Operators Manual BNWAS150 Iss01 Rev01 AMI MARINE (UK) LTD BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM (BNWAS) Operators Manual BNWAS150 © This Manual and the information contained therein is the property of AMI Marine (UK) Ltd. It must not be reproduced or otherwise disclosed without prior consent in writing from AMI Marine (UK) Ltd

Upload: hadieu

Post on 18-Mar-2018

223 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

Operators Manual BNWAS150 Iss01 Rev01

AMI MARINE (UK) LTD

BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM (BNWAS)

Operators Manual

BNWAS150

© This Manual and the information contained therein is the property of AMI Marine (UK) Ltd. It must not be reproduced or otherwise disclosed without prior consent in writing from AMI Marine (UK) Ltd

Page 2: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 1 of 21

Operational Guide BNWAS150 Iss01 Rev01

This Page Intentionally Blank

Page 3: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 2 of 21

Operational Guide BNWAS150 Iss01 Rev01

Document Revision

Date Modification Number (where applicable) Brief Record of Change and Reason for Change

Iss1 Rev0 06.02.12 Original Issue Iss1 Rev1 17.03.14 Change of address

NOTE: All alterations must be verified by re-authorisation and approval of the complete document. AMI MARINE (UK) LTD Unit 9, Crosshouse Centre Crosshouse Road Southampton SO14 5GZ United Kingdom Tel No: +44 (0) 23 8048 0450 Fax No: +44 (0) 23 8065 1126 Email: [email protected] Web: www.amimarine.net

Page 4: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 3 of 21

Operational Guide BNWAS150 Iss01 Rev01

This page Intentionally Blank

Page 5: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 4 of 21

Operational Guide BNWAS150 Iss01 Rev01

IMPORTANT WARNINGS

DANGER!

RISK OF ELECTRICAL SHOCK!

Disconnect from the power before removing protective covers. DO NOT remove the covers while the unit is switched on.

24/12 Volt DC electrical power on external units.

NOTICE Compass safe distance is 1 metre.

NOTICE No user serviceable parts inside, servicing only by properly qualified

and certified technical staff.

NOTICE This manual is for informational use only, and may be changed without notice. This manual should not be construed as a commitment of AMI Marine (UK) Ltd. Under no circumstances does AMI Marine (UK) Ltd assume any responsibility or liability for any errors or inaccuracies that may appear in this document. The equipment should only be used for the purposes intended by the manufacturer; any deviation from this will void the warranty of the product.

Page 6: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 5 of 21

Operational Guide BNWAS150 Iss01 Rev01

This page Intentionally Blank

Page 7: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 6 of 21

Operational Guide BNWAS150 Iss01 Rev01

CONTENTS - BNWAS 150 System Overview ..................................................................................... 8 - BNWAS 150 Controls and Functions .......................................................................... 10 - Software Setup and Operation .................................................................................... 12

Switching On The BNWAS 150 .............................................................................. 12 Entering Setup ....................................................................................................... 13 Mode Selection ...................................................................................................... 14 Stage 2 to Stage 3 Delay ....................................................................................... 14 Initial Dormant Period ............................................................................................ 14 Operational Sequence ........................................................................................... 15 Selecting Duty Cabins and Using Cabin Call ......................................................... 16 External Reset ....................................................................................................... 17 Unacknowledged Alarms ....................................................................................... 18

- System Faults ............................................................................................................. 19 - Maintenance guide ...................................................................................................... 20

