bubble column humidification dehumidification desalination system

67
Development of a Multi-Stage Bubble Column Dehumidifier for Application in a Humidification Dehumidification Desalination System by Steven Lam Submitted to the Department of Mechanical Engineering in partial fulfillment of the requirements for the degree of Bachelor of Science in Mechanical Engineering at the MASSACHUSETTS INSTITUTE OF TECHNOLOGY June 2012 © Massachusetts Institute of Technology 2012. All rights reserved. Author . Department of Mechanical Engineering May 24,2012 Certified by . John H. Lienhard V Samuel C. Collins Professor of Mechanical Engineering Thesis Supervisor Accepted by . John H. Lienhard V Samuel C. Collins Professor of Mechanical Engineering Undergraduate Officer

Upload: annjoe-mathews

Post on 28-Dec-2015

139 views

Category:

Documents


9 download

DESCRIPTION

HDH desalination systems.

TRANSCRIPT

Page 1: Bubble column humidification dehumidification desalination system

Development of a Multi-Stage Bubble Column

Dehumidifier for Application in a Humidification

Dehumidification Desalination System

by

Steven Lam

Submitted to the Department of Mechanical Engineeringin partial fulfillment of the requirements for the degree of

Bachelor of Science in Mechanical Engineering

at the

MASSACHUSETTS INSTITUTE OF TECHNOLOGY

June 2012

© Massachusetts Institute of Technology 2012. All rights reserved.

Author .Department of Mechanical Engineering

May 24,2012

Certified by .John H. Lienhard V

Samuel C. Collins Professor of Mechanical EngineeringThesis Supervisor

Accepted by .John H. Lienhard V

Samuel C. Collins Professor of Mechanical EngineeringUndergraduate Officer

Page 2: Bubble column humidification dehumidification desalination system

2

Page 3: Bubble column humidification dehumidification desalination system

Development of a Multi-Stage Bubble Column Dehumidifier

for Application in a Humidification Dehumidification

Desalination System

by

Steven Lam

Submitted to the Department of Mechanical Engineeringon May 24, 2012, in partial fulfillment of the

requirements for the degree ofBachelor of Science in Mechanical Engineering

Abstract

The Center for Clean Water and Clean Energy at MIT and KFUPM have been de­veloping many novel desalination systems. One of the new technologies originatingfrom the Lienhard Research Laboratory is the Humidification Dehumidification de­salination system, or HDH. In many ways HDH resembles the natural rain cyclefor producing fresh water, in that sea water is evaporated from oceans into humidair that travels up into the atmosphere, before condensing and producing precipita­tion. That precipitation is then collected as fresh drinking water. One of the mainhindrances with carrier gas based desalination systems over traditional thermal de­salination systems like multi-flash distillation (MSF) systems is that there is a largethermal resistance in the dehumidifier between the carrier gas and the condensingcoils resulting in poor heat transfer rates. The proposed solution is to create a bub­ble column for improved condensation. The condensing coil will be submerged in abody of water while humid air is sent through a sieve plate to create bubbles in thisbody of water where it will condense directly. Firstly, a single stage bubble columnwas designed, built, modeled, and tested. The model theoretically predicts the effectsof bubble diameter, superficial velocity, liquid height in column, inlet mole fractionof vapor, impact on coils, and particle integration. Through experimentation it wasshown that it was possible to achieve heat transfer rates of of 4 kW1m2 up to 20kW1m2

; rates that are 10 to 30 times that of existing state-of-the-art dehumidifiers.Secondly, a multi stage bubble column was designed, built, modeled, and tested in afull HDH system. Multi-staging is done to improve the effectiveness of the system.A three stage column was able to achieve an effectiveness of 89.4%.

Thesis Supervisor: John H. Lienhard VTitle: Samuel C. Collins Professor of Mechanical Engineering

3

Page 4: Bubble column humidification dehumidification desalination system

4

Page 5: Bubble column humidification dehumidification desalination system

Acknowledgments

This project was a large undertaking that required hard work and numerous late

nights. However, there would not be anything without the help and guidance of

numerous people.

First of all I'd like to thank my dear friend Seth Berg. He has always been excited

and encouraging when I talked about my project. He also took a lot of time off during

finals week to review my thesis.

I'd like to thank the great folks at the Edgerton Machine Shop, Mark Belanger

and Josh Dittrich, and the folks at the Hobby Shop, Ken Stone, Hayami Arakawa,

and Brian Chan. There were several steps in building these large systems; the first

one being the design and the second is the fabrication of the design. These great folks

were always available to give me advice on how to properly machine my parts.

I'd like to thank Karan Mistry and Ronan McGovern of the Rohenshow Kendall

Lab for their helpful tips and positive encouragement. Ronan was one of the first

people that I had ever met in the lab and made me feel welcomed to be there. Karan

was always friendly and would later be my 2.006 recitation instructor. He taught me

core principles of 2.006 but more importantly helped me appreciate Thermal Fluid

Mechanics.

I'd like to thank Professor Mostafa H. Sharqawy from KFUPM and Dr. Fahad

AI-Sulaiman. Mostafa was integral in the development of the first single stage bubble

column. His column designs and experimental setup were the key initial components

that allowed the project to flourish. Mostafa provided a lot of guidance in the devel­

oping our first setup and gave me the encouragement to become heavily involved in

this group. Fahad helped me design the humidification system needed for our multi­

stage setup. With his proficiency in thermal systems he made suggestions about the

design of the humidification system that made it much more effective.

I'd like to thank Max St. John and Victor Nevarez for their assistance and com­

pany. As UROPs and thesis students we have worked on many different structures

side-by-side. Due to a lot of similarities between our projects we have ended sharing

5

Page 6: Bubble column humidification dehumidification desalination system

a lot of components and setups. Whenever I needed an extra hand both of you were

always willing to help out. In addition, your humorous company has made the work

all the more enjoyable.

I'd like to thank Professor John H. Lienhard V for all his knowledgeable input on

this project. As a leader in desalination technologies his expert advice has directed

my project in positive directions that has led to a lot of profound results in what I

would consider a very short amount of time.

Finally, and most importantly, I'd like to thank Prakash Govindan for his mentor­

ship in this project. It would not be an understatement to say that without Prakash

there would not be a project and we would not have made as many discoveries as we

have made. His constant supervision mixed with his leisure attitude allowed us to

make progress at an astounding pace. He gave me the perfect amount of supervision

and freedom. I was allowed to design the systems as I thought would best suit the

experiments and allowed to make mistakes and learn from my errors, and I can say

a lot of errors and oversights were made. That type of freedom shows that you were

confident in my abilities which gave me confidence to attack the problems in front of

us. I look forward to working together in the future and see what fortunes await us.

Thank you everyone.

