argus manual

62
TsRKF 656437.019 OM. 1 BORETS COMPANY LLC BORETS RESEARH & DEVELOPMENT CENTER VARIABLE SPEED DRIVE CONTROLLER "ARGUS" OPERATING MANUAL 2013

Upload: sandro-vargas

Post on 10-Nov-2015

607 views

Category:

Documents


7 download

DESCRIPTION

manual argus

TRANSCRIPT

  • TsRKF 656437.019 OM. 1

    BORETS COMPANY LLC

    BORETS RESEARH & DEVELOPMENT CENTER

    VARIABLE SPEED DRIVE CONTROLLER "ARGUS"

    OPERATING MANUAL

    2013

  • TsRKF 656437.019 OM. 2

    The following abbreviations are used throughout the document:

    AR - Automatic restart

    SCADA - Automated control system

    LAU - Lightning arrester unit

    Commissioning - Commissioning

    LCD - Liquid crystal display

    UL - Trip on underload

    OL - Overload protection

    UFCC

    LLC -

    Universal frequency converter controller

    (Low level controller)

    ARGUS - Variable speed drive controller

    Tubing - Tubing

    FC - Frequency converter

    motor - Induction motor

    PMM - Permanent magnet motor

    AOM - Alarm operation mode

    VSD - Variable speed drive

    SCADA - Upper level system

    DHG - Telemetry system

    Step-up

    transformer - Step-up transformer

    ESP system - Electric submersible pump system

    OGPD - Oil and Gas Production Department

    ESP - Electric submersible pump

  • TsRKF 656437.019 OM. 3

    1.1 Controller's functions

    VSD and motor operation modes control and protection functions are carried out by the software

    of the variable speed drive ARGUS controller (ARGUS).

    ARGUS controller is the upper level controller, it sets operation modes, carries out certain

    protection functions, and provides interface with operator, LLC controller, integrated auxiliary equipment

    and external automated control system (SCADA).

    Detailed list of parameters, commands and settings, the structure of on-screen menu of the

    ARGUS controller are described in Sections 2, 3, 4.

    1.1.1 Motor operation control functions:

    Controller provides:

    - operation with induction and permanent magnet motor;

    - motor switching on and tripping in manual control mode by the

    operator or in automated control mode (including, using the program with preset motor

    operation / shutdown time intervals);

    - remote motor switching on and tripping on SCADA command;

    - automated and manual control of motor speed using the ARGUS

    keypad without tripping the VSD and remote control on SCADA commands;

    - operation using the program with individually preset motor operation

    and shutdown time intervals;

    - automatic motor switching on with adjustable delay time when voltage

    is supplied or when voltage is recovered in accordance with the standard;

    - smooth acceleration and braking of motor with the set rate;

    - acceleration with omission of resonant frequencies when changing

    ESP system frequency (operation with the set minimum frequency and frequency hopping

    bandwidth);

    - changing of the motor rotation direction (reversal), also without VSD

    tripping by smooth deceleration to zero and smooth acceleration up to the set frequency;

    - motor braking with backspin with its further startup for direct rotation

    (backspin picking up mode);

    - automatic frequency shift at the output depending on the analog input

    signal;

    - automated maintaining of the set motor current value by changing the

    output frequency with possibility of motor current control;

    - automated current optimization when reaching the set frequency

    (selection of optimum voltage after ESP system has reached the steady state mode);

    - automated system unlocking mode using jogging mode ("heavy" and

    reverse startup);

    - system running up mode with heavy motor startup using jogging mode

    with the set "jogging" frequency;

    - "stirring" mode (to prevent depositions on pump stages);

    1.1.2 Protective functions

    1.1.2.1 motor tripping with automatic restarting (AR):

  • TsRKF 656437.019 OM. 4

    - when underloading in-phase current component of any phase with

    selection of the minimum phase current;

    - when overloading any phase with selection of the maximum phase

    current in accordance with the adjustable time-current characteristic via separate selection of the

    desired current settings and overload time;

    - when supply voltage is above or below the set values;

    - when the selected motor current imbalance setting is exceeded;

    - when the selected voltage imbalance setting is exceeded;

    1.1.2.2 When variable speed drive is provided with surface telemetry units of the sensor system,

    the controller shall support motor tripping with AR:

    - on DHG signal indicating that the set motor temperature value is

    exceeded;

    - on DHG signal indicating that pump intake pressure is above or below

    the set value;

    - on DHG signal indicating that motor vibration acceleration is above

    the set level;

    - when communication with DHG is lost.

    1.1.2.3 motor tripping and startup locking:

    - in case of unauthorized access to the power box of the cabinet;

    - on EXTERNAL LOCKING signal;

    - on signal from contact pressure gauge;

    - on reduction of insulation resistance of the Step-up transformercable

    motor circuit below the set value (recommended 30 kOhm).

    Note. ESP system may be allowed to operate with insulation resistance reduction below the

    setting, provided that the response speed of the current overload protection trip is automatically increased.

    1.1.2.4 motor startup locking:

    - in case of voltage recovery with incorrect phase sequence;

    - in case of backspinning with selection of the frequency exceeding the

    allowable value.

    1.1.2.5 Each protection is provided with:

    - selection of active (ON) and inactive (OFF ) condition;

    - adjustable delay time of protection activation after its operation;

    - adjustable delay time for protection activation (except for low

    insulation resistance protection, door opening protection);

    - separately adjustable delay time for tripping immediately after startup

    (except for low insulation resistance protection, door opening protection);

    - selection of protection mode (except for protections for maximum

    current load, low insulation resistance, contact pressure gauge) with restart (AR), and AR

    locking or without AR;

    1.1.2.6 AR function is provided with:

    - selection of active (ON, LOCKED) and inactive (OFF ) condition;

    - adjustable AR delay time;

    - selection of restarts number;

    - interlocking of AR when the set number of allowed restarts is

    exceeded;

    - manual unlocking of VSD tripping.

  • TsRKF 656437.019 OM. 5

    1.1.2.7 Prevention of operation modes switching, protections switching on / off and changing of

    settings without entering password.

    1.1.3 Monitoring and information functions

    1.1.3.1 Monitoring and display of current values of parameters and characteristics on ARGUS

    display:

    - supply voltages of three phases and their imbalance;

    - currents of three motor phases and their imbalance;

    - motor rotation speed;

    - insulation resistance of the Step-up transformer submersible cable

    motor circuit;

    - heat sink temperature;

    - phase sequence at the VSD input;

    - phase sequence at the VSD output;

    - current value of the power factor (cos );

    - current value of actual motor load in per cent of active current rated

    value;

    - motor condition (on - off) using DHG;

    - condition of the VSD with indication of the reason for this condition,

    uptime from the moment of the last startup in hours and minutes or time remaining to the

    startup in minutes and seconds, when operating in the automated control mode;

    - operation of specific protections;

    - opening of the power box doors (in case of unauthorized access);

    - current date and time.

    1.1.3.2 Monitoring and display of the preset and the current values of parameters on ARGUS

    display in VSD, equipped with surface DHG units:

    - motor winding temperature;

    - formation temperature;

    - pressure at the pump intake and discharge;

    - motor vibration level at the axes and Y.

    1.1.3.3 Monitoring and display on electric meter display and ARGUS display in VSD, provided

    with electric meter:

    - active energy in conducting direction with accrued total;

    - reactive energy with accrued total;

    - total energy in conducting direction with accrued total;

    - instantaneous values:

    linear voltage,

    active power (total and of each phase),

    reactive power (total and of each phase),

    apparent power (total and of each phase),

    power factor (total and of each phase),

    Unified Power Quality Index;

    - current time and current date (on electric meter display);

    - daily and monthly maximum power;

    - event log with daily (00-00 to 24-00) recording of power consumption

    (active and apparent power) and uptime per day, registered by VSD controller and transmission

    to the upper level.

  • TsRKF 656437.019 OM. 6

    1.1.3.4 VSD controller provides display and chronological recording of 50000 last changes of

    ESP system condition. In real time with adjustable time interval a recording is made in a memory unit,

    containing information on motor switching on and tripping reasons:

    - total ESP system run life;

    - total number of ESP system starts;

    - current date and time;

    - parameter, which value entered the zone that triggered a protection

    function;

    - power up and power off time;

    - current values of supply voltage;

    - current values of motor current;

    - current load values;

    - current power factor values;

    - pump system parameters (if sensor system is used);

    - date and time, when setting was changes, number of the changed

    setting, old and new value of changed setting.

    Set operation parameters and accumulated information are stored, when no power is supplied.

    1.1.3.5 Real time clock operate autonomously, when no external power supply source is

    available, during 360 days, clock adjustment is provided, including remote adjustment using SCADA

    command.

    1.1.4 Information reading and transmission functions

    - transmission of the set operation parameters, current and accumulated

    information into the SCADA system using the RS-485 interface;

    - transmission of accumulated information to PC via -port using

    the RS-232 interface;

    - transmission of accumulated information to the USB reader device, the

    information can further be converted on PC into Microsoft Office Excel format using a USB

    port.

    1.1.5 Process parameters settings

    - well number;

    - well pad number;

    - oil and gas field (OGF) number;

    - ESP system running depth, m;

    - Step-up transformer voltage, V;

    - recording step, min;

    - rotation speed measurement unit;

    - current consumption of DHG, mA;

    - VSD type;

    - motor type;

    - ESP system capacity, m3/day;

    - ESP system head, m;

    - DHG type;

    - number, type, manufacturer, date of manufacture of ARGUS;

    - number, type, manufacturer, date of manufacture of VSD;

  • TsRKF 656437.019 OM. 7

    - feeder number.

    1.1.6 Functions of intelligent control system

    1.1.6.1 Automated startup of ESP system in accordance with the pre-set program, including

    "sparing commissioning" with minimum possible pump flow rate, sufficient to cool the motor.

    1.1.6.2 Mode for surveying / scanning of well inflow the mode for determining the maximum

    possible well production rate at the current moment of time and adjustment of the ESP system for the

    maximum production rate.

    1.1.6.3 Efficient power consumption (automated optimization of power consumption) in all

    operation modes.

