McKee and Associates
Architecture and Interior Design Addendum
No. ONE Date: 09.10.18
631 South Hull Street – Montgomery, Alabama 36104 334-834-9933
Project: A NEW PRE-K BUILDING FOR BIG SPRING LAKE KINDERGARTEN SCHOOLFORTHE ALBERTVILLE CITY BOARD OF EDUCATIONALBERTVILLE, ALABAMA
PROJECT NO. 18-134
BC # 2018343
A1.1 GENERAL
A. The following changes and/or substitutions to the plans and specifications are hereby made a part of same and are incorporated in full force as part of the contract.
B. Bidders shall acknowledge receipt of this Addendum in writing on his Proposal Form.
C. Refer to the Advertisement for Bids, change as follows:
The sealed proposal shall be received by Dr. Boyd K. English, Superintendent, at The Albertville City Board of Education Board Room, located at 105 West Main Street, Albertville, Alabama until 2:00 PM, Tuesday, September 18, 2018, then opened and read aloud.
A1.2 SPECIFICATIONS
A. Refer to attached Section 08520 Aluminum Windows (FEMA), herein. This section is to replace original Section 08520 Aluminum Windows (Fixed Impact) in its entirety.
B. Refer to attached Section 08700, Finish Hardware, herein.
C. The following manufactures are hereby approved subject to the plans and specifications:
Section 13670 Extruded Aluminum Flat Canopy,Mitchell Metals, Smyrna, Georgia (770) 431-7305
Section 07411 Metal Wall Panels,Morin Corp., F-12 Concealed Fastener Series
631 South Hull Street – Montgomery, Alabama 36104 334-834-9933
A1.3 DRAWINGS
A. The following sheets are to be substituted into the drawings as follows:
Sheet C4 (dated 09-07-18)Sheet A1.1 (dated 09-07-18)Sheet A2.1 (dated 09-07-18)Sheet A5.1 (dated 09-07-18)Sheet A8.1 (dated 09-07-18)Sheet P1 (dated 09-07-18)Sheet M1 (dated 09-07-18)Sheet M2 (dated 09-07-18)Sheet E3.1 (dated 09-06-18)Sheet E4.1 (dated 09-06-18)
END OF ADDENDUM ONE
18-134 ALUMINUM WINDOWS 08520 - 1
SECTION 08520 - ALUMINUM WINDOWS (FEMA)
PART 1 – GENERAL
RELATED DOCUMENTS
Drawings and general provisions of Contract including General and Supplementary Conditions and Division 1 Specification sections apply to work of this section.
DESCRIPTION OF WORK
Extent of each type of aluminum window units including window column covers, panning trim, as shown on drawings.
QUALITY ASSURANCE
Standards: Except as otherwise indicated requirements for aluminum windows, terminology and standards of performance, and fabrication workmanship are those specified and recommended in ANSI/AAMA 101-85 and applicable general recommendations published by AAMA and AA. Where more stringent requirements are shown, manufacturer shall provide proof of compliance as required by the architect.
Performance and Testing:
General: Except as otherwise indicated, comply with air infiltration tests, water resistance tests, and applicable load tests specified in ANSI/AAMA 101-85 for type and classification of window units required in each case.
Prior Approval: Window manufacturers other than those specified requesting approval shall submit samples and test data ten days prior to bid opening for approval. Architect will list those approved manufacturers by addendum. No verbal approvals will be issued.
SUBMITTALS
Product Data: Submit manufacturer’s specifications, recommendations, and standard details for aluminum window units, including certified test laboratory reports as necessary to show compliance with requirements.
Shop Drawings: Submit shop drawings, including wall elevations at ¼” scale, typical unit elevations at ¾” scale and full size detail sections of every typical composite member. Show anchors, hardware, operators and other components not included in manufacturer’s standard data. Include glazing details.
18-134 ALUMINUM WINDOWS 08520 - 2
1. Architect reserves right to require additional samples which will show fabrication techniques, workmanship of component parts, and design of hardware and other exposed auxiliary items.
SPECIAL PROJECT WARRANTY
Submit written warranty signed by manufacturer, installer and contractor, agreeing to replace aluminum window units which fail in materials or workmanship within 3 years of date of acceptance. Failure of materials or workmanship shall include (but not be limited to) excessive leakage or air infiltration, excessive deflections, faulty operation of sash, deterioration of finish or metal in excess of normal weathering, and defects in hardware, weather-stripping and other components of work.
PART 2 – PRODUCTS
MATERIALS
Aluminum Extrusions: Alloy and temper recommended by window manufacturer for strength, corrosion resistance, and application of required finish, but not less than 22,000 psi ultimate tensile strength and not less than 0.062” thickness at any location for main frame and sash members. Comply with ASTM B 221.
Fasteners: Aluminum, non-magnetic stainless steel, or other materials warranted by manufacturer to be noncorrosive and compatible with aluminum window members, trim, hardware, anchors and other components of window units.
1. Reinforcement: Where fasteners screw-anchor into aluminum less than 0.125” thick, reinforce interior with aluminum or non-magnetic stainless steel to receive screw threads, or provide standard non-corrosive pressed in splined grommet nuts.
2. Do not use exposed fasteners except where unavoidable for application of hardware. Match finish of adjoining metal.
3. Provide Phillips flat-head machine screws for exposed fasteners.
Anchors, Clips and Window Accessories: Depending on strength and corrosion-inhibiting requirements, fabricate units of aluminum, non-magnetic stainless steel, or hot-dip zinc coated steel or iron complying with ASTM A 386.
Sealant: Unless otherwise indicated for sealants required within fabricated window units, provide type recommended by window manufacturer for joint size and movement, to remain permanently elastic, non-shrinking and non-migrating. Comply with Division 7 sections for installation of sealants.
18-134 ALUMINUM WINDOWS 08520 - 3
GENERAL: All aluminum windows shall be fixed type and shall conform to the Architectural Aluminum Manufacturer’s Association specification AAMA/WDMA/CSA 101/I.S.2/A440 requirements
All windows shall be of the type and size shown on the drawings. The following are approved manufacturers:
A. Acceptable Manufacturer: Winco Window Co., which is located at: 6200 Maple Ave. ; St. Louis, MO 63130-3305; Toll Free Tel: 800-525-8089;www.wincowindow.com
B. Requests for substitutions will be considered in accordance with provisions of Section 01600 and supply a complete window sample test data and other information deemed necessary by the owner and Architect.
MATERIALS:
A. Aluminum:1. Frame: Extruded aluminum, 6063-T6 alloy and temper, tensile
strength of 25,000 psi.2. Ventilator: Extruded tubular aluminum, 6063-T6 alloy and
temper, tensile strength of 25,000 psi.
B. Thermal Barrier:1. Poured-in-place structural thermal barrier shall transfer shear
during bending and provide composite action between frame components.
2. Thermal barrier pocket on aluminum extrusions shall be Azo-Braded to create a mechanical lock to improve the adhesion properties between the polyurethane polymer and the surface of the thermal barrier pocket.
