astsoft starter · bypass contact(km) 3 phase power supply 3~ m breaker(qf) ast1 soft starters have...

8
R AST Soft Starter AST LOW Voltage Soft Starter Manual

Upload: others

Post on 17-May-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ASTSoft Starter · Bypass Contact(KM) 3 Phase Power Supply 3~ M Breaker(QF) AST1 Soft Starters have communication function, Modbus/RS485, D9 Connector is standard, Please read Manual

R

ASTSoft Starter

AST LOW Voltage Soft Starter Manual

Page 2: ASTSoft Starter · Bypass Contact(KM) 3 Phase Power Supply 3~ M Breaker(QF) AST1 Soft Starters have communication function, Modbus/RS485, D9 Connector is standard, Please read Manual

1

AST1 Soft Starter

Power: . -5 5KW 630KW

Voltage: -3AC 220V 690V

AST1 series soft starter's key features

The main purposes of the soft starter

Soft starter overviewAST1 series smart motor soft starter is new equipment based on the latest

motor control theory, proprietary motor protection technology and advancedsoftware technology. It's the ideal replacement of former starting equipmentsuch as star/delta transformation, auto transformer voltage reduction,and magnetic control voltage reduction, etc. Its performance is farbeyond that of most ordinary soft starters in the marketplace whichdo not include the intelligent starting control technology.

1、Reduce the motor's starting current effectively, reduce the

capacity of power distribution and avoid investment of gridexpansion.2 Reduce the starting stress of motor and load equipment';、

Prolong the motor and related equipment's service life.3 Soft stop function can effectively solve surge problem、

during stop of inertial systems that traditional startingequipment can't achieve.4 It has six unique starting modes to suit the complex motor、

and load condition to achieve perfect start effect.5 Complete and reliable protection function protects the、

motor and related production equipment to be used safely.6 The intelligent of motor soft starter and the application of、

network technology makes the motor control technology adaptto the higher requirements of fast developing power automation

technology.

1 The perfect humanity design:、

The harmony of beautiful appearance and reasonable structureThe harmony of perfect function and easy operationThe harmony of solid reliability and compact structureState of the art design for industrial products

2 The product with independent intellectual property rights:、

Patent of appearance designIndependent software copyrightProprietary motor start and protection technologyUnique measuring and testing equipment and process

3 Reliable quality guarantee:、

The computerized simulation designSMT production processGood EMC performanceHigh temperature, vibration test of the machine before delivery

4 Quick and thoughtful after-sales service:、

Reliable performance and quality lay the foundation of quality serviceProvide good and complete solution design scheme

5 The complete and reliable protection function:、

Power loss, under voltage, over voltage protectionSoft starter overheating, motor under-loading, excess starting time protectionInput phase loss, output phase loss, three-phase imbalance protectionStart over current, operation overload ,short circuit protection for load

Page 3: ASTSoft Starter · Bypass Contact(KM) 3 Phase Power Supply 3~ M Breaker(QF) AST1 Soft Starters have communication function, Modbus/RS485, D9 Connector is standard, Please read Manual

AST1 Soft Starter

External terminal connection Introduce

(KM)

KFRS1S2FR

3������

Http en aubochina com:// . . 2

AST1Soft Starter

Digital Keypad LCD Keypad

Ex Factory is Digital keypad LCD Keypad for chosen- !, is 。

Keypad Introlduce

Communication Introduce

START

STOP

ENTER

SET

READY

A

PASS

%

TRIP

S

START

STOP

ENTER

SET

AUBO

Bypass Contact(KM)

3 Phase Power Supply

3~

M

Breaker(QF)

AST1 Soft Starters have communication function,Modbus/RS485, D9 Connector is standard, Please read Manualof detail function and this function for chosen

Including

D9 Connector

COMStartStop

3 Line Control 2Line Control

output

input

output

(Limit Current 50mA)

GND

Blank

Input U1 3 380 500V 50 60Hz I1 200A: ~ - / :

Type:AST1-090-V5-ED

S/N:201 0408014

BID: 131501

Output: U 3~380-500V 50/60Hz I2:200A2

Software: V1.0

Mad

e b

y Au

bo

AST 1 090 V5 ED

���

� ����,090��90KW

������

����

V5:200VAC~525VACV7:200VAC~690VAC

ED:����CN:��!"��EN:#�!"��

��

$%&

�'

Product Type Introduce

Type

No.

