booster system basics: constant speed systems
DESCRIPTION
Booster System Basics: Constant Speed Systems. Pressure Booster Systems. WHAT IS A BOOSTER SYSTEM? BOOSTER SIZING REQUIREMENTS BOOSTER SYSTEM CONTROL ENERGY SAVING STRATEGIES DRAWDOWN TANKS. What is a Pressure Booster System?. Pumps. - PowerPoint PPT PresentationTRANSCRIPT
Friday, April 21, 2023
Booster System Basics:Constant Speed Systems
Friday, April 21, 2023
• WHAT IS A BOOSTER SYSTEM? • BOOSTER SIZING REQUIREMENTS• BOOSTER SYSTEM CONTROL• ENERGY SAVING STRATEGIES• DRAWDOWN TANKS
Pressure Booster Systems
Friday, April 21, 2023
• All components mounted on a common base, tested and calibrated to site conditions
What is a Pressure Booster System?
Pumps
Control Panel
Headers, Piping and Isolation Valves, Pressure gauges, Solenoid Valve, Aquastat and copper tubing
Pressure Reducing Valves
Friday, April 21, 2023
What you need to size a booster system?
• Calculate the total flow requirement for the building– Number of Domestic Water Fixtures– Type of fixtures in the building– Type of building (residential, public, heavy use)– Special services
Friday, April 21, 2023
Total Flow = Total Fixture Units100100
100 100
50 50
50 50
Fixture Units
GPM HUNTERS CURVE
Friday, April 21, 2023
What you need to size a booster system?
• Calculate the total flow requirement for the building
• Calculate the total pressure required for the building
Friday, April 21, 2023
Static Pressure
• Based on the vertical boost required above the packaged system manifold
• This component never varies
PPstatstat
Friday, April 21, 2023
Fixture Pressure
• Required pressure to operate fixture at farthest point from system.
• Must overcome valve “start-up” pressure (i.e. 25 PSI min. required for flush valves to operate)
• Never varies, this is always required as a minimum
PPfixfix
Friday, April 21, 2023
Packaged System Losses
• Systems are designed to have no more than 5psi loss from suction manifold to discharge manifold
• This must always be added into pressure calculations
PPlossloss
Friday, April 21, 2023
Available Suction Pressure
• Typically varies by about 10-30 PSI
• Can vary over time due to growth
• Can also vary due to municipal re-structuring
PPcitycity
Friday, April 21, 2023
Friction Losses
• Usually calculated at 10% of total static requirement
• Typically a very small boost pressure component
• Can be larger as in the case of boost over a “campus-style” area or large low-rise building
PPfricfric
Friday, April 21, 2023
Pressure Requirement
Supply pressure after water meter
Friction Head
Static head
PRV Losses
Fixture pressureSystem Pressure
Pump Boost Pressure
E
D
C
B
A
Friday, April 21, 2023
Pressure Requirement
Pump Boost Pressure (TDH)= Fixture Pressure+ Package Losses+ Static Head+ Friction Head- Supply Pressure
Friday, April 21, 2023
Pressure Requirement
Boost Pressure= System Pressure - Supply Pressure
Friday, April 21, 2023
Significance of System Flow in Booster Systems
• Flow impacts system demand, not pressure - as demand increases, flow must increase at a constant output pressure
• Flow governs pump actuation - therefore, flow should govern pump sequencing and actuation
• System capacity matched to system flow requirement is most efficient and cost effective for domestic water pressure boosting
Friday, April 21, 2023
What are the most popular methods of booster pump control ?
• Flow meter or flow switch – Instrument is in contact with corrosive water
therefore requiring more maintenance
Friday, April 21, 2023
What are the most popular methods of booster pump control ?
• Flow meter or flow switch • Pressure Switch
– Requires non-overloading (NOL) motors– Requires a pressure drop across
operating range– Can be unstable in operation resulting in
“starving” the system of water (end of curve operation)
– Mechanical switches increase possibility of failure
Friday, April 21, 2023
Effect of Suction PressurePRESSURE
10
20
30
40
50
50 100 150 200 250 300 350 GPM
SuctionPressure
DischargePressure
0
(PSI)
HP
Friday, April 21, 2023
Effect of Suction Pressure
50
PRESSURE
10
20
30
40
50 100 150 200 250 300 350 GPM
SuctionPressure
Suction Pressure
DischargePressure
0
(PSI)
HP
Friday, April 21, 2023
What are the most popular methods of booster pump control ?