3. Window manufacturer must provide a warranty from the manufacturer of the polyurethane thermal barrier that warrants against product failure as a result of thermal shrinkage beyond 1/8 inch (3.2 mm) from each end and fracturing of the polyurethane for a period not to exceed ten years from the date of window manufacture.
1.2 THERMAL FLUSH VENT PROJECTED/FIXED WINDOWS - WINCO 3350 SERIES
A. Acceptable Product:1. Winco 3350 Series: 3-1/2 inch Heavy Commercial Thermally
Improved Window.
B. Performance: AAMA/WDMA/CSA 101/I.S.2/A440.1. Architectural Window: AW-80.
18-134 ALUMINUM WINDOWS 08520 - 4
2. Water Resistance, ÅSTM E 331: 12 psf (575 Pa).3. Water Resistance, ÅSTM E 547: 12 psf (575 Pa) for AW rated
windows.4. Air Infiltration, ASTM E 283 at static air pressure of 6.24 psf:
0.05 cfm/sf.5. Uniform Load Structural Test, ASTM E 330: 120 psf (5748 Pa).6. Forced Entry Resistance, ASTM F 588: Grade 10.7. Condensation Resistance Factor (CRF), AAMA 1503.1:
a. Frame: 63.b. Glass: 66.
8. Thermal Performance (U= .25), AAMA 1503.1: 0.39 BTU/Hr-F°-Ft2.
9. Blast Resistant: Provide a complete blast resistant window assembly meeting UFC 4-010-01. Reference the Project Blast Load Table for specific Charge Weights and Standoff distances per elevation.
C. Ventilator and Access Sash:1. Vent Frame: Thermally broken.2. Vent and access panel shall be flush with exterior frame when
closed. Overlap sash is unacceptable.3. Wall Thickness: 0.125 inches (3.2 mm).4. Ventilator Depth: 3-5/16 inches (84 mm).5. Corners: Mitered and mechanically fastened with screws and
sealed.
HARDWARE
D. Hinged Sash Supports: Stainless steel four bar arms.
FINISH
E. Anodic Finish: All exposed areas of aluminum windows and components shall receive a two step finish: clear anodize components, then color coat with electrostatically deposited finish in accordance with Aluminum Association Designation AA-M12-C22-A, color as indicated.1. Color: To be selected by the Architect from the manufacturer’s
standard colors.
F. Paint Finish: Finish all exposed areas of aluminum windows and components with the following:1.70 percent Kynar in accordance with AA-M12-C42-R1X, AAMA
2605-982.50 percent Kynar in accordance with AA-M12-C42-R1X, and AAMA 2604-98.3. Color: To be selected by the Architect from the manufacturer’s
standard colors.
18-134 ALUMINUM WINDOWS 08520 - 5
GLAZING
G. Glazing Bead, for Tornado Resistant Windows:1. Window Series: Winco 3350 Series 3-1/2 inch Heavy
Commercial.a. Glazing Bead: 1-11/16 inch (43 mm) with screwed-in
glazing bead.
GLASS AND GLAZING: Provide factory glazed insulated glazing construction (1” nominal laminated insulated glass composed of (2) 3/16” heat strengthened glass on exterior – 5/16” air space – (1) 3/16” heat strengthened glass on the interior – ¼” air space – ½” polycarbonate on the interior) as indicated on the drawings, with exterior pane to be tempered Low E. Equal to Solarban 70XL (2)
OPTIGRAY + CLEAR, 47% Visible Trans, 8% Visible Reflect (Out), SHGC
0.24, U value 0.28. Glass shall be backbedded with an approved bedding compound and held securely in place with an extruded aluminum snap in glazing bead for easy replacement of broken glass. Wrap around or marine type glazing will not be permitted. Muttins shall be of vinyl shapes and shall be applied to the exterior face.
PART 3 – EXECUTION
Comply with manufacturer’s specifications and recommendations for installation of window units, hardware, operators, and other components of work.
Set units plumb, level and true to line, without warp or rack of frames or sash. Anchor securely in place. Separate aluminum and other corrodible surfaces from sources of corrosion or electrolytic action.
Set sill members and other members in bed of compound as shown, or with joint fillers or gaskets as shown, to provide weathertight construction. Refer to Division 7 sealant sections for compounds, fillers and gaskets to be installed with window units. Coordinate installation with wall flashings and other components of work.
ADJUST AND CLEAN
Adjust operating sash and hardware to provide tight fit at contact points and at weather-stripping, for smooth operation and weathertight closure.
Clean aluminum surfaces promptly after installation of windows, exercising are to avoid damage to protective coatings and finishes. Remove excess glazing and sealant compounds, dirt and other substances. Lubricate hardware and moving parts.
18-134 ALUMINUM WINDOWS 08520 - 6
Initiate and maintain all protection and other precautions required to ensure that window units will be without damage or deterioration (other than normal weathering) at time of acceptance.
END OF SECTION 08520
18-134 FINISH HARDWARE 08700-1(Revised 9.10.18)
SECTION 08700 – FINISH HARDWARE (Revised 9.10.18)
PART 1 - GENERAL
RELATED DOCUMENTS
Drawings and general provisions of Contract including General and Supplementary Conditions and Division 1 Specification Sections apply to this Section.
SUMMARY:
This Section includes items known commercially as finish or door hardware that are required for swing, sliding, and folding doors, except special types of unique hardware specified in the same sections as the doors and door frames on which they are installed.
A. Section Includes: Finish Hardware for door openings, except as otherwise specified herein.
1. Door hardware for steel (hollow metal) doors.2. Door hardware for aluminum doors.3. Door hardware for wood doors.4. Door hardware for other doors indicated.5. Keyed cylinders as indicated.
B. Related Sections:
1. Division 6: Rough Carpentry.2. Division 8: Aluminum Doors and Frames3. Division 8: Hollow Metal Doors and Frames.4. Division 8: Wood Doors.5. Division 26 Electrical
C. References: Comply with applicable requirements of the following standards. Where these standards conflict with other specific requirements, the most restrictive shall govern.
1. Builders Hardware Manufacturing Association (BHMA)2. NFPA 101 Life Safety Code3. NFPA 80 -Fire Doors and Windows4. ANSI-A156.xx- Various Performance Standards for Finish Hardware5. UL10C – Positive Pressure Fire Test of Door Assemblies6. ANSI-A117.1 – Accessible and Usable Buildings and Facilities7. DHI /ANSI A115.IG – Installation Guide for Doors and Hardware8. ICC – International Building Code
D. Intent of Hardware Groups
1. Should items of hardware not definitely specified be required for completion of the Work, furnish such items of type and quality comparable to adjacent hardware and appropriate for service required.
18-134 FINISH HARDWARE 08700-2(Revised 9.10.18)
2. Where items of hardware aren’t definitely or correctly specified, are required for completion of the Work, a written statement of such omission, error, or other discrepancy to be submitted to Architect, prior to date specified for receipt of bids for clarification by addendum; or, furnish such items in the type and quality established by this specification, and appropriate to the service intended.
