

pe va

lue t

rans

form

er 3

u16

1...65

535

r/w10

03

4w

_CTR

LTr

ansfo

rmer

setti

ngu1

60..

.6553

5bi

t cod

edr/w

84

5U_

TyP

Type

valu

e U ne

twor

ku1

61…

260

r/w23

05

7T0

Mea

surin

g and

cycle

time

u16

1…15

00r/w

*50

R309

739

DAC1

_OF

Offse

t 1u1

60…

4095

4096

= 10

Vr/w

039

40DA

C1_F

ASc

ale en

d va

lue 1

u16

0…40

961 /

819

r/w81

940

41DA

C1_C

TRL

Outp

ut va

lue 1

u16

1…16

trans

forme

r1, tra

nsfor

mer2,

trans

forme

r3, U

mains

, setpo

int1,

setpo

int2,

R309

, R31

0, tem

p., re

s., co

ntroll

er1,…

, contr

oller6

r/w1

41

42DA

C2_O

FOff

set 2

u16

0…40

9540

96 =

10 V

r/w0

4243

DAC2

_FA

Scale

end

valu

e 2u1

60…

4096

1 / 81

9r/w

819

4344

DAC2

_CTR

LOu

tput

valu

e 2u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

244

45DA

C3_O

FOff

set 3

u16

0…40

9540

96 =

10 V

r/w0

4546

DAC3

_FA

Scale

end

valu

e 3u1

60…

4096

1 / 81

9r/w

819

4647

DAC3

_CTR

LOu

tput

valu

e 3u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

347

48DA

C4_O

FOff

set 4

u16

0…40

9540

96 =

10 V

r/w0

4849

DAC4

_FA

Scale

end

valu

e 4u1

60…

4096

1 / 81

9r/w

819

4950

DAC4

_CTR

LOu

tput

valu

e 4u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

450

51DA

C5_O

FOff

set 5

u16

0…40

9540

96 =

10 V

r/w0

5152

DAC5

_FA

Scale

end

valu

e 5u1

60…

4096

1 / 81

9r/w

819

5253

DAC5

_CTR

LOu

tput

valu

e 5u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

953

54DA

C6_O

FOff

set 6

u16

0…40

9540

96 =

10 V

r/w0

5455

DAC6

_FA

Scale

end

valu

e 6u1

60…

4096

1 / 81

9r/w

819

5556

DAC6

_CTR

LOu

tput

valu

e 6u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

1656

57DA

C_M

ITTE

LAv

erag

eu1

61…

6553

5r/w

100

5758

SPg_

MIN

Lowe

r lim

it main

s vol

tage

u16

0…51

20r/w

3473

5859

SPg_

MAX

Uppe

r lim

it main

s vol

tage

u16

0…51

20r/w

4541

5960

w1_

MAX

Limit t

rans

form

er 1

u16

0…81

92r/w

*51

18R3

1060

59

61w

2_M

AXLim

it tra

nsfo

rmer

2u1

60…

8192

r/w*

5118

R310

6162

w3_

MAX

Limit t

rans

form

er 3

u16

0…81

92r/w

*51

18R3

1062

63w

A_CT

RLMo

nitor

ing m

ode t

ransfo

rmer

u16

0...65

535

bit c

oded

r/w16

399

6364

Faul

t out

put

u16

0...65

535

bit c

oded

r/w12

764

66Al

arm

outp

utu1

60..

.6553

5bi

t cod

edr/w

504

6668

Vers_

DFir

mwa

re ve

rsion

day

u16

1…31

r68

69Ve

rs_M

Firm

ware

versi

on m

onth

u16

1…12

r69

70Ve

rs_y

Firm

ware

versi

on ye

aru1

60…

9999

r70

72Sa

veu1

60…

1off

, sav

er/w

072

74Op

erat

ing h

ours

f32

0…h

r74

76TE

MP_

MAX

Limiti

ng va

lue t

empe

ratu

reu1

60…

255

°Cr/w

8076

99En

ergy

f32

0…kw

hr

9910

5An

alog o

utpu

t 1u1

60…

4096

r10

510

6An

alog o

utpu

t 2u1

60…

4096

r10

610

7An

alog o

utpu

t 3u1

60…

4096

r10

710

8An

alog o

utpu

t 4u1

60…

4096

r10

810

9An

alog o

utpu

t 5u1

60…

4096

r10

911

0An

alog o

utpu

t 6u1

60…

4096

r11

011

9DC

inpu

t 3 (x

5.10)

u16

0…40

9640

96=1

00%

r11

912

1De

vice n

umbe

ru3

20…

r12

112

3Se

rial n

umbe

ru1

60…

r12

312

4PC

B num

ber

u32

0…r

124

126

F_M

IN_M

AXFr

eque

ncy l

imit

u16

100…

2500

r/w17

0912

612

7F_

TOL

Freq

uenc

y tol

eran

ceu1

61…

25%

r/w9

127

TABL

E E:

TM

U P

ARA

MET

ERS

SLO

T 1-

8

606.

Acy

clic

par

amet

er ta

ble

Thyr

o In

put-

Out

put U

nit

CONT

ROLL

ER PA

RAM

ETER

INDEX

SyM

BOL

NAM

EDA

TA Ty

PEVA

LUE R

ANgE

COM

BO-O

PTUN

ITR/

wDE

FAUL

TNO

TEIN

DEX

1w

1_Ty

PTy

pe va

lue t

rans

form

er 1

u16

1...65

535

r/w10

01

2w

2_Ty

PTy

pe va

lue t

rans

form

er 2

u16

1...65

535

r/w10

02

3w

3_Ty

PTy

pe va

lue t

rans

form

er 3

u16

1...65

535

r/w10

03

4w

_CTR

LTr

ansfo

rmer

setti

ngu1

60..

