bookfm6
TRANSCRIPT
-
7/31/2019 BOOKfm6
1/161
Ministry of High Education
El-Shorouk Academy
High Institute of Engineering
Electrical Power and Machines Department
DESIGN OF ELECTRICAL DISTRIBUTION
SYSTEM FORRESEDENTIAL AREASThis thesis is submitted as a partial fulfilment of the requirements for the
Bachelor of Science Degree in Electrical Engineering
Supervised by
Assoc. Prof. Dr. Amged El Wakeel
Prepared by
Abdalla Tallat Tolba. Osama Abd El Mohsen Osman.
Abd El shafi Abdalla Bakr. Maisara Neyazy Abd El Sattar.
Ahmed Maged Ezzat. Mhdi Mohamed Emam.
Ahmed Mamdouh Abd El Mongy. Mohamed Abd El Aziz El Komy.
Ahmed Moatamed Saied. Mohamed Taha Abdalla.
Ahmed Mohamed Abd El Hamed. Mostafa Mohamed Abdo El Soaud.Ahmed Younis Younis. Wael Mohamed El Hady.
Ahmed Zakaria Shokry. Wael Mohamed Sbak.
Amr Baiomy Saied. Walied Ali Khatab.
Amr Mohsen Gemei. Yaser Ragaey Mohamed.
El Sayed Mohamed Baraka.
Gaber Abd El Latif Gaber.
Hani Abd El Hamed Soliman.
Ibrahim Mohamed Kutp.
Islam Gaber Abd El Wahab.
-
7/31/2019 BOOKfm6
2/161
-
7/31/2019 BOOKfm6
3/161
ABSTRACT
In parallel to the increasing in population size, the requirement of new
residential buildings becomes vital particularly in crowded areas. In developing
countries such as Egypt, construction of residential buildings is being carried out
as part of strategic development programs. It is expected that residential buildings
should provide a safety and comfort and maximize the degree of resident
satisfaction within reasonable cost.
Residential buildings can encompass everything from a single apartment
or single-family dwelling unit to an apartment building with two hundred units.
Although residential designs vary greatly, there are considerations that must be
taken into account regardless of the size of the project. Location, materials,
safety, energy and cost are just a few of the things that should be kept in mind
during design stage. A good residence design shall take into consideration the
overall "streetscape" as well as the needs of individual occupants.
From above, it is clear that comprehensive and cohesive design
methodology for residential building including outlets distribution, load
estimation, branch circuit design, cable sizing, and switchboard design is a
difficult and specialised task. Comprehensive design is usually achieved through
a step-by-step procedure and design checks. Although, electrical Egyptian code
does cover residential building design, it does not ban the using of other
national/international codes. This enables us searching in different national codes
in order to achieve proper design.In this project, constructional features of residential buildings are
explained in detail to explore their effects on indoor and outdoor lighting
schemes, elevator design, cable selection and protection system. Different design
methodologies have been applied throughout the work; however the design by
synthesis is applied for the most of the work including indoor and outdoor design.
Also different codes and regulation have been applied such as NEC, BS, Egyptian
Electrical code and IEE regulations.
III
-
7/31/2019 BOOKfm6
4/161
-
7/31/2019 BOOKfm6
5/161
TABLE OF CONTENTS
ABSTRACT.............................................................................................................. IIIACKNOWLEDGEMENT............................................................................................. IVTABLE OF CONTENTS............................................................................................... V
LIST OF FIGURES...................................................................................................... XLIST OF TABLES...................................................................................................... XI
CHAPTER 1 INTRODUCTION.......................................................................................1
1.1 General ....................................................................................................................1
1.2 Dwelling or Residential areas design .....................................................................1
1.3 Project Objectives ..................................................................................................2
1.4 Outline .....................................................................................................................2
CHAPTER 2 ILLUMINATION SYSTEMS.........................................................................4
2.1 Indoor lighting ........................................................................................................4
2.1.1 Introduction ...................................................................................................4
2.1.2 Basic Definitions ...........................................................................................4
2.1.3 Types of lamps ..............................................................................................6
2.1.4 Designing of the lighting scheme ...............................................................11
2.1.5 method of calculations ................................................................................12
2.2 Street lighting: .......................................................................................................17
2.2.1 Introduction: ................................................................................................17
2.2.2 Arrangement of luminaries .........................................................................17
Street lighting arrangements...............................................................................18
Curves 19
2.2.3 Choose of lamps for street lighting .............................................................20
2.2.6 Calculation of street lighting: ...................................................................20
2.2.4 llumination level for street for lighting and mounting height of lamps .....21
2.2.5 Methods of streets lighting design ..............................................................22
2.3 Comparison between good and bad design of outdoor lighting .......................... 22
2.3.1 Bad Lighting design Examples ...................................................................23
2.3.2 Good Lighting design Examples ...............................................................24
CHAPTER 3 BRANCH CIRCUIT DESIGN.......................................................................26
3.1 Introduction ...........................................................................................................26
3.2 General ..................................................................................................................26
3.2.1 The definition of branch circuit ..................................................................27
3.2.2 General purposes of branch circuit: ............................................................27
3.2.3 Individual branch circuit: ............................................................................27
V
-
7/31/2019 BOOKfm6
6/161
3.2.4 Multi wire branch circuit : ..........................................................................27
3.2.5 Rating of branch circuit: .............................................................................27
3.2.6 The electrical requirements for place have equipment or devices: ............28
3.2.7 Ungrounded conductors: .............................................................................29
3.3 Lighting branch circuit: ........................................................................................30
3.3.1 The electrical applications of different voltages: ......................................30
3.3.2 Continuous and non-continuous loads: .....................................................31
3.3.3 The ground fault circuit interrupter protection for personnel: ..................33
3.3.4 Storage or equipment: ................................................................................33
3.3.5 Other than dwelling units: ...........................................................................33
3.3.6 Lighting outlets required: ...........................................................................33
3.3.7 15-and 20- ampere branch-circuit: ...........................................................34
3.3.8 30-ampere branch circuits: ........................................................................34
3.3.9 Required outlets ........................................................................................34
3.3.10 Dwelling unit receptacle outlets: ............................................................35
3.3.11 40 and 50 Ampere branch circuit: ..........................................................35
3.3.12 Branch circuits larger than 50 amperes: .................................................35
3.4 Receptacles ............................................................................................................35
3.4.1 Single Receptacle on an Individual Branch Circuit: ..................................35
3.4.2 Total Cord-and-Plug-Connected Load: ......................................................35
3.4.3 Receptacle Ratings ......................................................................................36
3.4.4 Branch-Circuit Requirements Summary ...............................................36
3.4.5 Dwelling Unit Receptacle Outlets ..............................................................37
3.4.6 Spacing ........................................................................................................38
3.4.7 Wall Space ..................................................................................................383.4.8 Floor Receptacles ........................................................................................38
3.4.9 Bathrooms ...................................................................................................39
3.4.10 Hallways ...................................................................................................40
3.4.11 Heating, Air-Conditioning, and Refrigeration Equipment Outlet ..........40
3.4.12 Receptacle Outlets ...................................................................................40
3.4.13 Small Appliance Circuit Load .................................................................42
3.4.14 Appliance Load Dwelling Unit(s) ......................................................42
3.4.15 Heating and Air-Conditioning Load ........................................................43
VI
-
7/31/2019 BOOKfm6
7/161
3.5 Motor Branch Circuit Design ...............................................................................44
3.5.1 Motor Overload protection .........................................................................45
3.5.2 Motor Branch-Circuit Short-Circuit and Ground-Fault Protection ...........46
3.6 Components of low voltage distribution system ..................................................49
3.6.1 Distribution transformer .............................................................................50
3.6.2 Distribution boxe (Pillar) ............................................................................50
3.6.3 Building box (coffree) ................................................................................51
CHAPTER 4 CABLE SIZING AND PANELBOARDE DESIGN............................................52
4.1 Introduction ...........................................................................................................52
4.2 Under Ground Cables ...........................................................................................52
4.2.1 Introduction .................................................................................................52
4.2.2 Basic definition ...........................................................................................53
4.2.3 Main Requirements OF Cable ....................................................................55
4.2.4 General construction of cables ....................................................................55
4.2.5 Type and classification of cables ................................................................62
4.2.6 Method of laying under ground cables ......................................................64
4.2.7 Method of laying under ground cable in special location ..........................65
4.2.8 Cable Sizing ................................................................................................66
