“Function maintenance” means the guarantee o the power supply to saety-relevant installations,
such as emergency lighting and smoke extractors, in the event o re.
OBO oers a broad range o practical systems or electrical installations or unction maintenance or almost
every eld o application and mounting type. All the OBO systems are tested according to DIN 4102 Part 12
and can thus be used easily.
BSS166
8/3/2019 Bss Funktionserhalt En
http://slidepdf.com/reader/full/bss-funktionserhalt-en 2/12
Protection aim 168
Obligation to label,
installation situations 169
Fire tests and proos 170
Selection aid 172
Overview
Standard support structures 174
Overview
Cable-specifc support structures 175
Cable list with approved
routing combinations 176
Basic principles o unction maintenance systems
BSS 167
8/3/2019 Bss Funktionserhalt En
http://slidepdf.com/reader/full/bss-funktionserhalt-en 3/12
3rd protection aim:
Important electrical systems must continue to unction.
Solution: unction maintenance or electrical systems
To ensure that emergency and es-cape routes remain usable and also
important technical equipment such
as emergency lighting, re alarm sys-
tems, smoke exhaust systems, etc.
in case o re, it is absolutely essen-tial to provide special protection or
the power supply or these systems.
The use o special cables and rout-
ing systems means that it is possible
to maintain the power supply, evenin the case o re, thus guaranteeing
the unction maintenance.
What is a cable system with
integrated unction maintenance?
A cable system with integrated unc-
tion maintenance is, according to
DIN 4102 Part 12, the combination o
the routing system (cable ladder,
cable tray, etc.) and cables with inte-grated unction maintenance.
Cables and standard routing
systems
The standard species that unction
maintenance o an electrical cable
system includes not just the cables
themselves, but also the routing sys-
tems. DIN 4102 Part 12 denes threestandard routing systems:
Routing on cable ladders Routing on cable trays Individual cable routing under
the ceiling
All the OBO routing system or elec-
trical installations with unction main-
tenance correspond to DIN 4102
Part 12.
Function maintenance
in the building regulations
The requirement or electrical instal-
lations with unction maintenance is
a component part o the building
regulations o the German ederal
states. This type o installation isparticularly required or buildings in
which many people meet regularly:
public buildings, hotels, meeting
places, large industrial complexes,
etc. Function maintenance applies
solely to those areas which provide
the power supply to saety-relevant
systems such as emergency light-
ing, alarm systems, re alarm sys-
tems, smoke extraction systems, etc.
Here, the regulations require the
power supply to be guaranteed or a
specic period o time, even i there
is a re.
Routing system
+
Cables with integrated
unction maintenance
=
Cable system with integrated
unction maintenance accord-
ing to DIN 4102 Part 12
BSS168
8/3/2019 Bss Funktionserhalt En
http://slidepdf.com/reader/full/bss-funktionserhalt-en 4/12
System labelling by the
installation engineer
Each cable system must be perman-
ently labelled with a sign. This label-
ling must contain the ollowing inor-
mation:
Name o the erection engineer o
the cable system (installation en-
gineer) Function maintenance class E... Test certicate number
Owner o the test certicate Year o manuacture
BSS 169
Besides the type and quantity o
cables, the selection o the cor-
rect system is dependent on the
actual conditions on the con-
struction site.
Fastening systems
O equal importance to the selection
o the support system is the decision
or the most suitable astening sys-
tem. Here, too, the individual actors
on the construction site must be
taken into account. The Fastening
systems section contains proes-
sional, easy-to-mount solutions or
any requirements.
Space with multiple girders
Please note that, i there are jumps in
height, the installed cables must be
supported. This may be required,
when cables with large cross-sec-
tions are not supported by the sup-
port system.
Combination
with other systems
Ventilation systems, pipes, etc. may
not be mounted above the electrical
installation with unction mainten-
ance, as, i there is a re, parts may
all down, damaging the unction
maintenance cables. The solution is to
employ cable mounting with clips
directly under the ceiling or on the wall.
