Edition 09.10 www.docuthek.com D GB F NL I SK © 2008 – 2010 Elster GmbH Please read and keep in a safe place Please read through these instructions carefully before installing or operating. Follow- ing the installation, pass the instructions on to the operator. These instructions can also be found at www.docuthek.com. Explanation of symbols • , 1 , , ... = Action = Instruction Liability We will not be held liable for damages resulting from non-observance of the instructions and non- compliant use. Safety instructions Information that is relevant for safety is indicated in the instructions as follows: DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb. CAUTION Indicates possible material damage. All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians. Conversion, spare parts All technical changes are prohibited. Only use OEM spare parts. Transport Diaphragm gas meters are always to be transported in the upright position. On receipt of the product, check that the delivery is complete (see Part desig- nations). Report any transport damage immediately. Storage Diaphragm gas meters are always to be stored in the upright position and in a dry place. Ambient tempera- ture: see Technical data. Operating instructions Translation from the German GB GB-1 Safety Contents Diaphragm gas meters BK-G1.6 to BK-G5 Diaphragm gas meters BK-G1.6 to BK-G5 ..................... 1 Contents .............................. 1 Safety................................. 1 Checking the usage ..................... Diaphragm gas meters BK-G1.6 to G25 ...... 2 BK with integrated “Smart Valve” ............ 2 Type code.............................. 2 Part designations ........................ 2 Type label/Index plate ..................... 2 Installation ............................ Temperature test point................... Connecting the pressure measuring line.... Tightness test .......................... 4 Commissioning......................... 4 BK-G..M with interface for mechanical index . . . 4 BK-G..A with interface for Absolute ENCODER index AE1/Z6 .................. 4 BK-G..A with Absolute ENCODER AE2 and communication module ACM............... 4 BK-G..E with electronic index............... 4 Diaphragm gas meters BK with integrated “Smart Valve” ........................... 5 “Smart Valve” valve function ................ 5 Maintenance/Removal................... 5 Technical data.......................... 5 Declaration of conformity ................ 6 Contact ............................... 6 03250886/002

Upload: truongkhue

Post on 01-Feb-2018

234 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: BK-G1.6 to BK-G25 - Dalemans Gas · PDF fileDiaphragm gas meters BK-G1.6 to BK-G 5 ... (DVGW Code of Practice G260). ... Check the pipework for leaks prior to installation of the gas

Edition 09.10� www.docuthek.comD GB F NL I SK

© 2008 – 2010 Elster GmbH

Please read and keep in a safe place

Please read through these instructions carefully before installing or operating. Follow-ing the installation, pass the instructions on to the operator. These instructions can also be found at www.docuthek.com.

Explanation of symbols • , 1 , , ... = Action▷ = Instruction

LiabilityWe will not be held liable for damages resulting from non-observance of the instructions and non-compliant use.

Safety instructionsInformation that is relevant for safety is indicated in the instructions as follows:

DANGERIndicates potentially fatal situations.

WARNINGIndicates possible danger to life and limb.

CAUTIONIndicates possible material damage.

All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians.

Conversion, spare partsAll technical changes are prohibited. Only use OEM spare parts.

TransportDiaphragm gas meters are always to be transported in the upright position. On receipt of the product, check that the delivery is complete (see Part desig-nations). Report any transport damage immediately.

StorageDiaphragm gas meters are always to be stored in the upright position and in a dry place. Ambient tempera-ture: see Technical data.

Operating instructions

Translation from the German

D GB F NL I SK

GB-1

Safety

Contents

Diaphragm gas meters BK-G1.6 to BK-G5

Diaphragm gas meters BK-G1.6 to BK-G5 . . . . . . . . . . . . . . . . . . . . . 1Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Checking the usage . . . . . . . . . . . . . . . . . . . . . Diaphragm gas meters BK-G1.6 to G25 . . . . . . 2BK with integrated “Smart Valve” . . . . . . . . . . . . 2Type code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Part designations . . . . . . . . . . . . . . . . . . . . . . . . 2Type label/Index plate . . . . . . . . . . . . . . . . . . . . . 2Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . Temperature test point. . . . . . . . . . . . . . . . . . . Connecting the pressure measuring line. . . . Tightness test . . . . . . . . . . . . . . . . . . . . . . . . . . 4Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . 4BK-G..M with interface for mechanical index . . . 4BK-G..A with interface for Absolute ENCODER index AE1/Z6 . . . . . . . . . . . . . . . . . . 4BK-G..A with Absolute ENCODER AE2 and communication module ACM. . . . . . . . . . . . . . . 4BK-G..E with electronic index. . . . . . . . . . . . . . . 4Diaphragm gas meters BK with integrated “Smart Valve” . . . . . . . . . . . . . . . . . . . . . . . . . . . 5“Smart Valve” valve function . . . . . . . . . . . . . . . . 5Maintenance/Removal. . . . . . . . . . . . . . . . . . . 5Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . 5Declaration of conformity . . . . . . . . . . . . . . . . 6Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