Page 8: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 7 of 21

Operational Guide BNWAS150 Iss01 Rev01

This page Intentionally Blank

Page 9: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 8 of 21

Operational Guide BNWAS150 Iss01 Rev01

- BNWAS 150 System Overview The BNWAS 150 system is designed for use on a vessel’s navigation bridge. The remote alarm sounders cover key locations such as the officer cabins, mess area and ship’s office. Reset devices can be used on the bridge wings. The display control and monitoring equipment is to be installed in protected areas inside the bridge. Dormant Time This function is adjustable between 3-12 minutes in 1 minute increments only whilst in SETUP mode. Remote Resets BNWAS 150 has a reset mechanism which can be activated by a combination of reset pushbuttons and PIR motion detection sensors. Fail Alerts BNWAS 150 has alert messages for Tamper, Power and Battery. Tamper alert is also audible by means of an on-board buzzer within the display control unit. Emergency Call and Cabin Call BNWAS 150 has an Officer call configurable in up to 5 officer cabins within the menu. Power supply BNWAS 150 is powered by two separate 24 Volt supplies (main and backup) which will automatically switch to the backup supply in the event of a main supply failure. This will raise an alarm. Inputs from Valid Reset Devices & System Alarms BNWAS 150 provides additional Digital Inputs to accept signals from other devices and transfer alarms. An external equipment in alarm will send a digital input to the BNWAS and the source will be shown on LCD display. These might include RADAR or ECDIS. External valid reset inputs must be approved by the appropriate approval body before being used. AMI Marine (UK) Ltd will assist with recommendations wherever possible from previous experience but will not accept responsibility if not accepted. BNWAS 150 comprises: Hardware consisting of - Control display panel, interface unit, physical and sensory reset devices, alarm sounders and beacons. The BNWAS 150 Software Navigation Menu where the Master can configure and control the operational mode and parameters of the system. Overall Layout There are three areas within the vessel were the system and peripheral units are fitted:- Wheel house / Bridge Accommodation Areas Remote Locations

Page 10: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 9 of 21

Operational Guide BNWAS150 Iss01 Rev01

Wheel house / Bridge Equipment - Control display, Stage 1 Alarm sounders, Alarm Beacon, Directional PIR’s, and push button reset switches. Push buttons can be mounted on the Bridge wing, and are IP rated accordingly. Accommodation Decks Equipment - Stage 2 Alarms are located in the accommodation area. The system is configurable through the navigation menu, for five separate accommodation rooms, labelled: Cabin 1, Cabin 2, Cabin 3, Cabin 4, Cabin 5 - (Captain, Officer 1, 2, 3 and 4) The alarm sounders or sounder beacons can be used. Remote Locations Equipment - Stage 3 Alarms are located in remote locations which could include Officer’s mess, Office locations and Engine Control Room. They can be alarm sounders or sounder beacons.

Page 11: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 10 of 21

Operational Guide BNWAS150 Iss01 Rev01

- BNWAS 150 Controls and Functions

DC-150 Display and Control The BNWAS DC-150 Display Control Panel is the user interface and display for the BNWAS150 The display control panel is to be mounted at a suitable location within the ship bridge preferably at a location where the watch officer is expected to be stationed during normal on watch operations

Figure 1 - DC-150 Control Display Panel

The Key switch has 2 positions which change the function of the tactile buttons; 1. RUN - Normal operation position where the system is monitoring all sensor inputs. 2. SETUP – To set the ‘Operational Mode’ and to adjust the timing parameters.

EMERGENCY CALL / UP

CABIN CALL / DOWN

ALARM RESET / SELECT

Automatic Dimming of the LCD Display A light detection sensor automatically dims the display at low light levels to prevent light pollution during night time operation.

Page 12: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 11 of 21

Operational Guide BNWAS150 Iss01 Rev01

RI-150 Illuminated Reset Pushbutton and RE-150 Illuminated Reset Pushbutton with Buzzer The RI-150 reset pushbutton unit can be used to reset the BNWAS system’s timer before or during the 1st stage alarm. The RE-150 unit performs the same function but also has an audible alarm making it ideal for use on the bridge wings.

SD-150 Alarm Sounder and SB-150 Sounder Beacon The SD-150 alarm sounders are used for the 2nd or 3rd stage alarms and have adjustable volume between 85 and 105dB. The SB-150 performs the same function but also has a highly visible LED indication.

Figure 3 - RE-150 Illuminated Reset Pushbutton with Buzzer

Figure 2 - RI-150 Illuminated Reset Pushbutton

Figure 4 - SD-150 Alarm Sounder

Figure 5 - SD-150 Sounder Beacon

Page 13: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 12 of 21

Operational Guide BNWAS150 Iss01 Rev01

- Software Setup and Operation

Switching On The BNWAS 150 SETUP Menu The SETUP mode allows the user to access the SETUP MENU and customise the timing parameters within the BNWAS 150 menus. To enter the SETUP mode insert the key and turn clockwise to SETUP. Mode Selection In the SETUP menu you can step sequentially through the three different modes of operation by pressing the SELECT button. The three different modes are:-

ON The system functions as per the set timing parameters. Alarms as per IMO standard MSC128(75).