Display Type

Digital

Chinese LCD

English LCD

Input Voltage

Motor KW

Generation

Seriers No.

� Terminals 1, 2 are the bypass output: it's used to control the bypass

contactor,and it's the passive contacts that open normally, it closes

when start is done successfully. Output capacity, AC250V / 5A.

� Terminal 3, 4 are the programmable relay output: delay time is set

by parameter setting P4, and output moment is set by parameter

setting FE. It's the passive contacts that open normally, and it closes

when output is valid. as shown in the parameter Settings and

instructions. Passive contact capacity, AC250V / 5A

� Terminal 5, 6 is the fault output: It closes when soft starter has fault

or loses power. It opens when it works correctly, and it's the passive

contact. The contact capacity, AC250V / 0.3A.

� Terminal 7 is the instantaneous stop output: this terminal should be

linked with terminal 10 when soft starter works normally. If this link

between terminal and the terminal 10 is open, the soft starter stops

working unconditionally in a state of fault protection. This terminal

can be controlled by external protection device's output of a normally

closed contact. When setting parameter PA is set to 0 (primary

protection), the terminal's function is banned.

� Terminal 8,9,10 are the input terminals for external start and stop

control button. They can be connected on requirement. As shown in

figure 4.3.

� Terminal, 11, 12 are the current of 0-20Am analog AC output, which

used to monitor the motor's current. The instruction motor current is

the 4 times of the soft starter rated current when full to 20mA, then

can external connect 0 to 20MA AC ammeter to observate, the

maximum output load resistance is 300 Ω.

� External terminal connection shouldn't be wrong, otherwise may

cause the damage of soft starter.

Fault Fault RUN/STOP COM

Page 4: ASTSoft Starter · Bypass Contact(KM) 3 Phase Power Supply 3~ M Breaker(QF) AST1 Soft Starters have communication function, Modbus/RS485, D9 Connector is standard, Please read Manual

AST1 Soft Starter

AST1 Soft starter Install Dimension 5 5 630KW: . -

>100

>50>50

>100>10

AST1 series soft starter installation requirements

Picture1 Picture2 Picture3

3

Installation direction and clearance:To ensure soft starter has goodventilation and cooling conditions, thesoft starter should be installed vertically,and leave enough heat dissipation spacearound the equipment.When soft starter is installed in thecabinet, in addition to the aboverequirements, it also should choose thecabinet well-ventilated from top tobottom. Unit in the figure: mm( )

Air Into

Exhaust

Rated Power and Rated Current is the max value,in general, the motors’ parameter can’t exceed this

Install Screw

Install Screw

Rated Power Rated current Outside Dimension Install Dimension Net weight

Rated Power Rated Current Outside Dimension Install Dimension Net Weight

Install Screw

Page 5: ASTSoft Starter · Bypass Contact(KM) 3 Phase Power Supply 3~ M Breaker(QF) AST1 Soft Starters have communication function, Modbus/RS485, D9 Connector is standard, Please read Manual

AST1 Soft Starter

���������

���� � ����

5http://en.aubochina.com

FR

AST1

N

AST

AS

T

Soft starter main loop connection

(Breaker)

(Bypass Contactor)

Motor 3~

Bypass output

Output Delay Output Fault

Fault Stop Run COM

DC 0~20mA Output

Ma

in L

oo

p

Stop

Start

4

Power

Fuse

R/S Control

COM

Fault Stop

Bypass

Fault light

Run light

Stop light

Co

ntr

ol L

oo

pTe

st L

oo

pCurrent

Voltage

To r

em

ote

co

ntr

ol b

ox

To re

mote

cont

rol b

ox

StartStopcom

Run light

COM

17

19

01 2AC 380V

1917

09

07

com

Stop light

Soft starter one by one standard connection diagram

Http en aubochina com:// . .