E. Hardware Allowance:
Allowance of $1,800.00 for Certified AHC (Architectural Hardware Consultant) & FDAI (Fire Door Assembly Inspector – document of certification from DHI must be provided) to visit job site upon substantial completion as directed by Architect. A written report will be required for the Owner, Architect, and Contractor.
F. Door hardware supplier's responsibilities shall be as follows:
1. Submittals: Submit through Contractor required product data, final hardware schedule; separate keying schedule, and samples as specified in this Section, unless otherwise indicated.
2. Hardware Review Meeting: Hardware Supplier shall attend a scheduled “Hardware Review Meeting” with the Contractor, Owner and Architect representative. All Hardware products, hardware installation locations, finishes, color selections, ratings and keying is to be reviewed and discussed. The Hardware Supplier understands the Hardware Submittal is not deemed “Fully Approved” until the Owner has completed their review and given “Approval”.
3. Construction Schedule: Inform Contractor promptly of estimated times and dates that will be required to process submittals, to furnish templates, to deliver hardware, and to perform other work associated with furnishing door hardware for purposes of including this data in construction schedule. Comply with this schedule.
4. Coordination and Templates: Assist Contractor as required to coordinate hardware with other work in respect to both fabrication and installation. Furnish Contractor with templates and deliver hardware to proper locations.
5. Product Handling: Package, identify, deliver, and inventory door hardware specified in this Section.
6. Discrepancies: Based on requirements indicated in Contract Documents in effect at time of door hardware selection, furnish types, finishes, and quantities of door hardware, including fasteners, and Owner's maintenance tools required to comply with specified requirements and as needed to install and maintain hardware. Furnish or replace any items of door hardware resulting from shortages and incorrect items at no cost to the Owner or Contractor. Obtain signed receipts from Contractor for all delivered materials.
G. Contractor's responsibilities shall be as follows:
1. Submittals: Coordinate and process submittals for door hardware in same manner as submittals for other work.
18-134 FINISH HARDWARE 08700-3(Revised 9.10.18)
2. Hardware Review Meeting: Contractor is to schedule and attend a “Hardware Review Meeting” with the Owner, Hardware Supplier and Architect Representative. All Hardware products, hardware installation locations, finishes, color selections, ratings and keying is to be reviewed and discussed. The Contractor understands the Hardware Submittal is not deemed “Fully Approved” until the Owner has completed their review and given “Approval”.
3. Construction Schedule: Cooperate with door hardware supplier in establishing scheduled dates for submittals and delivery of templates and door hardware. Incorporate in construction schedule the times and dates related to furnishing hardware by door hardware supplier.
4. Coordination: Coordinate door hardware with other Work. Furnish hardware supplier or manufacturer with shop drawings of other work where required or requested. Verify completeness and suitability of hardware with supplier.
5. Product Handling: Provide secure lock-up for hardware delivered to the site. Inventory hardware jointly with representative of hardware supplier and issue signed receipts for all delivered materials.
6. Installation Information: The general types and approximate quantities of hardware required for this Project are indicated at the end of this Section in order to establish Contractor's costs for installation and other work not included in allowance.
7. No adjustments in Contract sum will be made for costs other than those covered by the allowances for subsequent increases or decreases in quantity of one or more hardware types that do not exceed 5 percent.
SUBMITTALS:
A. Submit the following in accordance with Conditions of Contract and Division 1 Specification sections.
B. Special Submittal Requirements: Combine submittals of this Section with Sections listed below to ensure the "design intent" of the system/assembly is understood and can be reviewed together.
C. Product Data: Manufacturer's specifications and technical data including the following:
1. Detailed specification of construction and fabrication.2. Manufacturer's installation instructions.3. Wiring diagrams for each electric product specified. Coordinate voltage with
electrical before submitting.4. Submit 6 copies of catalog cuts with hardware schedule. 5. Provide 9001-Quality Management and 14001-Environmental Management
for products listed in Materials Section 2.2
D. Shop Drawings - Hardware Schedule: Submit 6 complete reproducible copy of detailed hardware schedule in a vertical format.
18-134 FINISH HARDWARE 08700-4(Revised 9.10.18)
1. List groups and suffixes in proper sequence.2. Completely describe door and list architectural door number.3. Manufacturer, product name, and catalog number.4. Function, type, and style.5. Size and finish of each item.6. Mounting heights.7. Explanation of abbreviations and symbols used within schedule.8. Detailed wiring diagrams, specially developed for each opening, indicating all
electric hardware, security equipment and access control equipment, and door and frame rough-ins required for specific opening.
E. Templates: Submit templates and "reviewed Hardware Schedule" to door and frame supplier and others as applicable to enable proper and accurate sizing and locations of cutouts and reinforcing.
1. Templates, wiring diagrams and "reviewed Hardware Schedule" of electrical terms to electrical for coordination and verification of voltages and locations.
F. Samples: (If requested by the Owner/Architect)
1. 1 sample of Lever and Rose/Escutcheon design, (pair).2. 3 samples of metal finishes
G. Contract Closeout Submittals: Comply with Division 1 including specific requirements indicated.
1. Operating and maintenance manuals: Submit 3 sets containing the following.
a. Complete information in care, maintenance, and adjustment, and data on repair and replacement parts, and information on preservation of finishes.
b. Catalog pages for each product.c. Name, address, and phone number of local representative for each
manufacturer.d. Parts list for each product.
2. Copy of final hardware schedule, edited to reflect, "As installed". Final hardware schedule coordinated with doors, frames, and related work to ensure proper size, thickness, hand, function, and finish of door hardware.
3. Upon return of the reviewed finish hardware schedule, arrange for a meeting with the Owner and representatives of Architect. A keying schedule will be established and submitted to the Architect and Owner. After review, the keying schedule will be returned to representatives of Finish Hardware Supplier so that permanent cylinders and keys can be prepared on a timely basis.
4. Copy of final keying schedule5. As installed “Wiring Diagrams” for each piece of hardware connected to power,
both low voltage and 110 volts.6. One set of special tools required for maintenance and adjustment of hardware,
including changing of cylinders.
18-134 FINISH HARDWARE 08700-5(Revised 9.10.18)
QUALITY ASSURANCE
A. Comply with Division 1.
1. Statement of qualification for distributor and installers.2. Statement of compliance with regulatory requirements and single source
responsibility.3. Distributor's Qualifications: Firm with 3 years experience in the distribution of
commercial hardware.
a. Distributor to employ full time Architectural Hardware Consultants (AHC) for the purpose of scheduling and coordinating hardware and establishing keying schedule.
b. Hardware Schedule shall be prepared and signed by an AHC.
4. Installer's Qualifications: Firm with 3 years experienced in installation of similar hardware to that required for this Project, including specific requirements indicated.
5. Regulatory Label Requirements: Provide testing agency label or stamp on hardware for labeled openings.
a. Provide UL listed hardware for labeled and 20 minute openings in conformance with requirements for class of opening scheduled.
b. Underwriters Laboratories requirements have precedence over this specification where conflict exists.
6. Single Source Responsibility: Except where specified in hardware schedule, furnish products of only one manufacturer for each type of hardware.