6

Page 7: Bubble column humidification dehumidification desalination system

Contents

1 Introduction

1.2 Conventional Desalination Technologies .

1.2.1 Multi-Stage Flash Desalination

1.2.2 Reverse Osmosis Desalination .

1.1 Motivation for Desalination

17

18

19

19

20

2 Humidification Dehumidification Desalination

2.1 Overview.

2.2 Benefits

2.3 Demerits.

3 Single Stage Bubble Column

3.1 Overall Concept .

3.2 Design ....

3.2.1 Frame

3.2.2 Sieve Plate Profile

3.2.3 Coil Designs .

3.2.4 Humidifier ..

3.2.5 Experimental Setup.

3.3 Analysis

3.4 Results.

3.4.1 Bubble Diameter

3.4.2 Superficial Velocity

7

23

23

24

25

27

27

29

29

30

32

32

34

36

38

38

39

Page 8: Bubble column humidification dehumidification desalination system

3.4.3 Liquid Height in Column. . . 40

3.4.4 Inlet Mole Fraction of Vapor . 41

3.4.5 Impact . 41

3.4.6 Particles 42

3.4.7 Others Variables 43

4 Multi Stage 45

4.1 Overall Concept . 45

4.2 Analysis 47

4.3 Design 49

4.3.1 Column 49

4.3.2 Sparger Plate 51

4.3.3 Coils ..... 52

4.3.4 Air Chamber 53

4.3.5 Humidifier .. 53

4.3.6 Experimental Setup. 54

4.4 Results ............ 55

4.4.1 Temperature Profiles 55

4.4.2 Effectiveness. . . . 56

4.4.3 Column Diameter . 56

4.5 Cost .......... 57

5 Conclusion 59

A CAD Drawings 61

B Tables 63

8

Page 9: Bubble column humidification dehumidification desalination system

List of Figures

1-1 Water scarcity across the globe [3] . . . . . . . . . . . . . . . . . . 18

1-2 Schematic diagram for a multi stage flash desalination system [10] 20

1-3 Depiction of a Reverse Osmosis membrane . . . . . . . . . . . . . 21

2-1 Schematic diagram of a closed loop HDH system [9] 24

3-1 Schematic diagram for a single stage bubble columnaiche 28

3-2 Resistance model for a bubble column heat exchanger [6] 29

3-3 Left: CAD depiction of tank. Right: Actual fabricated tank. 30

3-4 Mott Corp. 2240-AI6-10-AOO-I0-AB Precision Sparger Element with

connector fitting. . . . . . . . . . . . . . . . . . . . . . . . . . . . .. 31

3-5 Left: Cad model with no.2 sparger plate. Right: Actual fabricated

sparger box with no.5 sparger plate. . . . . 31

3-6 Left: Circular design Right: Serpentine design 32

3-7 Left: Bubbles avoid impacting the coils Right: Bubbles makes several

impacts while rising. . . . . . . . . . . . . . . 33

3-8 Schematic diagram of the humidification tank. 33

3-9 Left: The humidification tank with C-clamps sealing the tank. Right:

Inside of tank. Note that the water is not boiling. 34

3-10 Schematic diagram of test apparatus [6] . 35

3-11 Single stage bubble column HDH setup . 35

3-12 Chart for humidity ratios that vary with temperature [2] 37

3-13 Effect of bubble diameter on the total heat flux in the bubble column 39

3-14 Effect of superficial velocity on the total heat flux in the bubble column 40

9

Page 10: Bubble column humidification dehumidification desalination system

3-15 Effect of inlet mole fraction on the total heat flux in the bubble column 41

3-16 Effect of impact on the total heat flux in the bubble column . . . .. 42

4-1 Left: Parallel flow Right: Counterflow. . . . . . . . . . . . . 46

4-2 Left: Parallel Heat Exchanger Right: Counterflow Heat Exchanger. 46

4-3 Different counterflow temperature profiles 48

4-4 Counterflow exchanger with poor effectiveness 48

4-5 Multistage parallel flow temperature profiles . 49

4-6 Left: CAD model w/ 1 stage Right: Fabricated model w/ 2 stages and

insulation . . . . . . . 50

4-7 Circular sparger plate. 51

4-8 MS coil designs . . 52

4-9 MS coil side profile 53

4-10 MS humidifier showing the spray nozzle and platform 54

4-11 Schematic diagram of MS system and instrumental layout 55

4-12 Effect of number of stages on the total heat flux in the bubble column 56

4-13 Effect of column diameter on heat flux in the bubble column 57

4-14 Left: Path of Condensing Fluid Right: Column bubbling 58

A-I CAD diagram of the polypropylene blocks 61

A-2 CAD diagram of SS sparger plate . . . . . 62

10

Page 11: Bubble column humidification dehumidification desalination system

List of Tables

B.1 Dimensions of 5 different configurations for sparger plates.

B.2 Instrument designation chart ..

B.3 MS condensing coil dimensions.

3.1

4.1

Different particle properties ... .

Circular sparger plates dimensions.

43

52

64

64

65

11

Page 12: Bubble column humidification dehumidification desalination system

12

Page 13: Bubble column humidification dehumidification desalination system

Nomenclature

Different symbols used through the paper

Acronyms

BC Bubble Column

HDH Humidification Dehumidification

MS Multi Stage

MSF Multi-Stage Flash

RO Reverse Osmosis

Re Reynolds Number

SS Single Stage

OD Oustide Diameter

ID Inside Diameter

13

Page 14: Bubble column humidification dehumidification desalination system

A Area[m2]

cp Specific Heat Capacity [J /kgK]

d Diameter [m]

h Enthalpy [J /kg]

m Mass Flow [kg/s]

P Pressure [kPa]

T Temperature [K]

¥- Volumetric Flow [m3 /s]

E Energy [J]

Q Heat [J]

Symbols Q Heat Transfer Rate [W]

W Work [J]

\IV Work Rate [W]

v Velocity [m/s2]

p Density [kg/m3]

9 Gravity [m/s3]

C Heat capacity rate [W /K]

z Height [m]

E Heat loss [%]

qflux Heat Flux [kW/m2]

X ratio of water vapor mass to dry air mass

14

Page 15: Bubble column humidification dehumidification desalination system

in,i inlet side

out,o outlet side

w water

da dry air

Subscripts wv water vapor

c cold

h hot

min minimum

max maximum

15

Page 16: Bubble column humidification dehumidification desalination system

16

Page 17: Bubble column humidification dehumidification desalination system

Chapter 1

Introduction

Water scarcity is a problem that affects one-third of the population across the globe,

up to 2 billion people [3]. This global problem is expected to worsen due to increasing

population. A way to counter this problem is to produce more fresh water to meet

our needs. One of the technologies that the Lienhard Research Group is working on

is to desalinate seawater using Humidification Dehumification Desalination System,

or HDH. HDH has several advantages but its main demerit is the poor heat transfer

rate in the condensing coils in the dehumidifier. The proposed solution is to create

a bubble column dehumidifier [4]. Air is sent through a sieve plate to create bubbles

in a body of pure water. The water from the humid air bubble is condensed in the

bulk and the energy is transferred to the coil immersed in the column of liquid. This

leads to very high heat and mass transfer rates for dehumidification. In addition,

the effectiveness of the device is maximized by multi-staging the bubble column to

recover as much energy as possible from the dehumidification process.

In the following chapter, a brief description of HDH systems is given so the reader

has background on the HDH technology and why it is used. Single stage bubbles

columns are fully analyzed in Chapter 3 along with experimental modeling, designs

for the system, and test results. A system approach analysis is used to analyze multi­

stage bubble columns for their effectiveness in chapter 4. Finally a description on

implementability, scalability, and feasibility is given on HDH systems, on page 57, as

designed in this thesis. An overall energy consumption analysis is not given, however

17

Page 18: Bubble column humidification dehumidification desalination system

a comparison is made between this system and those existing in the market.

1.1 Motivation for Desalination

Water scarcity is a growing problem around the world with nearly 1/5 of the pop­

ulation living in areas of physical scarcity and every year this problem worsens [3].