4.2.9 Voltage drop calculation: ............................................................................69
4.2.10 Calculation of short circuit current ..........................................................70
4.3 Panelboards and power factor improvement ........................................................70
4.3.1 Panel boards ................................................................................................70
The selection of circuit breaker is based on: ......................................................76
4.3.2 Power Factor Improvement ........................................................................76
CHAPTER 5 GROUNDING AND STANDBY SYSTEMS....................................................78
5.1 Introduction ...........................................................................................................78
5.2 The main objectives of the grounding are to: .......................................................78
5.3 The qualities of a good grounding system are: ....................................................78
5.4 System Grounding: ...............................................................................................78
5.5 IEC nomenclature: ................................................................................................79
5.5.1 TN network: ................................................................................................80
5.5.2 TN-S: ...........................................................................................................81
5.5.3 TN-C: ..........................................................................................................815.5.4 TN-C-S grounding system: .........................................................................82
VII
-
7/31/2019 BOOKfm6
8/161
5.5.5 TT network: ...............................................................................................83
5.5.6 IT network: ..................................................................................................83
5.5.7 Example of The Various Earthing Systems Included In The Same
Installation :: .........................................................................................................84
5.6 Earth Conductors: .................................................................................................84
5.6.1 Conductor sizing : .......................................................................................85
5.7 Earth Electrodes: ...................................................................................................86
5.7.1 Rod Electrode: .............................................................................................87
5.7.2 Plates: ..........................................................................................................88
5.7.3 Earth Plates (courtesy A N Wallis and Co): ...............................................88
5.8 Earth Resistivity and Design of Driven Grounding: ............................................88
5.8.1 Calculation Procedure: ................................................................................88
5.9 Lightning Protection .............................................................................................92
5.9.1 Introduction: ................................................................................................92
5.9.2 Risk Assessment: ........................................................................................93
5.9.3 Components of the Lightning Protection System: .....................................94
5.9.4 Air terminations: .........................................................................................94
5.9.5 Down leads and bonding conductors: .........................................................95
5.9.6 Earth termination: .......................................................................................95
5.9.7 Electrical Safety in the Workplace: ............................................................95
5.9.8 Ten Golden Rules: ......................................................................................95
5.10 Emergency and standby systems .......................................................................97
5.10.1 Introduction ...............................................................................................97
5.10.2 Definitions ................................................................................................97
5.10.3 Main idea ...................................................................................................975.10.4 Tests and Maintenance ..............................................................................98
5.10.5 Capacity .....................................................................................................99
5.10.6 Generator Set .............................................................................................99
5.10.7 Precautions should be made before using emergency and standby
systems 100
CHAPTER 6 HELIOPOLIS SPORTING CLUB HOUSING PROJECT CASE STUDY..............103
6.1 General ...............................................................................................................103
6.2 Models A and B .................................................................................................105
VIII
-
7/31/2019 BOOKfm6
9/161
6.2.1 Model A description ................................................................................105
6.2.2 Model A, flat type1( 145 m2): ..................................................................105
6.2.3 Model A, flat type2( 120 m2): ................................................................107
6.2.4 Model A, Riser and feeder calculations: ..................................................108
6.2.5 Elevator calculations .................................................................................109
6.2.6 Calculation of the main feeder for model A: ...........................................110
6.3 Models C and D .................................................................................................112
6.3.1 Model C, flat type1( 115 m2): ..................................................................112
6.3.2 Model C, flat type2( 145 m2): ..................................................................114
6.3.3 Model C, Riser and feeder calculations: ...................................................115
6.4 Outdoor lighting .................................................................................................118
6.4.1 Lighting Pillars calculations: ....................................................................118
6.5 Transformer Calculations ...................................................................................119
6.5.1 Transformer sizing ....................................................................................119
6.5.2 Short circuit calculation ...........................................................................128
6.6 Summary .............................................................................................................130
CHAPTER 7 CONCLUSIONS..................................................................................... 131
7.1 General ................................................................................................................131
7.2 Conclusions ........................................................................................................131
APPENDIX A: LUMINAIRES DATA........................................................................ 133APPENDIX B: CABLES DATA.................................................................................142
APPENDIX C GROUNDING DATA...........................................................................148
IX
-
7/31/2019 BOOKfm6
10/161
LIST OF FIGURES
Figure 2-1 Filament Lamp...............................................................................................6Figure 2-2 Fluorescent lamps............................................................................................9
Figure 2-3 OSRAM clear Mercury vapour lamp HQA 80 Watt............................10Figure 2-4 OSRAM colour corrected Mercury vapour lamp HQL 80........................................11
Figure 2-5 Single sided arrangement................................................................................18Figure 2-6 Staggered arrangement....................................................................................18Figure 2-7 Opposite arrangement.....................................................................................19
Figure 2-8 Middle arrangement.......................................................................................19Figure 2-9 Bad street lighting design.................................................................................23
Figure 2-10 Bad canopy lighting design.............................................................................24Figure 2-11 Good street lighting design.............................................................................24
Figure 2-12 Good canopy lighting design...........................................................................25Figure 3-13 Branch circuit layout.....................................................................................27
Figure 3-14 Combination receptacle.................................................................................28Figure 3-15 Combination receptacle and switch...................................................................29
Figure 3-16 Multiconductor armoured cable.......................................................................29 Figure 3-17 Branch circuit panelboard...............................................................................30Figure 3-18 Street-tunnel lighting....................................................................................31
Figure 3-19 Continuous load branch circuit........................................................................32Figure 3-20 Dwelling unit receptacle outlets.......................................................................37
Figure 3-21 Wall space.................................................................................................38Figure 3-22 General load branch circuit.............................................................................39
Figure 3-23 Receptacle outlets........................................................................................41Figure 3-24 Receptacle branch circuit...............................................................................42
Figure 3-25 A main distribution center supplying individual branch..........................................48Figure 3-26 A feeder supplying individual branch circuits to each motor.....................................48
Figure 3-27 A 20-ampere branch circuit supplying lighting, small motors, and appliances...............49Figure 3-28 A motor branch circuit showing the essential parts................................................49
Figure 4-29 Hand hole enclosure.....................................................................................55Figure 4-30 construction of cable.....................................................................................56
Figure 4-31 Aluminium cable.........................................................................................57Figure 4-32 Copper cable..................................................................57
Figure 4-33 Insulation materials................................................................58Figure 4-34 Single core cable..........................................................................................63
Figure 4-35 Multicore cable...........................................................................................63Figure 4-36 Direct laying method....................................................................................65
Figure 4-37 Road crossing.............................................................................................65Figure 4-38 In tunnel....................................................................................................66
Figure 4-39 A panelboard with main circuit breaker disconnect, suitable for use as service equipment.. .72
Figure 4-40 An arrangement of three individual lighting and appliance branch circuit panelboards with