Restricted spaces
The solution here is either cable
mounting with clips or pressure clips
directly under the ceiling or the
installation o multiple narrow cabletracks above each other instead o
one wide track.
Problematic substrate
As, or old ceiling structures, e.g. dur-
ing renovation projects, the support
orce cannot be ocially claried, we
recommend wall mounting.
8/3/2019 Bss Funktionserhalt En
http://slidepdf.com/reader/full/bss-funktionserhalt-en 5/12
Fire testing
The proo o the unction mainten-
ance property o electrical installa-
tion material must be provided by
re testing to DIN 4102 Part 12 in an
independent materials testing oce.
The test is carried out in a special
testing urnace in which the installa-
tion to be tested is heated up ac-
cording to a standard temperature-
time curve. The cable systems areawarded the classes E30 to E90,
depending on the length or which
they manage to survive.
Proos and approvals
The result o the re test is docu-
mented in a construction testing
certicate. This test certicate is valid
or cable systems with
cable-specic support
structures as a proo
o unction maintenance. With standard support struc-
tures, the proo o unction
maintenance also requiressurveyor’s comments in addition
to the testing certicate.
Start of fire
Fire formation phase
Flash over
Fully developed fire
Cooling-down-phase
Time
Temperature
Time (Min)
Temperature rise (C)
1000
500
0
0
30 60 90 120
Standard temperature-time curve
BSS170
Fire tests, proos and approvals
Phases o natural fres / standard temperature-time curve (ETK)
8/3/2019 Bss Funktionserhalt En
http://slidepdf.com/reader/full/bss-funktionserhalt-en 6/12
Extreme loads or
cables
I there is a re, the cables are sub- jected to extreme loads rom fames
and heat. Nevertheless, cables used
or a unction maintenance installa-
tion must be able to withstand tem-
peratures o 1,000 °C and more or a
certain period o time, without there
being a short-circuit o the copper
conductor. As the copper conductor
may anneal at these extreme tem-
peratures, thus impairing its own
mechanical stability, the support
system serving as a “support cor-
set” has a special signicance.
Cables with integrated unction
maintenance
Thereore, in the case o cables with
integrated unction maintenance, the
insulation has a special role to play.
These cables possess a special
winding around the copper conduct-
or made o glass silk or mica tape. I
there is a re, then the cable insula-tion burns completely, creating a
layer o ash. This is kept together by
the windings and ensures that the
copper conductors are kept apart
and that no short-circuit o the sup-
port system can take place. In add-
ition, a new product on the market is
a cable, which, instead o special
windings, has a ceramising plastic
insulation. I there is a re, this spe-
cial plastic orms a ceramising ash,
which also produces the required in-
sulation o the current-carrying cores.
Halogen-ree plastic
Cables with integrated unction main-
tenance are always made o halogen-
ree plastic. These materials, which do
not contain any chlorine, bromine or
fuorine, do not create any corrosive
re gases during combustion.
Low smoke and reducedfre spread
In addition, cables with integrated
unction maintenance have addition-
al positive properties during a re,
or example:
Low smoke and/or Reduced re spread
BSS 171
A glimpse into the testing urnace:
glowing o the support structure,
cable with insulating layer o ash
Electrical monitoring
during the test
8/3/2019 Bss Funktionserhalt En
http://slidepdf.com/reader/full/bss-funktionserhalt-en 7/12
Selection aid, unction maintenance systems
Standard support structureWith standard support structures, it
is possible to select reely the cables
required or the installation. This is
possible, as all the cable manuac-
turers have proven the unction main-
tenance o their cables or the stand-
ard support systems.
Benefts Free choice o cables, as the
combination o cables and the
standard support structure has
the unction maintenance proo Not bound to one specic
cable type This structure is ideal or smaller
projects Testing means that the countless
installation variants are approved
or many years
Summary:
Here, the installation engineer
can “play it sae”.
