![Page 1: ASTSoft Starter · Bypass Contact(KM) 3 Phase Power Supply 3~ M Breaker(QF) AST1 Soft Starters have communication function, Modbus/RS485, D9 Connector is standard, Please read Manual](https://reader034.vdocuments.site/reader034/viewer/2022042217/5ec149034c77dd32f03778d2/html5/thumbnails/1.jpg)
R
ASTSoft Starter
AST LOW Voltage Soft Starter Manual
![Page 2: ASTSoft Starter · Bypass Contact(KM) 3 Phase Power Supply 3~ M Breaker(QF) AST1 Soft Starters have communication function, Modbus/RS485, D9 Connector is standard, Please read Manual](https://reader034.vdocuments.site/reader034/viewer/2022042217/5ec149034c77dd32f03778d2/html5/thumbnails/2.jpg)
1
AST1 Soft Starter
Power: . -5 5KW 630KW
Voltage: -3AC 220V 690V
AST1 series soft starter's key features
The main purposes of the soft starter
Soft starter overviewAST1 series smart motor soft starter is new equipment based on the latest
motor control theory, proprietary motor protection technology and advancedsoftware technology. It's the ideal replacement of former starting equipmentsuch as star/delta transformation, auto transformer voltage reduction,and magnetic control voltage reduction, etc. Its performance is farbeyond that of most ordinary soft starters in the marketplace whichdo not include the intelligent starting control technology.
1、Reduce the motor's starting current effectively, reduce the
capacity of power distribution and avoid investment of gridexpansion.2 Reduce the starting stress of motor and load equipment';、
Prolong the motor and related equipment's service life.3 Soft stop function can effectively solve surge problem、
during stop of inertial systems that traditional startingequipment can't achieve.4 It has six unique starting modes to suit the complex motor、
and load condition to achieve perfect start effect.5 Complete and reliable protection function protects the、
motor and related production equipment to be used safely.6 The intelligent of motor soft starter and the application of、
network technology makes the motor control technology adaptto the higher requirements of fast developing power automation
technology.
1 The perfect humanity design:、
The harmony of beautiful appearance and reasonable structureThe harmony of perfect function and easy operationThe harmony of solid reliability and compact structureState of the art design for industrial products
2 The product with independent intellectual property rights:、
Patent of appearance designIndependent software copyrightProprietary motor start and protection technologyUnique measuring and testing equipment and process
3 Reliable quality guarantee:、
The computerized simulation designSMT production processGood EMC performanceHigh temperature, vibration test of the machine before delivery
4 Quick and thoughtful after-sales service:、
Reliable performance and quality lay the foundation of quality serviceProvide good and complete solution design scheme
5 The complete and reliable protection function:、
Power loss, under voltage, over voltage protectionSoft starter overheating, motor under-loading, excess starting time protectionInput phase loss, output phase loss, three-phase imbalance protectionStart over current, operation overload ,short circuit protection for load
![Page 3: ASTSoft Starter · Bypass Contact(KM) 3 Phase Power Supply 3~ M Breaker(QF) AST1 Soft Starters have communication function, Modbus/RS485, D9 Connector is standard, Please read Manual](https://reader034.vdocuments.site/reader034/viewer/2022042217/5ec149034c77dd32f03778d2/html5/thumbnails/3.jpg)
AST1 Soft Starter
External terminal connection Introduce
(KM)
KFRS1S2FR
3������
Http en aubochina com:// . . 2
AST1Soft Starter
Digital Keypad LCD Keypad
Ex Factory is Digital keypad LCD Keypad for chosen- !, is 。
Keypad Introlduce
Communication Introduce
START
STOP
ENTER
SET
READY
A
PASS
%
TRIP
S
START
STOP
ENTER
SET
AUBO
Bypass Contact(KM)
3 Phase Power Supply
3~
M
Breaker(QF)
AST1 Soft Starters have communication function,Modbus/RS485, D9 Connector is standard, Please read Manualof detail function and this function for chosen
Including
D9 Connector
COMStartStop
3 Line Control 2Line Control
output
input
output
(Limit Current 50mA)
GND
Blank
Input U1 3 380 500V 50 60Hz I1 200A: ~ - / :
Type:AST1-090-V5-ED
S/N:201 0408014
BID: 131501
Output: U 3~380-500V 50/60Hz I2:200A2
Software: V1.0
Mad
e b
y Au
bo
AST 1 090 V5 ED
���
� ����,090��90KW
������
����
V5:200VAC~525VACV7:200VAC~690VAC
ED:����CN:��!"��EN:#�!"��
��
$%&
�'
Product Type Introduce
Type
No.