main overcurrent protection remote from the panelboards.......................................................73Figure 4-41 Circuitry for a 200-ampere (left) and a 150-ampere (right) split-bus panelboard............73
Figure 5-42 TN system.................................................................................................80Figure 5-43 TN-S system...............................................................................................81
.Figure 5-44 TN-C system.............................................................................................82Figure 5-45 TN-C-S system............................................................................................82
Figure 5-46 TT system..................................................................................................83Figure 5-47 IT...........................................................................................................84
Figure 6-48 Landscape of the buildings area.....................................................................103Figure 6-49 Picture for the entire buildings.......................................................................104
Figure 6-50 single line diagram for x-Floor of model A.......................................................106Figure 6-51 single line diagram of the ground floor in model A.............................................108
Figure 6-52 MDB for buildings of model A......................................................................111 Figure 6-53 single line diagram of ground floor of model C..................................................113Figure 6-54 single line diagram of x- floors of model C.......................................................115
X
-
7/31/2019 BOOKfm6
11/161
Figure 6-55 MDB of buildings of model C.......................................................................118
LIST OF TABLES
Table 2-1 Main characteristics of incandescent lamp...............................................................7Table 2-2 Advantages and Disadvantages of Fluorescent Lamps.................................................9
Table 2-3 VA per square meter [NEC]..............................................................................13Table 2-4 Utilization factor table.....................................................................................17
Table 2-5 Arrangement of Luminaires...............................................................................17Table 2-6 Primary initial design.......................................................................................21
Table 3-7 Maximum Cord-and-Plug-Connected Load to Receptacle..........................................35Table 3-8 Receptacle Ratings for Various Size Circuits..........................................................36
Table 3-9 Summary of Branch-Circuit Requirements............................................................36Table 3-10 Motor overload protection...............................................................................45
Table 3-11 Motor overload relay protection........................................................................45Table 3-12 Motor thermal protector..................................................................................45
Table 3-13 motor branch circuit short-circuit and ground-fault protection...................................47Table 4-14 Comparison between Copper and Aluminium materials...........................................56
Table 4-15 the main properties of insulating material............................................................59Table 4-16 Ambient temperature (A)................................................................................69
Table 5-17 IEC nomenclature.........................................................................................79Table 5-18 IEC nomenclature.........................................................................................79
Table 5-19 Three variants of TN systems...........................................................................80Table 5-20 Formulas for Calculation of Resistances to grounding.............................................89
Table 5-21 Resistivity of Different Soils............................................................................90Table 5-22 Effect of Moisture Content on Resistivity of Soil...................................................91
Table 5-23 Effect of Temperature on Resistivity of Sandy Loan, 15.2 Percent Moisture................91Table 6-24 loads in VA of flat 145 m2 , model A...............................................................105Table 6-25 loads in VA of flat 120 m2 , model A...............................................................107
Table 6-26 Total VA connected to the feeder of buildings of model A......................................110Table 6-27 Loads in VA of flat 115 m2 , model C..............................................................112
Table 6-28 Loads in VA of flat design 145 m2, model C......................................................114Table 6-29 total VA connected to the feeder of model C.......................................................116
Table 6-30 Actual design of street lighting.......................................................................118 Table 6-31 Available Short Circuit Current for Transformers.................................................129Table 6-32 Short circuit calculation for AL cables..............................................................129
XI
-
7/31/2019 BOOKfm6
12/161
Table 6-33 Short circuit calculation for CU cables..............................................................129
XII
-
7/31/2019 BOOKfm6
13/161
Chapter 1 Introduction
CHAPTER 1 INTRODUCTION
General
The distribution of electrical energy on a consumers premises begins at
the supply intake position. The latter can take many forms depending on the type
of premises from the simple single phase arrangement in domestic premises to a
large private substation supplying an industrial complex. Whatever the size of the
installation, however certain basic requirements statutory and otherwise must be
satisfied. The main function of any internal distribution system is to divide and
subdivide the total load at the consumers terminal into small individual loads,each of which is protected and controlled by suitable rated protective devices and
switches.
1.2 Dwelling or Residential areas design
Dwelling Unit is a single unit, providing complete and independent living
facilities for one or more persons, including permanent provisions for living,
sleeping, cooking and sanitation. Dwelling unit could be One-Family which is a
building that consists solely of one dwelling unit or a Multifamily which is a
building that contains two, three or more dwelling units.
In residential areas planning, careful consideration needs to be given to the
spatial quality of layouts. Roads and buildings must be designed and located to
ensure that the scale of space between buildings is related to the pedestrian, i.e.
on a human scale and not large nor impersonal. In mixed development schemes,
open spaces should be illuminated and related to building height to provide
variety and interest and careful thought given to its intended function.
This project will focus in the electrical distribution system design for
residential areas. This will cover not only the indoor or interior design of the
building but also the outdoor design. The outdoor design includes, the design of
street lighting, outdoor pillars and electrical transformers sizing.
1
-
7/31/2019 BOOKfm6
14/161
Chapter 1 Introduction
1.3 Project Objectives
Generally, the main objective of designing an electrical distribution system for
any application is to achieve the consumer requirements in acceptableengineering way. The design procedure itself contains the following tasks:
Determining
the correct size of cables.
Choosing the
suitable capacity for switchgear system.
Deducing the
current rating of overcurrent devices.
So, in order to achieve these tasks, there are many considerations must be taken
into account as:
Subdivision
and number of circuits needed.
Nature and
type of electrical loads.
Normal
current of protective devices.
Different cable
derating factors.
Necessary
design checks such as voltage drop and short circuit calculation.
1.4 Outline
The thesis is structured into seven chapters and three appendixes as follows:
Chapter 1: general, objectives, and thesis outline are described.
Chapter 2:presents a detailed design of lighting scheme including indoor
lighting, street lighting, and comparison between good and bad design.
Chapter 3: explains the load estimation and design of lighting branch circuit,
receptacles, and motors branch circuit.
2
-
7/31/2019 BOOKfm6
15/161
Chapter 1 Introduction
Chapter 4: in this chapter cable sizing and panelboard design are detailed for
comprehensive design.
Chapter 5: covers the grounding and standby systems which are required for safe
and reliable operation of any electrical system design.
Chapter 6: discusses the capabilities of the proposed design procedure by
deigning a real case study.
Chapter 7: summarises the work and highlights the main conclusions.
Appendix A: includes the main luminaires data required for lighting calculation.
Appendix B: includes the main cables data required for branch circuit and cable
sizing.
Appendix C: contains main important grounding data.
3
-
7/31/2019 BOOKfm6
16/161
Chapter 2 Illumination Systems
CHAPTER 2 ILLUMINATION SYSTEMS
2.1 Indoor lighting
2.1.1 Introduction
Light is the prime factor in the human life as all activities of human beings Ultimately
depend upon the light.
Light on surfaces on which it falls. Thus the illumination makes the surface look more
or less bright with a certain colour and is this brightness and colour which the eye sees
and interprets as something useful, or pleasant or otherwise. Where there is no natural
light, use of artificial light is made. Artificial lighting produced electrically, on account
of its cleanliness ease of control, reliability, steady output, as well as its low cost. Is
playing an increasingly important part in modern every day life. Light may be
produced by passing electric currents through filaments as in the Incandescent lamps,
through arcs between carbon or metal rods, or through suitable gases as in neon and
other gas tubes. In some forms of lamps the light is due to fluorescence excited by
radiation arising from the passage of electricity through mercury vapour.
2.1.2 Basic Definitions
- Light
It is defined as the radiant energy from a hot body, which produces the visual sensation
upon the human eye.
- Luminous Flux ( ):
It is defined as the total quantity of light energy emitted per second from a luminous
body. It is represented by symbol F and is measured in lumens.
-Illumination ( E )
The number of lumens, falling on the surface per unit area. It is denoted by symbol E
and is measured in lumens per square meter or lux.
E
=
4
-
7/31/2019 BOOKfm6
17/161
Chapter 2 Illumination Systems
-Luminous Intensity ( I)
The luminous flux from a source, In a specified direction inside a small solid angle.
And measured in lumen per steradian or candela (cd)
I
=
- Luminance ( L )
It is the intensity per apparent unit area of the surface of the actual light source. And
measured in candela per square meter (cdm-2)
IL
A=
-Reflectance (Error! Objects cannot be created from editing field codes.):
The ratio of reflected flux to incident flux (either luminous or radiant)
Luminous Efficacy ( )
It is defined as the ratio of the luminous flux to the power input, And measured in
lumen per watt ( -1lumen W ).
-Utilization factor (U.F.)
The ratio of the lumens actually received by a particular surface to the total lumens
emitted by a luminous source. This factor is varies widely according to the following
factors:
a-The type of lighting system whether it is direct or indirect.
b-The shape and relative dimension of the room.
c-The wall surface and its colour fit reflectance of light.
-Maintenance factor (M.F.)
During the deterioration of lamp accumulation of dust on the globes and reflectors, the
efficiency of reflection of light from walls due to the insufficient clearing. The
illumination under normal conditions usually less than that when every thing is
perfectly clear the relative between the two cases is the maintenance factor.
