bhe install

Upload: nikey2k

Post on 04-Jun-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/13/2019 BHE Install

    1/9

    Brazed Heat

    Exchanger

    Installation Manual

  • 8/13/2019 BHE Install

    2/9

    I. Introduction

    The Brazed Plate Heat Exchanger

    Alfa Laval is credited with

    inventing the original brazed plate heatexchanger. The brazed heat exchanger

    is a compact variation of the traditionalplate heat exchanger. But, unlike the

    traditional plate heat exchanger, the

    BHE does not have a carbon steel frame,gaskets, tightening bolts or carrying bar.

    It consists simply of AISI 316 stainless

    steel corrugated channel plates, apressure plate and a frame plate with

    connections that are brazed together in a

    vacuum furnace.

    How It Works

    When the plate pack is

    compressed, it creates a continuousseries of channels with portholes in each

    of the four corners. The media enters

    the inlet connections and is distributedinto the narrow channels between the

    plates. The passages between the plates

    and corner portholes are arranged so thatthe two heat-transfer media can travel in

    alternate channels. A brazed seal around

    the outer edge of the plates retains themedia within the channels. As the

    warmer medium passes through the unit,

    it releases heat energy to the thin plate

    wall, which instantly transfers it to the

    colder medium on the other side.The thin plates have a uniquely

    designed herringbone geometry that

    creates high turbulence and low pressure

    loss. This optimal plate pattern gives theBHE and extremely high overall heat

    transfer coefficient. This pattern has

    been developed through theoreticalcalculations, checked by laboratory tests

    and proven itself in the field.

    II. The Alfa Laval Brazed

    Heat Exchanger Series

    The Copper-Brazed Heat Exchanger Line

    Alfa Laval has developed astandard line of BHEs to encompass

    different applications and heat loads.

    These heat exchangers, from the smallestunit, the CB14, to the largest, the

    CB300, are brazed with 99.9% pure

    copper.

    The Nickel Brazed Plate HeatExchanger is an alternative for

    applications where copper is not

    appropriate, such as de-ionized water orammonia.

    Brazed Heat Exchangers aresuitable for liquid/liquid, steam/liquid,

    and gas/liquid applications.

    - 2 -

  • 8/13/2019 BHE Install

    3/9

    Standard BHEs

    Custom-designed BHEs can be

    equipped with:

    Multiple passes

    Different connection positions Non-standard connections

    Three-media configurations

    Multi-pass BHEs

    Multi-pass units are used to

    increase the thermal length of the heat

    exchanger. With this design, more heat

    is transferred from the hot medium to thecold medium, at the expense of a higher

    pressure drop. Figures 3A and 3B

    illustrate the difference between the oneand two pass design.

    III. BHE Specifications

    Fluid Quality

    To minimize risk of corrosion,the media pH values should be neutral.

    The media must not contain chemicalscorrosive to stainless steel (AISI 316) or

    the brazing material (copper or nickel).

    Stainless steel is especially sensitive tolocalized spot and crevice corrosion due

    to chloride, sulfite and sulfate ions.

    Above a critical ion concentration thepassivity of the steel breaks down and

    local spot corrosion occurs.

    Materials Plates and connections AISI 316Brazing material

    CB units Copper 99.9%NB units Nickel Alloy

    ApprovalSweden Statens Anlaggningsprovning (SA)

    Germany Technische Uberwachungsverein

    USA Underwriters Laboratories (UL)American Society of Mechanical

    Engineers (ASME) upon request

    for some modelsCanada Canadian Standards Association

    (CSA)

    The data label shows:

    1) Alfa Laval manufacturing number

    - 3 -

  • 8/13/2019 BHE Install

    4/9

    2) Connection position. S indicates

    the front cover plate, T the backcover plate.

    3) Unit description as follows:

    a. Model

    b. Plate number and typec. Connection configuration code

    Example: CB26-70H S52

    CB26 Model Type70 Number of Plates

    H Type of Plate in Model

    S52 Connection Code

    BHE Connections

    BHE connections are available inthe following:

    Threaded and/or soldered

    Flange (some models)

    Rotolock

    Victualic

    For further details, please refer to theBrazed Plate Heat Exchanger Product

    Catalog(Pub. No. ENSR00005EN 0207).

    IV. Installation

    General Information

    For the highest heat transfer,

    connect the unit so that a countercurrentflow is obtained.

    Installation

    Figure 5 shows the installation of

    an evaporator. For evaporators connectthe refrigerant to the side with the

    soldered connections (S3, S4) so that it

    enters the unit at the bottom. Theexpansion device should be positioned

    not less than 6-8 inches from the

    connection (S3). Bent tubes and elbows

    between the expansion device and theconnection should be avoided. Connect

    the liquid to that side of the BHE that

    best suits your installation (S1, S2) or(T1, T2).

    NOTE: Units with the option of the

    real double circuit have a single water

    circuit with connections in a central

    position and two independentrefrigerant circuits. The refrigerant

    circuits, unless otherwise indicated,

    have diagonal flow. The refrigerant

    side connections follow the normal

    rules with the additional note of being

    diagonally opposite.