    1.1.6.4 Avoiding emergency operation modes of ESP system.

    1.1.6.5 Pump operation on the boundary of pump underload (prevention of tripping due to pump

    underload in terms of head, pump underload in terms of gas etc.);

    1.1.6.6 Cyclic operation mode of the ESP system.

    Automatic switching over from cyclic operation mode into continuous operation mode, provided that the

    appropriate conditions for continuous operation mode are available.

    2 Controller

    2.1 General provisions

    Variable speed drive controller (ARGUS) provides:

    - implementation of various motor control algorithms;

    - browsing of current values of operating parameters of motor and VSD;

    - reprogramming of ARGUS and LLC without VSD tripping;

    - reading of ESP system operation history.

    In terms of design, ARGUS is a complete system, front panel of operator's interface is installed

    on the VSD front door.

    All information required for operator is shown on LCD display on the front panel in text format.

    Data entry is carried out with keypad using menus.

    ARGUS software allows using several types of menu, both those already used in serial VSD

    manufactured by BORETS COMPANY, and other menus, made to specific customer's requirements.

    ARGUS controller is used as standard. Other controller modifications may be manufactured,

    provided that the software continuity is preserved. ARGUS controller description is provided in TsRKF

    ... Description of its front panel is given below.

  • TsRKF 656437.019 OM. 8

    2.2 Front panel of ARGUS controller

    Front panel of ARGUS controller is shown in Figure 1.

    Figure 1 Front panel of ARGUS controller

    The ARGUS controller front panel is provided with:

    - four line liquid crystal display, 20 characters in each line, which displays information in text

    format;

    - ten digital buttons of membrane keypad ("0" "9");

    - four keypad control buttons "ENTER", "CANCEL", "ALT", "HELP";

    - LED display "ALT";

    - two VSD control buttons "START", "STOP";

    - LED indicator "PREHEATING";

    - 15 pin connector "PORT", with two interfaces connected to it: RS232 and USB to connect with

    SCADA system and reading of accumulated information from the controller.

  • TsRKF 656437.019 OM. 9

    3 ARGUS controller menu Controller menu provides established operator's access to viewing equipment condition, setting

    system operating modes, protection parameters. ARGUS software supports various types of menu,

    meeting the specific requirements of the customers and allowing it use in serial VSD manufactured by

    BORETS COMPANY.

    All the messages related to ESP system operation are shown on LCD display in text format.

    Information is displayed in 4 lines, hereinafter referred to as "window". All operations on data entry into

    controller are carried out using its keypad.

    Controller menu provides access to the parameters via multilevel structure of subfolders (as in

    controller "Borets PMM"). Menu contains 15 items at the 1-st level, which may have nested menus of

    the 2-nd, 3-rd and 4-th level. Menu structure is given in Table 3.1. The complete list of menu parameters

    is given in Table 1 A (see Appendix A).

    The columns of each of the tables of the list provides the following information:

    - the list of parameters having the same designations, as they are shown on LCD display,

    - parameter appearance (parameter, setting, command)

    - measurement unit,

    - explanation of abbreviations and brief description of the parameter,

    - range of possible values,

    - factory setting of the parameter's value,

    - reference to a more detailed description of the parameter.

    The "Reference" column of each of the table of the list provides reference to the comment clause

    in Section 8 "Description of the displayed parameters and system operation modes"

    The complete list of parameters, commands and settings, used in operation with submersible

    system, there are parameters, applicable only for specific configuration and execution of the equipment,

    depending on the type of VSD, LLC, motor, auxiliary equipment. Menu is made in a way that, when

    entering specific equipment configuration, display shows the parameters, applicable only to the selected

    configuration.

    3.1 Controller menu

    3.1.1 Menu structure

    Menu structure is given in Table 3.1.

    Table 3.1

    Name of subfolders

    Reference to

    the parameters

    list 9

    Current parameters 9

    Settings 9.1

    Settings I 9.1.1

    Settings U 9.1.2

    Other settings 9.1.3

    DHG settings 9.1.4

    Analog inputs settings 9.1.5

    REG settings 9.1.6

  • TsRKF 656437.019 OM. 10

    External devices 9.2

    Settings 9.3

    Measurement units 0

    Date and time 9.5

    Configuration of VSD 0

    Settings of motor 0

    Settings of SS 0

    VSD technical data sheet 0

    DHG technical data sheet 0

    SDHG 0

    SurfDHG 0

    DHG configuration 0

    Commands 9.7

    Change password 9.7.1

    Calibration 9.8

    SCADA 9.9

    Language 0

    LCD 0

    Electric meter 9.12

    Readings 0

    Current day 0

    Previous day 9.12.1.2

    Current month 9.12.1.3

    Previous month 9.12.1.4

    Current year 9.12.1.5

    Previous year 9.12.1.6

    Total 9.12.1.7

    Quadrants 0

    Current day 0

    Previous day 0

    Current month 0

    Previous month 0

    Current year 0

    Previous year 0

    Total 0

    Settings 9.12.3

    Information 0

    Parameters 9.12.5

    Basic 0

    Power 0

    Other 0

    Commissioning parameters 9.13

  • TsRKF 656437.019 OM. 11

    Intelligence 9.14

    Parameters 0

    Commissioning Error!

    Reference

    source not

    found.

    Optimization 9.14.3

    Gas lock 0

    Pulses 0

    Working submergence 0

    Deposits Error!

    Reference

    source not

    found.

    Intelligence 0

    Service 9.15

    Variable speed drive 0

    Settings 9.15.1.1

    Coefficients 0

    Analog inputs 0

    Condition 9.15.1.2

    Parameters 9.15.1.3

    Motor 0

    LL controller 0

    Parameters 0

    Condition 0

    Autonomous operation 0

    aut.op,min 0

    DHG 0

    Adjustment settings 0

    Condition 0

    Parameters 0

    RS DHG 0

    USB stick 9.16

    Read history 0

    ARGUS programming 0

    FCC programming 0

    Accept settings 0

  • TsRKF 656437.019 OM. 12

    3.1.2 Buttons function in the menu

    3.1.2.1 Buttons functions are changed depending on the type of operations with the menu. There

    are four types of operations with the menu:

    - viewing of lists of parameters, settings and system operation history;

    - editing of settings;

    - performance of commands from submenu "Commands";

    - calibration of the insulation resistance measurement channel.

    Buttons functions depending on the type of operations are given in Table 2.

    Table 2

    Button

    Operation type

    Viewing Editing Execution of

    commands Calibration

    09 Digit entry

    Cursor movement

    one line up

    - Changing of parameters values.

    - Changing of the current symbol to the

    next value

    Cursor movement

    one line up

    Cursor movement

    one line down

    Cursor movement

    one line down

    Moving to the

    next window

    Moving one character

    to the right

    Moving to the

    next window

    Moving to the

    previous window

    Moving one character

    to the left

    Moving to the

    previous window

    ENTER

    Moving to the

    next menu level

    Exit from editing,

    saving the entered

    value

    Execution of

    command

    Moving to the

    next calibration

    step

    CANCEL

    Moving to the

    previous menu

    level

    Exit from editing,

    without saving the

    entered value

    Moving to the

    previous menu

    level

    Calibration exit

    without saving

    the results

    Alt

    Switching from the

    digit entry mode to the

    arrows navigation

    mode

    Help

    Display of

    parameter

    reference

    information for 2

    seconds

    Moving one character

    to the left

    START MOTOR STARTUP (if no wafer type switch is available)

    STOP MOTOR SHUTDOWN (if no wafer type switch is available)

    3.1.2.2 In "viewing" mode operator can view elements lists in menu windows. Use ENTER

    button to switching from the last level viewing mode to editing of parameters and settings

    3.1.2.3 Editing mode allows changing settings values within the given ranges. Switching to

    editing mode is possible only after password entry, if the password was not cancelled. To cancel the

    password, change the password to 0000. If the value of the entered setting is beyond the possible range,

    then, while still in editing mode, operator is suggested possible limiting values.

  • TsRKF 656437.019 OM. 13

    3.1.3 Entry into the 1 type menu

    3.1.3.1 When powering the controller, its booting is started (it takes about 2 minutes), after that,

    the main window is displayed on LCD.

    The first three line of the main window display the parameters:

    - "No., rpm" rotation speed;

    - "I PMM, A" motor current;

    - "R,kOhm" insulation resistance;

    - the fourth line is the status bar.

    Status bar displays current date and time or current condition (reason for drive start failure, if

    yellow lamp is constantly on).

    The main window is different from other menu windows, since it has additional indications on

    the right side of the window.

    Additional indications area may display the following information symbols.

    3.1.3.2 Line "No., rpm" may display the following symbols: "", "", "~", "^".

    Symbol "", "" indicates that the Step-up transformer voltage is not optimum. If the voltage is

    higher, variable speed drive is running at the increased frequency converter current; if lower variable

    speed drive can not reach the required rotation speed, due to undervoltage.

    Symbol "~" indicates that variable speed drive is operating in motor acceleration or deceleration

    mode.

    Symbol "^" indicates that motor is running at increased speed to remove gas locks.

    3.1.3.3 Line "IPMM, A" may display symbol "", which indicates undercurrent. This happens:

    - when Step-up transformer transformer stage voltage is set high above the required value,

    - when incorrectly selected configuration of the drive engineering package is lacking power for

    the variable speed drive provide the required rotation speed of motor.

    3.1.3.4 Line "R, kOhm" may display symbol "", appearance of which shows that insulation

    resistance is below the set value.

    3.1.3.5 The lower line may show the following symbols:

    - "DHG" indicating that the variable speed drive operates with the telemetry system;

    - "DOOR" indicating that the VSD door is open;

    - "MAN","AUT","PRG" indicates VSD operation mode;

    - "REL" indicates that independent automatic circuit breaker QF5 release has operated;

    - ">>>" or "" indicates that the VSD is in standby mode for automatic startup;

    - " ", " " or " !! " accordingly indicate that decrease of the rotation speed or sudden

    decrease of the dynamic level of the formation fluid in the well in auto adaptation mode.