B. Review Project for extent of finish hardware required to complete the Work. Where there is a conflict between these Specifications and the existing hardware, notify the Architect in writing and furnish hardware in compliance with the Specification unless otherwise directed in writing by the Architect.
C. Fire-Rated Openings: Provide door hardware for fire-rated openings that complies with NFPA Standard No. 80 and requirements of authorities having jurisdiction. Provide only items of door hardware that are listed and are identical to products tested by UL, Warnock Hersey, FM, or other testing and inspecting organization acceptable to authorities having jurisdiction for use on types and sizes of doors indicated in compliance with requirements of fire-rated door and door frame labels.
DELIVERY, STORAGE, AND HANDLING
A. Packing and Shipping: Comply with Division 1.
1. Deliver products in original unopened packaging with legible manufacturer's identification.
2. Package hardware to prevent damage during transit and storage.3. Mark hardware to correspond with "reviewed hardware schedule".4. Deliver hardware to door and frame manufacturer upon request.
18-134 FINISH HARDWARE 08700-6(Revised 9.10.18)
B. Storage and Protection: Comply with manufacturer's recommendations.
PROJECT CONDITIONS:
A. Coordinate hardware with other work. Furnish hardware items of proper design for use on doors and frames of the thickness, profile, swing, security and similar requirements indicated, as necessary for the proper installation and function, regardless of omissions or conflicts in the information on the Contract Documents.
B. Review Shop Drawings for doors and entrances to confirm that adequate provisions will be made for the proper installation of hardware.
WARRANTY:
A. Refer to Conditions of the Contract
B. Manufacturer’s Warranty:
1. Closers: Ten years2. Exit Devices: Five Years3. Locksets & Cylinders: Three years4. All other Hardware: Two years.
OWNER’S INSTRUCTION:
A. Instruct Owner’s personnel in operation and maintenance of hardware units.
MAINTENANCE:
A. Extra Service Materials: Deliver to Owner extra materials from same production run as products installed. Package products with protective covering and identify with descriptive labels. Comply with Division 1 Closeout Submittals Section.
1. Special Tools: Provide special wrenches and tools applicable to each different or special hardware component.
2. Maintenance Tools: Provide maintenance tools and accessories supplied by hardware component manufacturer.
3. Delivery, Storage and Protection: Comply with Owner’s requirements for delivery, storage and protection of extra service materials.
B. Maintenance Service: Submit for Owner’s consideration maintenance service agreement for electronic products installed.
18-134 FINISH HARDWARE 08700-7(Revised 9.10.18)
PART 2 - PRODUCTS
MANUFACTURERS:
A. The following manufacturers are approved subject to compliance with requirements of the Contract Documents. Approval of manufacturers other than those listed shall be in accordance with Division 1.
Item: Manufacturer: Approved:Hinges Stanley Bommer, H.B. IvesContinuous Hinges National Guard Stanley, SelectLocksets Best 45H Sargent, Cylinders Best 1E Sargent,Exit Devices Precision 2000 Von Duprin, SargentClosers Stanley D-4550 LCN 4040XP, Sargent 281Push/Pull Plates Trimco Burns, DonJo Protection Plates Trimco Burns, DonJo Overhead Stops ABH Rixson, Glynn JohnsonDoor Stops Trimco Burns, DonJoFlush Bolts Trimco Burns, DonJoCoordinator & Brackets Trimco Burns, DonJoThreshold & Gasketing National Guard Reese, Zero
MATERIALS:
A. Hinges: Shall be Five Knuckle Ball bearing hinges
1. Template screw hole locations2. Bearings are to be fully hardened. 3. Bearing shell is to be consistent shape with barrel. 4. Minimum of 2 permanently lubricated non-detachable bearings on standard
weight hinge and 4 permanently lubricated bearing on heavy weight hinges.5. Equip with easily seated, non-rising pins. 6. Non Removable Pin screws shall be slotted stainless steel screws.7. Hinges shall be full polished, front, back and barrel.8. Hinge pin is to be fully plated.9. Bearing assembly is to be installed after plating. 10. Sufficient size to allow 180-degree swing of door11. Furnish five knuckles with flush ball bearings12. Provide hinge type as listed in schedule.13. Furnish 3 hinges per leaf to 7 foot 6 inch height. Add one for each additional
30 inches in height or fraction thereof.14. Tested and approved by BHMA for all applicable ANSI Standards for type,
size, function and finish15. UL10C listed for Fire rated doors.
B. Geared Continuous Hinges:
1. Tested and approved by BHMA for ANSI A156.26-1996 Grade 1
18-134 FINISH HARDWARE 08700-8(Revised 9.10.18)
2. Anti-spinning through fastener3. UL10C listed for 3 hour Fire rating4. Non-handed5. Lifetime warranty6. Provide Fire Pins for 3-hour fire ratings7. Sufficient size to permit door to swing 180 degrees
C. Mortise Type Locks and Latches:
1. Tested and approved by BHMA for ANSI A156.13, Series 1000, Operational Grade 1, Extra-Heavy Duty, Security Grade 2 and be UL10C.
2. Furnish UL or recognized independent laboratory certified mechanical operational testing to 4 million cycles minimum.
3. Provide 9001-Quality Management and 14001-Environmental Management. 4. Fit ANSI A115.1 door preparation5. Functions and design as indicated in the hardware groups6. Solid, one-piece, 3/4-inch (19mm) throw, anti-friction latchbolt made of self-
lubricating stainless steel7. Deadbolt functions shall have 1 inch (25mm) throw bolt made of hardened
stainless steel8. Latchbolt and Deadbolt are to extend into the case a minimum of 3/8 inch
(9.5mm) when fully extended9. Auxiliary deadlatch to be made of one piece stainless steel, permanently
lubricated10. Provide sufficient curved strike lip to protect door trim11. Lever handles must be of forged or cast brass, bronze or stainless steel
construction and conform to ANSI A117.1. Levers that contain a hollow cavity are not acceptable
12. Lock shall have self-aligning, thru-bolted trim13. Levers to operate a roller bearing spindle hub mechanism14. Mortise cylinders of lock shall have a concealed internal setscrew for securing
the cylinder to the lockset. The internal setscrew will be accessible only by removing the core, with the control key, from the cylinder body.
15. Spindle to be designed to prevent forced entry from attacking of lever16. Provide locksets with 7-pin removable and interchangeable core cylinders17. Each lever to have independent spring mechanism controlling it18. Core face must be the same finish as the lockset.
D. Exit Devices:
1. Exit devices to meet or exceed BHMA for ANSI 156.3, Grade 1. 2. Exit devices to be tested and certified by UL or by a recognized independent
laboratory for mechanical operational testing to 10 million cycles minimum with inspection confirming Grade 1 Loaded Forces have been maintained.
3. Exit devices chassis to be investment cast steel, zinc dichromate.4. Exit devices to have stainless steel deadlocking ¾” through latch bolt.5. Exit devices to be equipped with sound dampening on touchbar. 6. Non-fire rated exit devices to have cylinder dogging.