• Flow meter or flow switch • Pressure Switch• Current or kW Sensing
Friday, April 21, 2023
Current Sensing
• As the flow increases, so does the pump load• The motor must match the pump load• Current / Power draw for motors is proportional to
the load (pump flow work)
Friday, April 21, 2023
Current - Flow RelationshipPRESSURE
10
20
30
40
50
50 100 150 200 250 300 350 GPM
Motor Amps
0
(PSI)
HPPUMP CURVE
Friday, April 21, 2023
Effect of Suction PressurePRESSURE
10
20
30
40
50
50 100 150 200 250 300 350 GPM
SuctionPressure
DischargePressure
Motor Amps
0
(PSI)
HP
Friday, April 21, 2023
Effect of Suction Pressure
50
PRESSURE
10
20
30
40
50 100 150 200 250 300 350 GPM
SuctionPressure
Suction Pressure
DischargePressure
Motor Amps
0
(PSI)
HP
Friday, April 21, 2023
Effects of Voltage Fluctuations on Motors
% Voltage Change
10+10-
% C
han
ge F
ull
Load
Am
ps
- 7
+11
Friday, April 21, 2023
Current Sensing
• Motors sized to match the power requirement• Current sensing allows flexible pump sizing to
match the system load profile and energy requirement
• Duplex:• Triplex: 33% - 67% capacity split
20% - 40% - 40% capacity split
Friday, April 21, 2023
• Duplex allows up to three steps of sequencing
0%
20%
40%
60%
80%
100%
P1 P2 P1&P2
Current Sensing
Friday, April 21, 2023
Current Sensing
• Triplex allows up to five steps of sequencing
0%
20%
40%
60%
80%
100%
P1
P2
P1
/P2
P2
/P3
P1
/P2
/P3
Friday, April 21, 2023
Typical Daily Demand Curve0h00
1h00
2h00
3h00
4h00
5h00
6h00
7h00
8h00
9h00
10h00
11h00
12h00
13h00
14h00
15h00
16h00
17h00
18h00
19h00
20h00
21h00
22h00
23h00
0
50
100
150
200
250
300
350
400
450
500
Flo
w R
ate
( G
PM
)
Time
Actual Consumption
50-50 Split
Friday, April 21, 2023
Duplex Booster - 50/50 SplitConventional Split
0h00
1h00
2h00
3h00
4h00
5h00
6h00
7h00
8h00
9h00
10h00
11h00
12h00
13h00
14h00
15h00
16h00
17h00
18h00
19h00
20h00
21h00
22h00
23h00
0
50
100
150
200
250
300
350
400
450
500
Flo
w R
ate
( G
PM
)
Time
Actual Consumption
50-50Split
Friday, April 21, 2023
Duplex Booster - 33/67 Split3 Step Control with No-flow shutdown
0h00
1h00
2h00
3h00
4h00
5h00
6h00
7h00
8h00
9h00
10h00
11h00
12h00
13h00
14h00
15h00
16h00
17h00
18h00
19h00
20h00
21h00
22h00
23h00
0
50
100
150
200
250
300
350
400
450
500
Flo
w R
ate
( G
PM
)
Time
Actual Consumption
33-67 Split
50-50 Split
Friday, April 21, 2023
HP = GPM X Feet (Head)
Energy Consumption
• Smaller pump at lower flows will be more efficient and consume less energy
• Smaller motor is more efficient at lower loads
3960 X (Pump Eff) x (Motor Eff)
Friday, April 21, 2023
Energy SavingsConventional vs. 33/67 Split
0h00
1h00
2h00
3h00
4h00
5h00
6h00
7h00
8h00
9h00
10h0
0
11h0
0
12h0
0
13h0
0
14h0
0
15h0
0
16h0
0
17h0
0
18h0
0
19h0
0
20h0
0
21h0
0
22h0
0
23h0
0 0
2
4
6
8
10
12
14
Con
sum
pti
on (
kW
hrs
)
Time
Actual Consumption
33-67 Split
50-50 Split
33-67% Energy Savings: 19%
Friday, April 21, 2023
Total Energy SavingsTotal Energy Savings == 19% 19%
Energy Cost = Energy Cost = $0.12 / $0.12 / kWhrkWhr
Savings per Year: $2,280Savings per Year: $2,280
Energy SavingsConventional vs. 33/67 Split
Friday, April 21, 2023
What are the most popular methods of booster pump control ?