    3.1.3.6 The list of the current parameters may be viewed in the main window.

    3.1.3.7 Moving from the current parameters window to other menu windows is carried out by

    pressing the "ENTER" button.

    3.1.3.8 LCD displays only the information applicable to the selected equipment.

  • TsRKF 656437.019 OM. 14

    4.1 Preparing VSD for switching on

    - enter ESP system equipment parameters into ARGUS in accordance with Table 4.1. If required, check the compliance of the existing settings with the factory settings or enter "Restore factory settings"

    command.

    Table 4.1. Equipment parameters, entered in ARGUS

    Parameter name Navigation in menu

    Menu appearance Service | VSD | Settings | Menu appearance

    Restore factory settings Commands |

    Unlocking Commands |

    Nominal mains voltage, V Service | VSD | Settings | U mains|

    Field number Settings | Field No. |

    Well pad number Settings | Well pad No. |

    Well number Settings | Well No. |

    Nominal pump capacity DEP configuration | ESP|

    Pump head, m; DEP configuration | Head|

    Installation depth, m Settings | Lrunning|

    Cable cross section, mm Settings | Cross section mm2 |

    VSD type DEP configuration | VSD type |

    Operating mode Settings | Other settings | Mode |

    Input filter Service | VSD | Settings | Inp. filter |

    Rotary switch Service | VSD | Settings | Rotary switch|

    motor type DEP configuration | motor type |

    motor nominal power, kW DEP configuration | Pnom.| |

    motor nominal current, A DEP configuration | Inom. |

    motor nominal voltage, V DEP configuration | Unom. |

    motor idle current, A, DEP configuration | Ixx|

    Nominal power factor of motor DEP configuration | motor settings| COSnom. |

    motor rotation speed Settings | Other settings | No. rpm |

    motor rotation direction Settings | Other settings | Rotation dir.|

    Step-up transformer nominal power, kVA Settings | nom. Step-up transformer, kVA|

    Primary voltage of Step-up transformer

    transformer, V

    Settings | Uprim.trans.,V |

    Voltage of Step-up transformer secondary

    winding tap, V1)

    Settings | Usec.trans.,V |

    Total voltage of motor and cable (Umotor +

    Ucab.)

    DEP configuration | motor settings| Umotor + Ucab. |

    - Procedure for calculation of the secondary winding tap of the Step-up transformer transformer

    is described in Appendix B.

  • TsRKF 656437.019 OM. 15

  • TsRKF 656437.019 OM. 16

    4.2 Description of the displayed parameters and operation modes of the system

    Detailed description of the parameters and operation modes of the submersible system, displayed

    on the LCD of the ARGUS controller.

    8.1 VSD equipment configuration

    ARGUS software is designed for controller operation with various types of VSD, LLC and

    motor.

    During manufacturing or service maintenance of VSD, settings and technical data sheet

    information is entered into its memory:

    - type, manufacturer (manufacturer's code), serial number, date of manufacture of VSD; - type, manufacturer, serial number, date of manufacture of ARGUS; - type, manufacturer, serial number, date of manufacture of LLC;

    Software data: version, LLC firmware installation date and version, generation date, date of

    ARGUS "protection" firmware installation in the appropriate software, this information is shown on

    display as parameters.

    When preparing the system for start, settings applicable to the specific configuration of the

    equipment is entered into ARGUS and LLC.

    8.1.1 VSD type is selected from the list:

    Borets VD80 Borets VD500 Borets VD105

    Borets VD40 Borets VD160 Borets15-400

    Borets VD250 Borets VD300

    Borets VD50

    8.1.2 LLC type is selected from the list:

    - Direct start - FC FCC controller or UFCC - Drivers controller - Rockwell - Smooth start

    8.1.3 motor type is selected from the list, which is determined by the selected VSD:

    Borets VD40 Borets VD50 Borets VD80 Borets VD250

    1VEDBT-117 1VEDBT-117 1VEDBT-117 1VEDBT-117

    2VEDBT-117 2VEDBT-117 2VEDBT-117 2VEDBT-117

    11VEDBT-103

    11VEDBT-103

    11VEDBT-103

    2VEDBT-117

    11VEDBT-130

    11VEDBT-130

    11VEDBT-130

    11VEDBT-103

    PVEDN-1170 PVEDN-1170 PVEDN-1170 11VEDBT-130

    5VEDBT-117 5VEDBT-117 5VEDBT-117 PVEDN-1170

    12VEDBT-117

    12VEDBT-117

    12VEDBT-117

    5VEDBT-117

  • TsRKF 656437.019 OM. 17

    12VEDBT-117

    Borets VD105 Borets VD160 Borets VD300 Borets VD500

    1VEDBT-117 1VEDBT-117 1VEDBT-117 1VEDBT-117

    2VEDBT-117 2VEDBT-117 2VEDBT-117 2VEDBT-117

    11VEDBT-103

    11VEDBT-103

    11VEDBT-103

    11VEDBT-103

    11VEDBT-130

    11VEDBT-130

    11VEDBT-130

    11VEDBT-130

    PVEDN-117 PVEDN-117 PVEDN-117 PVEDN-1170

    5VEDBT-117 5VEDBT-117 5VEDBT-117 5VEDBT-117

    12VEDBT-117

    12VEDBT-117

    12VEDBT-117

    12VEDBT-117

    Borets15-400

    motor

    The following motor technical data sheet settings are entered while preparing for startup:

    - type; - nominal power, nominal power factor (for induction motor only); - nominal current, nominal voltage, idle current.

    8.1.4 DHG type is selected from the list:

    DHG - none DHG SKAD DHG Elekton-3

    DHG SPT-2 DHG BST5 DHG TT37

    DHG SPT-1 DHG SPT1_25

    DHG Elekton DHG ViewPoint

    DHG BST1 DHG Novomet

    DHG Weatherford DHG IR-2

    Name plate data about manufacturer, date of manufacture, serial numbers of surface and

    submersible parts of DHG, sensors configurations, and technical data and data on design features and

    version of "protection" software in DHG software, these data may be shown on the display as parameters

    in accordance with the selected DHG type. These data are given in sufficient detail in the menu tables

    (see Appendix A and B).

    8.2 Mains parameters

    Description of parameters and related settings is given below

    8.2.1 Input voltage.

    Current value of the input voltage is changed in UFCC, transmitted via internal interface into

    ARGUS and shown on display as an average three phase linear voltage value Umains

    =(Uab+Ubc+Uac)/3.

    Mains voltage and frequency are selectable.

  • TsRKF 656437.019 OM. 18

    UFCC contains the parameters, and the following protection settings are entered to provide

    operation of protection functions depending on the mains voltage:

    - selection of the mains voltage and frequency 380 V /50 Hz or 480 V /60 Hz - hardware protection on exceeding the maximum linear voltage

    Umains max=542 V,

    - protection on exceeding the threshold 25% from the nominal value, - protection on reduction by more than 25% from the nominal value, - protection with variable threshold within 15% from the nominal.

    The following can also be entered:

    - protection operation mode, - delay time of switching on / tripping of the VSD after operation of protection, after startup or in

    case of alternative automatic restarting after power loss,

    - compensation factors of the measured voltage, (in UFCC correction is not provided, since precision is ensured by hardware).

    8.2.2 Input voltage imbalance.

    The following are entered as settings:

    - threshold value of imbalance in % from the nominal voltage, - operation mode of protection on exceeding the threshold, - switching on / tripping time after operation of protection.

    8.2.3 Phase sequence of mains voltage

    Monitoring of phase sequence is carried out in ARGUS using the signals from the phase

    sequence indication unit PSIU. Information about this parameter is relevant for VSD with smooth starter,

    during startup after maintenance and repair work

    8.2.4 Power consumption

    VSD versions, equipped with standard electric meters, all the mains parameters, including:

    - active power consumption, - power consumption, - power factor

    are transmitted from the meter to the ARGUS using internal interface RS485

    Meter type is selected from the list:

    SET Merkuriy Energomera

    8.3 VSD output voltage

    Current value of the output voltage is measured in UFCC and shown on the display.

    8.3.1 Procedure for VSD output voltage generation

    The procedure is selected in ARGUS menu, depending on the selected types of motor, VSD and

    LLC, from the following:

    - "6 step" commutation producing trapezoidal form of output voltage. The procedure is implemented in PMM VSD with UFCC. Adjustment of output voltage to control permanent magnet motor is

    carried out by PWM converter under control of UFCC in accordance with the voltage in DC buses or output

    current (depending on the setting or by automatic selection).

    - "Sine" and "Sine+" modulation of output voltage. The procedure is implemented in PMM VSD with UFCC. Adjustment of output voltage to control induction motor is carried out by PWM converter the

  • TsRKF 656437.019 OM. 19

    same as in 6-clock commutation. Software used for this procedure carries out continuous harmonic analysis

    of the output current (1, 5 and 7 harmonics), which is used to calculate motor consumption parameters.

    - "Sine PWM" modulation of output voltage. Implemented in PWM VSD with UFCC with built in output filter (VSD Borets-15-400). Adjustment of induction motor speed is carried out using output voltage

    or current.

    8.3.2 Current value of the output linear voltage

    8.3.2.1 In PMM VSD with UFCC with "6 step" commutation is calculated using the formula:

    Uuv=Uvw=Uwu=Udc*0.74,

    where: - Udc average voltage in the VSD direct current bus for the period,

    - 0.74 factor of the form of the linear output voltage.

    8.3.2.2 With "Sine" and "Sine+" commutation, the DC bus voltage is measured. Using the value

    measured during the period in 128 points, and the known PWM modulation factor, output voltage is

    calculated for the given point.

    8.3.2.3 With "Sine PWM" modulation, output voltage is calculated using the DC bus voltage

    with frequency of 45-50 kHz with account of the current PWM conversion factor.

    8.3.3 Output voltage protection settings:

    - linear output voltages Uuv,Uvw,Uwu; - hardware protection on exceeding voltage in DC buses Umax.dc=765 V, is implemented in

    UFCC.

    8.3.4 Output voltage imbalance

    The menu has the following settings

    - Selection of the operation mode for the output voltage imbalance protection, - output voltage imbalance protection threshold in % from the nominal value, - tripping and AR delay time in case of output voltage imbalance.