0325

0886

/002

Page 2: BK-G1.6 to BK-G25 - Dalemans Gas · PDF fileDiaphragm gas meters BK-G1.6 to BK-G 5 ... (DVGW Code of Practice G260). ... Check the pipework for leaks prior to installation of the gas

GB-2

D GB F NL I SK

Checking the usage

Diaphragm gas meters BK-G1.6 to G5Residential or commercial diaphragm gas meters BK for recording gas consumption values for natural gas, town gas, propane and butane, gases of the first to third families pursuant to DIN EN 437:2003 (DVGW Code of Practice G260). If used for internal measurements which are not subject to statutory testing, the gas meter is also suitable for hydrogen, nitrogen, air and inert gases.

BK with integrated “Smart Valve”Not suitable for highly contaminated gases, e.g. town gas.

Potentially explosive atmosphereDiaphragm gas meters that are labelled with and

(see sticker next to the index) are suitable for operation in potentially explosive atmospheres of Category 2G (Zone 1) of Class II 2G c IIB (TÜV 09 ATEX 554884X), see [Declaration of conformity – p. 6].

This function is only guaranteed when used under the specified operating conditions – see [Technical data – p. 5]. Any other use is considered as non-compliant.

Type codeCode DescriptionBK-G Diaphragm gas meter 1.6 .5 4 6 10 16 5

Flow rate 0.016 – 2.5 m3/h

0.025 – 4 m3/h0.04 – 6 m3/h

0.06 – 10 m3/h0.1 – 16 m3/h

0.16 – 25 m3/h0.25 – 40 m3/h

M C A E

Mechanical index Chekker mechanical index Absolute ENCODER index

Electronic index

T Te

Temperature conversion: Mechanical

Electronic

Part designations

2

1

3

46

5

1 Diaphragm gas meter BK Index with index plate Connectors4 Protective caps5 2 x thermowells (optional)6 Pressure test point with sealing sleeve (optional)

Type label/Index plateDiaphragm gas meters BK-G..M..

m3, -

BK-G..M..12345678DE-07-MI002-PTB001

002545632734 1 imp =̂ 0,01 m 3

class 1,5

NG-47001BM0443 DIN EN 1359:2007

Q max Q min

DE-07-MI002-PTB001

002545632734

class 1,5

NG-47001BM0443 DIN EN 1359:2007

BK-G..A..ENCODER VALVE

M09 0102

M09 0102

m3, -

Diaphragm gas meters BK-G..A.. with Absolute ENCODER index and integrated “Smart Valve”

m3, -

BK-G..M..12345678DE-07-MI002-PTB001

002545632734 1 imp =̂ 0,01 m 3

class 1,5

NG-47001BM0443 DIN EN 1359:2007

Q max Q min

DE-07-MI002-PTB001

002545632734

class 1,5

NG-47001BM0443 DIN EN 1359:2007

BK-G..A..ENCODER VALVE

M09 0102

M09 0102

m3, -

Page 3: BK-G1.6 to BK-G25 - Dalemans Gas · PDF fileDiaphragm gas meters BK-G1.6 to BK-G 5 ... (DVGW Code of Practice G260). ... Check the pipework for leaks prior to installation of the gas

GB-3

D GB F NL I SK

Installation

WARNINGPlease observe the following to ensure that neither persons nor the gas meter are damaged during installation and operation:– Note the max. allowable operating pressure pmax.

and measuring range Qmax., see [Type label/Index plate – p. 2].

– Note the permitted ambient temperature tm and gas temperature tg, see [Type label/Index plate – p. 2] or [Technical data – p. 5].

– The gas meter is suitable for mechanical ambient conditions of Class M1 of Directive 2004/22/EC. For gas meters with an Absolute ENCODER index, Class E2 for electromagnetic ambient conditions also applies.

– When installing the diaphragm gas meter BK with integrated “Smart Valve”, make sure that no dirt particles get into the meter and thus into the valve.