BSS172
7
_ K
t
l
_
/
/
/
3 /
( L L E
r t_
1
Funktionserhalt - Kabelrinnen- und Gitterrinnen-Systeme
Normtragekonstruktionen: Deckenmontage mit 2 Kabelrinnen
- n i l , n hr r l n, lrinn , n r in r, l r, l n nk r, r n h -
l, nn i hn n hil .
Systemkomponenten
Die Verlegeart mit 2 Kabelrinnen am U-Hängestiel erf üllt die Forderungen der DIN 4102 Teil 12 als Normtragekon-
struktion f ür die Funktionserhaltsklassen E30 und E90.Durch die gemeinsame Verlegung von zwei Kabelrinnen mit einer Holmhöhe von 60 mm pro Ausleger verdoppelt
sich die verlegbare Kabelmenge. Die maximal zulässige Kabelbelegung pro Kabelrinne von 10 kg/m bleibt aber unver ändert.
Ebenfalls unver ändert ist die frei w ählbare Positionierung der Stoßstelle zwischen den einzelnen Auflagepunkten.
Auch die Ausbildung der Stoßstelle mit verschraubten Verbindern im Rinnenholm und verschraubter Stoßstellen-leiste auf dem Rinnenboden bleibt trotz der Doppelanordnung der K abelrinnen bestehen.
Normtragekonstruktion nach
DIN 4102 Teil 12
Gutachterliche Stellungnahme
Nr. 3917/4635-2-Mu
Funktionserhaltsklassen
E30 und E90
ZulässigeDaten
Stützweitemax. 1,2m
Kabelgewichtpro Rinnemax. 10kg/m
Lagenanzahlmax. 3Lagen
Kabelrinnenbreiten 100,200,300mm
Gesamtbreitemax. 500mm
1 l i r t r n tru ti n u
K K l ri nn n i t 3 H n t i l, u l r Ty 1 /.... in iti nti rt.
n w nd un g b r i c h D c , i n i ti g
1 l i r t r n tru ti n u
K K l ri nn n i t H n t i l , u l r Ty 3 /....in iti nti rt.
n w nd un g b r i c h D c , i n i ti g
l i r tr n t ru t i n uK K l ri nn n i t 3 H n t i l, u l r
Ty 1 /.... in iti nti rt.
n w nd un g b r i c h D c , i n i ti g
Standard support structures are marked in
blue in the catalogue.
Cable-specifc support systems are marked
in orange in the catalogue.
Cable-specifc support systems
With cable-specic support systems,
specic cables are required. Any
proo is only valid or the actually
tested combination o laying variant
and cable. A summary cable list pro-
vides inormation on tested com-
bination options.
Benefts Low material and
mounting costs Limited cable selection
(approval only valid or the cables
tested with the system) Higher planning costs:
the complete cable system
(cable and support system) must
be ully planned out Ideal or larger buildings
(project business)
Summary:
Here, the possibilities o the
combination o cables and
support systems can be ully
exploited – the system is opti-
mised or the appropriate
application.
_ K
t l
_
/
/
/
3 /
( L L E
r t_
1
Funktionserhalt - Kabelrinnen- und Gitterrinnen-Systeme
Kabelspezifische Tragekonstruktionen: Deckenmontage mit RKS-Magic ®
- n i l , n - n i l l r, h k , lrinn n, r n h l, nn i hn n hil
Systemkomponenten
Das Highlight unter den kabelspezifischen Tragekonstruktionen f ür den elektrischen Funktionserhalt nach DIN4102 Teil 12 ist zweifelsfrei die Verlegeart mit der Kabelrinne RKS-Magic. Geschwindigkeit, Wirtschaftlichkeit und
hohe Tragf ähigkeit kennzeichnen dieses System. Die RKS-M wird einfach zusammengesteckt und erf üllt doch alleAnforderungen an eine brandsichere Verlegung von Kabeln f ür sicherheitsrelevante Anlagen. Die hohe Belastbar-
keit schafft Reserven, die gewindestangenlose Befestigung vereinfacht auch hier die Montage. Bis zu f ünf Lagen
können an einem Stiel befestigt werden.Highspeed trifft Economy!