5
-
7/31/2019 BOOKfm6
18/161
-
7/31/2019 BOOKfm6
19/161
Chapter 2 Illumination Systems
The following comparison illustrates this point:
Table 2-1 Main characteristics of incandescent lamp
Lamp type
Light
Output
(Lumens)
Efficacy
(lumens/watt)
100W GLS 1350 13.5
100W Double Life 1200 12.0
100W Plus life 1050 10.5
- Incandescent Lamp Advantages
(1) Simple to use - direct connection into socket.
(2) Lowest initial lamp cost.
(3) Immediate starting and re-starting - no warm-up or cool down required.
(4) Excellent optical control - concentrated light source is easiest to direct or focus.
(5) Easiest to dim - simple variable resistor circuitry may be all that is required.
(6) Wide design flexibility - variety of styles, outputs, and colours fill nearly every
need.
(7) Output not affected by operation over a wide range of ambient temperature.
(8) Available in wattage ratings from 10 to 100W.
- Incandescent Lamp Disadvantages
(1) Sensitive to shock and vibration .
(2) High overall operating cost - low efficacy and short life.
(3) Sensitive to voltage variations
(4) Sensitive to thermal shock - high bulb surface temperature requires that the lamp
be protected from moisture. Exceptions are hard glass bulbs and low wattage lamps
(less than l0W). Lowest efficacy - all other lamp types surpass incandescent
performance by a large margin.
(ii) Halogen Lamps
7
-
7/31/2019 BOOKfm6
20/161
Chapter 2 Illumination Systems
A halogen lamp is a special kind of incandescent lamp. The light output is more
consistent than a standard incandescent lamp and the life is longer. Size is smaller
because it is important for the halogen cycle to have a high bulb wall temperature,
which requires quartz or hard glass to be used. Better beam control is possible because
of the small source size. Basic Halogen Lamp Types The common types of halogen
lamps are:
(1) Linear (sometimes called double-ended)
(2) Single-ended
(3) Capsule (single-ended but no outer bulb)
(4) PAR (capsule contained in PAR shape bulb) Used for gardens or stage lighting.
Also known as spot or reflector lamps Lens
(5) Low Voltage Reflector (Precise lamps)
(A) Features Of The Halogen Lamps
(1) Luminous Efficacy :
Luminous efficancy increases with higher tungsten temperature. Using Xenon (larger
atoms) the temperature can be raised to increase the luminous efficacy by 5%-10%
and colour temperature by about 100 degrees Kelvin. Xenon can only be used in low
voltage lamps because the lower ionizing energy of Xenon would lead to an electrical
discharge with higher voltages.
(iii) Fluorescent Lamps
The fluorescent lamp is commonly used. It has hundreds of sizes, wattage, colours,
voltages and specific application designs the typical fluorescent lamp is a hot cathode
type, consisting of a sealed glass tube containing a mixture of inert gas and mercury
vapour. The cathode causes a mercury arc to form inside the tube. This arc produces
ultraviolet (UV) light, which is not visible to the naked eye. The UV light strikes the
phosphors coating that is inside of the tube which will fluoresce producing visible
light. By changing the type of phosphors, the lamp colour, output can be controlled.
The fluorescent lamp requires a ballast in its circuit. Its purpose it limits the current in
the circuit, without the ballast the lamp would draw excessive current, and the fuse or
circuit breaker would open. The lamp also
consists of a starter, which acts as switch.
8
-
7/31/2019 BOOKfm6
21/161
Chapter 2 Illumination Systems
Figure 2-2 Fluorescent lamps
(A) The life of fluorescent lamps
Fluorescent lamps have outstandingly long life. This life however is affected by the
number of times the lamp is turned on and off, since switching tends to wear out the
cathode. An average fluorescent lamp burned continuously will last about 30000hours;
with 3 burning hours per start, it will last about 12000hours.Most users replace lamps
when they reach about 75% of burn out life because the light output has dropped at that
point to about two third.
(B) Power Factor of Fluorescent LampOrdinary incandescent lamps have a power factor of 100%. A fluorescent lamp
connected to a circuit has a power factor of somewhere between 50% and 65% to
improve power factor.
(C) Advantages and Disadvantages of Fluorescent Lamps
Table 2-2 Advantages and Disadvantages of Fluorescent Lamps
Advantages Disadvantages
Low surface brightness Requires a ballast and sometimes a starter
Low heat output Sensitive to ambient temperature
Low bulb wall temperature Ballast may produce audible hum if
not operated by an electronic ballast
Variety of colours Lamp flicker may irritate some
occupants if not operated by an electronic
ballast
Long life (easier maintenance) Colour rendering not as good asincandescent, but can be very close
9
http://en.wikipedia.org/wiki/Image:Leuchtstofflampen-chtaube050409.jpg -
7/31/2019 BOOKfm6
22/161
Chapter 2 Illumination Systems
Reduced shadowing
Efficiency is much higher
(D) Compact Fluorescent
Compact fluorescent lamps resulted from research into energy saving lighting. The
goal was to develop smaller, more efficient light sources with greater lumen output
per watt. One solution was to re-design the fluorescent lamp and its cap. Two basic
designs have emerged:
(1) Biaxial
(2) Square plane
The internal construction and function of all variants is very similar to linear (straight)
fluorescent lamps.
(iv) Discharge Lamps
Gas discharge lamps are used in virtually all areas of modern lighting
As for fluorescent lamps the electrical energy is transformed into radiated energy by
the discharge through a gas/metal vapour, The spectral distribution is dependant on the
chemical and the pressure/temperature of the discharge
(A) Types of Discharge Lamps
(1) Low Pressure Sodium
(2) High Pressure Sodium
(3) High Pressure Mercury
(4) Metal Halide
Figure 2-3 OSRAM clear Mercury vapour lamp HQA 80 Watt.
10
-
7/31/2019 BOOKfm6
23/161
Chapter 2 Illumination Systems
Figure 2-4 OSRAM colour corrected Mercury vapour lamp HQL 80
The choice of colours, size and rating is greater for Metal Halide than any other lamp
type Some Metal Halide lamps use a third electrode for starting, but other, especially
the smaller display lamps, require a high voltage ignition pulse The halides act in a
similar manner to the tungsten halogen cycle. As the temperature increases there is
disassociation of the halide compound releasing the metal into the arc. The halides
prevent the quartz wall getting attacked by the alkali metals.
2.1.4 Designing of the lighting scheme
(i) Some factors should be considered(1) Illumination level:
This is the most vital factor because a sufficient illumination is the basic means by
where we are able to see our surroundings; it is the task of illumination to give objects
a distributed brightness.
Objects which are seen for longer duration of time require more illumination than
those for casual work. Similarly moving objects require more illumination than those
for stationary object.
(2) Colour of light:
The appearance of the body colour entirely depends upon the colour of the incident
light. In general the composition of the light should be such that the colour appears
natural i.e. its appearance by artificial light is not appreciably different from that by
day light.
(3) Shadows:
11
-
7/31/2019 BOOKfm6
24/161
Chapter 2 Illumination Systems
In lighting installations, formation of long and hard shadow causes fatigue of eyes and
therefore is considered to be a short coming. Complete absence of shadows altogether
again does not necessarily mean an ideal condition of lighting installations.
(4) Mounting Height:
The mounting height will largely be governed by the type of building and type of
lighting scheme employed. In the case of direct lighting, in rooms of large floor area,
the luminaries should be mounted as close to the ceiling as possible. Lowering them
not only will make the illumination less uniform, but will also bring them more into the
field of vision, thus increasing the glare, without causing an appreciable increase in the
coefficient of utilization. In the usual case of small
rooms with high ceilings, there is something to be gained by lowering the luminaries.
(5) Spacing of luminaries:
Correct spacing is of great importance to provide uniform illumination. With
fluorescent luminaries it is good practice to aim at a value of unity for this ratio, and to
set an upper limit of () In this case of tungsten lamps combined with focusing
reflectors, it is good practice to aim at a horizontal spacing between rows
approximately equal to the height of the ceiling above the working plane, and in
no case should the horizontal spacing exceed 1 times this height.
(6) Colour of surroundings walls:The illumination in any room depends upon the light
reflected from the walls and ceiling. White walls and ceiling reflect more light as
compared to colored ones
2.1.5 method of calculations
For lighting distribution calculations, two methods are introduced:(1) VA method.