Page 6: ASTSoft Starter · Bypass Contact(KM) 3 Phase Power Supply 3~ M Breaker(QF) AST1 Soft Starters have communication function, Modbus/RS485, D9 Connector is standard, Please read Manual

AST1 Soft Starter

5

Code Name Setting RangeFactory

DefaultComment

P0 Initial voltage 30-70% 30% It is valid in voltage ramp mode ;In current mode starting level is 40%

P1 start time 2-60S 16S Not valid in current limit mode

P2 stop time 0-60S 0S Freewheel when it is set to 0; to be set to 0 when sequencial controlof two motors is applied

P3 Start delay 0-999S 0S Bycountdown time delay. When the setting is 0, it start immediatelywithout delay.

P4 Programmable delay 0-999S 0S for programmable relayoutput

P5 Restart delay 0-999S 60S Delay is still on when Overload is reset;Status indicator lights flashing during the time delay

P6 Start current limit 50-500% 320% Valid in current limit mode; The maximum value of ramp mode for current limit is 400%

P7 Maximum operating current 50-200% 1 P6 and P7 parameters' input mode decided byP8

P8 Input displaymethod 0-3 100% See note on P16 page

P9 Under-voltage protection 40-90% 0.8 Below the set point protection

PA Over-voltage protection 100%-140% 120% More than set point protection

PB Start mode 0-5 10 current limit; 1 voltage; 2 kickstart+ current limit; 3 kickstart+ voltage; 4 current ramp; 5 dual closed

loop

PC The output protection allows 0-4 200% 0 primary; 1 light load; 2 standard; 3 heavy load; 4 advanced

PD Operation control mode 0-7 4 No start or stop operation when set to 7 ,see note on P16 page

PE Restart permission 0-13 0% See note on P15

PF Parameter changes permission 0-3 1 See note P16

PH Communication Address 0-199 0% For several soft starters to communicate with the PCs of higher level

PJ Programmed output 0-20 7 See note on P14

PL Soft stop current limit 20-100% 80% See note on P27

PP Motor rated current rated value motor rated current to be inputed

PU Motor underload protection forbid See note on P16

Note:

4. Press the confirmation key(YES) to start ,which can reset the parameters (except PJ) to the factory default values.

Parameters' Setup Code Description

Setup Code Description

1. Parameter P7, maximum working current of is the maximum sustainable working current based on the calculation of PP setting number according to motor load .Inverse time

thermal protection will be functinoning when the current is over this value

2. If there is no button operation within 2 minutes ,it exits automatically from parameter programing status.

3. The parameters can not be set during soft start and soft stop,yet can be done under other conditions.

Display Description Problems and solutions

Err00 Fault removedSome fault just happened, such as undervoltage , or overvoltage, overload, open circuit of instantaneous stop terminal etc. Nowit's normal

with readyindicator on. It can start motor after reset

Err01 Open circuit of external instantaneous stop terminalConnect the external stantaneous stop terminal 7 with public terminal 10,or connect with normally-closed contact on the other protection

device

Err02 Soft starter is overload Start too frequentlyor motor power doesn't match that of soft starter

Err03 Starting time is too long, more than 60 seconds Starting parameters setting is not appropriate or the load is too heavy,or power supply's capacityis insufficient , etc

Err04 Input phase loss Checkthe input or the main line fault, or whether bypass contactor is stuckin the closed position or whether thyristor is short circuited, etc

Err05 Output phase loss Checkthe output or the main line fault, or whether bypass contactor is stuckin the closed position or whether thyristor is short circuited, etc

Err06 Three-phase imbalance Checkwhether three-phase power supplyand load motor is exceptional