Kabelspezifische
Tragekonstruktion nach
DIN 4102 Teil 12
Funktionserhaltsklassen
E30 und E90
ZulässigeDaten
Stützweitemax. 1,5m
Kabelgewichtpro Rinnemax.bisRinnenbreite300mm
20kg/m
Kabelgewichtpro Rinnemax.beiRinnenbreite400mm
30kg/m
Lagenanzahlmax. 5Lagen
Kabelrinnenbreiten 100,200,300,400mm
i r l g ig r i n t b i d i t
Ein i vi r l i nt v r i nt i t H n ti lK un i nn n r i t n i 3 .
D r i l g i g r i n t i n i ti g
Ein i r i l i nt v r i nt in iti nti r t i t H n ti l K un inn n r i t n
.
D r il g i g r i nt b i d i t
Ein i r i l i nt v r i nt i i ti nti r t i t H n ti l K un inn n r i t n
.
8/3/2019 Bss Funktionserhalt En
http://slidepdf.com/reader/full/bss-funktionserhalt-en 8/12BSS 173
Selection aid, unction maintenance systems
Individual cable
(unlimited cross-section)
Small cable bundle
(limited cross-section)
Multiple cables
StandardCable-
specifcStandard
Cable-
specifcStandard
Cable-
specifc
Clip types:
732, 733
Clip types:
732, 733
Clip types:
732, 733
2056M
2056M LW (with long trough)
Clip types:
732, 733
2056M
2056M LW (with long trough)
electrical pipes
– Models:
2031 M15
2031 M30
2031 M70 2033M
2034M
Clearance:
0.3 m
Clearance:
cable-specifc, see
note
Clearance:
0.3 m, with long
trough 0.6 m
Clearance:
cable-specifc, see
note
– Clearance:
cable-specifc, see
note
Retro-installation in the system:
not possible
Retro-installation in the system:
limited possibility
Retro-installation in the system:
limited possibility
Many cables(small cross-sections)
Many cables(large cross-sections)
StandardCable-
specifc
StandardCable-
specifc
Tray type:
SKS
Tray types:
RKSM, GRM,
EKS
Ladder type:
LG6
Ladder type:
SL
Clearance:
1.2 m
Cable load: max.
10 kg/m per tray
with threaded rod
lock
Clearance:
cable-specifc, see
note
Cable load: up to
30 kg/m per tray
with or without
threaded lock
Clearance:
1.2 m
Cable load: max.
20 kg/m per ladder
with or without
threaded rod lock
Clearance:
cable-specifc, see
note
Support spacing:
1.5 m
with or without
threaded rod lock
Retro-installation in the system:
single
Retro-installation in the system:
single
Note:
Data or cable cross-
sections, distances and
maximum loads may vary
according to cable type
and cable manuacturer.
Do not exceed
the maximum approved
cable load.
For retro-installations in
cable-specifc routingtypes, observe the
approved cable types.
8/3/2019 Bss Funktionserhalt En
http://slidepdf.com/reader/full/bss-funktionserhalt-en 9/12
Overview o standard support structures
The standard laying systems dened
in the testing standard DIN 4102 Part
12 include installation on cable trays,
cable ladders, individual cable laying
under the ceiling with prole rails,
clamp clips and long troughs, and
the individual cable laying under the
ceiling with single clips. Please com-
ply with the specications o the
planner in the selection o products
approved or unction maintenance.
In addition, the on-site actors on the
construction site must be taken into
account.