    8.4 Output current

    Current value of the VSD output current is measured in UFCC and shown on the display.

    Output current is measured using the signals from the current sensors, installed on the direct

    current bus and output buses.

    8.4.1 Current value of the output current

    8.4.1.1 In PMM VSD with UFCC with "6 clock" commutation is calculated using the formula:

    Iu=Iv=Iw=Idc*0.816,

    where: Idc current amplitude in the direct current loop, averaged for the commutation time of the

    measured current,

    0.816 factor of the output current form.

    8.4.1.2 With "Sine" and "Sine+" commutation, the current value of the output current is

    calculated using the formula:

    Iout=Iu (v,w)=SUM(In2/N)

    where: In instantaneous current,

    N=256 number of measurements per period.

    8.4.1.3 With "Sine PWM" modulation, the calculations are made using the formula in 0, with

    measurement rate of instantaneous output current of 45-50 kHz.

    8.4.2 Output current protection settings

  • TsRKF 656437.019 OM. 20

    - Hardware protection from exceeding the maximum allowed value of output phase current. Protection operates with Imax =(1,2 - 1,7) I nom, depending on VSD power.

    8.5 VSD output power

    VSD output power is calculated using the formula:

    out = 3*Uuv (vw, wu)*Iu (v,w)

    where: - Uuv (vw, wu) current value of the linear output voltage (8.3)

    - Iu (v,w) current value of output current (8.4),

    8.6 Step-up transformer parameters

    Menu contains the settings, corresponding to the technical data sheet value of Step-up

    transformer parameters:

    - apparent nominal power of Step-up transformer. - Step-up transformer primary voltage,

    and:

    - Step-up transformer secondary winding tap voltage, which is calculated or selected from the table with account of the cable length and nominal parameters of motor: voltage, current, power (Appendix B)

    8.7 Cable parameters

    8.7.1 Cable insulation resistance

    In the menu, the current parameters display the cable insulation resistance value Rins., which

    can be measured by VSD using two methods: VSD hardware or DHG equipment.

    8.7.2 Cable insulation resistance protection

    Condition menu displays the following Rins. protection functions:

    - reduction of Rins. down to minimum allowable value Rins. min=20-35 kOhm, - no calibration is carried out for the insulation resistance measurement channel in ARGUS, - failure of the current sensor Rins. in the submersible DHG unit.

    8.8 motor parameters

    8.8.1 motor phase current

    The displayed motor phase current is calculated using the following formula:

    Imot = Iout / avot

    where: Iout- VSD output current,

    avot = U2avot / U1avot multiplying transformation ratio of Step-up transformer.

    where: U1avot, U2avot voltages of the primary and the secondary Step-up transformer

    windings, correspondingly

    With "Sine" and "Sine +" commutation, Imot calculation accounts for losses in Step-up

    transformer and cable, which are calculated by the software on the basis of the corresponding technical

    data sheet data.

    Compensation factors settings for the measured voltage, (in UFCC correction is not provided,

    since precision is ensured by hardware).

    8.8.2 Motor current protection settings:

  • TsRKF 656437.019 OM. 21

    The menu provides for two types of motor current protections, which cause equipment

    breakdown: overload protection (OL) and underload protection (trip on underload UL). In case of motor

    overload, motor current exceed the maximum nominal current, which causes overheating of winding. In

    case of underload, motor current is below the nominal value, pump stops pumping the fluid, motor and

    pump are not cooled, which may lead to motor overheating, burning of cable, motor seal failure.

    The following settings are made for operation of the protection functions:

    - selection of the protection operation mode in case of overload (underload); - motor current value, determining the protection threshold, in % from the nominal current; - tripping delay time at overload (underload); - tripping delay time at overload (underload) after startup; - AR delay time at overload (underload); - number of AR on OL and UL.

    8.8.3 Motor currents imbalance

    The following protection settings are available in the menu:

    - motor current imbalance protection threshold in % from the nominal value, - selection of the operation mode for the motor current imbalance protection; - imbalance trip delay time; - imbalance trip delay time after startup; - AR delay time with motor current imbalance;

    8.8.4 motor operation modes

    Motor control in steady state mode implies maintenance of the set motor rotation speed No. rpm.

    Current value No. rpm is displayed

    The menu provides entry of the following rpm settings:

    - rotation speed setting number of rpm in the steady state mode, - acceleration time time required for motor to reach the set values of steady state mode, - Initial acceleration speed speed setting for normal acceleration, which is the starting point for

    reaching the steady state mode.

    - rotation direction symbol on display indicates the current forward or inverse phase sequence of the output voltage, which may be changed.

    8.8.5 motor load

    Motor "Load" parameters is displayed in the current mode and is calculated using the following

    formulae,

    8.8.5.1 In permanent magnet motor cos is taken equal to 1 and

    PMM load =(Imot / Imot.nom)*100 [%]

    where: Imot.nom. motor nominal current is entered using the setting from the technical data sheet

    (8.1.3),

    Imot. current value of the motor phase current (8.8).

    8.8.5.2 When controlling induction motor using "Sine" and "Sine +" procedures and "Sine

    PWM" modulation, load is calculated using the formula:

    motor load =(Imot* cos mot / Imot.nom* cos nom)*100 [%]

    where: cos nom =0.98 for motor nominal current.

    Imot with "Sine" and "Sine+", the current value is calculated with account of the 5th and the 7th

    harmonics, cos mot is calculated using the 1-st harmonics.

  • TsRKF 656437.019 OM. 22

    With "Sine PWM" modulation in PWM VSD with output filter, harmonic current components

    are negligible and are not accounted for

    8.8.5.3 In idle mode, load is determined as:

    Load min=(1.3*I*0.35/ Imot.nom)*100 [%]

    where: I motor idle current,

    1.3 factor, accounting for minimum mechanical load on motor shaft,

    0.35 cos with minimum mechanical load on motor shaft,

    8.9 Energy consumption parameters with load applied

    The following parameters are displayed:

    act.cons.=3*Iout*Uout*cos active power consumption,

    Fp= Imot 1 / Imot power factor,

    cons.=act.cons.* consumed active energy.

    where: out vsd

    Table 8.1 contains formulae for the implemented output voltage generation procedures

    Table 8.1. Formulae for calculation of energy parameters of ESP system

    Commutation method act.cons. Fp cons.

    "6 step"

    (PMM VSD, PMM

    motor)

    3*Iout*Uout

    close to 1 act.cons.*

    "Sine" and "Sine+" 3*Iout*Uout*cos Imot1 / Iout

    "Sine PWM" cos

    where: Iout,Uout see 8.3, 8.4,

    Imot1 -1-st current harmonic,

    8.10 DHG parameters

    8.10.1 Information

    The menu contains the following information:

    - DHG condition: "DHG failure" - SDHG technical data sheet, containing the information about the submersible unit - SurfDHG technical data sheet, containing information about the surface unit - DHG configuration, displaying TSM sensors configuration

    8.10.2 Current parameters

    The menu displays the following current parameters of DHG operation:

    - pressure at pump intake and discharge - vibration in three space axes - temperature at pump intake and discharge - motor winding temperature.

    8.10.3 DHG protection settings

    The following protection settings are entered in the menu:

    - selection of the protection operation mode (on|off); - protection on maximum and minimum pressure at the pump intake - protection on motor maximum winding temperature

  • TsRKF 656437.019 OM. 23

    - protection on minimum insulation resistance in the cable - delay time for tripping on operation of protection for allowable pressure, motor temperature,

    vibration,

    - delay time for AR on low pressure, motor winding temperature, allowable vibration.

    8.11 Adjustment settings

    Provisions are made for entry of settings, adjusting allowable changes of parameters when

    controlling the production process:

    - deviation of pressure from the set value - rpm increase, when adjusting rotation speed - time interval of adjustment - pressure change rate when performing pressure adjustment

    8.12 SCADA settings

    The following settings are made in the menu:

    - SCADA type from the list, suggested in the menu: 1. No SCADA

    2. SCADA Surgut NG N3

    3. SCADA Region - 2000

    4. GPRS modem

    5. SCADA MODBUS2

    6. SCADA MODBUS3

    7. SCADA Lukoil-3S

    - SCADA address in the telemetry system - data exchange rate 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 - switching on of recording in SCADA

    8.13 Service settings

    Service settings include the settings providing convenient operator's interface environment:

    - setting of the display parameters input language, brightness, contrast, - selection of units for parameters display pressure, frequency, temperature - selection of the menu type, - calibration corrections

    8.14 Additional inputs

    When using additional analog inputs, the following settings are made in the menu:

    - protections operation modes on signals from analog inputs, - delay time for protective trips and AR - maximum and minimum protection levels, - maximum and minimum physical signal levels for automatic setting of the appropriate

    measurement range,

    8.15 Operating technical data sheet

    Technical data sheet data for the well pad, well, cable for identification of information, read

    from ARGUS (see cl. 9)

    8.16 VSD operation time counters

    This group includes displayed information parameters indicating continuous operation of the

    system: number of VSD trips on protection operation, number of starts, total operating time and idle time.

  • TsRKF 656437.019 OM. 24

    8.17 Operating modes

    The settings for the following operating modes are entered in the ARGUS menu: "Startup",

    "Shutdown", "Acceleration and braking", "Jogging mode", "Startup with backspin", "Gas locks

    removal", "Stirring", "Maintenance of one of the set parameters", "Intelligent mode".

    8.17.1 Startup

    Operator's actions to startup the system are allowed only after the VSD and the controllers have

    reached the allowable temperature range (see cl.). The next step is selection of the menu type and entry

    of the settings required for the startup and normal operation in manual, automatic or program mode.

    Availability of settings depends on the selected equipment type.

    8.17.1.1 The algorithm for PMM startup by PMM VSD with "6 step" commutation is as follows.

    On STARTUP command, the PMM rotation condition diagnostics is carried out. If PMM is

    rotating in the direction reverse to the set direction, with the speed, exceeding the allowable for startup

    with backspin, it is prohibited to carry out the startup.