– The yellow sealing sleeve protects the pressure test point on the gas meter. It may only be opened for connecting a pressure measuring line.

– Use seals made from tested materials. Elastomer seals or asbestos-free flat seals from Elster are recommended.

– For meters resistant to high temperatures, only use seals tested to be resistant to high tempera-tures.

– Only use the seals once.– For installation and operation, note the applicable

national regulations and the directives of the gas supply company. For Germany, the valid DVGW Code of Practice G600 (DVGW-TRGI) applies.

– If the calibration seal has been damaged or re-moved, the gas meter is no longer approved for measurements which are subject to statutory testing.

▷▷ If the gas meter is stored or installed outdoors, protect the site against rain. Condensing humidity is permitted.

1 Remove protective caps.▷▷ Installation in the horizontal position: connectors

must be pointing upwards.▷▷ Note direction of flow (arrow).▷▷ The gas meter must not be in contact with ma-

sonry or other parts.▷▷ Ensure that there is sufficient installation space.▷▷ Ensure unobstructed view of the index.▷▷ The seal faces on the screw unions must be clean

and damage-free.▷▷ For the compression of seals and the resulting

tightening torques for the screw unions, the seal manufacturers’ specifications must be observed.

Tightening torques for the recommended flat seals in conjunction with screw connectors pursuant to DIN 3376-1 and 3376-2, see www.docuthek.com →▷Elster-Instromet →▷Products →▷Gas measuring

devices → Diaphragm meters → Ergänzung für Betriebsanleitung BK, Verschraubungen und An-zugsmomente für BK-G1,6 bis BK-G25 (Supple-ment for BK operating instructions, Screw unions and tightening torques for BK-G1.6 to BK-G25) (D).

Install the gas meter free of mechanical stress.

▷▷ The gas meter marked with must be included in the equipotential bond when being installed in a potentially explosive atmosphere, e.g. by con-necting it to a grounded pipeline.▷▷ If a pulse sensor IN-Z6x is used for pulse tap-

ping on the gas meter marked with – see Data sheet for pulse sensor IN-Z6x (D, GB) www.docuthek.com → Elster-Instromet → Prod-ucts → Gas measuring devices → Diaphragm meters →▷Pulse sensor IN-Z61 and the standard EN 60079-14 (Explosive atmospheres).

Temperature test point▷▷ Temperature sensors can be inserted into the

thermowells for measuring the gas temperature in the meter housing.

1 2

Secure each of the temperature sensors using the capstan screw provided.

Connecting the pressure measuring line

WARNINGIn order to ensure that the gas meter is tight:– The pressure test nipple must not be twisted, bent,

or otherwise manipulated.– When installing, always secure the pressure test

nipple using a suitable spanner.

▷▷ Functional safety and reliability are ensured only if the material combination of the screw connector and the pressure line are intermatched.▷▷ Only use the olive and the attached union nut

supplied. The olive is secured to the sealing sleeve.▷▷ When re-ordering, use original Parker EO progres-

sive ring fittings PSR/DPR.

1

6 7

2 3

4 5

Page 4: BK-G1.6 to BK-G25 - Dalemans Gas · PDF fileDiaphragm gas meters BK-G1.6 to BK-G 5 ... (DVGW Code of Practice G260). ... Check the pipework for leaks prior to installation of the gas

GB-4

D GB F NL I SK

1

6 7

2 3

4 5

▷▷ Use corrosion-resistant, seamless precision steel tube pursuant to DIN EN 10305-4 (external di-ameter 6 mm, material E235 = 1.0308). For other materials, use a suitable adapter and note the Parker/EO recommendations.▷▷ Install pipes free of mechanical stress.

1

6 7

2 3

4 5

8 Screw on the union nut by hand as far as it will go.▷▷ At the same time, press the end of the pipe firmly

against the stop. 9 Mark the position of the union nut and tighten

with about 1½ turns.

1

6 7

2 3

4 5

▷▷ When re-installing, the union nut will be turned to the original position and then further tightened through approx. 30°.

11 Once the installation and tightness test are com-plete, see [Tightness test – p. 4], protect the pres-sure test point against external access with the sealing sleeve and the seal.