(2) Lux method.
(i) the VA method
The procedures:
(1) Determine the area of the room, (A) =width X length.
(2) Identify VA/m2 according to the room purpose.
(3) Total VA = (VA/m2) x area (A).
12
-
7/31/2019 BOOKfm6
25/161
Chapter 2 Illumination Systems
(4) Identify the used luminary type.
(5) Calculate the output VA of one luminary.
(6) Number of luminaries = (total VA) / (VA of one luminary).
(7) Calculate the proposed number of luminaries.
(8) Calculate the new total VA.
(9) Distribute the number of luminaries on the area
Table 2-3 VA per square meter [NEC]
Type of occupancy Unit load
VA per square meter
BanksChurches
Clubs
Court rooms
Dwelling units
Hospitals
Industrial commercial buildings
Lodge rooms
Office buildings
Restaurants
SchoolsStores
Halls, corridors, stairways
Storage spaces
Bathroom
Cafeteria
Rest room
3911
22
22
33
22
22
17
39
22
3333
6
3
32.26
22
32.26
13
-
7/31/2019 BOOKfm6
26/161
Chapter 2 Illumination Systems
(ii) by using lux method
The lumen method is used in calculating the average illuminance Eon the working
plane in an interior. This is defined as:
EA
=
where is the lighting flux [lumen], and A is the working plane area .A coefficient of
utilisation (UC) gives the fraction of lamp lumens that reach the workplane, directly
from sources and from inter-reflections. TheUC takes into account the efficiency of
the luminaire and the impact of the luminaire distribution and the room surfaces in its
derivation. Thus the number of lumens produced by the lamps, multiplied by thisUC ,
determines the number that reaches the workplane:
UcE=
Since the design objective usually is maintained illuminance, a light loss factorLLF
must be applied to allow for the estimated depreciation in lamp lumens over time, the
estimated losses from dirt collection on the luminaire surfaces (including lamps), and
other factors that affect luminaire lumen output over time. Theformula thus becomes
UC LLF E
A
=
Although design calculations are based on the LLF using both non-recoverable and
recoverable factors, it is sometimes necessary to calculate illuminance in a new
lighting installation. In such cases, repeat the calculation using the non-recoverable
losses, since the recoverable losses do not occur at 100 hours, the time at which lamps
are nominally at rated lumens[16].The lamp lumens in the formula are most
14
-
7/31/2019 BOOKfm6
27/161
Chapter 2 Illumination Systems
conveniently taken as the total rated lamp lumens in the luminaires. If the desired
maintained illuminance is known, this equation can be solved for the
total number of luminaires needed:
E ANOL
LPL LL UC LLF
=
where NOL is the number of Luminaires, LL is the lamp lumen and LPL is the
number of lamps per luminaire.
(A) Limitations
The illuminance computed by the lumen method is an average value that is
representative only if the luminaires are spaced to obtain reasonably uniform
illuminance. The calculation of the coefficients of utilisation is based on empty
interiors having surfaces that exhibit perfectly diffuse reflectance. The average
illuminance determined by the lumen method is defined to be the total lumens reaching
the workplane divided by the area of the workplane. The average value
determined this way might vary considerably from that obtained by averaging discrete
values of illuminance at several points [16].
(B) Cavity Ratios
The radiative exchange between the top and the base of a rectangular space is a
function of the proportions of its length, width, and height. Cavity ratio values
approximate this effect by combining these proportions into a single quantity. In the
Zonal-cavity method, the effects of room proportions, luminaire suspension length, and
workplane height upon the coefficient of utilisation are respectively represented by the
room cavity ratio, ceiling cavity ratio, and floor cavity ratio. These ratios are
determined by dividing the room into three cavities, and substituting dimensions (in m
or ft) into the following formula[16, 17]:
5 ( )h l wCRl w+=
15
-
7/31/2019 BOOKfm6
28/161
Chapter 2 Illumination Systems
where CR is the cavity ratio, h is the cavity height, l is the cavity length, and w is
the cavity width. The illuminance in rooms of irregular shape can be determined by
calculating the room cavity ratio using the following formula and solving the problem
in the usual
manner:
2.5h CCCR
CA
=
where CA is the cavity base area, and CC is the cavity circumference.
(C) Effective Cavity Reflectances
Table 2-10 provides a means of converting the combination of wall and ceiling or wall
and floor reflectances into a single effective ceiling cavity reflectance, CC ,and a
single effective floor cavity reflectance, FC . In lumen method calculations, the
ceiling, wall, and floor reflectances should be initial values. Note that for surface-
mounted and recessed luminaires, the ceiling cavity ratio equals zero and the actual
ceiling reflectance may be used for CC . Luminaires coefficient of utilization:
Absorption of light in a luminaire is taken into account in the computation of
coefficient of utilisation (UC) for that luminaire. Appendix A is a tabulation of
coefficients of utilisation calculated by the Zonal-cavity method for representative
luminaire types. These coefficients are for an effective floor cavity reflectance of 20%,
but any UC obtained from the table may be corrected for a different value of FC by
applying the appropriate multiplier from table Since the light loss factor includes the
effect of dirt deposited on wall surfaces, the selection of the proper column of wall
reflectances, W , should be based on the initial values expected. The wall reflectance
should also represent the weighted average of the reflectances of the painted areas,
fenestration or daylight controls,
chalkboards, shelves, and so forth in the area to be lighted. The weighting should be
based on the relative areas of each type of surface within the cavity being considered.
In using, it is often necessary to interpolate between room cavity ratios CR and
16
-
7/31/2019 BOOKfm6
29/161
Chapter 2 Illumination Systems
effective ceiling cavity reflectances. This is most easily accomplished by interpolating
first between room CR to obtain CU for effective
ceiling cavity reflectances that straddle the actual CC
, and then interpolating between
these CU values.As a guide line the following utilisation factors can be adopted with
good accuracy for most applications [39]:
Table 2-4 Utilization factor table
Type of illumination Approximate Utilisation factor
Range average
Direct 0.45:0.6 0.53
Manly direct 0.4:0.55 0.48
Uniform 0.35:0.50 0.43
Mainly indirect 0.35:0.45 0.4
Indirect 0.2:0.35 0.28
Indirect (cornice) 0.10:0.20 0.15
2.2 Street lighting:
2.2.1 Introduction:
With the increase of high-speed traffic upon our roads, it has become essential ,in order
to reduce accidents, to provide adequate illumination on all streets ,roads, traffic
junctions, tunnels, bridges etc.
2.2.2 Arrangement of luminaries
The next table shows the most used type of arrangement according to height-to-width
Ratio:
Table 2-5 Arrangement of Luminaires
type of arrangement Ratio (height of luminaries / width of
carriage way)
Single sided 0.85(min. value) 1(recommended value)Staggered 0.5(min. value) 2/3(recommended value)
17
-
7/31/2019 BOOKfm6
30/161
Chapter 2 Illumination Systems
opposite 1/3(min. value) ( recommended value)
Street lighting arrangements
2.2.3.1 Two way traffic roads
There are four basic types of street lighting arrangements, which can be
summarized in the following points.
Single sided
This type of arrangement, in which all luminaries are located on one side of the
road, is used only when the width of the road is equal to, or less than the mounting
height of the luminaries. This is shown in the next figure.
Figure 2-5 Single sided arrangement
Staggered or zigzag array
This type of arrangement in which the luminaries are located on both sides of the
road in a staggered or zigzag arrangement is used mainly when the width of the road is
between 1 to 1.5 times the mounting heights of the luminaries.
Figure 2-6 Staggered arrangement
18
-
7/31/2019 BOOKfm6
31/161
Chapter 2 Illumination Systems
Opposite double side array
This type of arrangement, with the luminaries located on both sides of the road
opposite to one another, is used mainly when the width of the road is greater than 1.5
times the mounting height of the luminaries.
Figure 2-7 Opposite arrangement
Middle one side array
This type of arrangement, with the luminaries suspended along the axis of the road,
is normally used for narrow roads that have buildings on both sides.
Figure 2-8 Middle arrangement
Curves
Curves of large radius (in the order of 300 m) can be treated as straight roads and the
luminaries can be sited in accordance with one of the schemes outlined above.