• Flow meter or flow switch • Pressure Switch• Current or kW Sensing• VFD with pressure transducers
Friday, April 21, 2023
When do you use it? Where should you install it? What size should it be?
No-Flow Shutdown and Tank Sizing
Friday, April 21, 2023
Sizing and Selecting Drawdown Tank
• Tanks are to be used in systems that do not have a continuous water demand
• Tanks should NOT be sized according to booster size
• Tanks should be sized to store 20 - 30 Gallons of water (2 - 3 GPM leak loads)
• Tanks maintain pressure in piping system and supply small demands to allow pumps to be shutdown
Friday, April 21, 2023
Sizing and Selecting Drawdown Tank
• Tank Storage Volume is governed by the Ideal Gas Law
• Solving for storage volume gives:
• Vstorage = Pdifferential x VTotal Tank
(PTotal +PAtmosphere)
• 3 factors must be considered
Friday, April 21, 2023
Tank Volume
• Vstorage = Pdifferential x VTotal Tank
(PTotal +PAtmosphere)
• The bigger the tank, the better the storage
Friday, April 21, 2023
Differential Pressure
• Tank storage Volume is proportional to the difference in the cut out and cut in pressures of the pumps
• The larger the pressure differential the more water that will be stored in the tank
• Vstorage = Pdifferential x VTotal Tank
(PTotal +PAtmosphere)
Friday, April 21, 2023
Pressure Differential Calculation
• Pdifferential = Pstop - Pstart
• Pstop = Pressure at the tank when the system shuts down
• For adjacent or package mounted tanks, this means the suction pressure plus the shutoff head of the pump
• For remote mounted tanks, this is simply the normal system pressure at the location of the tank
Friday, April 21, 2023
Pressure Differential Calculation
• Pdifferential = Pstop - Pstart
• Pstart = Pressure at the tank when the system starts again down
• For adjacent or package mounted tanks, this means the setting on the no flow (call on) pressure switch
• For remote mounted tanks, this is simply the system pressure at the location of the tank when the call on pressure switch brings the system back on
Friday, April 21, 2023
Total Pressure
• A lower Total Pressure will yield larger water storage for the same pressure differential
• Lower Total Pressure allows for lower tank pressure rating
• Vstorage = Pdifferential x VTotal Tank
(Ptotal +PAtmosphere)
• Lower tank pressure rating
Friday, April 21, 2023
Sizing and Selecting Drawdown Tank
• All three of these factors must be considered in selecting the appropriate tank
• Vstorage = Pdifferential x VTotal Tank
(PTotal +PAtmosphere)
Friday, April 21, 2023
Where Should the Tank be Installed ?
• Packaged Mounted– Tank water storage may
be limited by tank size– Will require higher tank
pressure rating– More Costly– Difficult to maneuver due
to weight and may require building structural reinforcement.
Friday, April 21, 2023
Where Should the Tank be Installed ?
• Adjacent Mounted– Tank is supplied as a
loose component for connection on site
– Tank is not mounted on skid with pumps
– Contractor has freedom to locate tank in mechanical room
– System is easier to maneuver
Friday, April 21, 2023
Where Should the Tank be Installed?
• Remote Mounted– Roof mounting - Lowers Tank
Total Pressure and Tank Pressure Rating Required
– Allows for the use of smaller tanks for desired water storage
– Contractor has flexibility locating and installing tank
Friday, April 21, 2023
Questions & Answers
Friday, April 21, 2023
Thank You