Fresh water lakes are shrinking and ground water supplies are being depleted. There

are areas in the world, like the Sahara, that have more evaporation than precipitation

that makes the land very dry, and those that do not are under a lot of water stress.

Water stress is the amount of water withdrawal over the difference in precipitation

and evaporation. Even many of the developed countries are experiencing a high water

stress, meaning each year they use up all the precipitation they receive and consume

water from a reserve.

lillie or no water searoily

PhYSilca) water scaJcity

t estimated Approaching phy§i"cawaler Sicarcily

Figure 1-1: Water scarcity across the globe [3]

The world is covered by 71 % of water, 97% of that water is salt water. That means

a mere 3% is fresh water, and most of that is trapped in glaciers [7]. By these figures

alone it would seem sensible to turn some of the salt water into usable fresh water

18

Page 19: Bubble column humidification dehumidification desalination system

through desalination. With the current state of desalination technology, desalination

is only viable as a local solution. Fortunately, half of the people in the world live in

cities and most of those cities are near coasts with a near endless supply of saltwater

to treat.

1.2 Conventional Desalination Technologies

Various desalination methods are available on the market and are being actively

used across the world. Saudi Arabia, the country that produces the most amount of

desalinated water, produces nearly 70% of their fresh water through desalination; the

US is the third largest desalination country. The two most widely used methods are

multi-stage flash desalination and reverse osmosis desalination [7]

1.2.1 Multi-Stage Flash Desalination

The most common way of producing fresh water is to distill water from saltwater

known as multi-stage flash distillation. The process is simple and starts with salt­

water being heated to high temperatures (around 100°C). At those temperatures

water is flashed (pressure is dropped via a hydraulic pressure drop) to evaporate as

steam, leaving behind the brine which contains the contaminants and the ionized salt

particles. The steam then rises and hits the heat exchanger resulting in a loss of heat,

condensation, and collection in the form of freshwater. To improve the effectiveness

of this system the saltwater is used as the cool fluid flowing through the exchanger.

As seen in Figure 1-2, there is a hot end and a cold end of the system with mod­

erate temperatures in the midsection. Saltwater starts at the cool end, heating up

as it goes through the stages, until it reaches the hot end where it is almost at the

appropriate temperature, needing only a bit more heat. That vaporized saltwater is

sent through the system as described above is cooled down and is collected as brine

at the last stage. The counter flow heat exchanger is used to minimize the heat loss

in the system.

The drawback of multi-flash distillation is the large amounts of thermal energy

19

Page 20: Bubble column humidification dehumidification desalination system

rJ

~4---:-----1

C ....~r---

A .....--------------------------,B >------..

A - Steam in, B - Seawater in, C - Potable water out, 0 - Waste out, E - Steam out, F - Heat exchange, G -

Condensation collection, H - Brine heater

Figure 1-2: Schematic diagram for a multi stage flash desalination system [10]

needed to drive the system. This thermal energy is typically produced using fossil

fuels although that can lead to a large carbon footprint. Multi-stage flash systems are

applied in large-scale (several 100,000s of m3 /day) systems and almost exclusively in

co-generation (water and power) situations. They are not normally applied in small­

scale standalone desalination systems.

1.2.2 Reverse Osmosis Desalination

The second most common method being used is a membrane filtration system known

as reverse osmosis. The membrane is designed to prevent particles and ions from

flowing through its filter while allowing water to flow through. Typically an electric

pump is used to pressurize the inlet fluid to overcome the osmotic pressure difference

across the membrane. The solute is contained within the pressurized side while the

distillate emerges on the other side.

In a system like this there are still many drawbacks. The membrane is costly

to produce and needs to be maintained very frequently by expert technicians due to

fouling by ions. The separation efficiency of the membrane varies according to salinity,

pressure, and water flow, and a solution with high salinity can very adversely affect

the performance of the membrane. For applications in developing world situations,

RO systems are thought to be too resource intensive.

20

Page 21: Bubble column humidification dehumidification desalination system

Salt Water

High Pressure

Clean Water

Figure 1-3: Depiction of a Reverse Osmosis membrane

21

Page 22: Bubble column humidification dehumidification desalination system

22

Page 23: Bubble column humidification dehumidification desalination system

Chapter 2

Humidification Dehumidification

Desalination

An overview of HDH is necessary to understand the importance of the improvements

suggested in this thesis. HDH desalination has been known for many decades but

is still a rather poorly understood technology when you compare it to MSF or RO

which have been thoroughly studied for many years. Only recently have large strides

been made that allow HDH to be a feasible solution to the freshwater problem.

2.1 Overview

Humidification Dehumidification is a form of thermal desalination that is based on

simultaneous heat and mass transfer devices. It is similar to MSF in that it is a dis­

tillation technology although it uses air as a carrier gas. Some of the main attractions

of this device is that it uses low grade heat to provide the thermal energy needed to

power the cycle and can be operated at near ambient pressures. Low grade heat such

as low-pressure steam from a power plant, or from renewable sources of energy such

as solar energy, or even by geothermal sources can be used to power the HDH system.

There are three main components to this technology- the humidifier, the dehumid­

ifier, and the brine heater. Seawater is brought to the humidifier where it evaporates,

turning into water vapor and combining with dry air to form humid air. This humid

23

Page 24: Bubble column humidification dehumidification desalination system

air is brought to the dehumidifier where the humid air hits a heat exchanger and

condenses to form fresh water which can be collected to drink.

HDH system

Packed bed

Humidifier~

Brine,li1b

~ Dehumidifier

tSea water

in, lllw,i ,To

Figure 2-1: Schematic diagram of a closed loop HDH system [9]

2.2 Benefits

HDH desalination systems are inexpensive to build and maintain, as will be demon­

strated in the construction of the single stage bubble column, which makes it a perfect

candidate for small scale, off-grid, decentralized desalination. Unlike RO, there are

no specialized membranes that are costly to produce and require frequent replace­

ments after a limited number of cycles. In an HDH system it is the packed bed of

the humidifier that is quickly fouled by salt particles that deposit on its surface.

HDH also has many manufacturing benefits over MSF as well. MSF works at vary­

ing pressures and operates at temperatures above 100°C to flash the fluid. By oper­

ating at more modest pressures and temperatures systems, HDH can be constructed

at lower costs using plastic materials and simple machining operations. Moreover,

MSF has not been applied at a smaller scale (10-100m3 jday).

24

Page 25: Bubble column humidification dehumidification desalination system

2.3 Demerits

HDH is not widely used because there are barriers to the technology that do not

make it commercially viable. However, although there are numerous advancements

currently being made. HDH systems suffer from low energy efficiency and high capital

cost resulting in a high cost of water production. Through a thermodynamic analysis

it is clear that HDH has not reached its thermodynamic limit and that there are

many improvements that can be developed to increase the energy efficiencies of HDH

systems [5]

The high capital cost can be attributed to the non-condensable carrier gas present

in the condensing mixture in the dehumidifier. High concentrations of the gas in­

creases the resistance to heat transfer. Poor heat transfer decreases the condensation

rate and lowers the amount of heat recovery. The effect of diffusion resistance to trans­

port of vapor in non-condensable gas-vapor mixtures has been studied by researchers,

and they have concluded that there is a quadratic variation of heat transfer with

change in mole fraction of non-condensable gas present in the condensing vapor [8].