18-134 FINISH HARDWARE 08700-9(Revised 9.10.18)
7. Non-fire rated exit devices to have ¼” minimum turn hex key dogging.8. Touchpad to be “T” style constructed of architectural metal with matching metal
end caps.9. Touch bar assembly on wide style exit devices to have a ¼” clearance to allow
for vision frames. 10. All exposed exit device components to be of architectural metals and “true”
architectural finishes.11. Provide strikes as required by application.12. Fire exit hardware to conform to UL10C and UBC 7-2. UL tested for Accident
Hazard.13. The strike is to be black powder coated finish.14. Exit devices to have field reversible handing.15. Provide heavy duty vandal resistant lever trim with heavy duty investment cast
stainless steel components and extra strength shock absorbing overload springs. Lever shall not require resetting. Lever design to match locksets and latchsets.
16. Provide 9001-Quality Management and 14001-Environmental Management.17. Vertical Latch Assemblies to have gravity operation, no springs.18. Approved Manufacturers
a. The following manufacturers will be approved contingent on meeting or exceeding the above performance criteria:1) PrecisionManufactured by Stanley Security Solutions
E. Door Closers shall:
1. Tested and approved by BHMA for ANSI 156.4, Grade 12. UL10C certified3. Provide 9001-Quality Management and 14001-Environmental Management. 4. Closer shall have extra-duty arms and knuckles5. Conform to ANSI 117.16. Maximum 2 7/16 inch case projection with non-ferrous cover7. Separate adjusting valves for closing and latching speed, and backcheck8. Provide adapter plates, shim spacers and blade stop spacers as required by
frame and door conditions9. Full rack and pinion type closer with 1½“ minimum bore10. Mount closers on non-public side of door, unless otherwise noted in
specification11. Closers shall be non-handed, non-sized and multi-sized.
F. Door Stops: Provide a dome floor or wall stop for every opening as listed in the hardware sets.
1. Wall stop and floor stop shall be wrought bronze, brass or stainless steel.2. Provide fastener suitable for wall construction.3. Coordinate reinforcement of walls where wall stop is specified. 4. Provide dome stops where wall stops are not practical. Provide spacers or
carpet riser for floor conditions encountered
18-134 FINISH HARDWARE 08700-10(Revised 9.10.18)
G. Over Head Stops: Provide a Surface mounted or concealed overhead when a floor or wall stop cannot be used or when listed in the hardware set.
1. Concealed overhead stops shall be heavy duty bronze or stainless steel.2. Surface overhead stops shall be heavy duty bronze or stainless steel.
H. Push Plates: Provide with four beveled edges ANSI J301, .050 thickness, size as indicated in hardware set. Furnish oval-head countersunk screws to match finish.
I. Pulls with plates: Provide with four beveled edges ANSI J301, .050 thickness Plate s with ANSI J401 Pull as listed in hardware set. Provide proper fasteners for door construction.
J. Kickplates: Provide with four beveled edges ANSI J102, 10 inches high by width less 2 inches on single doors and 1 inch on pairs of doors. Furnish oval-head countersunk screws to match finish.
K. Mop plates: Provide with four beveled edges ANSI J103, 4 inches high by width less 1 inch on single doors and 1 inch on pairs of doors. Furnish oval-head countersunk screws to match finish.
L. Door Bolts: Flush bolts for wood or metal doors.
1. Manual flush bolts, Certified ANSI/BHMA 156.16 at openings where allowed local authority.
2. Provide Dust Proof Strike, Certified ANSI/BHMA 156.16 at doors with flush bolts without thresholds.
M. Coordinator and Brackets: Provide a surface mounted coordinator when automatic bolts are used in the hardware set.
1. Coordinator, Certified ANSI/BHMA A1156.3 Type 21A for full width of the opening.
2. Provide mounting brackets for soffit applied hardware.3. Provide hardware preparation (cutouts) for latches as necessary.
N. Magnetic Door Holders: Provide magnetic door holders with Tri-Voltage that can be wired 12VDC, 24V AC/DC or 120V AC
1. Wall magnetic door holders shall be recessed.2. Armature shall be thru-bolted and can be provided with any projection
required.3. Models will be available in US28, sprayed finishes and US32D. 4 Floor mounted shall be provided for a single door or double door hold open
application.
O. Seals: All seals shall be finished to match adjacent frame color. Seals shall be furnished as listed in schedule. Material shall be UL listed for labeled openings.
18-134 FINISH HARDWARE 08700-11(Revised 9.10.18)
P. Provide one wall mounted Telkee, Lund or MMF series key cabinet complete with hooks, index and tags to accommodate 50% expansion. Coordinate mounting location with architect.
Q. Silencers: Furnish silencers on all interior frames, 3 for single doors, 2 for pairs. Omit where any type of seals occur.
FINISH:
A. Designations used in Schedule of Finish Hardware - 3.05, and elsewhere to indicate hardware finishes are those listed in ANSI/BHMA A156.18 including coordination with traditional U.S. finishes shown by certain manufacturers for their products
B. Powder coat door closers to match other hardware, unless otherwise noted.
C. Aluminum items shall be finished to match predominant adjacent material. Seals to coordinate with frame color.
2.2 KEYS AND KEYING:
A. Provide keyed brass construction cores and keys during the construction period. Construction control and operating keys and core shall not be part of the Owner's permanent keying system or furnished in the same keyway (or key section) as the Owner's permanent keying system. Permanent cores and keys (prepared according to the accepted keying schedule) will be furnished to the Owner.
B. Cylinders, removable and interchangeable core system: Existing Marshall Best Grand Master Key System.
C. Permanent keys and cores: Stamped with the applicable key mark for identification. These visual key control marks or codes will not include the actual key cuts. Permanent keys will also be stamped "Do Not Duplicate."
D. Transmit Grand Masterkeys, Masterkeys and other Security keys to Owner by Registered Mail, return receipt requested.
E. Furnish keys in the following quantities:
1. 1 each Grand Masterkeys2. 4 each Masterkeys3. 2 each Change keys each keyed core4. 15 each Construction masterkeys5. 1 each Control keys
F. The Owner, or the Owner's agent, will install permanent cores and return the construction cores to the Hardware Supplier. Construction cores and keys remain the property of the Hardware Supplier.
G. Keying Schedule: Arrange for a keying meeting, and programming meeting with Architect Owner and hardware supplier, and other involved parties to ensure
18-134 FINISH HARDWARE 08700-12(Revised 9.10.18)
locksets and locking hardware, are functionally correct and keying and programming complies with project requirements. Furnish 3 typed copies of keying and programming schedule to Architect.
PART 3 - EXECUTION
EXAMINATION
A. Verification of conditions: Examine doors, frames, related items and conditions under which Work is to be performed and identify conditions detrimental to proper and or timely completion.
1. Do not proceed until unsatisfactory conditions have been corrected.
HARDWARE LOCATIONS:
A. Mount hardware units at heights indicated in the following publications except as specifically indicated or required to comply with the governing regulations.
1. Recommended Locations for Builder’s Hardware for Standard Steel Doors and Frames, by the Door and Hardware Institute (DHI).