Display Type
Digital
Chinese LCD
English LCD
Input Voltage
Motor KW
Generation
Seriers No.
� Terminals 1, 2 are the bypass output: it's used to control the bypass
contactor,and it's the passive contacts that open normally, it closes
when start is done successfully. Output capacity, AC250V / 5A.
� Terminal 3, 4 are the programmable relay output: delay time is set
by parameter setting P4, and output moment is set by parameter
setting FE. It's the passive contacts that open normally, and it closes
when output is valid. as shown in the parameter Settings and
instructions. Passive contact capacity, AC250V / 5A
� Terminal 5, 6 is the fault output: It closes when soft starter has fault
or loses power. It opens when it works correctly, and it's the passive
contact. The contact capacity, AC250V / 0.3A.
� Terminal 7 is the instantaneous stop output: this terminal should be
linked with terminal 10 when soft starter works normally. If this link
between terminal and the terminal 10 is open, the soft starter stops
working unconditionally in a state of fault protection. This terminal
can be controlled by external protection device's output of a normally
closed contact. When setting parameter PA is set to 0 (primary
protection), the terminal's function is banned.
� Terminal 8,9,10 are the input terminals for external start and stop
control button. They can be connected on requirement. As shown in
figure 4.3.
� Terminal, 11, 12 are the current of 0-20Am analog AC output, which
used to monitor the motor's current. The instruction motor current is
the 4 times of the soft starter rated current when full to 20mA, then
can external connect 0 to 20MA AC ammeter to observate, the
maximum output load resistance is 300 Ω.
� External terminal connection shouldn't be wrong, otherwise may
cause the damage of soft starter.
Fault Fault RUN/STOP COM
![Page 4: ASTSoft Starter · Bypass Contact(KM) 3 Phase Power Supply 3~ M Breaker(QF) AST1 Soft Starters have communication function, Modbus/RS485, D9 Connector is standard, Please read Manual](https://reader034.vdocuments.site/reader034/viewer/2022042217/5ec149034c77dd32f03778d2/html5/thumbnails/4.jpg)
AST1 Soft Starter
AST1 Soft starter Install Dimension 5 5 630KW: . -
>100
>50>50
>100>10
AST1 series soft starter installation requirements
Picture1 Picture2 Picture3
3
Installation direction and clearance:To ensure soft starter has goodventilation and cooling conditions, thesoft starter should be installed vertically,and leave enough heat dissipation spacearound the equipment.When soft starter is installed in thecabinet, in addition to the aboverequirements, it also should choose thecabinet well-ventilated from top tobottom. Unit in the figure: mm( )
Air Into
Exhaust
Rated Power and Rated Current is the max value,in general, the motors’ parameter can’t exceed this
Install Screw
Install Screw
Rated Power Rated current Outside Dimension Install Dimension Net weight
Rated Power Rated Current Outside Dimension Install Dimension Net Weight
Install Screw
![Page 5: ASTSoft Starter · Bypass Contact(KM) 3 Phase Power Supply 3~ M Breaker(QF) AST1 Soft Starters have communication function, Modbus/RS485, D9 Connector is standard, Please read Manual](https://reader034.vdocuments.site/reader034/viewer/2022042217/5ec149034c77dd32f03778d2/html5/thumbnails/5.jpg)
AST1 Soft Starter
���������
���� � ����
5http://en.aubochina.com
FR
AST1
N
AST
AS
T
Soft starter main loop connection
(Breaker)
(Bypass Contactor)
Motor 3~
Bypass output
Output Delay Output Fault
Fault Stop Run COM
DC 0~20mA Output
Ma
in L
oo
p
Stop
Start
4
Power
Fuse
R/S Control
COM
Fault Stop
Bypass
Fault light
Run light
Stop light
Co
ntr
ol L
oo
pTe
st L
oo
pCurrent
Voltage
To r
em
ote
co
ntr
ol b
ox
To re
mote
cont
rol b
ox
StartStopcom
Run light
COM
17
19
01 2AC 380V
1917
09
07
com
Stop light
Soft starter one by one standard connection diagram
Http en aubochina com:// . .