    If PMM is at a standstill, which is indicated by static condition of comparator unit of UFCC,

    which are used to determine the condition of PMM rotor rotation, voltage is generated at the VSD

    output, which with the set rate creates rotating magnetic field in the PMM (six positions per period) and

    the torque with the set current. PMM rotor is started from the initial position and accelerates to the set

    rotation speed

    If PMM did not start rotating during the time, set by the time current characteristic, which is

    possible at increased load, then the current is automatically, in 3-4 stages, increased until PMM starts

    rotating. Threshold value is limited with maximum current hardware protection, operation of which

    disables the startup mode.

    8.17.1.2 Induction motor startup algorithm with "Sine" and "Sine +" commutation is as follows.

    Starting torque of motor with this commutation type (PMM VSD, UFCC) is set by the initial

    voltage setting, which is changed by voltage / rotation speed ratio, and starting current. Current increase

    is monitored and limited in the same way as it is done for VSD startup.

    8.17.1.3 Induction motor startup algorithm with "Sine PWM" commutation is similar to that

    described for "Sine" and "Sine+" with the difference that, total acceleration time and maximum jamming

    time at the startup are set.

    8.17.2 Jogging mode

    Motor jogging startup mode (or "Unlock" mode for PMM) is used when the system is jammed.

    In this mode the startup is carried out by programmed reversing of rotation direction with the set torque.

    The following settings are made: jogging mode time, number of jogs, current protection values,

    phase sequence, parameters, setting the maximum jog current values. With "Sine PWM" commutation,

    the values of the prohibited frequency range are additionally entered.

    8.17.3 Acceleration and braking

  • TsRKF 656437.019 OM. 25

    To change the current rotation speed, operator enters new speed setting value and time for

    reaching the new value. VSD uses the entered value to generate time distributed sequence of rotation

    speed settings for LLC controller and monitors their observance.

    8.17.4 Startup with backspin

    Motor backspin may occur, when operating ESP system is tripped. Startup from the backspin

    condition is carried out when reverse rotation speed is decreased to the set minimum. This condition may

    arise either with complete draining of the fluid column above the pump or by braking motor backspin.

    PMM and motor braking techniques are different.

    PMM VSD when braking PMM, the energy generated by PMM is dissipated either in the

    connected braking resistors unit (in PMM VSD for cavity pumps) or in submersible cable (in PMM VSD

    for ESP pumps). The latter is implemented by short circuiting output phases of VSD using frequency

    converter keys. Monitoring of the startup condition occurrence is carried out by rotation speed or output

    current, accordingly. When startup conditions occurs, frequency and phase synchronization of the motor

    rotation speeds and commutation of output phases is carried out, the startup mode is then switched on.

    The settings specify the mode and the values of the rotation speed and startup current with backspin.

    With motor backspin, no energy is produced, and braking is carried out in rotation speed pickup

    mode with further switching over to the normal mode. The settings specify the mode and the values of

    the startup rotation speed with backspin.

    8.17.5 Gas locks removal

    When enabling UL protection (trip on underload), motor rotation speed increases by the set

    value and is maintained during the specified time. If during this time, UL condition persist, increased

    rpm remain constant, until UL protection operates. If UL conditions no longer exist, rpm is reduced to

    the initial value.

    The following settings are made for the mode:

    - Enabling of the mode, - rotation speed change value, - gas lock removal time

    8.17.6 Shaking

    "Shaking" mode is used to clean the motor from deposits by sudden decrease of its rotation

    speed with further recovery of the rotation speed. The following settings are made for the mode:

    - Enabling of the mode, - shaking intervals, - number of shakes, - two values of rotation speed change (can not exceed the value, specified by the setting) and the

    appropriate rates of the change.

    8.17.7 Maintenance of one of the parameters

    In this mode, the setting allows selecting one of the parameters, which is used for automatic

    control of:

  • TsRKF 656437.019 OM. 26

    - rotation speed, - pump intake pressure, - motor current, - in intelligent control mode.

    In rotation speed maintenance mode, automatic adjustment of output current and voltage of VSD

    are carried out, the current value of which is measured by LLC.

    In current maintenance mode, when it is increased or decreased due to load variations, motor

    rpm are automatically, accordingly, decreased or increased until the current reaches the set value. When

    this value is reached, motor returns to the reached speed. If rotation speed has reached the maximum,

    specified by the setting, and the current did not increase to the setting value, UL protection is triggered.

    Minimum rotation speed is set in pressure maintenance mode.

    Intellectual control mode implies entry of the settings for factors for static and dynamic

    parameter deviations during control, which are selected by operator or automatically per the specified

    criteria: prevention of underload, head maintenance, optimum power consumption, allowable load on

    motor etc. Changing of factors settings may be carried out without VSD tripping.

    Maintenance of the selected parameter is interrupted when acceleration and braking mode is

    enabled, or gas locks removal mode is required, until operation in these modes is completed.

    8.18 Protection settings

    The menu provides two types of protection operation modes settings: "On/Off" and

    "Off/Lock/AR", where:

    - Off protection disabled, - On" protection enabled, - AR protection enabled with restart of VSD specified number of times (from 1 to 5) after

    protection operation,

    - Lock interlocking of restart for protection functions, supporting AR mode. If protection is enabled, after its operation (with AR operation after the last startup) VSD

    startup is interlocked and in order to restart it, "Unlocking" command need to be entered.

    8.19 Commands

    "Test" command, the command allows testing indicator lamps and fan operation. When it is

    executed:

    - the controller successively displays indication symbols, - fan is switched on, - green, red and yellow lamps are successively switched on on the door.

    The test ends in a minute after it was started or by pressing the "Cancel" button.

    8.20 Event log (history)

    When this menu is selected, VSD operation events history may be viewed on the display.

    History limits are marked by the words: "Beginning of the history", "End of the history".

    8.21 USB stick

    This menu allows selecting commands for the operations with the USB stick.

    - Read history event log history is read.

  • TsRKF 656437.019 OM. 27

    - ARGUS programming, FCC programming using USB stick are selected to install ARGUS or FCC firmware version, accordingly.

    - Accept settings settings are read from the USB stick

    8.22 Condition of equipment

    Menu Condition of VSD, ARGUS, DHG contains the list of protections against electrical

    parameters exceeding the allowable limits (including those caused by the equipment malfunction).

    However, there are protections, which are related only to the units and elements, included in the VSD.

    This clause provides description of these protections, shown on the display. Possible protections

    operation reasons are provided.

    8.22.1 "Ipwm sens. fail." failure of PWM current sensor. PWM modulation circuit is used to

    change output voltage in PMM VSD. A current sensor is used in this circuit, readings of which are used

    for adjustments. Protection operates when the sensor, its power circuits are faulty or sensor's signal path is

    damaged.

    8.22.2 "THYR protection" failure of thyristors of power rectifier, TCB board, TCB power

    circuit. At that, if any thyristor module is not switched on when control command is sent, the appropriate

    LED indicator lights up on the TCB board.

    8.22.3 "SWB protection" failure of IGBT modules in the switchboard, PdRK driver board,

    short circuit of the switchboard power circuit. In case of short circuit in the power circuit or overload on

    PdRK board, the appropriate LED indicator lights up.

    8.22.4 "I GND Protection" operates when the difference between the VSD output currents

    exceeds 10% from the nominal current I nom. Protection operates in case of failure of any current sensors

    in output circuits of VSD, their power circuits, ground fault of any of the VSD output phases.

    8.22.5 "Overheat" protection operates, when the frequency converter heat sink temperature

    exceeds 95 according to the measurements of at least one of the two temperature sensors installed on the

    heat sink.

    8.22.6 "Temp. sens. 1 failure", "Temp. sens. 2 failure" multiple failure of temperature

    sensor 1 or 2, accordingly, of power circuits and signals paths of these sensors.

    8.22.7 "H. brige failure" failure of IGBT module in switchboard or short circuit in the

    switchboard power circuits. Registered, when "SWB protection" signal recurs (8.22.1)

    8.22.8 "Choke failure" short circuit of choke coil in PWM circuit, choke inductance loss,

    failure of UFCC board, Measuring resistors board in PMM VSD.

    8.22.9 "Phase break" main voltage phase break. Main voltage is measured by UFCC

    controller.

    8.22.10 "No protocol" no record of VSD parameters measurement is kept. Appears in case of

    record ROM failure in UFCC.

    8.22.11 "Comp. conf.error" FCC comparator unit condition failure. Appears during

    automatic testing of VSD before startup due to UFCC failure or when mains voltage range is exceeded.

    8.22.12 "motor conn. err." the output current value at VSD startup is not increased,

    approaches zero in the current parameters of current value. It means that load (motor) is not connected.

    8.22.13 "Rins. sens. failure" failure of insulation resistance measurement channel.

    Determined in VSD, if insulation resistance between any of the output phases and cable sheath is below

    the acceptable value (35 kOhm).

  • TsRKF 656437.019 OM. 28

    8.22.14 "Rins. cal. fail." VSD insulation resistance measurement channel was not calibrated.

    8.22.15 "Dig. FCC failure" failure of digital analog section of FCC controllers. Occurs when

    UFCC board is faulty, when digital devices on the board do not respond when they are addressed via

    internal I2C interface.

    8.22.16 "Analog FCC failure" failure of analog paths for normalization and conversion in

    UFCC board.

    8.22.17 "I2Cpot failure" no communication via I2C line in UFCC board with any of the

    integrated circuits of digital potentiometers.

    8.22.18 "FCC fault" restarting of FCC processors with 40 seconds interval, without

    determining its cause.

    8.22.19 "FC RS timeout" timeout on exchange line LLC and ARGUS longer than 8 minutes

    (PMM VSD and longer than 15 min in series 15 VSD)

    8.22.20 "LLC failure" fault in exchange between ARGUS and LLC in series 15 VSD.

    8.22.21 "Rect. RS failure" fault in exchange between ARGUS and SCADA.

    8.22.22 "WAFF failure" failure of VSD operation modes waffer type switch on the front

    door.

    8.22.23 "LCD failure" failure of ARGUS liquid crystal display. Occurs when connection with

    the LCD driver is lost.