Tightness test▷▷ Check the pipework for leaks prior to installation of

the gas meter, in case the pipework is tested with a greater test pressure than the max. allowable operating pressure pmax. for the gas meter. Oth-erwise, the installed gas meter may be damaged.▷▷ If a valve is integrated in the diaphragm gas meter

BK, see [Type label/Index plate – p. 2], this must be opened for the tightness test.▷▷ Ensure the customer’s consumers are closed,

see [Diaphragm gas meters BK with integrated “Smart Valve” – p. 5].

1 Apply the test pressure slowly to the gas meter.

2

3▷▷ If a pressure measuring line has been retrofitted

to the diaphragm gas meter, check this connec-tion for tightness.

2

3

4 After the tightness test, slowly vent the gas meter. 5 If a pressure measuring line has been retrofitted

to the diaphragm gas meter, protect the pressure test point against external access with a sealing sleeve and a seal.

CommissioningOnce the tightness test has been successfully com-pleted, the gas meter is ready for operation.▷▷ Slowly open the manual valve.

BK-G..M with interface for mechanical indexThe pulse sensor IN-Z6x can be used for pulse tap-ping – see Data sheet for pulse sensor IN-Z6x (D, GB) → www.docuthek.com → Elster-Instromet → Products → Gas measuring devices → Diaphragm meters → Pulse sensor IN-Z61.

BK-G..A with interface for Absolute ENCODER index AE1/Z6Interface description for gas meters with ENCODER index – see Specification (D, GB) → www.docuthek.com → Elster-Instromet → Products → Gas measur-ing devices → Diaphragm meters → Smart metering → Specification M-BUS or SCR+.

BK-G..A with Absolute ENCODER AE and communication module ACMIf the diaphragm gas meter BK-G..A is fitted with communication module ACM – for further com-missioning see Communication module ACM M-BUS WIRE, ACM SCR+ WIRE... operating in-structions or Communication module ACM WAVE SYSTEM RF operating instructions (D, GB, NL) → www.docuthek.com → Elster-Instromet → Products → Gas measuring devices → Diaphragm meters → Smart metering.

BK-G..E with electronic indexIf the diaphragm gas meter BK-G..E is fitted with an electronic index – for further commissioning see Electronic index operating instructions (D, GB) → www.docuthek.com → Elster-Instromet → Products → Gas measuring devices → Diaphragm meters → Smart metering.

Page 5: BK-G1.6 to BK-G25 - Dalemans Gas · PDF fileDiaphragm gas meters BK-G1.6 to BK-G 5 ... (DVGW Code of Practice G260). ... Check the pipework for leaks prior to installation of the gas

GB-5

D GB F NL I SK

Diaphragm gas meters BK with integrated “Smart Valve”In the event that the diaphragm gas meter BK is fittedwith an integrated “Smart Valve”, see „Type label/Index plate“ auf Seite 2, the gas supply can be con-nectedor disconnected remotely.

WARNINGThe network provider is responsible for the safe remote shut-down and restart of the diaphragm gas meter:– The “Smart Valve” does not assume the safety

functions of a safety shut-off valve.– Depending on national regulations, a limited and

technically safe gas flow rate in the customer’s open consumer piping is allowed, see [Technical data – p. 5].

– Assessment of the non-critical gas flow rate with regard to amount and duration, which occurs when the valve is released, is to be defined by the network provider.

– The minimum operating pressure on the inlet must not be undershot, see [Technical data – p. 5]. Otherwise, when the valve is released and if the customer’s consumer piping is open at the same time, the valve may be completely opened.

“Smart Valve” valve functionThe “Smart Valve” is switched remotely by the data management system. The valve first switches to the

“Released” position. From the “Released” position, the valve automatically switches to the “Open” position, if the downstream installation is tight.

ReleasedThe “Smart Valve” opens an internal bypass and releases a minimum gas flow into the customer’s closed consumer piping. Pressure equalization takes place between the inlet and outlet side of the valve.

OpenFollowing pressure equalization, the valve automati-cally opens by spring force and fully releases the gas supply. If consumers of the customer are open, pressure equalization cannot occur and the valve remains in the “Released” position and continues to release only the minimum gas flow rate of the bypass.

ClosedThe valve and the bypass are closed in the event of remote shut-down.▷▷ All valve positions are kept de-energized.

Maintenance/RemovalGas meters BK-G1.6 to 25 from Elster are mainte-nance-free.▷▷ When used for custody transfer measurements,

recalibration must be carried out in accordance with national Directives.▷▷ If the screw unions are loosened for maintenance

work or retesting, replace the seals.▷▷ After the gas meter has been removed, immedi-

ately close the connectors with protective caps, in order to prevent an ingress of dirt particles.

