automatic refrigerant monitoring system€¦ · automatic refrigerant monitoring system 1300 850...

2
The ARMS 2 is a pre-calibrated automac monitoring system for detecng leakage of fluorinated greenhouse gases around compressors, cold rooms or chillers and provide site operators with It provides early warning of refrigerant loss. The ARMS 2 is designed to provide stand alone conformity with F-Gas Regulaon and complies to AS1677 (mandatory for sites with an overall refrigerant charge in excess of 300kg). Mulcomponent and mul-zone The ARMS 2 uses a mul-gas infrared sensor technology and can be supplied as an 8, 16, 24 or 32 channels model, to provide mul-zone leak detecon based on the simultaneous real- me measurement of HFC/HCFCs - CO2 - NH3 - Hydrocarbons - CH4. ARMS II® Automac Refrigerant Monitoring System 1300 850 862 I www.aquagas.com.au I [email protected] I 3 Wirranina Place - Currumbin - 4223 QLD ARMS II ® Key Features Simultaneous mulgas IR detecon eradicates need for mulple systems and supports site changes Pre-calibrated for HFC/HCFCs, CH4, NH3, CO2, CH4 and hydrocarbons. Unique detecon of 8, 16, or 32 individual points to ena- ble accurate idenficaon of leak QuickScan bypass pump to minimise system cycle me and overall response me Instant visualisaon & one touch access to current sengs, status & alarms, event history. 8, 16, 24 and 32 sampling channels

Upload: others

Post on 24-Jul-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Automatic Refrigerant Monitoring System€¦ · Automatic Refrigerant Monitoring System 1300 850 862 I I info@aquagas.com.au I 3 Wirranina Place - Currumbin - 4223 QLD ARMS II ®

The ARMS 2 is a pre-calibrated automatic monitoring system for detecting leakage of fluorinated greenhouse

gases around compressors, cold rooms or chillers and provide site operators with It provides early warning of

refrigerant loss. The ARMS 2 is designed to provide stand alone conformity with F-Gas Regulation and

complies to AS1677 (mandatory for sites with an overall refrigerant charge in excess of 300kg).

Multicomponent and multi-zone The ARMS 2 uses a multi-gas infrared sensor technology and can be supplied

as an 8, 16, 24 or 32 channels model, to provide multi-zone leak detection based on the simultaneous real-

time measurement of HFC/HCFC’s - CO2 - NH3 - Hydrocarbons - CH4.

ARMS II® Automatic Refrigerant Monitoring System

1300 850 862 I www.aquagas.com.au I [email protected] I 3 Wirranina Place - Currumbin - 4223 QLD

ARMS II ® Key Features

Simultaneous multigas IR detection eradicates need for

multiple systems and supports site changes

Pre-calibrated for HFC/HCFCs, CH4, NH3, CO2, CH4

and hydrocarbons.

Unique detection of 8, 16, or 32 individual points to ena-

ble accurate identification of leak

QuickScan bypass pump to minimise system cycle time

and overall response time

Instant visualisation & one touch access to current

settings, status & alarms, event history.

8, 16, 24 and 32 sampling channels

Page 2: Automatic Refrigerant Monitoring System€¦ · Automatic Refrigerant Monitoring System 1300 850 862 I I info@aquagas.com.au I 3 Wirranina Place - Currumbin - 4223 QLD ARMS II ®

ARMS II ® Ease of integration

1300 850 862 I www.aquagas.com.au I [email protected] I 3 Wirranina Place - Currumbin - 4223 QLD

ARMS II ® Specifications

CONSTRUCTION & ENVIRONMENT

Dimensions 520 x 400 x 160 mm (L x W x H)

Wall mount assembly

Weight 16 kg

Measured components HFCs/HCFCs/CH4/HCs/NH3/CO2

Interface Colour touchscreen display and USB Ports

Data storage 2 GB Built-in SD memory

Output 5 user programmable dry contact alarm output/

threshold

On-board RS232/485 and Ethernet comms

Relative humidity 15 to 95% non condensing

Ambient T° 0 to +40°C

Conformity F-Gases regulation / AS1677 /EN378

ELECTRICAL UTILITIES

Power supply 240 VAC 50 Hz - 3A

The ARMS II is capable of initiating alarms, activating building ventilation systems and integrating with building automation

system.

Onboard RS232/485

Ethernet

5 programmable

alarms

Touch screen HMI

Up to 32 zones