  • TsRKF 656437.019 OM. 29

    9 Menu parameters list Table 9.1 contains the menu parameters list. Parameters format in column Menu item short name corresponds to that of LCD display; the number

    of symbols preceding the name stands for the number of jumps to the next menu level (from 1 to 4) before opening the list of parameters, settings and

    commands; symbol * is related to the protection setting with an option to select an operation mode (Off/Interlock/AR), and the settings given below in

    the list (up to the next asterisk) enable setting of the protection.

    Table 9.1.

    Menu item short name Parameter Measure

    ment unit Menu item full name

    Minimum

    value

    Maximum

    value

    Factory

    setting Reference

    9 0

    Speed Parameter Rpm/H

    z motor rotation speed 0 65535 0

    Nturb.,rpm Parameter rpm motor backspin speed 0 3500 0

    Rins.,kOhm Parameter kOhm Insulation resistance 0 65535 9999

    Imotor, Parameter A motor current 0 150 0

    Date Parameter Current date 01.01.2001 01.01.2001 01.01.2001

    U in,V Parameter V Linear network voltage 0 480 380

    Mode end time, min Parameter min Mode end time 0 65535 0

    Number of starts Parameter Number of starts 0 65535 0

    Load, % Parameter % motor load 0 65535 0

    P,kW Parameter kW Power consumption 0 65535 0 8.2.4

    motor run life, h Parameter h motor run life 0 65535 0

    W,MW`h Parameter MWh Power consumption 0 65535 0

    Software version Parameter ARGUS software version 1 99,99 1407

    Ainp.1 Parameter V Analog input 1 voltage 0 10 0

    Ainp.2 Parameter V Analog input 2 voltage 0 10 0

    I imbal., % Parameter % Current imbalance 0 100 0

    Uin. imbal., % Parameter % Network voltage imbalance 0 100 0

  • TsRKF 656437.019 OM. 30

    Uout. imbal., % Parameter % Output voltage imbalance 0 100 0

    UL number Parameter Number of UL shutdown time intervals 0 65535 0

    OL number Parameter Number of OL shutdown time intervals 0 65535 0

    Misc. protections number Parameter Number of miscellaneous protections shutdown time

    intervals 0 65535 0

    Startup run life, min Parameter min motor run life after the last startup 0 600000 0

    VSD run life, h Parameter h motor idle time 0 65535 0

    Ileak,mA Parameter mA Current leakage 0 99,999 0

    SS version Parameter SS version 0 65535 0

    ESP, m3/day Parameter m

    3/day ESP system capacity 0 65535 0

    os Parameter os 0 0.999 0.98

    Pi,atm Parameter atm Pump intake pressure 0 1000 0

    Pd.,atm Parameter atm Pump discharge pressure 0 999.99 0

    Tm,C Parameter C motor temperature -300 300 0

    Td, Parameter Pump discharge fluid temperature -32768 32768 0

    oil, Parameter Oil temperature -80 32000 0

    Ti, Parameter Pump intake fluid temperature -80 300 0

    Vibr. X,g Parameter g Vibration along axis X 0 99.99 0

    Vibr. XY,g Parameter g Root-mean-square vibration along axes X and Y 0 99.99 0

    Vibr. Y,g Parameter g Vibration along axis Y 0 99.99 0

    Vibr. Z,g Parameter g Vibration along axis Z 0 99.99 0

    Phase seq. Parameter Phase sequence /

    9.1 1

    9.1.1 1.1

    *OL Setting motor overload protection Off/Interlock/AR AR

    I OL, A Setting motor overload current 0 9999

    OL dl.t.trip,s Setting A motor overload delay time for tripping 0 120 20

    AR dl.t. OL, min Setting s motor overload AR delay time 0 3000 5

    OL AR number Setting min Number of OL AR 1 3000 5

    *UL Setting motor underloading protection switching on Off/Interlock/AR Off

    I UL, A Setting motor underloading motor current 0 9999

  • TsRKF 656437.019 OM. 31

    UL dl.t.trip,s Setting A motor underloading delay time for tripping 0 600 40

    AR dl.t. UL, min Setting s motor underloading AR delay time 0 3000 60

    UL AR number Setting min Number of UL AR 1 21 3

    *I imbal.pr. Setting Current imbalance protection Off/Interlock/AR AR

    I imbal.,% Setting Current imbalance 0 25 25

    I imbal.dl.t.trip, s Setting s Current imbalance delay time for tripping 0 60 5

    I imbal.AR dl.t., min Setting min Current imbalance AR delay time 0 300 5

    I imbal.dl.t., s Setting s

    Current imbalance delay time for tripping after

    motor start 0 3600 15

    OL dl.t., s Setting s Overload delay time for tripping after motor start 0 3600 5

    UL dl.t., s Setting s

    Underloading delay time for tripping after motor

    start 0 3600 5

    *GasLck removal Setting Gas locks removal mode Off/On Off

    dNgas,rpm Setting rpm motor rotation speed change value 50 500 100

    Ngas dl.t.,s Setting s motor high rotation speed keeping delay time 1 600 5

    9.1.2 1.2

    Umax dl.t.,s Setting s Umax protection delay time for tripping after start 0 3600 5

    *Umin prot. Setting Protection switching on at low network voltage Off/Interlock/AR AR

    Umin,% Setting % Minimum network voltage 0 100 75

    Umin dl.t.trip,s Setting s Umin protection delay time for tripping 0 60 5

    *Umax prot. Setting Protection switching on at high network voltage Off/Interlock/AR AR

    Umax, % Setting % Maximum network voltage 100 125 110

    Umax dl.t.trip,s Setting s Umax protection delay time for tripping 0 60 5

    *Uinp. imbal. prot. Setting Network voltage imbalance protection Off/Interlock/AR AR

    Uinp. imbal., % Setting % Network voltage imbalance 0 20 20

    Uinp.imbal.dl.t.trip,s Setting s Network U imbalance delay time for tripping 0 60 5

    *Uout. imbal. prot. Setting Output voltage imbalance protection Off/Interlock/AR AR

    Uout. imbal., % Setting % Output voltage imbalance 0 20 20

    Uout.imbal.dl.t.trip,s Setting s Uout. imbalance delay time for tripping 0 60 5

    Uout.imbal.AR dl.t., min Setting min AR delay time at Uout. imbalance 0 300 5

    Umin dl.t.,s Setting s Umin protection delay time for tripping after start 0 3600 15

    Uinp.imbal.dl.t.,s Setting s Network voltage imbalance delay time for 0 3600 5

  • TsRKF 656437.019 OM. 32

    tripping after start

    9.1.3 1.3

    Speed Setting

    Rpm/H

    z Rotation speed setting in rpm 250 4200 1000

    Accel. Time, min Setting min

    Time to reach preset rotation speed at

    acceleration 0 1000 0

    Rot.dir. Setting Rotation direction >>>

    Mode Setting Operating mode MAN/AUT MAN

    *Rins. prot. Setting Insulation resistance protection Off/On On

    Rins.min,kOhm Setting kOhm Insulation resistance setting 30 500 50

    *CPGP Setting Contact pressure gauge protection Off/Interlock/AR Off

    CPG dl.t.trip,s Setting s Contact pressure gauge delay time for tripping 0 999 0

    CPG AR dl.t., min Setting min

    AR delay time by a signal from the contact

    pressure gauge 0 300 60

    CPG dl.t.,s Setting s

    Contact pressure gauge delay time for tripping

    after start 0 999 15

    Misc. protections AR number Setting

    AR number at miscellaneous protections

    operation 0 9999 5

    AR zer.time, min Setting min Time to zero AR number meters 0 9999 5

    *PRG Setting Program mode enabling Off/On Off

    Oper. PRG, min Setting min Program operation time 1 9999 1

    Pause PRG, min Setting min Program operation pause 1 9999 1

    Sw on dl.t., min Setting min Alternative start time 1 60 1

    *D PROT. Setting Door protection Off/On On

    *Instab. prot. Setting Instability protection Off/Interlock/AR Off

    N init. accel.,rpm Setting rpm Initial rotation speed at controlled acceleration 500 4200 1500

    *Imax prot.overload. Setting Imax protection or PMM has not accelerated Interlock/AR AR

    AR dl.t. Imax,min Setting min Imax AR delay time and PMM has not

    accelerated 1 600 15

    AR number Imax Setting Imax AR number and PMM has not accelerated 0 25 5

  • TsRKF 656437.019 OM. 33

    *Backsp. prot. Setting Backspin protection Off/On On

    *Backsp.decel. Setting Backspin protection Off/On Off

    Ibacksp., Setting Start current at backspin below which start is

    permitted 0 24.99 0

    Nturb.,rpm Setting rpm

    Backspin rotation speed below which start is

    permitted 0 3000 0

    *Ext.lock. Setting External operation locking Off/On On

    Ctrl. Setting Control by I/by U by I

    dNstirr.,rpm Setting rpm Rotation speed change value at stirring 60 1800 500

    *Stirr. Setting Mode "Stirring" enabling Off/On Off

    Tstirr.,min Setting h Mode "Stirring" time 1 99 1

    Stirr.number Setting Number of stirrings 1 9 1

    F1stirr., Hz Setting Hz The first stirring frequency 30 200 50

    F2stirr., Hz Setting Hz The second stirring frequency 30 200 50

    V1stirr.,Hz/s Setting Hz/s The first stirring rotation speed 1 15 5

    V2stirr.,Hz/s Setting Hz/s The second stirring rotation speed 1 15 5

    9.1.4 1.4

    *Vibr.prot.,g Setting Vibration protection Off/Interlock/AR Off

    Vibr,g Setting g Maximum vibration 0 9999,00 0.1

    Vibr. dl.t.trip,s Setting s

    Delay time for tripping at too high maximum

    vibration 0 60 5

    Vibr. AR dl.t., min Setting min AR delay time at too high maximum vibration 0 300 60

    *motor prot. Setting Motor temperature protection Off/Interlock/AR Off

    Tmotor,C Setting C Maximum motor temperature 0 160 125

    motor dl.t.trip,s Setting s Delay time for tripping at maximum motor

    temperature 0 60 5

    motor AR dl.t., min Setting min AR delay time at maximum motor temperature 0 300 60