2. Recommended locations for Architectural Hardware for flush wood doors (DHI).
3. WDMA Industry Standard I.S.-1A-04, Industry Standard for Architectural wood flush doors.
INSTALLATION:
A. Install each hardware item per manufacturer's instructions and recommendations. Do not install surface mounted items until finishes have been completed on the substrate. Set units level, plumb and true to line and location. Adjust and reinforce the attachment substrate as necessary for proper installation and operation.
B. Conform to local governing agency security ordinance.
C. Install Conforming to ICC/ANSI A117.1 Accessible and Usable Building and Facilities.
1. Adjust door closer sweep periods so that from the open position of 70 degrees, the door will take at least 3 seconds to move to a point 3 inches from the latch, measured to the landing side of the door.
D. Installed hardware using the manufacturers fasteners provided. Drill and tap all screw holes located in metallic materials. Do not use “Riv-Nuts” or similar products.
18-134 FINISH HARDWARE 08700-13(Revised 9.10.18)
FIELD QUALITY CONTROL AND FINAL ADJUSTMENT
A. Contractor/Installers, Field Services: After installation is complete, contractor shall inspect the completed door openings on site to verify installation of hardware is complete and properly adjusted, in accordance with both the Contract Documents and final shop drawings.
1. Check and adjust closers to ensure proper operation.
2. Check latchset, lockset, and exit devices are properly installed and adjusted to ensure proper operation.
a. Verify levers are free from binding.b. Ensure latchbolts and dead bolts are engaged into strike and hardware
is functioning.
3. Report findings, in writing, to architect indicating that all hardware is installed and functioning properly. Include recommendations outlining corrective actions for improperly functioning hardware if required.
SCHEDULE OF FINISH HARDWARE:
Manufacturer List
Code NameAB ABH Manufacturing Inc.BE Best Access SystemsDM Dorma Door ControlsNA National GuardOT OthersPR PrecisionSD Stanley Door ClosersSECU SecuritechST StanleyTR Trimco
Option List
Code DescriptionCD CYLINDER DOGGINGFL Fire Exit HardwareLD Less DoggingSN Sex Nuts (Pkg. of 4)B4E BEVELED 4 EDGES - KICK PLATESCSK COUNTER SINKING OF KICK and MOP PLATESVIB Double Visual Indictor OptionS301 OPT. ROLLER. STRK - RIM AND TOP OF SVRCA-03 Cylinder Attachment Kit (Rim/SVR Device)SNB SEX BOLTS P45-180D Drop Plate for Narrow Top Rail
18-134 FINISH HARDWARE 08700-14(Revised 9.10.18)
Finish List
Code DescriptionAL Aluminum626 Satin Chromium Plated630 Satin Stainless Steel689 Aluminum PaintedBLACK BlackUS26D Chromium Plated, DullUS32D Stainless Steel, Dull
Hardware Sets
SET #01
Doors: A100, A104, A121
2 Continuous Hinge HD1400A x LAR NA1 Removable Mullion KR822 689 PR1 Exit Device-Storeroom 2103 CA-03 CD 630 PR1 Exit Device-Exit Only 2101 CD 630 PR2 Door Pull As selected by Architect OT1 Rim Cylinder 12E-72 PATD 626 BE2 Mortise Cylinder 1E-74 PATD 626 BE2 Door Closer CLD-4550 CS P45-180D SN 689 SD1 Perimeter Seals 5075 B x LAR NA1 Mullion Seal 5100N x LAR NA1 Door Sweep C627 A NA1 Handicap Threshold 513 x LAR AL NA
SET #02
Doors: A101
2 Continuous Hinge HD1400A x LAR NA1 Removable Mullion KR822 689 PR1 Exit Device-Exit Only 2101 CD 630 PR1 Exit Device-Storeroom 2103 X 4903D CD S301 SNB (2) 630 PR1 Rim Cylinder 12E-72 PATD 626 BE2 Mortise Cylinder 1E-74 PATD 626 BE2 Door Closer CLD-4550 CS P45-180D SN 689 SD1 Perimeter Seals 5075 B x LAR NA1 Mullion Seal 5100N x LAR NA
SET #03
Doors: A102A, A102B
3 Hinges FBB179 4 1/2 X 4 1/2 US26D ST1 Lockset-Intruder 45H-7IND14H PATD 630 BE1 Door Closer CLD-4550 STD W/PA BRKT SN 689 SD1 Kick Plate K0050 10" x LAR 630 TR1 Mop Plate KM050 6" x LAR 630 TR1 Perimeter Seals 5075 B x LAR NA
18-134 FINISH HARDWARE 08700-15(Revised 9.10.18)
SET #04
Doors: A103
3 Hinges FBB179 4 1/2 X 4 1/2 US26D ST1 Lockset-Intruder 45H-7IND14H PATD 630 BE1 Overhead Stop 1023 A US26D AB1 Mop Plate KM050 6" x LAR 630 TR1 Perimeter Seals 5075 B x LAR NA
SET #05
Doors: A105
3 Hinges FBB179 4 1/2 X 4 1/2 US26D ST1 Lockset-Intruder 45H-7IND14H PATD 630 BE1 Door Closer CLD-4550 STD W/PA BRKT SN 689 SD1 Kick Plate K0050 10" x LAR 630 TR1 Mop Plate KM050 6" x LAR 630 TR1 Wall Bumper 1270CV 626 TR1 Perimeter Seals 5075 B x LAR NA
SET #06
Doors: A125
3 Hinges FBB179 4 1/2 X 4 1/2 US26D ST1 Lockset 45H-7D14H PATD 630 BE1 Door Closer CLD-4550 STD W/PA BRKT SN 689 SD1 Kick Plate K0050 10" x LAR 630 TR1 Mop Plate KM050 6" x LAR 630 TR1 Wall Bumper 1270CV 626 TR1 Perimeter Seals 5075 B x LAR NA
SET #07
Doors: A107A, A111A
3 Hinges FBB168 4 1/2 X 4 1/2 US26D ST1 Multipoint Mortise Lock 5311-F13-IHD-HVL-F 630 SE1 Mortise Cylinder 1E-74 PATD 626 BE1 Door Closer CLD-4550 STD W/PA BRKT SN 689 SD1 Floor Stop & Holder 1224 626 TR1 Perimeter Seals 5075 B x LAR NA
NOTE: Electric magnetic hold-open to be wired to building fire panel and to release with notified from fire panel to allow the FEMA 361 Storm door to close. To secure the Storm door a facility member will need to manually throw the three point locking lockset to secure door.