The locations of luminaries on curves of smaller radius, however, should be such as
to ensure both adequate road-surface luminance and effective visual guidance. Where
the width of the road is 1.5 m less than the mounting height, the luminaries should be
placed above the outside of the curve in a single sided arrangement.
For wider roads an opposite arrangement should be used since the staggered
arrangement gives visual guidance, and should therefore be avoided.
19
-
7/31/2019 BOOKfm6
32/161
Chapter 2 Illumination Systems
2.2.3 Choose of lamps for street lighting
(i) The selection of luminaries according to its lighting distribution
two way streets crowded streets and high way crosses and intersection.
(ii) Type of lamps which are used for street lighting
(A) Low pressure sodium lamp.
-law pressure sodium lamps are the best for:
More sharpness vision. High speed response. Less discomfort glare.
Obtain large brightness area at the same value.Note: the power used in high ways is usually:-150 W for 12 m width street.
-200 W for 15 m width streets.
(B) High pressure sodium lamps
High pressure sodium lamps are the best for the crowded ways because it can
transmitted the colours.
Note:
The power which is used in crowed ways is:
-150 W/12 m.-250 or 400 W/15 m.
2.2.6 Calculation of street lighting:
. .F M F U FE
W L
=
Where:
F: total luminous flux of the lamp.
UF: utilization factor ranges from (0.2:0.6).
MF: maintenance factor (0.8:0.9).
L: space between the poles in meter.
W: width of the road in meter.
E: Average illumination over the working plane. (10 lux for Submain streets and upto
30 lux for main streets).
Notes:
For primary initial design the street loading can be estimated accordingto the next table.
20
-
7/31/2019 BOOKfm6
33/161
Chapter 2 Illumination Systems
Table 2-6 Primary initial designE(Lux) Rout loading with 8 m
road
Rout loading with 12 m
road
High pressure
mercury lamps
High pressure
sodium lamps
High pressure
mercury lamps
High pressure
sodium lamps
26
19
13
6
4
(15:28)KW/K
m
(12:14)KW/K
m
(8:16)KW/Km
(6:10)KW/Km
4 KW/Km
(11:18)KW/K
m
(9:14)KW/Km
(6:10)KW/Km
(24:38)KW/K
m
(18:29)KW/K
m
(12:20)KW/K
m
(9:14)KW/Km
(13:20)KW/K
m
(11:16)KW/K
m
(9:12)KW/Km
2.2.4 llumination level for street for lighting and mounting height of
lamps
Table 2-7 Lux according to type of road , way
Type of road , way lux level
high way , main road and main streets 20 30 lux
Secondary road 15 20 luxResidential area street ,industrial area street 10 15 lux
Table 2-8 Table of luminous flux of luminaries according to Mounting height of
luminaries
luminous flux of luminaries Mounting hight of luminaires
3000 to 10000 6 to 7 meter
10000 to 20000 7 to 9 meter
More than 20000 more than 9 meter
Example for street lighting
For 300 meter road of width 12 meter , compute the luminaries spacing (L) for average
illumination of E = 30 LUX using 250 watt h.p. sodium lamp of 25000 lumen (take uf
= 0.33 , Mf = 0.9 , pole height 6 meter)
Solution:
25000 0.9 0.3321
12 30
F MF UFL
W E
= = =
meter
So that, number of luminaires =300
21=15 luminaires
21
-
7/31/2019 BOOKfm6
34/161
Chapter 2 Illumination Systems
Note: the best tilt angle ( ) for maximum light utilization ranging from 10:15 degree
2.2.5 Methods of streets lighting design
(i) The factors which effect on the street lighting design
Passi
ng safety.
Safet
y of people.
The
region which pass through the street. Type
of street.
Numb
ers of crimes , rubbers and security requirement.
(ii) The steps which must be known design street lighting
Street
profile.
The
average lighting of street surface.
The
degree of permanent glare.
The
rate of visible direction which must be find.
The
degree of required the lighting regulation.
2.3 Comparison between good and bad design of outdoor lighting
Below are bad and good examples of outdoor lighting. Lighting with high glare will
have a bright ball of light around the fixture where as lighting that is well shielded, low
22
-
7/31/2019 BOOKfm6
35/161
Chapter 2 Illumination Systems
glare, and with minimal spillage will appear with a smaller or ball of light. First we
will look at some bad lighting examples, then some good.
2.3.1 Bad Lighting design Examples
Figure 2-9 Bad street lighting design
6 Mile by Laurel Park Mall. Notice the large halos around the lamps. These are bright
400 watt HPS fixtures that have very high glare giving a harsh appearance, plus
causing unnecessary stress and distraction to the eye . This problem could be
significantly reduced by using shielded fixtures and/or reduced wattage.
23
-
7/31/2019 BOOKfm6
36/161
Chapter 2 Illumination Systems
Figure 2-10 Bad canopy lighting design
Mobil gas station on NW corner of Merriman and I-96. Notice the bright balls of light
under the canopy, indicating high glare.
2.3.2 Good Lighting design Examples
Figure 2-11 Good street lighting design
Livonia City Hall's parking lot on Farmington and 5 Mile. The area uses non-excessive
flat glass shoe box fixtures rendering good visibility with low glare. Notice how halos
are smaller compared to previous pictures and the parking lot is well lit. (Camera
shows HPS brighter that the blue white Metal Halide fixtures in earlier photos).
24
-
7/31/2019 BOOKfm6
37/161
Chapter 2 Illumination Systems
Figure 2-12 Good canopy lighting design
Sunoco on SW corner of 6 Mile and Farmington. Although the fixtures are not
shielded, they are recessed under the overall canopy, and because they are not overly
bright, the station is well lit and does not have obtrusive glare. Because the fixtures are
not glaring or at excessive levels, attention is not drawn away from the area or activity
because of lighting.
25
-
7/31/2019 BOOKfm6
38/161
Chapter 4 Branch Circuit Design
CHAPTER 3 BRANCH CIRCUIT DESIGN
3.1 Introduction
-A branch circuit is any segment of a wiring system extending beyond the final
automatic over current protective device that is approved for use as branch circuit
protection & designated by the NEC as the branch circuit protective device.
-Branch circuits generally originate in panel boards, but individual branch circuits
to motors commonly originate at individual fused switches or C.B. tapped from
bus ways.
-In an electrical system, the branch circuits are the circuits of lowest capacity and
current rating. They are the circuits to which load devices (light, motors, etc.)
are connected.
-A branch circuit consists of two wires, which carry current at a particular voltage
from protective device to utilization device. Although the branch circuit
represents the last step in the transfer of power from the service or source of
energy to the utilization devices. It is the starting point for modern design
procedures.
-Each & every branch circuit , whether for a power or lighting load in a
commercial, industrial, or residential building , should be sized for its load, with
spare capacity added where possible load growth is indicated .
-The rating of the circuit fuse or C.B. must not be less than 125% of the
continuous current load.
3.2 General
A branch circuit consists of two wires, which carry current at a particular voltage
from protected device to utilization device. Although the branch circuit represents
the last step in the transfer of power from service or source of energy to the
utilization devices, it is the starting point from modern design procedures.
26
-
7/31/2019 BOOKfm6
39/161
Chapter 4 Branch Circuit Design
3.2.1 The definition of branch circuit
The circuit conductors between the final over current device protecting the circuit
And the outlet (load).
Figure 3-13 Branch circuit layout
3.2.2 General purposes of branch circuit:
Branch circuit that is supplies two or more outlets for lighting and other
equipment.
3.2.3 Individual branch circuit:
Branch circuit that is supplies only one utilization equipment.
3.2.4 Multi wire branch circuit :
It is consists of two or more ungrounded conductors that have voltage betweenthem and grounded conductor have equal volt between it and each ungrounded
conductor in the circuit and it is connected to neutral and the grounding of the
system
3.2.5 Rating of branch circuit:
The rate of branch circuit can be indicated according to the maximum current of
the circuit. and also the over current protective device will be rated according to
the maximum current of branch circuit.