.6553

5bi

t cod

edr/w

84

5U_

TyP

Type

valu

e U m

ains

u16

1…26

0r/w

230

57

T0M

easu

ring a

nd cy

cle tim

eu1

61…

1500

r/w*

50R3

097

39DA

C1_O

FOff

set 1

u16

0…40

9540

96 =

10 V

r/w0

3940

DAC1

_FA

Scale

end

valu

e 1u1

60…

4096

1 / 81

9r/w

819

4041

DAC1

_CTR

LOu

tput

valu

e 1u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

141

42DA

C2_O

FOff

set 2

u16

0…40

9540

96 =

10 V

r/w0

4243

DAC2

_FA

Scale

end

valu

e 2u1

60…

4096

1 / 81

9r/w

819

4344

DAC2

_CTR

LOu

tput

valu

e 2u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

244

45DA

C3_O

FOff

set 3

u16

0…40

9540

96 =

10 V

r/w0

4546

DAC3

_FA

Scale

end

valu

e 3u1

60…

4096

1 / 81

9r/w

819

4647

DAC3

_CTR

LOu

tput

valu

e 3u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

347

48DA

C4_O

FOff

set 4

u16

0…40

9540

96 =

10 V

r/w0

4849

DAC4

_FA

Scale

end

valu

e 4u1

60…

4096

1 / 81

9r/w

819

4950

DAC4

_CTR

LOu

tput

valu

e 4u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

450

51DA

C5_O

FOff

set 5

u16

0…40

9540

96 =

10 V

r/w0

5152

DAC5

_FA

Scale

end

valu

e 5u1

60…

4096

1 / 81

9r/w

819

5253

DAC5

_CTR

LOu

tput

valu

e 5u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

953

54DA

C6_O

FOff

set 6

u16

0…40

9540

96 =

10 V

r/w0

5455

DAC6

_FA

Scale

end

valu

e 6u1

60…

4096

1 / 81

9r/w

819

5556

DAC6

_CTR

LOu

tput

valu

e 6u1

61…

16tra

nsfor

mer1,

trans

forme

r2, tra

nsfor

mer3,

U ma

ins, se

tpoint

1, set

point

2, R3

09, R

310,

temp.,

res.,

contr

oller1

,…, co

ntroll

er6r/w

1656

57DA

C_M

ITTE

LAv

erag

eu1

61…

6553

5r/w

100

5758

SPg_

MIN

Lowe

r lim

it main

s vol

tage

u16

0…51

20r/w

3473

5859

SPg_

MAX

Uppe

r lim

it main

s vol

tage

u16

0…51

20r/w

4541

5960

w1_

MAX

Limit t

rans

form

er 1

u16

0…81

92r/w

*51

18R3

1060

61

61w

2_M

AXLim

it tra

nsfo

rmer

2u1

60…

8192

r/w*

5118

R310

6162

w3_

MAX

Limit t

rans

form

er 3

u16

0…81

92r/w

*51

18R3

1062

63w

A_CT

RLMo

nitor

ing m

ode t

ransfo

rmer

u16

0...65

535

bit c

oded

r/w16

399

6364

Faul

t out

put

u16

0...65

535

bit c

oded

r/w12

764

66Al

arm

outp

utu1

60..

.6553

5bi

t cod

edr/w

504

6668

Vers_

DFir

mwa

re ve

rsion

day

u16

1…31

r68

69Ve

rs_M

Firm

ware

versi

on m

onth

u16

1…12

r69

70Ve

rs_y

Firm

ware

versi

on ye

aru1

60…

9999

r70

72Sa

veu1

60…

1off

, sav

er/w

072

74Op

erat

ing h

ours

f32

0…h

r74

76TE

MP_

MAX

Limiti

ng va

lue t

empe

ratu

reu1

60…

255

°Cr/w

8076

99En

ergy

f32

0…kw

hr

9910

5An

alog o

utpu

t 1u1

60…

4096

r10

510

6An

alog o

utpu

t 2u1

60…

4096

r10

610

7An

alog o

utpu

t 3u1

60…

4096

r10

710

8An

alog o

utpu

t 4u1

60…

4096

r10

810

9An

alog o

utpu

t 5u1

60…

4096

r10

911

0An

alog o

utpu

t 6u1

60…

4096

r11

011

9DC

inpu

t 3 (x

5.10)

u16

0…40

9640

96=1

00%

r11

912

1De

vice n

umbe

ru3

20…

r12

112

3Se

rial n

umbe

ru1

60…

r12

312

4PC

B num

ber

u32

0…r

124

126

F_M

IN_M

AXFr

eque

ncy l

imit

u16

100…

2500

r/w17

0912

612

7F_

TOL

Freq

uenc

y tol

eran

ceu1

61…

25%

r/w9

127

TABL

E F:

TIO

PA

RAM

ETER

S SL

OT

1-8

62

world headquarters

1625 Sharp Point Drive

Fort Collins, CO 80525 USA

970.221.4670 Main

970.221.5583 Fax

www.advanced-energy.com

Specifications are subject to change without notice.

© 2014 Advanced Energy Industries, Inc. All rights reserved. Advanced Energy® and Thyro-S™, Thyro-A™, Thyro-AX™ are trademarks of Advanced Energy Industries, Inc.

63