WARNINGA certain amount of gas may remain in the gas meter. Taking into consideration the risk of explo-sion, it is important to adopt safety measures, e.g.:– Following removal of the gas meter, purge it thor-

oughly with inert gas.– For transporting the gas meter with gas residue,

use a vehicle with an open or a ventilated loading area.

Technical data

Diaphragm gas meters BKGas type: natural gas, town gas, propane and butane, as gases of the first to third families pursuant to DIN EN 437:2003 (DVGW Code of Practice G260).Max. allowable operating pressure pmax., see [Type label/Index plate – p. 2].Max. allowable measuring range Qmin./Qmax., see [Type label/Index plate – p. 2].Max. allowable ambient temperature range tm, see [Type label/Index plate – p. 2].Max. allowable storage temperature range: -25 to +60°C.Gas temperature tg, where the measuring error still lies within the error limits set out in the Directive, see [Type label/Index plate – p. 2]. If no gas temperature tg is specified on the index plate, tg = tm applies.

Diaphragm gas meters BK with pressure test pointPressure test point: 24° olive fitting to EN ISO 8434-1, L6 x M12 x 1.5-St

Diaphragm gas meters BK with explosion protectionMax. allowable ambient temperature range tm/gas temperature range tg: -20 to +55°C, for constraints see [Type label/Index plate – p. 2].

Page 6: BK-G1.6 to BK-G25 - Dalemans Gas · PDF fileDiaphragm gas meters BK-G1.6 to BK-G 5 ... (DVGW Code of Practice G260). ... Check the pipework for leaks prior to installation of the gas

GB-6

D GB F NL I SK

We

rese

rve

the

right

to m

ake

tech

nica

l mod

ifica

tions

in

the

inte

rest

s of

pro

gres

s.United KingdomElster Metering LimitedElster JeavonsTollgate Business ParkBeaconsideStafford, ST16 3EFT +44 1785 275200F +44 1785 [email protected]

IrelandActive Energy Control Ltd.Unit 4, Clare MartsQuin RoadEnnis, Co. ClareT +353 65 6840600F +353 65 [email protected]

GermanyElster GmbHPostfach 129, D-55248 Mainz-KastelSteinern Straße 19-21, 55252 Mainz-KastelT +49 6134 605-0F +49 6134 [email protected]

Contact

Diaphragm gas meters BK with integrated “Smart Valve”Not suitable for highly contaminated gases, e.g. town gas.Opening time from closed to open/released state: ≤ 4 s,closing time: ≤ 0.5 s.Min. operating pressure: 17.5 mbar.Allowed leakage flow in the customer’s piping: valve released: max. 13 l/h at 35 mbar, valve closed: max. 5 l/h.

Declaration of conformity

Diaphragm gas meters BKWe, the manufacturer, hereby declare that the prod-uct BK, marked with No. DE-07-MI002-PTB001/DE-07-MI002-PTB002, complies with the requirements of the listed Directives and Standards.Directives:– 2004/22/EC (MID)Standards:– DIN EN 1359:2007 (EN 1359:1998 / A1:2006)The relevant product corresponds to the tested type sample.The production is subject to the surveillance proce-dure pursuant to 2004/22/EC, Annex D, Physika-lisch-Technische Bundesanstalt (German National Metrological Institute), Notified Body 0102.Elster GmbH

Conformity with Directive 2004/22/EC is declared by affixing the following markings:

M... 0102

After the “M”, the year of construction is given.

Diaphragm gas meters BK with explosion protectionWe, the manufacturer, hereby declare that the prod-uct BK, marked with II 2G c IIB, complies with the requirements of the listed Directives and Standards.Directives:– 94/9/ECStandards:– EN 13463-1:2001, EN 13463-5:2003 and

EN 1127-1:2007The production is subject to the conformity assess-ment procedure pursuant to 94/9/EC, Annex VIII, Declaration of conformity No. TÜV 09 ATEX 554884 X, TÜV NORD CERT GmbH, Notified Body 0044.Elster GmbH

= Marking of explosion protectionII = Equipment group ll for general industries (with

the exception of mines)2G = Equipment category for gases, hazes and va-

pours for Zone 1c = “Constructional safety” explosion protection

typeIIB = Explosion groupThe unit is not a source of heat and therefore not labelled with a temperature class.

Scan of the Declarations of conformity – see www.docuthek.com