OFF System operation inhibited. The Emergency Call function is still operational AUTO When this mode is selected the system runs as per “ON” mode only if Autopilot signal is active; otherwise operation is inhibited. This function should only be used with class approval.

STAGE ALARM 3 Timing Selection Press the SELECT button until you arrive at the Stage Alarm 3 timing option.

Stage 2 to Stage 3 Delay Time The Stage 2 to Stage 3 delay is defined in seconds. This is the time from the Stage 2 alarm becoming active to the Stage 3 alarms becoming activate, assuming Stage 2 is not acknowledged in the meantime. The Stage 2 to Stage 3 delay is configured using the UP and DOWN buttons. A time between 90 seconds and 180 seconds in 10 second steps can be entered. When the desired timing is displayed press the SELECT button.

DORMANT Period Timing Selection Press the SELECT button until you arrive at the dormant period timing option.

Dormant Period Time The dormant period is defined in minutes. This period is the time taken from initial start-up, or operator reset, to the Visual Alert Stage being initiated. The dormant period is configured using the UP and DOWN buttons to toggle between digits 3 and 12. When the desired period is displayed press the SELECT button.

Page 14: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 13 of 21

Operational Guide BNWAS150 Iss01 Rev01

BNWAS150 Startup On first power up a message from the system designers will appear on the display. The software version and date will then be displayed followed by CPU 1 and CPU 2 running a self-test, a short beep will be heard on completion. After a few seconds the operating screen will be displayed.

Entering Setup Insert the MODE key and turn clockwise – the status indication will change from RUN to SETUP Press SELECT button - mode will change from ON to OFF The BNWAS is now set to OFF. Pressing the SELECT button again, will cause the mode to change from OFF to Auto OFF If the Autopilot is connected the system will automatically turn ON and OFF as the autopilot is engaged and disengaged.

Designed and built by AMI Marine In Great Britain

ON 03 : 00 SETUP Cabin 1 _ 3 _ _

OFF 03 : 00 SETUP Cabin 1 _ 3 _ _

Auto OFF 03 : 00 SETUP Cabin 1 _ 3 _ _

V 1.00 10/11/11 CPU 1 OK CPU 2 OK

ON 02 : 27 RUN Cabin 1 _ 3 _ _

Page 15: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 14 of 21

Operational Guide BNWAS150 Iss01 Rev01

Mode Selection Pressing the SELECT button again, will change Dormant Period to ON. If the key is now turned to the RUN position and removed, the system is now in the ON mode. Pressing the SELECT button again will change ON to OFF. If the key is turned to RUN and removed the system is now in the OFF mode. Pressing the SELECT button again will change OFF to Auto OFF. If the key is turned to RUN and removed the system is now in the Automatic mode. The display will change to Auto ON if the Autopilot is connected and the Autopilot is engaged.

Stage 2 to Stage 3 Delay

Pressing the SELECT button again will change Auto OFF to Stage Alarm 3. By using the UP and DOWN buttons the stage 3 alarm time can be changed, from 90 seconds (1:30) up to 180 seconds (3:00 minutes) in 10 second steps.

Initial Dormant Period Pressing the SELECT button again will change Stage

Alarm 3 to Dormant Period. By using the UP and DOWN buttons the dormant period time can be changed from 3 minutes to 12 minutes, in 1 minute steps.