    *Pmin prot. Setting low pump intake pressure protection Off/Interlock/AR Off

    min,atm Setting atm Minimum pump intake pressure 0 299.99 40

    max,atm Setting atm Maximum pump intake pressure for startup 0 299.99 80

    Pmin dl.t.trip,s Setting s Delay time for tripping at minimum pressure 0 60 5

  • TsRKF 656437.019 OM. 34

    Pmin AR dl.t., min Setting min AR delay time at low pump intake pressure 0 3000 60

    Pmin dl.t.,s Setting s

    Delay time for tripping at minimum pressure after

    motor start 0 3600 5

    motorMin, C Setting C motor minimum temperature enabling startup 0 160 120

    Tmax dl.t.,s Setting s

    motor delay time for tripping at maximum motor

    temperature after motor start 0 3600 5

    Vibr.dl.t.,s Setting s Delay time for tripping at vibration after motor start 0 3600 5

    9.1.5 1.5

    *Uan.inp.1 prot. Setting Protection by a signal from analog input 1 Off/Interlock/AR Off

    An.inp.1max,% Setting V

    Maximum level of protection actuation by analog

    input 1 0 9999 0

    UAn.inp.1dl.t.trip,s Setting s Delay time for tripping by analog input 1 0 120 5

    UAn.inp.1 AR dl.t., min Setting min AR delay time for tripping by analog input 1 0 300 1

    UAn.inp.1 AR number Setting AR number by analog input 1 protection 0 9999 5

    UAn.inp.1 dl.t., s Setting s

    Delay time for tripping by analog input 1 after

    start 0 60 15

    *UAn.inp.2 prot. Setting Protection by a signal from analog input 2 Off/Interlock/AR Off

    An.inp.2max,% Setting V

    Maximum level of protection actuation by analog

    input 2 -9999 99999 0

    UAn.inp.2dl.t.trip,s Setting s Delay time for tripping by analog input 2 0 120 5

    UAn.inp.2 AR dl.t., min Setting min AR delay time for tripping by analog input 2 0 300 1

    UAn.inp.2 AR number Setting AR number by analog input 2 protection 0 9999 5

    UAn.inp.2 dl.t., s Setting s

    Delay time for tripping by analog input 2 after

    start 0 60 15

    An.inp.1min,% Setting %

    Minimum level of protection actuation by analog

    input 1 0 9999 0

    An.inp.2min,% Setting %

    Minimum level of protection actuation by analog

    input 2 0 9999 0

    An.inp.1nom Setting V Nominal level by analog input 1 0 9999 0

    An.inp.2nom Setting V Nominal level by analog input 2 0 9999 0

  • TsRKF 656437.019 OM. 35

    9.1.6 1.6

    *Adj. Setting Automatic adjustment enabling Parameters list

    by

    rotation

    speed

    See the

    item

    Ppump Adj.,atm Setting atm Required pump intake pressure 0 299.99 90

    Nmax adj., rpm Setting rpm motor maximum rotation speed at adjustment 500 4200 1500

    Nmin adj., rpm Setting rpm motor minimum rotation speed at adjustment 500 4200 1500

    Iadj., Setting Current in current adjustment mode 0 999.99 5

    9.2 2

    Electric meter Setting Electric meter availability Meter types list type

    See the

    item

    EFC availability Parameter External frequency converter availability No/Yes No

    SS availability Parameter Soft starter availability No/Yes No

    Radio channel Parameter Radio channel availability No/Yes No

    ESU availability Setting External sensor unit availability No/Yes No

    ?Polyans

    k

    An. input 1 Parameter Analog input 1 availability No/Yes No

    An. input 2 Parameter Analog input 2 availability No/Yes No

    Communications module Parameter Communications module No/Yes No

    CPG availability Setting Contact pressure gauge availability No/Yes No

    DHG type Parameter DHG type Current selection

    9.3 3

    Well No. Setting Well number 0 65535 0

    Well pad No. Setting Well pad number 1 65535 1

    Field No. Setting Field number 1 65535 1

    Lrunning, m Setting m Installation depth 0 9999 0

    Usec.trans.,V Setting V Transformer secondary winding voltage 380 5000 983

    Recording step, min Setting min Parameter recording step 0 9999 120

  • TsRKF 656437.019 OM. 36

    DHG Icons., mA Setting mA Leak current measured by Zenith type DHG 8 12 10

    Uprim.trans.,V Setting V Transformer primary winding voltage 380 700 380

    PnomStep-up transformer,

    kVA Setting kVA Step-up transformer transformer nominal power 0 2000 0

    Cross section, mm2 Setting mm

    2 Cable cross section 1 200 1

    9.4 Measurement units 3.1

    N meas. unit Setting motor rotation speed measurement units rpm/Hz rpm

    I meas.unit Setting Current protection measurement units / % %

    An.inp.meas. unit Setting Analog input protection measurement units V / % %

    P meas.unit Setting Pressure measurement units atm / psi / MPa atm

    T meas.unit Setting Temperature measurement units / F

    9.5 4

    Date Setting Current date 01.01.2001 01.01.2029

    Time Setting Current time 00:00:00 23:59:59

    Summer time/winter time Setting Daylight saving enabling Off/On Off

    9.6 Drive engineering package configuration 5

    VSD type Setting Variable speed drive controller type Types list

    See the

    item

    Motor type Setting Motor type Motors list

    See the

    item

    ESP, m3/day Setting m

    3/day ESP system capacity 0 2000 0

    ESP head, m Setting m ESP head 0 5000 0

    DHG type Setting DHG type DHG types list

    See the

    item

    Unom.,V Setting V motor nominal voltage 100 4000 380

    Inom., Setting motor nominal current 10 1500 18

    Pnom.,kW Setting kW motor nominal power 1 500 8

  • TsRKF 656437.019 OM. 37

    Iidle curr.,A Setting A Idle current 0 99.99 0.1

    9.6.1 Induction motor settings 5.1

    I1 off,% Setting % Ampere-second, cutoff current I1 characteristics 50 250 120

    T1off,s Setting s

    Ampere-second, delay time for tripping 1 characteristics 1 60 20

    I2 off,% Setting % Ampere-second, cutoff current I2 characteristics 50 250 150

    T2off,s Setting s

    Ampere-second, delay time for tripping 2 characteristics 1 60 4

    I3 off,% Setting % Ampere-second, cutoff current I3 characteristics 50 250 200

    T3off,s Setting s

    Ampere-second, delay time for tripping 3 characteristics 1 60 1

    Fnom.,Hz Setting Hz motor nominal frequency 50/60 50

    Umotor+Ucab.,V Setting V Umotor+Ucable,V 100 4000 380

    COSnom. Setting Power factor 0 1 0.82

    Istart,% Setting % Starting current level 50 350 100

    Tjamm.,s Setting s Maximum jamming time, s 1 20 5

    Ustart,% Setting % Starting voltage level 50 200 100

    Fstart,Hz Setting Hz motor start frequency 2 24 03

    *Jog Setting PMM start mode ?

    IFF/RIFF/Pfreq./Freq.

    /Off IFF see

    Tjog,s Setting s Jog mode time 1 20 10

    Jog numb. Setting Number of jogs 1 15 4

    accel.,s Setting s Acceleration time 5 125 30

    Decel. Setting s Deceleration time ? ? ?

    Uwaveform Setting Voltage waveform 6clock/Sin/Sin+ Sin+

    *Iaccel. Prot. Setting Current limiting in acceleration mode Off/On On

    motor Fnom.,Hz Setting Hz motor nominal frequency 0 200 50

    VSD Uinp., V

    Setting V VSD input voltage 1 500 380

    Pole pair numb. Setting Number of pole pairs 1 15 2

    Fproh.zone, Hz Setting Hz Prohibited zone frequency 3 100 30

  • TsRKF 656437.019 OM. 38

    Wproh.zone, Hz Setting Hz Prohibited zone width 0 6 0.1

    Pumping type Setting Power key modulation waveform

    sine/6clock/6clock+/tr

    apez. Sine

    Ustart,% Setting % Starting voltage level 70/80/90/100/105/112/120 70

    *Jog Setting motor start mode

    Common/direct/revers

    e/swing/push Common see

    F PWM, kHz Setting kHz PWM frequency 1 3 1

    Fnetwork,Hz Setting Hz Network frequency 50/60 50

    Fpickup Setting Initial frequency after power off 3 30 5

    *Netw. Prot.tripping Setting Protective tripping function Off/On Off

    Uswitch init., V Setting V Switchboard initial voltage 10 600 100

    Upulse, V Setting V Voltage ripple threshold on diode bridge 10 99 20

    Uswitch ref., V Setting V Switchboard reference voltage 0 500 200

    Phase seq. Setting Phase sequence /

    9.6.2 Soft starter settings 5.2

    SS mode Setting Soft starter operation mode 1 3 1

    Start.moment, % Setting % SS starting moment 2 99 2

    Accel.time, s Setting s SS acceleration time 1 30 2

    Boost, ms Setting ms SS boost, ms 2 200 20

    Jamm. time, s Setting s SS jamming 1 8 2

    Ijamm.,% Setting % Motor overloading by jamming 100 500 150

    Imax.start., % Setting % Maximum starting current 70 130 80

    9.6.3 Technical data sheet 5.3

    ARGUS No. Parameter ARGUS serial number 0 9999999 0

    ARGUS type Parameter Variable speed drive controller type 0 9999 0

    ARGUS manuf. Parameter ARGUS manufacturer's code 0 9999 2

    ARGUS date Parameter ARGUS date of manufacture 01.01.200 31.12.20 01.01.201

    VSD No. Parameter Variable speed drive serial number 0 9999999 0

  • TsRKF 656437.019 OM. 39

    VSD type Parameter VSD type as per the manufacturers classification 0 9999 0

    VSD manuf. Parameter VSD manufacturer's code 0 9999 2

    VSD date Parameter VSD date of manufacture 01.01.200 31.12.20 01.01.201

    Note Parameter Note 0 9999999

    9.6.4 DHG technical data sheet 5.4

    9.6.4.1 Information on DHG submersible part 5.5

    Vibr.max,g Parameter g Maximum vibration measured by DHG 0 99.99 0

    SDHG manuf. Parameter DHG submersible unit manufacturer's code Manufacturers list 2