In a system like ours, with the mixture containing 60-90% air, the heat exchanger in

the condenser will have orders of magnitude lower heat transfer coefficients, as low

as 1 W /m2K, when compared to pure vapor systems.

25

Page 26: Bubble column humidification dehumidification desalination system

26

Page 27: Bubble column humidification dehumidification desalination system

Chapter 3

Single Stage Bubble Column

This thesis suggests a unique design using a bubble column as part of the dehumidifier

to improve the heat transfer rate. The first section will explain the function of the

bubble column along with a thermal network resistance model for this system. The

second part of this section will go into detail about the design and construction of

the dehumidifier, and experimental setup. The third subsection will explain and

model different parameters that will drive the design of our setup. Much of this

section has been discussed in a paper titled "Bubble columns for condensation at

high concentrations of non-condensable gas: heat transfer model and experiments"

[6] written by members of the Center for Clean Water and Clean Energy, and myself.

That paper has been submitted to American Institute of Chemical Engineers, AIChE,

journal for publication. As such this paper will not go into full detail about the

modeling of the parameters selected for this experiment. Lastly, the results will be

analyzed alongside the model and a conclusion will be made about different effects

on heat transfer rates.

3.1 Overall Concept

Humidification Dehumidification is a form of thermal desalination that is based on

simultaneous heat and mass transfer devices. It is similar to MSF in that it is a dis­

tillation technology although it uses air as a carrier gas. Some of the main attractions

27

Page 28: Bubble column humidification dehumidification desalination system

of this device is that it uses low grade heat to provide the thermal energy needed to

power the cycle and can be operated at near ambient pressures. Low grade heat such

as low-pressure steam from a power plant, or from renewable sources of energy such

as solar energy, or even by geothermal sources can be used to power the HDH system.

There are three main components to this technology- the humidifier, the dehumid­

ifier, and the brine heater. Seawater is brought to the humidifier where it evaporates,

turning into water vapor and combining with dry air to form humid air. This humid

air is brought to the dehumidifier where the humid air hits a heat exchanger and

condenses to form fresh water which can be collected to drink.

Coolant Coolant in

out i 1

Condensate out

Vapor/gas mixture out

1fr

+- f--

I...+- f--

Vapor/gas mixture in

Cooling coils

Liquid in column

Bubbles

Sparger

Air distribution chamber

Figure 3-1: Schematic diagram for a single stage bubble columnaiche

By using a bubble column the pool of liquid acts as a medium for the air to transfer

heat to the coolant in the coils but also creates turbulence around the condensing coils.

It is proposed by Kast that the rising bubbles receive radial momentum and break

up the boundary layer surrounding the coil wall [11]. These two effects improve heat

transfer rates.

The heat transfer within the column is modeled as a thermal resistance network

using bulk temperatures and approximating one-dimensional heat transfer. Shown

in the figure below, there are four main temperature nodes- humid air (Tair ) , water

28

Page 29: Bubble column humidification dehumidification desalination system

column (Tcolumn), coil wall (Tcoil ), and coolant (Tcoolant). R coil represents the resistance

due to the coil wall, which is negligible when using copper coils. Rimpact represents

the resistance between the coil surface and the bubbles. In a typical dehumidifier

Rimpact would be the only thermal resistance between T air and T coil and is very large

for air-water vapor mixtures. To improve performance Rimpact needs to be improved.

Adding a body of water creates another bridge between T air and T coil through Rsensible,

resistance between bubble and water, and Rbc , resistance between water and coil, and

also reduces Rimpact by the two effects described above.

RsenSibleTcoo1am

Figure 3-2: Resistance model for a bubble column heat exchanger [6]

3.2 Design

Several different designs for the system have been developed through the course of

this experiment, however only one variation was used to conduct the experiments.

3.2.1 Frame

The column of the dehumidifier is constructed from several sheets of transparent

CPVC, 3/8" thick. CPVC has a temperature range of O°C to 93°C, outside of our

expected operating conditions of 10 °c to 80°C. Four sheets, approximately 12" wide

by 18" tall, were used for the sides and two sheets, 12" wide by 12" tall, were used

for the bottom and top cover. Aluminum L-brackets, I" by I" by 18", were used on

29

Page 30: Bubble column humidification dehumidification desalination system

the corners attached with gasketed binding barrels. A Buna-N gasket seals the top

and bottom plates of the column.

Figure 3-3: Left: CAD depiction of tank. Right: Actual fabricated tank.

3.2.2 Sieve Plate Profile

The sieve plate serves two functions- diffuse the incoming air into small bubbles and

to prevent the water from flooding the air chamber. The first sparger chosen was

a cartridge type from Mott Corporation. It is an in tank precision sparger element

made of 316L stainless steel porous media. The media is rolled and has welded ends.

It is I" in length, and 2.5" in diameter. This cylindrical sparger produces fine Imm

bubbles with a pressure drop of less than 13.7 kPa.

After initial testing it appeared that the cylindrical sparger could not produce a

completely uniform array of bubbles, translating into poor bubble impact on portions

of the condensing coil. In addition, modeling the effects of impact on the coil be­

comes significantly more difficult when there is uneven impact and when the air is

dissipating through a cylindrical vessel. An alternative sparger design was chosen for

the dehumidifier although the cylindrical sparger is used in the humidification column

30

Page 31: Bubble column humidification dehumidification desalination system

Figure 3-4: Mott Corp. 2240-A16-10-AOO-10-AB Precision Sparger Element withconnector fitting.

because the humidification column only needs to produce humid air and will not be

modeled. For equal volumes of gas the cylindrical sparger can produce bubbles which

have 6.35 times more gas-liquid contact surface area than a sparger with 6.35 mm

bubbles which is advantageous for a humidification system.

The chosen design for the new sparger is an aluminum sparger box measuring

10"x10"x1". There is a 3/4"x 3/4" ABS trim in the sparger box to facilitate switching

sparger plates. Over the box is an acrylic sheet with a grid of small through holes.

There are 5 variations in sieve design that vary in the number of holes, hole diameter,

and hole pitch size in order to test the effect of bubble size to heat transfer rates.

They are listed in the appendix.

Figure 3-5: Left: Cad model with no.2 sparger plate. Right: Actual fabricated spargerbox with no.5 sparger plate.

31

Page 32: Bubble column humidification dehumidification desalination system

The features of the sieve plate were generated by a program written by Dr. A. V.

Kulkarni, from the Institute of Chemical Technology in Mumbai.

3.2.3 Coil Designs

Two different condensing coils were designed to study the effect of impact of bubbles

on the coil. Both coils were made from copper tubing, alloy 122, with an outside

diameter of 0.375" and an inner diameter of 0.311" and were turned by hand. The

circular coil has an overall turn diameter of 9" over the active sparger area of 8" by

8". As seen in the image below, the circulation of the water forces the bubbles to

move away from the sides of the wall and through the center of the coil with minimal

contact. The second coil, a serpentine design, is designed to pass over the sparger

holes therefore deliberately contacting the bubbles.