27
-
7/31/2019 BOOKfm6
40/161
Chapter 4 Branch Circuit Design
The wiring conductor must be withstand the current pass through it The rate of
branch circuit based to the rate of over current protective device.
For example:
Branch circuit wire with 10 AWG copper has an allowable ampacity of at least 30
ampere, however if branch circuit over current protective device is 20 ampere
circuit breaker of fuse the rating of branch circuit is 20 ampere on the size or
rating of over current protective device. The branch circuit greater than 50
ampere used to supply the non lighting loads for the industrial purposes we can
use the several single receptacles to make easy to relocation for production or
maintenance purposes such as electric welders machine.
3.2.6 The electrical requirements for place have equipment or
devices:
Receptacles, switches, lampholders, dimmers, pilot lamp and home automatic
control the receptacles can be supplied from different nominal voltages which one
half of the receptacles supply by line to neutral voltage and another half supply by
line to line voltage and this type of receptacle called split wired receptacle The
branch circuit which supply the receptacle must have an over current protective
device such as two pole circuit breakers or single pole circuit breakers which
handle Tie.
Figure 3-14 Combination receptacle
28
-
7/31/2019 BOOKfm6
41/161
Chapter 4 Branch Circuit Design
Figure 3-15 Combination receptacle and switch
3.2.7 Ungrounded conductors:
If multiwire branch circuit supplied from different nominal voltages the under
grounded conductors in multiwire branch circuit shall be identified by separated
colour coding, marking tape ,tagging and shall be permanently posted at each
branch circuit panelboard.
Figure 3-16 Multiconductor armoured cable
29
-
7/31/2019 BOOKfm6
42/161
Chapter 4 Branch Circuit Design
Figure 3-17 Branch circuit panelboard
3.3 Lighting branch circuit:
3.3.1 The electrical applications of different voltages:
(i) The voltages does not exceeds of 120 volt ot is used as the followings:
- luminaries(lighting fixtures).
- cord and plug connected loads 1440 VA.
the voltage of 120 volt between conductors is used to supply the followings:
-the terminals of lampholders which rated by this limit of voltage the auxiliary
equipments of electric discharge lamps such as ballasts and starting devices.
-cord and plug connected or permanently connected utilization equipment.
(ii) the voltage of 277 volt to ground used to supplies the following:
-electric discharge luminaries.
-the incandescent luminaries which supplied be voltage of 120 volt output from
Step-down autotransformer.
-lampholders which rated by this value of voltage.
-auxiliary equipments of electric discharge lamps.
30
-
7/31/2019 BOOKfm6
43/161
Chapter 4 Branch Circuit Design
-Cord and plug connected or permanently connected of utilization equipments
The voltage of 600 volt between conductors which used to supply the electric
discharge lamps where the height of must not less than 6.7 meter for high ways
roads and bridges and less than 5.5 meter for tunnels.
Figure 3-18 Street-tunnel lighting
3.3.2 Continuous and non-continuous loads:
The rate of over current protective device must be not less than the rate of non-
continuous loads plus 125% of continuous loads.
For example:
if the continuous load is equal to 16 ampere we can select the over current
protective device according to 125%x16=20 ampere.
And the branch circuit rating can be indicated as 20 ampere.
31
-
7/31/2019 BOOKfm6
44/161
Chapter 4 Branch Circuit Design
Figure 3-19 Continuous load branch circuit
Another example:
Determine the minimum size over current protective device and the minimum
conductor size for the following circuit:
-25 ampere of continuous load.
-60 degree over current device terminal rating.
-type THWN conductors.
-four current carrying copper conductors in a raceway.
Solution:
-the size of over current protective device =125%x25=31.5 ampere
-we can take 35 ampere as an rating
-computed load
the conductor ampacity=percent adjustment factor
-the percent adjustment factor is indicated from table at 60 degree
so that:
-the conductor ampacity=31.5
0.8=39.06 ampere
from the above we can select the conductor size which permitted to pass through
it 40 ampere at 60 degree.
32
-
7/31/2019 BOOKfm6
45/161
Chapter 4 Branch Circuit Design
3.3.3 The ground fault circuit interrupter protection for
personnel:
When fault circuit contact with ground the high current pass through the circuit
and this value of current must be reduced by any protection methods.
3.3.4 Storage or equipment:
For attics, underfloor spaces, utility rooms, and basements at least one lighting
outlet containing or controlled by a wall switch shall be installed where these
spaces are used for storage or contain equipment requiring servicing. At least one
point of control shall be at the usual point of entry to these spaces.The lighting
outlet shall be provided at or near the equipment requiring servicing.
3.3.5 Other than dwelling units:
For attics and underfloor spaces containing equipment requiring servicing, such
as heating, air-conditioning, and refrigeration equipment, at least one lighting
outlet containing a switch or controlled by a wall switch shall be installed in such
spaces at least one point of controlled shall be at the usual point of entry to these
spaces the lighting outlet shall be provided at or near the equipment requirement
servicing.
3.3.6 Lighting outlets required:
-dwelling units:
in dwelling units, lighting outlets shall be installed in accordance with:
-habitable rooms:
at least one wall switch controlled lighting outlet shall be installed in every
habitable room and bathroom.-additional locations:
additional lighting outlets shall be installed in accordance with :
(1) at least one wall switch controlled lighting outlet shall be installed in
hallways , stairways ,attached garages, and detached garages with electric power.
(2)for dwelling unit ,attached garages ,and detached garages with electric
power ,at least one wall switch controlled lighting outlet shall le installed to
33
-
7/31/2019 BOOKfm6
46/161
Chapter 4 Branch Circuit Design
provide illumination on the exterior side of outdoor entrances or exits with grade
level access ,a vehicle door in a garage shall not be considered as an outdoor
entrance or exit.
(3) Where one or more lighting outlets are installed for interior stairways , there
shall be a wall switch at each floor level , and landing level that includes an
entryway , to control the lighting outlets where the stairway between floor levels
has six risers or more.
3.3.7 15-and 20- ampere branch-circuit:
A 15-and 20- ampere branch-circuit shall be permitted to supply lighting units or
other utilization equipment or a combination of both, and shall comply with:
-cord and plug connected equipment not fastened in place:
the rating of any one cord and plug connected utilization equipment not fastened
in place shall not exceed 80 percent of the branch-circuit ampere rating
3.3.8 30-ampere branch circuits:
A 30-ampere branch shall be permitted to supply fixed lighting unites with heavy-
duty lampholders in other than a dwelling unit(s) or utilization equipment on any
occupancy.
A rating of any one cord-and plug-connected utilization equipment shall not
exceed 80 percent of the branch-circuit ampere rating.
3.3.9 Required outlets
-cord pendants:
a cord connector that is supplied by a permanently connected cord pendant shall
be considered a receptacle outlet
-cord connections:
a receptacle outlet shall be installed wherever flexible cords with attachment
plugs are used . Where flexible cords are permitted to be permanently connected,
receptacles shall be permitted to be omitted for such cords.
34
-
7/31/2019 BOOKfm6
47/161
Chapter 4 Branch Circuit Design
-Appliance outlets:
appliance receptacle outlets installed in a dwelling unit for specific appliance
,such as laundry equipment , shall be installed within 1.8 m of the intended
location of the appliance.
3.3.10 Dwelling unit receptacle outlets:
This section provides requirements for 125 volt ,15 and 20 ampere receptacle
outlets ,receptacle outlets required by this section shall be in addition to any
receptacle that is part of a luminaries (lighting fixture) or appliance , located
within cabinets or cupboards.
3.3.11 40 and 50 Ampere branch circuit:
A 40-50 ampere branch circuit shall be permitted to supply cooking appliances
That are fastened in place in any occupancy. in other than dwelling unites, such
circuits shall be permitted to supply fixed lighting unites with heavy-duty lamp
holders, infrared heating units, or other utilization equipment.
3.3.12 Branch circuits larger than 50 amperes:
Branch circuits larger than 50 amperes shall supply only nonlghting out load
3.4 Receptacles
3.4.1 Single Receptacle on an Individual Branch Circuit:
A single receptacle installed on an individual branch circuit shall have an ampere
rating not less than that of the branch circuit.