Stage Alarm 3 0 1 : 30 SETUP Cabin 1 _ 3 _ _

Dormant Period 03 : 00 SETUP Cabin 1 _ 3 _ _

OFF 03 : 00 SETUP Cabin 1 _ 3 _ _

Auto OFF 03 : 00 SETUP Cabin 1 _ 3 _ _

ON 03 : 00 SETUP Cabin 1 _ 3 _ _

Page 16: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 15 of 21

Operational Guide BNWAS150 Iss01 Rev01

Operational Sequence When the BNWAS countdown reaches 00 : 00 the STAGE ALARM message will appear. The display and the remote reset buttons will now flash. To reset the system press the RESET button or press a remote reset button. 15 Seconds after Stage Alarm is displayed STAGE ALARM 1 will be displayed and the Stage 1 alarm on the display unit will audible alarm along with any local sounder. To reset the system press the RESET button or press a remote reset button. 15 Seconds after Stage Alarm 1 is displayed STAGE ALARM 2 will be displayed and Stage 2 and the selected cabin sounders will also begin to sound. To reset the system press the RESET button or press a remote reset button. 1:30 to 3:00 minutes after stage 2, depending on the stage 3 delay setting, STAGE ALARM 3 will be shown and all sounders will sound in all installed locations. To reset the system press the RESET button on the display. NB: Pressing the remote resets, or motion detected by the PIR will not reset the system once stage 3 alarm has been reached. EMERGENCY CALL, In the event of an emergency press and hold the EMERGENCY CALL button until the alarm sounds. All stage 1 and the selected cabin sounders will become active. To reset the system press the RESET button on the display. NB: Pressing the remote resets or motion detected by the PIR will not reset the EMERGENCY CALL.

ON 00 : 00 STAGE ALARM RUN Cabin 1 _ 3 _ _

ON 00 : 00 STAGE ALARM 1 RUN Cabin 1 _ 3 _ _

ON 00 : 00 STAGE ALARM 2 RUN Cabin 1 _ 3 _ _

ON 00 : 00 STAGE ALARM 3 RUN Cabin 1 _ 3 _ _

ON 0 1 : 27 STAGE ALARM 3 RUN EMERGENCY CALL Cabin 1 _ 3 _ _

Page 17: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 16 of 21

Operational Guide BNWAS150 Iss01 Rev01

Selecting Duty Cabins and Using Cabin Call Selecting Duty Cabins for Stage 2 Alarm The Selecting and De-selecting Cabins function can only be accessed when the system is in RUN MODE.

Press and hold the SELECT button until >_< appears. With the SELECT button held press UP to move between the cabins and press DOWN to select or de-select a cabin. When selected the cabin‘s number will be remain displayed. Example: Removing Cabin 4 - which is selected in the screen to the left. Press and hold the SELECT button and >_< will appear at cabin number 1 While still holding the SELECT button, press UP and the cursor >_< will move to the next cabin location. Repeat this past cabin >3<, still holding the SELECT button and pressing UP again. While still holding the SELECT button, press UP once more so that >4< is shown on the display. Continue to hold down the SELECT button. Once at cabin number >4<, press DOWN - >_< will now be shown instead of >4<. Cabin 4 is now de-selected and will not be alerted at stage 2 or when Cabin Call is pressed.

Using Cabin Call Function If the CABIN CALL button is pressed the CABIN CALL message appears and the cabins selected at the bottom of the screen will have their sounders activated. In this case cabins 1 and 3 will be called. Press the RESET button to clear the CABIN CALL.

ON 02 : 27 RUN Cabin >1< _ 3 4 _

ON 02 : 27 RUN Cabin >1< _ 3 4 _

ON 02 : 27 RUN Cabin 1 >_< 3 4 _

ON 02 : 27 RUN Cabin 1 _ >3< 4 _

ON 02 : 27 RUN Cabin 1 _ 3 >4< _

ON 02 : 27 RUN Cabin 1 _ 3 >_< _

ON 0 1 : 27 RUN CABIN CALL Cabin 1 _ 3 _ _

Page 18: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 17 of 21

Operational Guide BNWAS150 Iss01 Rev01

External Reset (if external equipment connected)

RADAR RESET message will be shown when the RADAR is in use by an operator and the BNWAS timer will reset. (This will only be shown if the RADAR in use connection is made) ECDIS RESET message will be shown when the ECDIS is in use by an operator and the BNWAS timer will reset. (This will only be shown if the ECDIS in use connection is made) AUXILIARY 1 RESET message will be shown when the equipment connected to Auxiliary 1 is in use by an operator and the BNWAS timer will reset. (This will only be shown if the Auxiliary 1 connection is made) AUXILIARY 2 RESET message will be shown when the equipment connected to Auxiliary 2 is in use by an operator and the BNWAS timer will reset (This will only be shown if the Auxiliary 2 connection is made)