    See the

    item

    SDHG date Parameter SDHG date of manufacture 01.01.2001 31.12.2029

    SDHG pr. No. Parameter

    DHG submersible part data exchange protocol

    number 1 255 0

    SDHG design Parameter DHG submersible part design type code 1 255 0

    SDHG software No. Parameter Software version for DHG submersible part 0 65535 0

    PpumpMax,atm Parameter atm

    Maximum pump intake pressure that can be

    measured by DHG 0 65535 0

    TmotorMax, C Parameter Maximum motor temperature that can be

    measured by DHG -32768 32768 0

    Tfluid Max, Parameter Maximum pump intake fluid temperature that can

    be measured by DHG -32768 32768 0

    SDHG No. Parameter DHG submersible part number 0 9999999 0

    9.6.4.2 Information on DHG surface part 5.6

    Pdisch.Max,atm Parameter atm Maximum pump discharge pressure 0 999.99 0

    ESPmax, m3/s Parameter m

    3/day

    Maximum ESP capacity, that can be measured by

    flow meter 0 65535 0

    ESPmin, m3/s Parameter m

    3/day

    Minimum ESP capacity, that can be measured by

    flow meter 0 65535 0

    SurfDHG manuf. Parameter DHG surface unit manufacturer's code 0 3 0 See the

  • TsRKF 656437.019 OM. 40

    item

    SurfDHG No. Parameter DHG surface part number 0 9999999 0

    SurfDHG date Parameter SurfDHG date of manufacture 01.01.2001 31.12.2029 ?

    SurfDHG pr. No. Parameter DHG surface part data exchange protocol number 1 255 0

    SurfDHG design Parameter DHG surface part design type code 1 255 0

    SurfDHG software No. Parameter Software version for DHG surface part 0 65535 0

    T bit, ms Parameter ms Single bit transmission period 0 65535 0

    meas. Rins.,s Parameter s Insulation resistance measurement time 0 65535 0

    T par. meas., ms Parameter ms DHG parameters measurement time 0 65535 0

    TmodeRins., ms Parameter ms

    Time to switch to insulation resistance

    measurement mode 0 65535 0

    Tfluid disch. Max, Parameter Maximum pump discharge fluid temperature that

    can be measured by DHG -32768 32768 0

    9.6.4.3 DHG sensors configuration 5.7

    Ppump sensor Parameter

    Availability of pressure sensor on the pump

    intake

    Tmotor sensor Parameter Availability of motor temperature sensor

    Tfluid pump sensor Parameter

    Availability of pump intake fluid temperature

    sensor

    Vibr. X sensor Parameter Availability of the sensor. Vibration along axis X

    Vibr. Y sensor Parameter Availability of the sensor. Vibration along axis Y

    Flow sensor Parameter Availability of the fluid flow sensor

    Pdisch. sensor Parameter

    Availability of the sensor The pump discharge

    pressure

    Tfluid pump discharge sensor Parameter

    Availability of the sensor. Pump intake/discharge

    fluid temperature

    Vibr. Z sensor Parameter Availability of the sensor. Vibration along axis Z

    Vibr. XY sensor Parameter

    Availability of the sensor. Root-mean-square

    vibration along axes X and Y

    Rins. sensor Parameter Availability of the insulation resistance sensor

  • TsRKF 656437.019 OM. 41

    Ileak sensor Parameter Availability of leak current sensor

    Toil sensor Parameter Availability of oil temperature sensor

    9.7 6

    Delete the history Command Delete the history

    Unlocking Command Unlocking

    Factory settings Command Factory settings restoration

    Test Command VSD test

    Meters reset Command All meters reset

    Phasing Command Testing phase sequence on VSD output

    Record Startup Command Record Startup

    Command Change password

    9.7.1 6.1

    Password 1 Setting Operator password 0 9999 0

    Password 2 Setting Engineer password 0 9999 0

    9.8 7

    Rins. Parameter kOhm Insulation resistance 0 9999

    Correction, kOhm Setting kOhm Rinsulation correction, kOhm 0 9999

    9.9 8

    SCADA type Setting SCADA type SCADA list

    See the

    item

    SCADA address Setting

    Variable speed drive address in the telemetry

    system SCADA address list 0

    See the

    item

    Baud-rate Setting baud Data exchange rate Rate list 4

    See the

    item

    Protocol # Setting Data exchange protocol number in the telemetry Protocols list 3 See the

  • TsRKF 656437.019 OM. 42

    system 255 item

    Recording from SCADA Setting Recording from SCADA Off/On On

    9.10 Language selection on LCD 9

    Russian Parameter Russian-language menu selection

    English Parameter English-language menu selection

    9.11 ARGUS LCD 10

    Brightness Setting Indicator brightness 0 255 70

    Contrast Setting Indicator contrast 0 255 100

    9.12 11

    9.12.1 Main readings of electric meter 11.1

    9.12.1.1 Electric meter data on current day 11.1.1

    Wa+d,kWA*h Parameter

    kWA*

    h

    Current day. Active energy. Conducting

    direction. 0 999999 0

    Wa-d,kWA*h Parameter

    kWA*

    h Current day. Active energy. Reverse. 0 999999 0

    W+d,kVr*h Parameter kVrA*

    h

    Current day. Reactive energy. Conducting

    direction. 0 999999 0

    W-d,kVr*h Parameter kVrA*

    h Current day. Reactive energy. Reverse. 0 999999 0

    9.12.1.2

  • TsRKF 656437.019 OM. 43

    Wa-pd,kWA*h Parameter

    kWA*

    h Previous day. Active energy. Reverse. 0 999999 0

    W+pd,kVr*h Parameter kVrA*

    h

    Previous day. Reactive energy. Conducting

    direction. 0 999999 0

    W-pd,kVr*h Parameter kVrA*

    h Previous day. Reactive energy. Reverse. 0 999999 0

    9.12.1.3 11.1.3

    Wa+m,MWA*h Parameter MWA*h

    Current month. Active energy. Conducting

    direction. 0 65535 0

    Wa-m,MWA*h Parameter MWA*h Current month. Active energy. Reverse. 0 65535 0

    W+m,MVr*h Parameter MVrA*h Current month. Reactive energy. Conducting

    direction. 0 65535 0

    W-m,MVr*h Parameter MVrA*h Current month. Reactive energy. Reverse. 0 65535 0

    9.12.1.4 11.1.4

    Wa+pm,MWA*h Parameter MWA*h

    Previous month. Active energy. Conducting

    direction. 0 65535 0

    Wa-pm,MWA*h Parameter MWA*h Previous month. Active energy. Reverse. 0 65535 0

    W+pm,MVr*h Parameter MVrA*h Previous month. Reactive energy. Conducting

    direction. 0 65535 0

    W-pm,MVr*h Parameter MVrA*h Previous month. Reactive energy. Reverse. 0 65535 0

    9.12.1.5 11.1.5

    Wa+y,MWA*h Parameter MWA*h

    Current year. Active energy. Conducting

    direction. 0 65535 0

    Wa-y,MWA*h Parameter MWA*h Current year. Active energy. Reverse. 0 65535 0

    W+y,MVr*h Parameter MVrA*h Current year. Reactive energy. Conducting

    direction. 0 65535 0

    W-y,MVr*h Parameter MVrA*h Current year. Reactive energy. Reverse. 0 65535 0

  • TsRKF 656437.019 OM. 44

    9.12.1.6 11.1.6

    Wa+py,MWA*h Parameter MWA*h

    Previous year. Active energy. Conducting

    direction. 0 65535 0

    Wa-py,MWA*h Parameter MWA*h Previous year. Active energy. Reverse. 0 65535 0

    W+py,MVr*h Parameter MVrA*h Previous year. Reactive energy. Conducting

    direction. 0 65535 0

    W-py,MVr*h Parameter MVrA*h Previous year. Reactive energy. Reverse. 0 65535 0

    9.12.1.7 11.1.7

    9.12.2 Electric meter quadrants 11.2

    9.12.2.1 Electric meter data on current day 11.2.1

    WdI,kVA*h Parameter kVA*h Current day. Reactive energy.

    Quadrant I. 0 0 0

    WdII,kVA*h Parameter kVA*h Current day. Reactive energy.

    Quadrant II. 0 0 0

    WdIII,kVA*h Parameter kVA*h Current day. Reactive energy.

    Quadrant III. 0 0 0

    WdIV,kVA*h Parameter kVA*h Current day. Reactive energy.

    Quadrant IV. 0 0 0

    9.12.2.2 Electric meter data on previous day 11.2.2

    WpdI,kVA*h Parameter kVA*h Previous day. Reactive energy. Quadrant I. 0 0 0

    WpdII,kVA*h Parameter kVA*h Previous day. Reactive energy. Quadrant II. 0 0 0

    WpdIII,kVA*h Parameter kVA*h Previous day. Reactive energy. Quadrant III. 0 0 0

    WpdIV,kVA*h Parameter kVA*h Previous day. Reactive energy. Quadrant IV. 0 0 0

    9.12.2.3 Electric meter data on current month 11.2.3

  • TsRKF 656437.019 OM. 45

    WmI,MVA*h Parameter MVA*

    h

    Current month. Reactive energy.

    Quadrant I. 0 600000 0

    WmII,MVA*h Parameter MVA*

    h

    Current month. Reactive energy.

    Quadrant II. 0 600000 0

    WmIII,MVA*h Parameter MVA*h Current month. Reactive energy.

    Quadrant III. 0 600000 0

    WmIV,MVA*h Parameter MVA*h Current month. Reactive energy.

    Quadrant IV. 0 600000 0

    9.12.2.4 Electric meter data on previous month 11.2.4

    WpmI,MVA*h Parameter MVA*h Previous month. Reactive energy. Quadrant I. 0 600000 0

    WpmIII,MVA*h Parameter MVA*h Previous month. Reactive energy. Quadrant II. 0 600000 0