Figure 3-6: Left: Circular design Right: Serpentine design

3.2.4 Humidifier

The initial design for the humidification column used the same framework as the

dehumidifier along with the original cylindrical sparger. Alternatively, an off-the­

shelf polypropylene tank, with a smooth seamless construction and a temperature

range up to 80°C, was used instead. This tank was capable of sealing better and

32

Page 33: Bubble column humidification dehumidification desalination system

Figure 3-7: Left: Bubbles avoid impacting the coils Right: Bubbles makes severalimpacts while rising

provided very stable and consistent air flows. A 3/8" polycarbonate lid with a 0­

ring seal was constructed to seal the tank and prevent leaking. The tank has an air

inlet that suspends the cylindrical sparger vertically to produce bubbles, an air outlet

with a mist eliminator screen, a water inlet valve, and a 1.5 kW submersion heater

that surrounds the sparger.The body of water in the humidification tank is heated to

70°C, below boiling temperature of water at atmospheric pressure.

Humid Air Outlet Air Inlet

Water Level

Submersion Heater

Figure 3-8: Schematic diagram of the humidification tank.

33

Page 34: Bubble column humidification dehumidification desalination system

Figure 3-9: Left: The humidification tank with C-clamps sealing the tank. Right:Inside of tank. Note that the water is not boiling.

3.2.5 Experimental Setup

The system temperatures and flow rates are monitored to allow adjustments in order

to achieve thermodynamic balancing. There are numerous k-type thermocouples

connected to a data logger with an uncertainty of ±0.1 °C. They are listed in the

appendix. There are two rotameters, one to measure liquid flow and one to measure

air flow. The air rotameter has a range of 0.8 - 8.2 ft 3 Imin (378 - 3870 m3 Is) with a

resolution of 0.2 ft 3 /min ( 94.4 m3 Is). The water rotameter has a range of 0.01 -0.85

L with a resolution of 0.01 L/min.

The following is a schematic of our experimental setup. Water flows in a closed

loop system from the water reservoir, through the pump, to the condensing coil, and

back. The temperature is regulated by a closed loop chilled water condensing coil

and by an electric heater. A bypass valve is included in the design to reduce the duty

on the pump. Air is supplied through an external wall source. The system is an open

loop as it goes from the humidifier column through the dehumidifier column and into

the atmosphere. System efficiency is not important because the study focuses on the

characteristics of the dehumidifier.

Through a series of reiterative testing the following initial conditions are used

a) dehumidifier air inlet temperature is 68°C, b) the condensing coil water inlet is

34

Page 35: Bubble column humidification dehumidification desalination system

Airsupply

3

910

T2

tT6

IIITTl 7

11 r----' ,1 T8 I

8PUMp

(1, 11, 12) valves, (2, 6, 13) rotameter, (3, 8) sparger, (4) humidifer colLulln, (5) submerged electric heater, (7) pressuregauge, (9) dehumidifer column, (l0) water coil, (14) inline water heater, (15) cooling water tank, (16) chilled water coil,(T 1T8) thermocouples

Figure 3-10: Schematic diagram of test apparatus [6]

24°C, near ambient temperature c) air flow rate is 5.0 sefm, d) water flow rate is 0.5

lpm.

Dehumidifier

Figure 3-11: Single stage bubble column HDH setup

35

Page 36: Bubble column humidification dehumidification desalination system

3.3 Analysis

To begin obtaining results the system needs to be in steady state and thermodynam­

ically balanced. For this an error term is created and whenever the error falls below a

threshold the system will be considered in steady state and thermodynamically bal­

anced. It is not possible to balance the system completely due to losses in heat. The

analysis begins by drawing a control volume around the dehumidification column and

using the First Law of Thermodynamics,

dE .. v 2 v 2

di = Q - W + 'L.m(h + 2 + gZ)in - 'L.m(h + 2 + gZ)out (3.1)

There is no work done on the system, and we assume steady state when taking

results. Mass flow and velocities at the inlet and outlet are the same. Potential energy

is negligible in this situation. With some rearranging of terms, equation 3.1 reduces

to

(3.2)

Specific enthalpy for an incompressible liquid can be written as,

(3.3)

where the difference in Pout and Pin is negligible. For water, the heat transfer rate

is,

(3.4)

where,

(3.5)

Finding the flow rate for dry air is not as straightforward as it is for water. The

humid air is a fully saturated mixture of H20 and air. The mass flow rate is dependent

36

Page 37: Bubble column humidification dehumidification desalination system

on this humidity ratio of kilograms of water vapor per kilogram of dry air. The

following image shows how the humidity ratio of air increases with temperature.

Sj.::.::......:cD:. 10.101o;:;ftl

0:::b 0.115":CII

E:i 10.101

~

J

"II,,

.JI

fI,

Jf,

./'~

~"'"~

"~engineeringto0 Ibox.C0 m-

I

101

Temperatu re ,(deg Ie)

Figure 3-12: Chart for humidity ratios that vary with temperature [2]

The mass flow rate of air can be written as

. ¥damda = 1 +X P

where,

(3.6)

(3.7)

Dry air is a compressible gas and its enthalpy values are taken from a property

37

Page 38: Bubble column humidification dehumidification desalination system

data table. The heat transfer rate for dry air is,

(3.8)

The heat loss is given by the equation

Once E is minimized the qflux is calculated as

Qdaqflux =-A

coil

(3.9)

(3.10)

qflux is calculated using Qda instead of Qw. While Qw would give a more accurate

qflux, the uncertainty due to the propagation of error is significantly larger than when

using Qda.

3.4 Results

The values for the model predictions are taken from "Bubble columns for condensation

at high concentrations of non-condensable gas: heat transfer model and experiments"

[6].

3.4.1 Bubble Diameter

Using different sparger plates, with different hole diameters, different bubble diame­

ters were generated. Within the scientific community there has not been a consensus

made as to whether bubble diameter affects mass transfer coefficient greatly [8]. Our

model and data shows a decreasing relationship between heat flux and bubble diam­

eter, although it is small. This is at a fixed superficial velocity of 3.8 cm/s, mole inlet

fraction of 21 %, and a water column height of 254 mm.

38

Page 39: Bubble column humidification dehumidification desalination system

3

• Current bubble column experiments

2.5

0.5

o

Model prediction

fo

fo

3 3.5 4 4.5 5 5.5 6 6.5 7

Bubble diameter [mml

Figure 3-13: Effect of bubble diameter on the total heat flux in the bubble column

3.4.2 Superficial Velocity

The effect of superficial velocity on mass transfer in bubble columns has been stud­

ied extensively already. However,these studies do not involve condensation into the

liquid column. From literature findings, models, and experimental data, it it can be

concluded that heat and mass transfer coefficients increase as superficial velocity in­

creases. This is done at a fixed hole diameter of 4 mm, mole inlet fraction of 21 %, and

water column height of 254 mm. The uncertainty of measurement on the superficial

velocity is ±O.l1 cm/s and the heat flux is ±5%. From 3 cm/s to 9 cm/s the system

is operating in the homogenous bubbly flow regime. The heat flux rapidly increases

once the system goes into the heterogeneously bubbly (extremely turbulent) regime,

and is seen in the multi-stage system tests.

39

Page 40: Bubble column humidification dehumidification desalination system

6

• Current bubble column experiments5

o Model Prediction

~ t='= 3-; t<II..c";j...~ 2

o

o

2 3 4 5 6 7 8 9 10

Superficial velocity, VG

[em/s1

Figure 3-14: Effect of superficial velocity on the total heat flux in the bubble column

3.4.3 Liquid Height In Column

In an HDH system a blower is needed to provide a high pressure end to drive the gas

through the humidifier and dehumidifier. For a typical dehumidifier the pressure drop

through it is minimal. In a bubble column dehumidifier a large portion of the pressure

drop is due to the hydrostatic head of the liquid in the column that the humid air needs

to overcome. To reduce pump size, and therefore costs, it is beneficial to minimize

the liquid height. Reducing the pool volume would also decrease the transient time

necessary to heat the pool before reaching steady state. The height would ideally be

the height that just fully immerses the coil in the liquid pool, in this case 152.4 mm.