18-134 FINISH HARDWARE 08700-16(Revised 9.10.18)
SET #08
Doors: A107B, A111B, A116, A117, A118, A119, A120
3 Hinges FBB179 4 1/2 X 4 1/2 US26D ST1 Lockset-Intruder 45H-7IND14H PATD 630 BE1 Door Closer CLD-4550 STD W/PA BRKT SN 689 SD1 Finger Guard 2248 A 82" NA1 Mop Plate KM050 6" x LAR 630 TR1 Kick Plate K0050 10" x LAR 630 TR1 Wall Bumper 1270CV 626 TR1 Perimeter Seals 5075 B x LAR NA
SET #09
Doors: A108A, A108B, A109A, A109B, A126
3 Hinges FBB179 4 1/2 X 4 1/2 US26D ST1 Privacy Set 45H-0L14H VIB 630 BE1 Finger Guard 2248 A 82" NA1 Kick Plate K0050 10" x LAR 630 TR1 Mop Plate KM050 6" x LAR 630 TR1 Wall Bumper 1270CV 626 TR1 Perimeter Seals 5075 B x LAR NA
SET #10
Doors: A110
3 Hinges FBB179 4 1/2 X 4 1/2 US26D ST1 Exit Device-Storeroom 2103 X 4903D CD S301 SNB (2) 630 PR1 Rim Cylinder 12E-72 PATD 626 BE1 Door Closer CLD-4550 CS SN 689 SD1 Kick Plate K0050 10" x LAR 630 TR1 Mop Plate KM050 6" x LAR 630 TR1 Perimeter Seals 5075 B x LAR NA
SET #11
Doors: A113B
6 Hinges FBB191 4 1/2 X 4 1/2 NRP US32D ST1 Removable Mullion KR822 689 PR1 Exit Device-Exit Only 2101 CD 630 PR1 Exit Device-Storeroom 2103 CA-03 CD 630 PR2 Door Pull As selected by Architect OT2 Rim Cylinder 12E-72 PATD 626 BE2 Mortise Cylinder 1E-74 PATD 626 BE2 Door Closer CLD-4550 CS SN 689 SD1 Perimeter Seals 5075 B x LAR NA1 Mullion Seal 5100N x LAR NA1 Door Sweep C627 A NA1 Handicap Threshold 513 x LAR AL NA
18-134 FINISH HARDWARE 08700-17(Revised 9.10.18)
SET #12
Doors: A113C
6 Hinges FBB191 4 1/2 X 4 1/2 NRP US32D ST1 Removable Mullion KR822 689 PR1 Rim Cylinder-Mullion 12E-72 PATD 626 BE1 Mullion Seal 5100N x LAR NA2 Exit Device-Exit Only 2101 LD 630 PR2 Door Closer CLD-4550 CS SN 689 SD1 Perimeter Seals 5075 B x LAR NA2 Door Sweep C627 A NA2 Kick Plate K0050 10" x LAR 630 TR1 Drip Cap 16 A x LAR NA1 Threshold 896 x LAR AL NA
SET #13
Doors: A113A
6 Hinges FBB179 4 1/2 X 4 1/2 US26D ST1 Removable Mullion FLKR822 689 PR1 Mullion Seal 5100N x LAR NA1 Exit Device-Intruder FL 2110 X V4908D S301 SNB (2) 630 PR1 Exit Device-Exit Only FL 2101 S301 SNB (6) 630 PR3 Rim Cylinder 12E-72 PATD 626 BE2 Door Closer CLD-4550 EDA SN 689 SD2 Mop Plate KM050 6" x LAR 630 TR2 Kick Plate K0050 10" x LAR 630 TR1 Perimeter Seals 5075 B x LAR NA2 Wall Bumper 1270CV 626 TR
SET #14
Doors: A114
6 Hinges FBB179 4 1/2 X 4 1/2 US26D ST1 Self-Latching Flushbolt 3820 x 12" 626 TR
NOTE: (Install at top of door)1 Flush Bolt 3917 x 12" 626 TR1 Lockset 45H-7D14H PATD 630 BE2 Mop Plate KM050 6" x LAR 630 TR2 Wall Bumper 1270CV 626 TR1 Dustproof Strike 3910 630 TR1 Perimeter Seals 5075 B x LAR NA1 Threshold 896 x LAR AL NA
18-134 FINISH HARDWARE 08700-18(Revised 9.10.18)
SET #15
Doors: A115
3 Hinges FBB191 4 1/2 X 4 1/2 NRP US32D ST1 Lockset-Storerm w/ Deadbolt 45H-7TD14H PATD 630 BE1 Door Closer CLD-4550 CS SN 689 SD1 Kick Plate K0050 10" x LAR 630 TR1 Door Sweep C627 A NA1 Perimeter Seals 5075 B x LAR NA1 Drip Cap 16 A x LAR NA1 Threshold 896 S x LAR AL NA
SET #16
Doors: A122, A123
3 Hinges FBB179 4 1/2 X 4 1/2 US26D ST1 Push Plate 1001-3 630 TR1 Pull Plate 1017-3C 630 TR1 Concealed Closer RTS/28 689 DM1 Finger Guard 2248 A 82" NA1 Mop Plate KM050 6" x LAR 630 TR1 Kick Plate K0050 10" x LAR 630 TR1 Perimeter Seals 5075 B x LAR NA
SET #17
Doors: A124
3 Hinges FBB179 4 1/2 X 4 1/2 US26D ST1 Set Auto Flush Bolts 3820 X 3810 626 TR1 Lockset 45H-7D14H PATD 630 BE1 Coordinator 3094B2 BLACK TR2 Door Closer CLD-4550 STD W/PA BRKT SN 689 SD1 Closer Mtg Bracket 3096 BLACK TR1 Mop Plate KM050 6" x LAR 630 TR1 Kick Plate K0050 10" x LAR 630 TR2 Wall Bumper 1270CV 626 TR1 Dustproof Strike 3910 630 TR1 Perimeter Seals 5075 B x LAR NA1 Astragal As supplied by Door Manufacturer BY
SET #18
Doors: A106
3 Hinges FBB179 4 1/2 X 4 1/2 US26D ST1 Lockset 45H-7D14H PATD 630 BE1 Wall Bumper 1270CV 626 TR1 Perimeter Seals 5075 B x LAR NA
18-134 FINISH HARDWARE 08700-19(Revised 9.10.18)
Opening List
Opening Hdw SetA100 01A101 02A102A 03A102B 03A103 04A104 01A105 05A106 18A107A 07A107B 08A108A 09A108B 09A109A 09A109B 09A110 10A111A 07A111B 08A113A 13A113B 11A113C 12A114 14A115 15A116 08A117 08A118 08A119 08A120 08A121 01A122 16A123 16A124 17A125 06A126 09
END OF SECTION 08700
A
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
W
W
W
W
W
W
REQUIRED
2" CLASS 200 PVC
WATER MAIN FOR
DOMESTIC
REQUIRED
1" COMPOUND
WATER METER
COORDINATE WITH MUB
REQUIRED:
1. COORDINATE UNDERGROUND
ELECTRIC SERVICE
WITH ELECTRICAL PLAN AND MUB
2. COORDINATE WATER TAPS
WITH MUB.