3.4.2 Total Cord-and-Plug-Connected Load:
Where connected to a branch circuits supplying two or more receptacles or
outlets, Receptacle shall not supply a total cord and-plug-connected load in
excess of the Maximum.
Table 3-7 Maximum Cord-and-Plug-Connected Load to Receptacle
Circuit rating in (A) Receptacle rating in
(A)
Maximum load in (A)
15 or 20 15 12
20 20 16
30 30 24
35
-
7/31/2019 BOOKfm6
48/161
Chapter 4 Branch Circuit Design
3.4.3 Receptacle Ratings
Where connected to a branch circuit supplying two or more receptacles or outlets,
receptacle ratings shall conform to the values listed in Table210.21(B)(3), or
where larger than 50 amperes, the receptacle rating shall not be less than the
branch-circuit rating.
Table 3-8 Receptacle Ratings for Various Size Circuits
Circuit rating in (A) Receptacle rating in (A)
15 Not over 15
20 15 or 20
30 30
40 40 or 50
50 50
A single receptacle installed on an individual branch circuit must have an ampere
rating not less than that of the branch circuit. For example, a single receptacle on
a 20-ampere individual branch circuit must be rated at 20 amperes; however, two
or more15-ampere receptacles or duplex receptacles are permitted on a 20-ampere
general purpose branch circuit. This requirement does not apply to specific types
of cord-and plug-connected arc welders.
3.4.4 Branch-Circuit Requirements Summary
Table 3-9 Summary of Branch-Circuit Requirements
36
-
7/31/2019 BOOKfm6
49/161
Chapter 4 Branch Circuit Design
Note that the conductor size is converted to square mm in the project
design to match the Egyptian market.
3.4.5 Dwelling Unit Receptacle Outlets
This section provides requirements for 125-volt, 15- and 20-ampere receptacle
outlets .Receptacle outlets required by this section shall be in addition to anyreceptacle that is part of a luminaries (lighting fixture) or appliance, located
within cabinets or cupboards, or located more than 1.7 m (5 1/ 2 ft) above the
floor.
Figure 3-20 Dwelling unit receptacle outlets
Circuit rating 15 20 30 40
Conductor (min size)
circuit wires
14 12 10 8
Taps 14 14 14 12
Over current protection 15 20 30 40
Outlet devices
Lamp holders Any type Any type Heavy duty Heavy duty
Receptacle rating 15 max. A 15-20 A 30 A 40 or 50 A
Maximum load 15 20 30 40
37
-
7/31/2019 BOOKfm6
50/161
Chapter 4 Branch Circuit Design
3.4.6 Spacing
Receptacles shall be installed so that no point measured horizontally along the
floor line in any wall space is more than 1.8 m (6 ft) from a receptacle outlet.
3.4.7 Wall Space
As used in this section, a wall space shall include the following:
-Any space 600 mm (2 ft) or more in width (including space measured around
corners) and unbroken along the floor line by doorways, fireplaces, and similar
openings.
-The space occupied by fixed panels in exterior walls, excluding sliding panels.-
The space afforded by fixed room dividers such as freestanding bar-type counters
or railings.
Figure 3-21 Wall space
3.4.8 Floor Receptacles
Receptacle outlets in floors shall not be counted as part of the required number of
receptacle outlets unless located within 450 mm (18 in.) of the wall.
38
-
7/31/2019 BOOKfm6
51/161
Chapter 4 Branch Circuit Design
3.4.9 Bathrooms
In dwelling units, at least one receptacle outlet shall be installed in bathrooms
within 900 mm (3 ft) of the outside edge of each basin. The receptacle outletshall
be located on a wall or partition that is adjacent to the basin or basin countertop.
Figure 3-22 General load branch circuit
39
-
7/31/2019 BOOKfm6
52/161
Chapter 4 Branch Circuit Design
3.4.10 Hallways
In dwelling units, hallways of 3.0 m (10 ft) or more in length shall have atleast
one receptacle outlet. As used in this subsection, the hall length shall be
considered the length along the centerline of the hall without passing through a
doorway.
3.4.11 Heating, Air-Conditioning, and Refrigeration Equipment
Outlet
A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be
installed at an accessible location for the servicing of heating, air-conditioning,
and refrigeration equipment. The receptacle shall be located on the same level
and within 7.5 m (25 ft) of the heating, air-conditioning, and refrigeration
equipment. The receptacle outlet shall not be connected to the load side of the
equipment disconnecting means.
3.4.12 Receptacle Outlets
Except as covered in 220.14(J) and (K), receptacle outlets shall be calculated at
not less than 180 volt-amperes for each single or for each multiple receptacle on
one yoke. A single piece of equipment consisting of a multiple receptacle
comprised of four or more receptacles shall be calculated at not less than 90 volt-
amperes per receptacle. This provision shall not be applicable to the receptacle
outlets specified in 210.11(C)(1) and (C)(2).As illustrated in Exhibit 220.3, the
load of 180 volt-amperes is applied to single And multiple receptacles mounted
on a single yoke or strap, and a load of 360 volt-amperes is applied to each
receptacle that consists of four receptacles. These are considered receptacle
outlets, in accordance with 220.14(I). The receptacle outlets are not the lighting
outlets installed for general illumination or the small-appliance branch circuits, as
indicated in 220.14(J). The receptacle load for outlets for general illumination in
one- and two-family and multifamily dwellings and in guestrooms of hotels and
motels is included in the general lighting load value assigned by Table 220.12.
The load requirement for the small-appliance branch circuits is 1500 volt-amperes
per circuit, as described in 220.52(A). Note in Exhibit 220.3 that the last outlet of
40
-
7/31/2019 BOOKfm6
53/161
Chapter 4 Branch Circuit Design
the top circuit consists of two Duplex receptacles on separate straps. That outlet is
calculated at 360 volt-amperes because each duplex receptacle is on one yoke.
The multiple receptacle supplied from the bottom circuit in the exhibit, which
comprises four receptacles, is calculated at 90 volt-amperes per receptacle (4 90
VA = 360 VA). For example, single-strap and multiple receptacle
devices are calculated as follows: Device Computed Load
Duplex receptacle 180 VA
Triplex receptacle 180 VA
Double duplex receptacle 360 VA (180 2)
Quad or four-plex-type receptacle 360 VA (90 4)
Figure 3-23 Receptacle outlets
In Exhibit 220.4, the maximum number of outlets permitted on 15- and 20-
Ampere branch circuits is 10 and 13 outlets, respectively. This restriction does
not apply to outlets connected to general lighting or small-appliance branch
circuits in dwelling units.
41
-
7/31/2019 BOOKfm6
54/161
Chapter 4 Branch Circuit Design
.
Figure 3-24 Receptacle branch circuit
Exhibit 220.4 Maximum number of outlets permitted on 15- and 20-amper branch
circuits. For circuits supplying loads consisting of motor-operated utilization
equipment that is fastened in place and has a motor larger than 1/ 8hp in
combination with other loads, the total calculated load shall be based on 125
percent of the largest motor load plus the sum of the other loads.
3.4.13 Small Appliance Circuit Load
In each dwelling unit, the load shall be calculated at1500 volt-amperes for each 2-
wire small-appliance branch circuit required by
Where the load is subdivided through two or more feeders, the calculated load for
each shall include not less than 1500 volt-amperes for each 2-wire small
appliance branch circuit. These loads shall be permitted to be included with the
general lighting load and subjected to the demand factors provided in Table
220.42.
3.4.14 Appliance Load Dwelling Unit(s)
It shall be permissible to apply a demand factor of 75 percent to the nameplate
rating load of four or more appliances fastened in place, other than electric
ranges, clothes dryers, space-heating equipment, or air-conditioning equipment,
that are served by the same feeder or service in a one-family, two-family, or
multifamily dwelling. For appliances fastened in place (other than ranges, clothes
dryers, and space-heating and air-conditioning equipment), feeder capacity must
42
-
7/31/2019 BOOKfm6
55/161
Chapter 4 Branch Circuit Design
be provided for the sum of these loads; for a total load of four or more such
appliances, a demand factor of 75 percent may be applied. See Table 430.248 for
the full-load current, in amperes, for single phase ac motors, in accordance with
220.50.
General Loads:
The general calculated load shall be not less than 1