Err07 Start over-current Whether the load is overweight or motor power doesn't match soft starter

Err08 Overload protection during running Whether the load is overweight or set improper P7, PP parameter

Err09 The power supply's voltage is too low Checkthe input voltage or set improper setting P9 parameter

Err10 The power supply's voltage is too high Checkthe input voltage or set improper setting PA parameter

Err11 Set the wrong parameter Modifythe Settings, or keep pressing confirmkeywhen power on to restore factorydefaults

Err12 Load short circuit Checkwhether the load or silicon controlled is short circuit or overload

Err13 Automatic restart , connection errors Checkwhether the start and stop terminals of external control are connect as 2 -wire type

Err14 External control stop, wrong terminal connection When external control is allowed , external control stop terminal is in open state and unable to start motor

Err15 motor under load Checkthe motor shaft and load fault

Err16 Power loss once Power loss at run time , press the reset button to return

Err45 Checkmain line Check three-phase input or output of main line

Fault code and Resolving methods

Note: some failure phenomenon is interlinked, such as report Err02 overload of soft starter is related to starting over current or load short circuit .Therefore,people should consider comprehensivelyto

identifythe failure point accuratelywhen theycheckfailures.

Note: when the soft starter starts the motor successfully, the indicator of running state is on , which is in the middle of panel, meaning it works in a bypass operation.If the bypass contactor is not closed,

causing the motor to stop , you should checkthe bypass contactor and related wiring to see if there is mistake or poor connection.

Page 7: ASTSoft Starter · Bypass Contact(KM) 3 Phase Power Supply 3~ M Breaker(QF) AST1 Soft Starters have communication function, Modbus/RS485, D9 Connector is standard, Please read Manual

AST1 Soft Starter

Http en aubochina com:// . . 6

Display Explanantions

AC:XXX Three digit voltmeter to measure three-phase AC power supply's voltage

055-3 This soft starter's specification is 55 A- 380VAC/50HZ

H1:E05 Information to remind of the last fault occurred Err05 (and so on)

H9:E00 Reminder,

UEr1.5 Reminder, software version for Ver1.5

Lxxxx XXXX is the total number of successful start

RUNxx xx is start(whether successful or not ) last time

Help information of AST1 soft starter

Help information as following table

Note: H1 - H9 , the record of newly happened 9 faults, being stored in a recursive way

In the state other than soft start and soft stop, not in the parameter setting, press the "confirmation "key

to enter the help menu and press plus and minus key to select the tip.

It can exit help state by press OK button or stop button in the condition of help

Load Start time (s) Primary voltageVoltage start

(Max limit A)Limit A start

Ball mill 30 60% 4 4.5

Fan 26 30% 4 3.5

Centrifugal pump 16 40% 4 2.5

Piston compressor 16 40% 4 3

Lift machine 16 60% 4 3.5

Blender 16 50% 4 3

Breaker 16 50% 4 3.5

Screw compressor 16 40% 4 3

Screw conveyor 20 40% 4 2

Light load Motor 16 30% 4 3

Belt conveyor 20 40% 4 2.5

Hot pump 16 40% 4 3

Note: The above diagram is for reference,choose it by the real situation

Page 8: ASTSoft Starter · Bypass Contact(KM) 3 Phase Power Supply 3~ M Breaker(QF) AST1 Soft Starters have communication function, Modbus/RS485, D9 Connector is standard, Please read Manual

ASTSoft StarterFile No.:AC AST V01 EN201410- - -

R

AUBO ElectricShanghai Office No 2 Bandaohaomen Villa ,1955None,Hongxin Road: .Minhang District,Shanghai China.

el axT 021 31 32 36 F :021 54362037: - / / -543620:N Zanjing Factory huzheng Town ,Liuhe District, Nanjing China

: - / / / : -T 025 1966 2066 2166 3766 F 025 85283866el ax8528:// . .http www aubochina com

@ .Email:george aubochina com