    Mounting

    Always mount the unit vertically

    in two-phase applications. For single-phase applications the BHE can be

    mounted horizontally or verticallywithout affecting the function.

    Units smaller than CB26-30 can

    be mounted directly on the pipes. Mountlarger units on anti-vibration plates or

    - 4 -

  • 8/13/2019 BHE Install

    5/9

    fasten with steel clamps (Figure 6 or 7)

    or stud bolts, when included. If there is

    risk of vibrations, use an anti-vibrationdevice as in Figure 8. Models with HX,

    MX, LX plate configurations or model

    AC must not be installed upside down.

    The tightening torque for the 5/16 studbolts is 90-105 in-lb; for the 3/8, it is

    195-221 in-lb. For larger sizes of units,removable feet and lifting lugs can be

    provided as an option.

    Threaded Connections

    Connect the pipe using adynamometric wrench respecting the

    indicated limits. The limits are

    measured on the largest diameters. Incase of smaller connections, the torque islower. In the AC units, the Victualic

    type connection can be supplied.

    To avoid damaging the threadedconnections, it is important to mount the

    BHE on the pipes within the

    recommended design limits. (See table

    below.) (See Figure 9.)

    Table: Design Limits

    BHE size T(lb) F(lb) MB(ft-lb) Mv(ft-lb)

    CB14 3330 1800(-1350) 27 125

    CB26,CB52

    5550 2160(-1660) 45 285

    CB76,AC120,

    AC13024950 6070(-4720) 545 740

    AC250 30800 7420(-5620) 675 2140

    Soldered and Welded Connections

    The temperature must not exceedthe melting point of the brazing material.

    Use a wet towel around the connection

    and the plate pack to reduce the heattransferred to the BHE plate pack during

    installation.

    Filling material: 30-55% silver alloy

    Flux material: Black Flux for silversoldering

    1. Clean the soldering assembly surface

    at the copper tubes and BHEconnections.

    a. Remove oil or other buildup with

    degreasing solventb. Polish the surfaces to remove

    oxides.

    2. Apply the flux to the surface with abrush to remove and prevent

    oxidation.3. For refrigeration installations, use a

    dry Nitrogen gas on the refrigerantside to prevent oxidation.

    4. Heat the soldering area to the

    soldering temperature of about

    1200F. (Higher temperatures will

    melt the brazing material.) Use a

    - 5 -

  • 8/13/2019 BHE Install

    6/9

    wet cloth to minimize the heating

    zone. WARNING: Unnecessary heating

    (above 1200 F) can melt the brazing

    material!

    5. Keep the tube in a fixed position and

    add the filler material.

    V. Regulation

    The efficient design of plate heat

    exchangers allows the total hold-up

    volume of the system (pumps, valves,piping and controls) to be much smaller

    than that of systems using conventional

    heat exchangers. This high efficiency

    results in a quick response time. Thevalve and regulation equipment should

    be designed accordingly.

    The valve with the shortestresponse time should be placed close to

    the outlet. This will give a faster

    response when there is a small load.Follow the instructions from the valve

    manufacturer and, if possible, use a PI

    regulator with a logarithmic response.This is especially recommended in steam

    applications.

    Welding

    1. Prepare the edge of the tube for

    welding with a 30bevel.2. Place the piping into the connection.

    Excessive cycling amplitude of

    pressure and temperature can lead to

    leakage after some time as a result offatigue phenomena. Thermal dynamicstresses are caused by large fast

    temperature changes (more than 50F)and can damage the BHE. An ON/OFF

    valve that causes pressure pulsation in

    the BHE must be avoided. To minimizethermal fatigue, it is especially important

    to avoid pressure and temperature

    pulsations in steam applications orchanges in the condensate level inside

    the steam condenser.

    3. TIG-weld or MIG-weld the tube to

    the connection, filling the groove

    formed by the two edges. Thismethod minimizes the heating zone.

    - 6 -

  • 8/13/2019 BHE Install

    7/9

    Shut Down

    VI. Operation Consult system instructions todetermine which pump should bestopped first.A liquid in motion in a pipe

    system generates a high level of energy.

    When a valve is closed or opened,causing the fluid to stop or continue, it

    must be done slowly to avoid shockingthe system.

    SLOWLY, close the valve

    controlling the flow rate of the pumpbeing stopped.

    When the valve is closed, stop the

    pump.

    Repeat for the other side.

    WARNING: Do not use fast-closing

    valves unless the pipes of the system

    are very short!

    If for any reason the heat exchanger

    is shut down for a long period, itshould be drained. If the media

    processed is corrosive, contains

    particles, or has a tendency tocoagulate, it is recommended that the

    heat exchanger be rinsed with waterand dried to avoid damage.

    Start Up

    Note: Consult equipmentmanufacturers start-up procedures forrefrigeration applications.