![Page 6: ASTSoft Starter · Bypass Contact(KM) 3 Phase Power Supply 3~ M Breaker(QF) AST1 Soft Starters have communication function, Modbus/RS485, D9 Connector is standard, Please read Manual](https://reader034.vdocuments.site/reader034/viewer/2022042217/5ec149034c77dd32f03778d2/html5/thumbnails/6.jpg)
AST1 Soft Starter
5
Code Name Setting RangeFactory
DefaultComment
P0 Initial voltage 30-70% 30% It is valid in voltage ramp mode ;In current mode starting level is 40%
P1 start time 2-60S 16S Not valid in current limit mode
P2 stop time 0-60S 0S Freewheel when it is set to 0; to be set to 0 when sequencial controlof two motors is applied
P3 Start delay 0-999S 0S Bycountdown time delay. When the setting is 0, it start immediatelywithout delay.
P4 Programmable delay 0-999S 0S for programmable relayoutput
P5 Restart delay 0-999S 60S Delay is still on when Overload is reset;Status indicator lights flashing during the time delay
P6 Start current limit 50-500% 320% Valid in current limit mode; The maximum value of ramp mode for current limit is 400%
P7 Maximum operating current 50-200% 1 P6 and P7 parameters' input mode decided byP8
P8 Input displaymethod 0-3 100% See note on P16 page
P9 Under-voltage protection 40-90% 0.8 Below the set point protection
PA Over-voltage protection 100%-140% 120% More than set point protection
PB Start mode 0-5 10 current limit; 1 voltage; 2 kickstart+ current limit; 3 kickstart+ voltage; 4 current ramp; 5 dual closed
loop
PC The output protection allows 0-4 200% 0 primary; 1 light load; 2 standard; 3 heavy load; 4 advanced
PD Operation control mode 0-7 4 No start or stop operation when set to 7 ,see note on P16 page
PE Restart permission 0-13 0% See note on P15
PF Parameter changes permission 0-3 1 See note P16
PH Communication Address 0-199 0% For several soft starters to communicate with the PCs of higher level
PJ Programmed output 0-20 7 See note on P14
PL Soft stop current limit 20-100% 80% See note on P27
PP Motor rated current rated value motor rated current to be inputed
PU Motor underload protection forbid See note on P16
Note:
4. Press the confirmation key(YES) to start ,which can reset the parameters (except PJ) to the factory default values.
Parameters' Setup Code Description
Setup Code Description
1. Parameter P7, maximum working current of is the maximum sustainable working current based on the calculation of PP setting number according to motor load .Inverse time