It must also be above the integral length of a bubble diameter, a few millimeters,

however this is easily achievable. With a superficial velocity of 6.53 cm/s, bubble

diameter of 4 mm, and an inlet mole fraction of 21 % there was no discernible effect

of liquid height on heat flux above the minimum necessary.

40

Page 41: Bubble column humidification dehumidification desalination system

3.4.4 Inlet Mole Fraction of Vapor

It was stated earlier that mole fraction of vapor has nearly a quadratic effect on heat

transfer rates, although this effect has not been applied to bubble columns. The

inlet mole fraction is varied from 10% to 25% at a fixed superficial velocity of 3.8

cm/s, mole inlet fraction of 21 %, and a water column height of 254 mm. The model

and experimental data both show a linear effect rather than quadratic. This is a

significant finding showing another benefit of bubble column dehumidifiers.

4.5

4 • Current bubble column experiments

.f'Model prediction

'" 3.5e--.~ 3

0~=!<:::~ 2.5~

.c:-; 2....~

1.5

0.5

o0.05 0.1 0.15 0.2

Inlet mole fraction of vapor [-10.25 0.3

Figure 3-15: Effect of inlet mole fraction on the total heat flux in the bubble column

3.4.5 Impact

In all of the above experiments, bubble-on-coil impact was avoided; including impact

into the predictive model would have been very difficult. This section studies the

effect of using a serpentine coil. Under standard conditions it is observed that impact

significantly increases heat transfer rates. For the serpentine design, a large portion

of heat transfer between the humid air bubbles and coil is through the direct impact

41

Page 42: Bubble column humidification dehumidification desalination system

between the two. To obtain higher heat transfer rates the condensing coil should be

designed for maximum impact.

9

.to 'iilhoU! hnpa t

<) with j rnpact

7 ...,...':'1:

~ 6:!.......,.

5... ......,.c>i.=.

! 4

3

2

o2 3 4 5

+

6 7 8

Superficial velocity, V~ Ie.mf I

Figure 3-16: Effect of impact on the total heat flux in the bubble column

3.4.6 Particles

The use of particles is tested for the effects on heat flux. Particles can have two

effects within the bubble columns. Particles circulating in the liquid pool will collide

with rising bubbles and break them up into smaller bubbles. Additionally bubbles

will impact the particles, transferring heat to the particle, and then the particle will

impact the coil, transferring heat to coil. Two categories of particles were used. The

first is polypropylene balls and the second is aluminum powder. The properties of the

particles are listed below. Polypropylene is less dense than water so the circulation

of the water pulls particles into the body to interact with the bubbles. Aluminum is

also considered because of its high thermal conductivity. However aluminum is much

denser than water so the diameter of the particle must be small enough so that it is

fluidized within the streams.

42

Page 43: Bubble column humidification dehumidification desalination system

Table 3.1: Different particle properties

Particle Density (g/cm 3) Diameter (mm) Thermal Conductivity (W/m K)

Water 1 - 0.58

Polypropylene 0.93 3.17 0.22

Aluminum 1.76 0.102 250

Using standard fixed parameters there were no apparent effects from either par­

ticles observed. As much as 500 ml, or 3 % of water volume, of aluminum powder

was added to the liquid body without an effect. One unfortunate side effect of using

particles is that the condensed water is contaminated by the particle which would re­

quire further filtering before drinking. A similar variation was done with a serpentine

coil without an effect.

3.4.7 Others Variables

A few other variables were examined merely to validate our modeling conditions. It

is assumed that the liquid body has a uniform temperature. The data shows that

temperature is uniform radially as well as along the height of the water column.

This is due to the constant mixing within the liquid body as the water circulates

turbulently.

The above results show a lot of promise for bubble column dehumidifiers. A state

of the art dehumidifier from George Fischer LLC [1] had a maximum heat flux of 1.8

kW1m2 while the bubble column dehumidifier was able to reach a flux of 8kW1m2.

The single stage bubble column dehumidifier was not designed for maximum heat

flux, but merely to test certain parameters. The multi-stage bubble column has been

better optimized and is able to obtain significantly higher heat fluxes.

43

Page 44: Bubble column humidification dehumidification desalination system

44

Page 45: Bubble column humidification dehumidification desalination system

Chapter 4

Multi Stage

All of the analysis done to this point has been on a single stage bubble column but

a multi-stage bubble column is necessary if it is used for any viable desalination

system. The first subsection explains why a multistage column is more effective. The

second su-section analyzes two different heat exchangers and which one to pursue.

The third subsection is a detailed description of the design of the multistage system.

The last subsection will show the results of the multistage system with an emphasis

on effectiveness rather than heat flux.

4.1 Overall Concept

There are different variations on heat exchangers which can be categorized by flow

arrangement and type of construction. The simplest constructions are concentric tube

heat exchangers with either parallel or counterflow. In a parallel flow, the hot and

cold stream enters from the same end and leave through the same end, flowing in the

same direction along its length. Counterflow has fluids entering and leaving different

ends and flowing in opposite directions.

In a parallel flow setup the two streams start at a high temperature differential

and the differential decreases through the length of the heat exchanger. As seen from

equation 3.4 as the temperature differential decreases the heat transfer rates decreases

as well. In an ideal, infinite length heat exchanger, the heat transfer rate will decrease

45

Page 46: Bubble column humidification dehumidification desalination system

Figure 4-1: Left: Parallel flow Right: Counterflow

to 0 when the hot stream and cold stream reach the same middle temperature. A

parallel flow system is simple to build but the heat recovery is poor. A counterflow

system is preferred.

- HotStream- Cold Stream

-------------------------------

- Hot Stream- Cold Stream

Length of Heat Exchanger Length of Heat Exchanger

Figure 4-2: Left: Parallel Heat Exchanger Right: Counterflow Heat Exchanger

In a counterflow setup the streams oppose each other, allowing more heat transfer

between the two streams. There are two parameters that will affect the shape of the

curve, heat capacity rate and effectiveness. Heat capacity rate is defined as follows,

(4.1)

where Ch is the heat capacity rate for the hot stream and Cc is the heat capacity

rate for the cold stream. The heat capacity rate affects the curvature of the streams

in the graphs. An exchangeraAZs effectiveness, defined as,

46

Page 47: Bubble column humidification dehumidification desalination system

or

QE 1 = -.-Qmax

(4.2)

(4.3)

is the ratio of the actual heat transferred to the heat that could be transferred by

an exchanger of infinite size.

or

!J.HE2 = ---.-.--

!J.Hmax

E_ (hh,i - hh,o)

2-(hh· - h .),2 C,1,

(4.4)

(4.5)

Effectiveness of this system is the greater of the two effectiveness. In the ideal

case, with E=l, the inlet of the hot streamaAZs temperature is equal to the oulet of

the cold streamaAZs temperature. For a desalination system with high recovery, the

ideal situation is when the condensing coil outlet temperature is equal to the humid

air inlet temperature. This is impossible to achieve due to finite thermal conductivity,

and other physical limitations. Although the system can be optimized so that the

difference between cold outlet and hot inlet is minimized,shown in figure 4-3 allowing

the system to use a smaller thermal heater.