    VII. Freeze Protection Before starting any pump, consultthe system instructions to determinewhich pump should be started first. For freeze protection use

    thermostats and/or temperature controlsin the connections opposite to the liquid

    inlet/outlet, if any, or in a temperature

    pocket close to the outlet.

    Make sure the control valve betweenthe pump and the unit is closed.

    If there is a valve at the exit, make

    sure it is completely open.

    Open the vent.Connect the water side pipes toensure that the whole unit runs filled

    with water.

    Open the valve SLOWLY.

    Close the vent after all of the air is

    let out. To minimize freezing risk: Repeat the procedure for the other

    side of the heat exchanger.1) Use a filter

  • 8/13/2019 BHE Install

    8/9

    Insulation

    Airtight insulation isrecommended. It is necessary when theunit is working as an evaporator at low

    temperatures. This can be made, among

    other solutions, using insulation sheets(Armaflex or similar) cut into

    appropriate sizes and glued together as

    shown. (See Figure 11.)

    VIII. Maintenance

    Heat Transfer

    The purpose of the BHE is totransfer heat from one medium to

    another. Heat passes very easily through

    the thin walls separating the two media.

    The pattern pressed into the plates makesthe plates strong and rigid and increases

    the rate of heat transfer. This high rate

    of heat transfer can be inhibited by the

    formation of deposits on the platesurfaces. The corrugated pattern on Alfa

    Laval plates induces turbulent flow.Turbulence provides strong resistance to

    deposit buildup, but it cannot always

    eliminate fouling. The deposits mayincrease the total wall thickness, and

    consist of materials of a much lower

    thermal conductivity than of the metal

    plate. Thus, a layer of deposits canseverely reduce the overall heat transfer

    rate. Corrosion can also occur under the

    deposits. For corrective action, please

    see Cleaning below.

    Pressure Drop

    Pressure drops are wasted

    energy. All pipe systems, andequipment included in them, offer

    resistance to the media flowing through

    them. Some pressure drop is inevitable,

    but it should be kept as close as possibleto the designed value for the BHE. The

    formation of deposits on the heat transfersurfaces reduces the free space betweenthe plates. This means that more energy

    is required to achieve the desired flow in

    the BHE. Large particles and fibers mayalso clog the heat exchanger if it is not

    equipped with a strainer. A reduced

    ability to maintain the desired

    temperatures along with an increasedpressure drop on either media, are

    symptoms of fouling or clogging. For

    corrective action, please see Cleaningbelow.

    - 8 -

  • 8/13/2019 BHE Install

    9/9

    - 9 -

    Cleaning

    Clean with detergents for fatty

    deposits. For heavier fouling usechemicals such as formic acid, citric

    acid, vinegar, or other organics in

    concentrations compatible with copper.Alfa Laval BHEs can be cleaned

    in place with the Cleaning-in-Place

    (CIP) system, which chemically removescalcium deposits and other forms of

    scaling from plate surfaces (See Figure

    12.) Different solutions can be used,depending on the type of deposits. Every

    application has to be considered

    separately. The Cleaning-in-Place

    procedure is generally the same,

    regardless of the solution used.

    CIP Procedure

    1. Drain the unit.

    2. Rinse with fresh water.3. Drain water.

    4. Fill with fresh water.

    5. Add cleaning agent (solution andconcentration depending on type of

    fouling).

    6. Circulate the cleaning solution (iffeasible).

    7. Drain the cleaning solution.8. Add and circulate the passivating

    liquid for corrosion inhibition of

    plate surfaces.9. Rinse with fresh water.

    10. Drain.

    CAUTION: Do not use liquids that

    are corrosive to stainless steel or the

    brazing material (copper or nickel)!Do not leave the unit on standby after

    cleaning! Contact the Alfa Laval

    Service Center (1-866-Alfa Laval) for

    more information about cleaning-in-

    place equipment, detergents or

    service.

    IX. Assistance and Field

    Service

    TroubleshootingTo assure correct performance of

    the unit, please check that:-it is correctly connected according

    to page 4 of this leaflet.

    -it is absolutely clean and free fromdeposits. Increased pressure drops

    can reveal fouling.

    -the control equipment is correctly

    set up and that freezing does notoccur.

    Alfa Laval maintains a largehighly specialized engineering staff tohandle your questions and problems.

    Your nearest Alfa Laval representative

    will be happy to provide you with quotesor answer to your questions. To assist

    your representative in finding the best

    solution, please provide the following

    sizing information along with yourinquiry:

    Hot Side Cold Side

    FluidMass flow

    Temperature InTemperature Out

    Maximum Pressure Drop

    Design Pressure

    For Refrigeration Applications

    Condensing TemperatureEvaporator Temperature

    TX Valve Superheat

    Total Heat of Rejection

    Total Evaporator Tons

    GPM

    F

    F

    psig

    psig

    F

    F

    F

    kBTU/H

    TR

    GPM

    F

    F

    psig

    psig

    F

    F

    F

    kBTU/H

    TR

    If you do not have this

    information, it may be sufficient todescribe the existing heat exchanger.