thermal protection will be functinoning when the current is over this value
2. If there is no button operation within 2 minutes ,it exits automatically from parameter programing status.
3. The parameters can not be set during soft start and soft stop,yet can be done under other conditions.
Display Description Problems and solutions
Err00 Fault removedSome fault just happened, such as undervoltage , or overvoltage, overload, open circuit of instantaneous stop terminal etc. Nowit's normal
with readyindicator on. It can start motor after reset
Err01 Open circuit of external instantaneous stop terminalConnect the external stantaneous stop terminal 7 with public terminal 10,or connect with normally-closed contact on the other protection
device
Err02 Soft starter is overload Start too frequentlyor motor power doesn't match that of soft starter
Err03 Starting time is too long, more than 60 seconds Starting parameters setting is not appropriate or the load is too heavy,or power supply's capacityis insufficient , etc
Err04 Input phase loss Checkthe input or the main line fault, or whether bypass contactor is stuckin the closed position or whether thyristor is short circuited, etc
Err05 Output phase loss Checkthe output or the main line fault, or whether bypass contactor is stuckin the closed position or whether thyristor is short circuited, etc
Err06 Three-phase imbalance Checkwhether three-phase power supplyand load motor is exceptional
Err07 Start over-current Whether the load is overweight or motor power doesn't match soft starter
Err08 Overload protection during running Whether the load is overweight or set improper P7, PP parameter
Err09 The power supply's voltage is too low Checkthe input voltage or set improper setting P9 parameter
Err10 The power supply's voltage is too high Checkthe input voltage or set improper setting PA parameter
Err11 Set the wrong parameter Modifythe Settings, or keep pressing confirmkeywhen power on to restore factorydefaults
Err12 Load short circuit Checkwhether the load or silicon controlled is short circuit or overload
Err13 Automatic restart , connection errors Checkwhether the start and stop terminals of external control are connect as 2 -wire type
Err14 External control stop, wrong terminal connection When external control is allowed , external control stop terminal is in open state and unable to start motor
Err15 motor under load Checkthe motor shaft and load fault
Err16 Power loss once Power loss at run time , press the reset button to return
Err45 Checkmain line Check three-phase input or output of main line
Fault code and Resolving methods
Note: some failure phenomenon is interlinked, such as report Err02 overload of soft starter is related to starting over current or load short circuit .Therefore,people should consider comprehensivelyto
identifythe failure point accuratelywhen theycheckfailures.
Note: when the soft starter starts the motor successfully, the indicator of running state is on , which is in the middle of panel, meaning it works in a bypass operation.If the bypass contactor is not closed,
causing the motor to stop , you should checkthe bypass contactor and related wiring to see if there is mistake or poor connection.
![Page 7: ASTSoft Starter · Bypass Contact(KM) 3 Phase Power Supply 3~ M Breaker(QF) AST1 Soft Starters have communication function, Modbus/RS485, D9 Connector is standard, Please read Manual](https://reader034.vdocuments.site/reader034/viewer/2022042217/5ec149034c77dd32f03778d2/html5/thumbnails/7.jpg)
AST1 Soft Starter
Http en aubochina com:// . . 6
Display Explanantions
AC:XXX Three digit voltmeter to measure three-phase AC power supply's voltage
055-3 This soft starter's specification is 55 A- 380VAC/50HZ
H1:E05 Information to remind of the last fault occurred Err05 (and so on)
H9:E00 Reminder,
UEr1.5 Reminder, software version for Ver1.5
Lxxxx XXXX is the total number of successful start
RUNxx xx is start(whether successful or not ) last time
Help information of AST1 soft starter
Help information as following table
Note: H1 - H9 , the record of newly happened 9 faults, being stored in a recursive way
In the state other than soft start and soft stop, not in the parameter setting, press the "confirmation "key
to enter the help menu and press plus and minus key to select the tip.
It can exit help state by press OK button or stop button in the condition of help
Load Start time (s) Primary voltageVoltage start
(Max limit A)Limit A start
Ball mill 30 60% 4 4.5
Fan 26 30% 4 3.5
Centrifugal pump 16 40% 4 2.5
Piston compressor 16 40% 4 3
Lift machine 16 60% 4 3.5
Blender 16 50% 4 3
Breaker 16 50% 4 3.5
Screw compressor 16 40% 4 3
Screw conveyor 20 40% 4 2
Light load Motor 16 30% 4 3
Belt conveyor 20 40% 4 2.5
Hot pump 16 40% 4 3
Note: The above diagram is for reference,choose it by the real situation
![Page 8: ASTSoft Starter · Bypass Contact(KM) 3 Phase Power Supply 3~ M Breaker(QF) AST1 Soft Starters have communication function, Modbus/RS485, D9 Connector is standard, Please read Manual](https://reader034.vdocuments.site/reader034/viewer/2022042217/5ec149034c77dd32f03778d2/html5/thumbnails/8.jpg)
ASTSoft StarterFile No.:AC AST V01 EN201410- - -
R
AUBO ElectricShanghai Office No 2 Bandaohaomen Villa ,1955None,Hongxin Road: .Minhang District,Shanghai China.
el axT 021 31 32 36 F :021 54362037: - / / -543620:N Zanjing Factory huzheng Town ,Liuhe District, Nanjing China
: - / / / : -T 025 1966 2066 2166 3766 F 025 85283866el ax8528:// . .http www aubochina com
@ .Email:george aubochina com
Partner Information