4.2 Analysis

There are numerous benefits to having a counterflow heat exchanger, however due

to the design of the system it is not possible to have a pure counterflow. In the

single stage bubble column, the hot air stream mixes with the liquid pool as the pool

circulates around the cool coils. The temperature more closely resembles temperature

curve in figure 4-4.

47

Page 48: Bubble column humidification dehumidification desalination system

Hot StreamCoild StreamCo:ld Stream with iE=l

........ -...

.... .... ...

I\\\\

... ..\. .. ... ...

" ... ...

length of Heat Excha nger

Figure 4-3: Different counterflow temperature profiles

Hot StreamCo:ld StreamUquid Body

Q)l....

::::::I+-"rol.... ------------------------------.Q)c..E~

lengtn of Heat Exchanger

Figure 4-4: Counterflow exchanger with poor effectiveness

48

Page 49: Bubble column humidification dehumidification desalination system

This temperature profile is similar to a parallel flow heat exchanger with poor

recovery. The solution is to use a multi-stage bubble column dehumidifier. By using

multiple stages the temperature curve begins to resemble a counterflow system with

discrete points, allowing more heat to be recovered.

3rd Stage2nd Stage1St Stage

Hot StreamCold Stream

--------~---=-~-~-~------- ------

~~~---------------------------

Length of Heat Exchanger

Figure 4-5: Multistage parallel flow temperature profiles

Having an infinite number of stages would have a recovery rate of 100%. In just

3 stages it has been the calculated that the efficiency is 92.5%.

4.3 Design

The humidification and dehumidification column has been redesigned to improve

sealing, ease of manufacturing, ease of assembling, and interchangeability.

4.3.1 Column

The main body of the column is made of an acrylic cylinder 6.5" wide and 12" tall.

Both ends of the cylinder has a 9" by 9" x 2" thick polypropylene cover with all

necessary features CNC milled on the blocks, ensuring there are no leaks through the

49

Page 50: Bubble column humidification dehumidification desalination system

sides of the column. Each block features a channel for the inlet and outlet of the

condensing coil, a drain for collecting condensate, and a bolt circle for mounting the

sparger plate. There is a channel with an o-ring on the top and bottom face of each

block that the cylindrical body sits in. A drawing of the covers has been included

in the appendix. The bottom chamber is used to distribute air and has a cover with

just an inlet for humid air and a drain. The top cover only has an outlet for dry air.

The system is held together by 17" lengths of 3/8" threaded rods so that a section

can be easily dismantled without disturbing other sections and that new sections can

be easily added. Swivel pads are attached to the bottom of the threaded rod to act

as legs for the system.

--+ 2nd Stage

...........~ lstStage

IJ--of- Air Chamber

Figure 4-6: Left: CAD model w/ 1 stage Right: Fabricated model w/ 2 stages andinsulation

50

Page 51: Bubble column humidification dehumidification desalination system

Air flows from the bottom end through the column while the coolant travels from

the top condensing coil to the bottom. The coils are connected through Aj<lAi tubing

that runs along the outside of the column.

4.3.2 Sparger Plate

The sparger plates are similar to the ones used in a single stage bubble column except

that they are circular. Additionally the holes are kept within a 5" circle as to not

interfere with the condensing coil fittings. Stages with smaller condensing coils use

sparger plates with greater number of holes because their column supports a lower

liquid pool height.

Figure 4-7: Circular sparger plate

51

Page 52: Bubble column humidification dehumidification desalination system

Table 4.1: Circular sparger plates dimensions

# Drill Size(mm) Pitch (mm) Number of holes

1 1,5 13 49

2 1,5 15,5 36

4.3.3 Coils

Taking what was learned from the single stage column the size of the coil could be

reduced greatly. Once again the coils are made of copper, alloy 122. The goal was to

minimize the height of the coil and to place it as close to the sparger plate without

being less than the integral length. Different coil designs were used for different stages,

and coil design was reiterated several times. Setup A is a single stage, B is a double

stage, and C is a triple stage. The dimensions of the coils for the three setups are

listed in the appendix.

In setup C, stage 3 coil has the largest area while the stage 1 coil has the smallest

because the first stage must have a minimal amount of heat transferred, otherwise

all heat transfer will occur in the first stage and make the system less effective. Also

note that stage 2 and stage 3 coils use a spiral design, as seen below. The serpentine

design has a large bend radius limited due to the bending tool which limits the the

number of bends that can be made in one layer. The spiral design can be made more

densely due to its large bend radius.

Figure 4-8: MS coil designs

52

Page 53: Bubble column humidification dehumidification desalination system

Figure 4-9: MS coil side profile

It can be seen from fig. 4-9, that the minimum amount of water needed to cover the

coil is small, a miniscule 0.65". The condensate collection port in the block was meant

to double as a means to fill the chamber with its initial liquid pool. Condensation

forms so rapidly that it takes only a matter of minutes before the necessary body of

water has formed. With such a small body of water the system reaches steady state

very rapidly.

4.3.4 Air Chamber

The air chamber is used to ensure that air is evenly distributed through the column.

It is similar to the other chambers although this chamber is empty and is only 6" tall.

It was found during testing that the heat loss through the sides condensed the humid

air slightly. This effect is minimized by minimizing the size of the air chamber.

4.3.5 Humidifier

The humidifier uses a similar design as the dehumidifier with the polypropylene blocks

and acrylic side walls. It serves a simpler function and does not need the plumbing

that is required with the dehumidifier. The humidifier is a large 12aAZ tall, 10" wide

air chamber with hot brackish water pouring from the top. Inside the column are

packed beds that improve contact between the dry air and the heated seawater.

Included in this design is a platform with dual purpose, to distribute air in the air

53

Page 54: Bubble column humidification dehumidification desalination system

Figure 4-10: MS humidifier showing the spray nozzle and platform

chamber and collect water. A simpler design has been devised but not implemented

that uses a cylindrical sparger with large air openings.

4.3.6 Experimental Setup

The same flow meters are used to measure air and water flow. Numerous K-type

thermocouples were added to the system to measure air temperature in the bubble

column and to measure the inlet/outlet temperatures of the condensing coil. The

thermocouples are the same as the one used in the previous experiment. Other

thermocouples were placed in the column to measure liquid body temperature, not

used in the analysis, but to ensure that the system was operating accordingly. Slightly

54

Page 55: Bubble column humidification dehumidification desalination system

different configurations were used for different setups.

Tll

m;l>:

...~

...~

m)j

I T7 v-r---IIII

nL.­IIII\(

T12 ~ - ~ ~ ~ - ~ ~ ~ - ~ I 1- -----~ -----~: BRINE HEATER I

I T2 II

, , In , I

II

III 13 I nocc:: Iw

n LL I

CII

~I

T4 I T9::J I::I: IW IC I

TSI

T8I

T6 II I

~ ,I,I

I

- - _. Seawater Pure water-- Carrlier gas

Figure 4-11: Schematic diagram of MS system and instrumental layout

4.4 Results

Conducting the experiment verified what the model had predicted.

4.4.1 Temperature Profiles

In the one stage humidifier the temperature curves behave very similarly to a parallel

flow heat exchanger. As more stages are included into the system the temperature