Cable tray systems Support width max. 1.2 m Cable weight max. 10 kg/m Tray width max. 300 mm
Cable ladder systems Support width max. 1.2 m Cable weight max. 20 kg/m Ladder width max. 400 mm
Vertical ladder systems Clip distance max. 300 mm Rising track width max. 600 mm Cable weight max. 20 kg/m
Individual routing systems Single clips max. 300 mm
astening distance Clamp clips with long troughs
max. 600 mm astening
distance
Fire protection duct
BSK and BSKH BSK or direct wall and ceiling
mounting BSKH or suspended mounting
No unction maintenance cablesrequired
You can nd additional inorma-
tion in the “Escape route installa-
tion system” chapter
BSS174
8/3/2019 Bss Funktionserhalt En
http://slidepdf.com/reader/full/bss-funktionserhalt-en 10/12
Overview o cable-specifc support structures
The ollowing cable-specic support
systems are viable or electrical in-
stallation with unction maintenance:
cable trays with and without thread-
ed rod lock, mesh cable trays, cable
ladders, single clips, collecting
clamps and pressure clips. Ensure
an approved combination with test-
ed cables.
Cable tray systems Support spacing max. 1.5 m Cable weight max. 30 kg/m Tray width max. 500 mm Variants: to 5-layer Also without threaded rod
Mesh cable tray systems Support spacing max. 1.2 m Cable weight max. 10 kg/m Widths 200 and 300 mm Variants: 1/2/3-layer
Cable ladder systems Support spacing max. 1.5 m Cable weight max. 20 kg/m Width max. 500 mm Variants: 1/2/3-layer
Cable and pipe clamps Various variants, e.g. larger xing
distances, bundling... Space-saving mounting
Collecting clamps and
pressure clips Various variants, e.g. larger xing
distances, bundling... Space-saving mounting
BSS 175
8/3/2019 Bss Funktionserhalt En
http://slidepdf.com/reader/full/bss-funktionserhalt-en 11/12
The cable list simplies the allocation
o cables and routing systems to the
cable system.
BSS176
Cable list
You can nd the current cable list at
www.obo.de
Kabelhersteller Kabeltyp Klasse Daten Bemerkung
Dätwyler NHXH E30-E90 nx1,5mm
NHXCH E30-E90 nx1,5/1,5mm
JE-H(St)H E30 nx2x0,8mm
JE-H(St)HRH E30 nx2x0,8mm
Eupen NHXH E30-E90 nx1,5mm
NHXCH E30 nx1,5/1,5mm B 300 mm
NHXCH E90 nx1,5/1,5mm B = 400 mm
JE-H(St)H E30 nx2x0,8mm
Nexans N2XH E30 nx1,5mm B = 400 mm
N2XCH E30 nx1,5/1,5mm
JE-H(St)H E30 nx2x0,8mm
Prysmian (N)HXH E30 nx1,5mm
(N)HXCH E30 nx2,5/2,5mm
JE-H(St)H E30 nx2x0,8mm
1
K a b e l r i n n e R
K S
Application example 1
Approved combination:
RKS-Magic® cable tray with power cable, type NHXH E30 – E90 o make Dätwyler,
unction maintenance class E90, useul cross-section ≥ n x 1.5 mm², without restrictionsusable with all tray widths or wall and ceiling mounting