ON 03 : 00 RUN RADAR RESET Cabin 1 _ 3 _ _

ON 03 : 00 RUN ECDIS RESET Cabin 1 _ 3 _ _

ON 03 : 00 RUN AUXILIARY 1 RESET Cabin 1 _ 3 _ _

ON 03 : 00 RUN AUXILIARY 2 RESET Cabin 1 _ 3 _ _

Page 19: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 18 of 21

Operational Guide BNWAS150 Iss01 Rev01

Unacknowledged Alarms (if external equipment connected)

RADAR ALARM. This will be displayed if an unacknowledged alarm is received from the Radar. Pressing the RESET button will display any other active alarms but will not reset the alarm. (This will only be shown if the RADAR alarm is connected) ECDIS ALARM. This will be displayed if an unacknowledged alarm is received from the ECDIS. Pressing the RESET button will display any other active alarms but will not reset the alarm. (This will only be shown if the ECDIS alarm is connected) AUTOPILOT ALARM This will be displayed if an unacknowledged alarm is received from the Autopilot. Pressing the RESET button will display any other active alarms but will not reset the alarm. (This will only be shown if the Autopilot alarm is connected) ECHO SOUNDER ALARM This will be displayed if an unacknowledged alarm is received from the Echo Sounder. Pressing the RESET button will display any other active alarms but will not reset the alarm. (This will only be shown if the Echo Sounder alarm is connected)

UNACKNOWLEDGED ALARM. This will be displayed if any unacknowledged alarms, other than those listed above, are received by the BNWAS. Pressing the RESET button will display any other active alarms but will not reset the alarm.

NOTE!! For all of the above unacknowledged alarms, pressing the RESET button will have not reset any alarm until the equipment generating the alarm has been acknowledged.

ON 00 : 00 STAGE ALARM 2 RUN RADAR ALARM Cabin 1 _ 3 _ _

ON 00 : 00 STAGE ALARM 2 RUN AUTOPILOT ALARM Cabin 1 _ 3 _ _

ON 00 : 00 STAGE ALARM 2 RUN ECHO SOUNDER ALARM Cabin 1 _ 3 _ _

ON 00 : 00 STAGE ALARM 2 RUN UNACKNOWLGED ALARM Cabin 1 _ 3 _ _

ON 00 : 00 STAGE ALARM 2 RUN ECDIS ALARM Cabin 1 _ 3 _ _

Page 20: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 19 of 21

Operational Guide BNWAS150 Iss01 Rev01

- System Faults Power Error If the main power fails the standby power will be used to power the system. This is indicated by the MAIN POWER FAIL being displayed on the LCD screen until the main power is restored to the system.

MAIN POWER FAIL will be shown if the main power input fails. Press the RESET button to clear message. If message does not clear check main power input.

If the standby power fails, while main power remains on, STANDBY POWER FAIL will be indicated on the LCD display until the standby power is restored.

STANDBY POWER FAIL will be shown if the standby power fails. Press the RESET button to clear message. If message does not clear check standby power input.

Tamper Error If the interface to any peripheral device is disconnected, “Tamper” will be displayed on the LCD screen. This will continue to be displayed until the cause of the tamper is removed.

If the Tamper message appears, the PIRs or one of the reset switches may have been tampered with or have become faulty. Check the PIR’s and reset switches for damage. Press the RESET button to clear the message once any fault has been rectified. If Tamper remains displayed there is a further problem with another PIR or reset switch.

ON 02 : 07 RUN Tamper Cabin 1 _ 3 _ _

ON 0 1 : 27 RUN STANDBY POWER FAIL Cabin 1 _ 3 _ _

ON 0 1 : 27 RUN MAIN POWER FAIL Cabin 1 _ 3 _ _

Page 21: Bridge Navigational Watchkeepers Alarm Systemamimarine.net/site/pdfs/3_operations_manual.pdf · BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM ... The Emergency Call function is still operational

BNWAS150 - Bridge Navigational Watch Alarm System

Page 20 of 21

Operational Guide BNWAS150 Iss01 Rev01

- Maintenance guide The BNWAS 150 system requires periodic (annually) confirmation that all sensors are active, and conduct a full system integrity check. Any damaged/inactive peripherals MUST be replaced by a suitable spare part by an approved engineer. All cabling and interfaces should be re-checked to confirm system integrity and any damaged cables must be replaced/re-wired if required by an approved engineer. Any changes made above must be tested to confirm system operation. Any warranty void marks/visible tampering must be logged to prevent future disruption and system damage.