curves begin to resemble a parallel flow heat exchanger.

55

Page 56: Bubble column humidification dehumidification desalination system

4.4.2 Effectiveness

The modeled effectiveness for a 3 stage is 92% while the experimental effectiveness

was 89.41%. The difference is less than 3 percentage points, however there is an ex­

planation as to why there is a difference. Firstly, the coil design needs more iterations

to achieve the necessary heat transfer.

1

0.9

OB

£: 0.7

~ 0.5Q;l

.~ 0.5

tl 0.4

~ 0_3

:t:

• % Model

• Experimental

0.2

0.1

0--'---------'----------'---------'---------'

o 1 2

NlJl1lberof Stages

Figure 4-12: Effect of number of stages on the total heat flux in the bubble column

Another important reason is that the heat transfer is being limited by the thermal

resistance as seen in the resistance model described in fig. 3-2. Poor performance of

HDH systems was previously due to the thermal resistance between the condensing

coil and the gas vapor mixture. This is no longer the case as the system is currently

operating in the heterogeneously bubbly (very turbulent) regime. The largest thermal

resistance is now between the coil and coolant fluid. As seen from the figure below,

in the multi-stage design the heat flux is significantly higher than in the single-stage

design and an order of magnitude higher than state of the art systems.

4.4.3 Column Diameter

By decreasing the column size without varying the air flow, the superficial velocity

of the stream increases dramatically. That is seen in the figure below, however,

56

Page 57: Bubble column humidification dehumidification desalination system

conditions are not fixed between results so a direct comparison is not appropriate.

30

25

20

15

10

5

• Single Stage

.A. Multi Stage

- St ate oft heA rt Syste m

0...l...- 1....-__----l. .....L... ...L.- 1....-__----l. ...J

o 50 100 150 200 250 300 350

Figure 4-13: Effect of column diameter on heat flux in the bubble column

The coil uses 1/4" copper tubing rather than 3/8" which allows the stream within

the coil to operate in the turbulent regime. These two effects account for the large

increase in heat flux. In order to increase the heat flux and increase the effectiveness of

a 3 stage bubble column the flow within the condensing coil must increase even more

and move into a higher turbulent regime. To do this, the diameter of the condensing

coil must decrease and then the velocity will increase as a squared function. The

Reynolds number for an extremely turbulent stream is 10,000. For the stream to

experience a Re=10,000 the tube needs to be 1/16" in diameter. At this size the

pressure drop through the tubing will be enormous.

4.5 Cost

With such a large heat flux and high energy recovery rate, this HDH system will be

able to produce water cheaply. High heat fluxes allow the system to be very small

even at large water production rates. Additionally the design is completely scalable.

If more water production is needed a wider system is easily designed, or several small

systems can be placed in parallel. This allows the capital costs for manufacturing to

57

Page 58: Bubble column humidification dehumidification desalination system

Figure 4-14: Left: Path of Condensing Fluid Right: Column bubbling

be low compared to other desalination technologies. The main operating cost is the

thermal energy, and with high energy recovery rates, the variable costs can be low.

If there is a source of waste heat or renewable energies, like solar, then the variable

costs can almost be o.

58

Page 59: Bubble column humidification dehumidification desalination system

Chapter 5

Conclusion

Some countries depend on desalination technologies to provide clean water to its

nation and this number will only increase as water becomes scarcer. This need is

what drives technological innovation like bubble column HDH desalination. Bubble

columns do not create small increases in efficiency but make fundamental leaps in

system performance. We saw that

• HDH bubble columns could achieve a heat flux of 20 kW1m2

• superficial velocity increases heat flux

• inlet mole fraction of vapor increases heat flux linearly

• liguid height of column has no effect on heat flux

• impact of bubbles on column nearly doubles heat flux

• 3 stage bubble column had an effectivness of nearly 90%

HDH desalination has been considered to be a low performance system, however with

the modifications suggested in this paper the effectiveness can be above 89%. It is a

simple, low maintenance, low cost system and it may not be long before HDH is the

leading desalination technology. There are a lot of merits to this system therefore a

few members from the CCWCE will be licensing this technology to begin a startup.

59

Page 60: Bubble column humidification dehumidification desalination system

60

Page 61: Bubble column humidification dehumidification desalination system

Appendix A

CAD Drawings

Throu h-hole for air to hit sorer

Channel for Condensin Coolant

SECTION B-B

Ii

Figure A-I: CAD diagram of the polypropylene blocks

61

Page 62: Bubble column humidification dehumidification desalination system

8qo

10; 10,000

Figure A-2: CAD diagram of SS sparger plate

62

Page 63: Bubble column humidification dehumidification desalination system

Appendix B

Tables

63

Page 64: Bubble column humidification dehumidification desalination system

Table B.1: Dimensions of 5 different configurations for sparger plates

# Drill Size(inch) Pitch (mm) Number of holes

1 1/16 16 121

2 3/32 23 64

3 1/8 26 36

4 5/32 32 25

5 3/16 40 16

Table B.2: Instrument designation chart

# Name

T1 Humidifier Water Column

T2 Dehumidifer Air Inlet

T3 Dehumidifer Air Column Top

T4 Dehumidifier Air Outlet

T5 Condensing Coil Water Inlet

T6 Condensing Coil Water Outlet

T7 Dehumidifier Water Column Top

T8 Dehumidifier Water Column Bottom

64

Page 65: Bubble column humidification dehumidification desalination system

Table B.3: MS condensing coil dimensions

Setup Stage# 0.0. (inch) 1.0. (inch) Length (inch) Type

A 1 1/4 0.19 50 Serpentine

B 1 114 0.19 28 Serpentine

B 2 3/8 0.311 60 Circular

C 1 1/4 0.19 16 Serpentine

C 2 114 0.19 30 Spiral

C 3 3/8 0.311 30 Spiral

65

Page 66: Bubble column humidification dehumidification desalination system

66

Page 67: Bubble column humidification dehumidification desalination system

References

[1] Calorplast heat exchangers. Website. http://www.us .piping. georgefischer.com/go/85FD4C79D60EB5F06E88713117408325/.

[2] Humidity ratio of air. Website.humidity-ratio-air-d686.html.

http://www.engineeringtoolbox.com/

[3] Coping with water scarcity: Challenge of the twenty-first century. Technicalreport, Food and Agriculture Organization of the United Nations, 2007.

[4] G. Prakash Narayan et al. Multi-stage bubble column vapor mixture condenser.Assigned to MIT, Patent pending, USSN 13/241,907.

[5] G. Prakash Narayan et al. Thermodynamic analysis of humidifcation dehumid­ification desalination cycles. Desalination and Water Treatment, 16:339-353,2010.

[6] G. Prakash Narayan Lam Steven et al. Bubble columns for condensation at highconcentrations of non-condensable gas: heat transfer model and experiments.American Institute of Chemical Engineers, 2012. in process of being published.

[7] Lienhard John H. Innovations in clean water technology: Desalination. LectureVideo, 2011.

[8] Saha D Maheshwari NK, Vijayan PK. Effects of non-condensable gases on con­densation heat transfer. Proceedings of 4th RCM on the IAEA CRP on NaturalCirculation Phenomena, 2007.

[9] G. Prakash Narayan. Status of humidification dehumidification desalination.IDA World Congress, International Desalination Association, September 2011.

[10] Castelnuovo Ruben. Multiflash. Website, 01 2010. http://en.wikipedia.org/wiki/File:Multiflash.svg.

[11] Analyse Kast W. Analyse des wrmebergans in blaensulen. International Journalof Heat and Mass Transfer, page 5:389, 1962.

67