1
1
Approved installation options or cable systems with integrated unction maintenance
in conjunction with routing systems rom OBO Bettermann, Menden
8/3/2019 Bss Funktionserhalt En
http://slidepdf.com/reader/full/bss-funktionserhalt-en 12/12
Kabelhersteller Kabeltyp Klasse Daten Abstände Bemerkung
Dätwyler NHXH E30 nx2,5mm 0,5 m mi t Langwanne, 1,1 kg/m
JE-H(St)H E30 nx2x0,8mm 0,5 m 1,1 kg/m
JE-H(St)H E60 nx2x0,8mm 0,5 m mit Langwanne, 1,1 kg/m, 20 Kabel
JE-H(St)HRH E30 nx2x0,8mm 0,5 m 1,1 kg/m
JE-H(St)HRH E60 nx2x0,8mm 0,5 m mit Langwanne, 1,1 kg/m, nur Wand, 20 Kabel
JE-H(St)HRH E90 nx2x0,8mm 0,5 m mit Langwanne, 1,1 kg/m, nur Decke, 20 Kabel
Eupen (N)HXH Keram E30 nx1,5mm 0,5 m mi t Langwanne, 1,1 kg/m, nur Wand
NHXH Mica E90 nx1,5mm 0,5 m mi t Langwanne, 1,1 kg/mNHXH Mica E90 nx1,5mm 0,5 m mi t Langwanne, 1,3 kg/m, nur Wand
JE-H(St)H Keram E30 nx2x0,8mm 0,6 m mit Langwanne, 1,1 kg/m
JE-H(St)H Keram E30 nx2x0,8mm 0,5 m 1,1 kg/m
JE-H(St)H Mica E90 nx2x0,8mm 0,5 m mit Langwanne, 1,3 kg/m, nur Wand
Facab Lynen JE-H(St)H E30 nx2x0,8mm 0,5 m 1,1 kg/m
JE-H(St)H E90 nx2x0,8mm 0,5 m mit Langwanne, 1,1 kg/m, nur Decke
JE-H(St)HRH E30 nx2x0,8mm 0,5 m 1,1 kg/m
JE-H(St)HRH E90 nx2x0,8mm 0,5 m mit Langwanne, 1,1 kg/m, nur Decke
Nexans N2XH E30 nx1,5mm bis 4mm 0,5 m mit Langwanne, 1,1 kg/m
N2XCH E30 nx1,5mm bis 4mm 0,5 m mit Langwanne, 1,1 kg/m
N2XH E90 nx1,5mm 0,5 m mi t Langwanne, 1,1 kg/m
N2XCH E90 nx1,5mm 0,5 m mi t Langwanne, 1,1 kg/m
J/JE-H(St)H E30 nx2x0,8mm 0,5 m mit Langwanne, 1,1 kg/m
Prysmian (N)HXH E30 nx1,5mm 0,5 m mi t Langwanne, 1,2 kg/m, nur Decke
Studer JE-H(St)H E30 nx2x0,8mm 0,5 m 1,1 kg/m
JE-H(St)HRH E30 nx2x0,8mm 0,5 m 1,1 kg/m
Kabelhersteller Kabeltyp Klasse Daten Abstände Bemerkung
Dätwyler JE-H(St)H E30 nx2x0,8mm 0,5 m 2,5 kg/m, nur Wand
JE-H(St)HRH E30 nx2x0,8mm 0,5 m 2,5 kg/m, nur WandEupen JE-H(St)H Keram E30 nx2x0,8mm 0,5 m 2,5 kg/m, nur Wand
Facab Lynen NHXH E90 nx6mm 0,5 m 2,2 kg/m, nur Wand
NHXH E90 nx1,5mm bis 6mm 0,5 m 2,2 kg/m, nur Decke
NHXCH E90 nx6mm 0,5 m 2,2 kg/m, nur Wand
JE-H(St)HRH E30 nx2x0,8mm 0,5 m 2,5 kg/m
Nexans JE-H(St)H E30 nx2x0,8mm 0,5 m 2,5 kg/m, nur Decke
Studer JE-H(St)H E30 nx2x0,8mm 0,5 m 2,5 kg/m
JE-H(St)HRH E30 nx2x0,8mm 0,5 m 2,5 kg/m
7 2 0 3 1 / M
1 5
8 2 0 3 1 / M 3 0
Application example 2
Approved combination:
Collecting clamp, type 2031M/15, with data cable, type J/JE-H(St)H, o make Nexans,
unction maintenance class E30, cable cross-section ≥ n x 2 x 0.8 mm, astening spacing 0.5 m,
restriction: with long trough and maximum cable load o 1.1 kg/m
2
2