S
S
S
S
S
SS
S
S
S
S
REQUIRED
TIE TO EXISTING SEWER
SERVICE AT THIS LOCATION
REQUIRED:
4' TALL CHAIN-LINK FENCE
WITH 4' WIDE ACCESS GATE
FOR PLAYGROUND AREA
REQUIRED
8' SIDEWALK
WITH AWNING
SEE ARCHITECT
PLAN FOR DETAILS
REQUIRED
8' SIDEWALK
WITH AWNING
SEE ARCHITECT
PLAN FOR DETAILS
REQUIRED
5' AT-GRADE
SIDEWALK (TYP)
126.0'
43.0'
24.0'
24.0'
27.0'
19.0'
9.0'
R10.0'
R5.0'
R10.0'
R10.0'
R74.0'
WW
W
REQUIRED:
NEW PLAYGROUND AREA
SEE ARCH. SPEC
FOR SURFACE MATERIALS
REQUIRED
4" SDR 35
PVC SEWER LATERAL
@ 2.0% MIN. SLOPE WITH
CLEANOUT (TYP)
REQUIRED
HC PARKING &
RAMP (TYP)
REQUIRED
8' AT-GRADE
SIDEWALK (TYP)
REQUIRED
LIGHT DUTY
PAVING
REQUIRED
THERMOPLASTIC
STRIPING
(TYP)
REQUIRED
8' SIDEWALK
WITH AWNING
SEE ARCHITECT
PLAN FOR DETAILS
REQUIRED
8' SIDEWALK
WITH AWNING
SEE ARCHITECT
PLAN FOR DETAILS
APPROXIMATE SIGN LOCATION
SIGN PROVIDED BY OWNER
CONTRACTOR TO FURNISH 110V POWER
TO SIGN VIA UNDERGROUND CONDUIT
D
Y
H
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
REQUIRED
HYDRANT ASSEMBLY
REQUIRED
6" CLASS 200 PVC
(OPEN CUT AND PATCH PAVING)
REQUIRED
2" CLASS SCH. 40
(OPEN CUT AND PATCH PAVING)
SCALE : 1"= 20'
40'20'020'
NORTH R
EFERENCE: ALABAMA S
TATE
PLANE C
OORDIN
ATE S
YSTEM (EAST Z
ONE)
ELEVATIO
N R
EFERENCE: NAVD83
404 E. McKinney Ave. Albertville, AL 35950 Ph: (256) 878-6054
Olympia Design-Build, Inc. d.b.a. Olympia Engineering
18-134
8-31-18
SHEET TITLE : SITE & UTILITY PLAN
MCKEE JOB # :
DRAWN BY :
DATE:
SHEET NO. :
M c K
E
E
a
n
d
A
S
S
O
C
I A
T
E
S
A R
C
H
I T
E
C
T
U
R
E
a n
d
I N
T
E
R
I O
R
D
E
S
I G
N
63
1 S
OU
TH
H
UL
L S
TR
EE
T M
ON
TG
OM
ER
Y , A
LA
BA
MA
3
61
04
(3
34
) 8
34
-9
93
3
- F
riday, S
eptem
ber 7, 2018 11:49:18 A
M
- F
:\O
lym
pia D
esign-B
uild, Inc\D
ropbox (O
lym
pia)\O
lym
pia E
ngineering T
eam
F
older\2018\28_A
lbertville C
ity S
chools-B
SLK
H
eadstart\B
AS
E.dw
g
JRP
REVISED DATE:
REVISED DATE:
REVISED DATE:
A N
ew
P
re-K
B
uilding
FO
R
BIG
S
PR
IN
G LA
KE
K
IN
DE
RG
AR
TE
N S
CH
OO
L
FO
R T
HE
ALB
ER
TV
ILLE
C
IT
Y B
OA
RD
of E
DU
CA
TIO
N
ALB
ER
TV
ILLE
, A
LA
BA
MA
C4
REQUIRED SODDING
9-7-18
1"3"WATER CLOSETP1 FL. MTD. - REG.
MOP BASINP7
ADA WATER CLOSET
ADA LAVATORY
LAVATORY
ADA URINAL
URINAL
P8 SPLIT LEVEL EWC
P6
P5
P4
P2
P3WALL HUNG - REG.
WALL HUNG - ADA
1/2"3" 1/2"FL. MTD. CORNER TYPE
1/2"
1/2"
1 1/2"
1 1/4"
1/2"
1/2"
1 1/4"
2"
3"
2" 3/4"
1/2"
3/4"
1"
WALL HUNG - HIGH/LOW
WALL HUNG - ADA
FL. MTD. - ADA
WALL HUNG - REG.
PLUMBING FIXTURE SCHEDULE
FIXTURE NO. H.W.WASTE C.W. REMARKS
**
**
**
PROVIDE A WATER TEMPERATURE LIMITING DEVICE EQUAL TO
SYMMONS #5-210-CK (ASSE STD. 1070) WITH 1/2" TEMPERED
WATER LINE TO FAUCET.
SINKP9
1/2"1 1/2" 1/2"
1-COMP. MTD. IN COUNTER
FACE OF SHORT SIDE OF STALL TO FINISHED WALL.
WALL TO CENTERLINE OF WATER CLOSET. MEASURE FROM
10. ROUGH HANDICAP WATER CLOSET 18" FROM FINISHED
AREA TO MEET A.D.A. REQUIREMENTS.
SHALL BE LOCATED ON WIDE SIDE OF TOILET STALL
9. FLUSH VALVE HANDLE FOR HANDICAP WATER CLOSET
8. H/C - HANDICAP - FIXTURES AND INSTALLATION
SHALL MEET AMERICANS WITH DISABILITIES ACT
VENTS TO HVAC FRESH AIR (OUTSIDE AIR) INTAKES.
7. MAINTAIN MIN. OF 10 LINEAR FEET FROM PLUMBING
(A.D.A.) REQUIREMENTS.
FOR EACH FLOOR DRAIN AND HUB DRAIN.
2. PROVIDE A DEEP SEAL P-TRAP
CODE. (GENERALLY MIN. 3 FEET).
CLEARANCE AS REQUIRED BY THE NATIONAL ELECTRICAL
TRANSFORMERS, PANELS AND EQUIPMENT. MAINTAIN
CONTRACTOR. DO NOT RUN PIPING OVER ELECTRICAL
5. COORDINATE ALL PIPING RUNS WITH THE ELECTRICAL
3. PROVIDE A VACUUM BREAKER FOR EACH
4. RUN ALL WATER PIPING WITHIN BUILDING
6. ALL WASTE AND VENT PIPING INSIDE RETURN
AIR PLENUM SPACES SHALL BE CAST IRON PIPE
AND FITTINGS AS SPECIFIED.
INSULATION ENVELOPE.
WALL HYDRANT AND HOSE BIBB.
N O T E S
SO THAT THE FLUSH TUBE IS VERTICALLY STRAIGHT.
1. ROUGH WATER CLOSET AND URINAL FLUSH VALVE
PLUMBING CODE AND SPECS..
NEAR THE BASE OF EACH WASTE AND VENT STACK PER
11. PROVIDE A READILY ACCESSIBLE CLEANOUT AT OR
TO MEET DESIGNED WATER PRESSURE.
PROVIDE WATER PRESSURE REDUCING VALVE, IF REQUIRED
TO VERIFY THAT THE PRESSURE IS WITHIN THOSE LIMITS.
PRESSURE OF 50 TO 75 PSI. GAUGE CITY WATER SUPPLY
12. WATER SUPPLY SYSTEM IS DESIGNED FOR STATIC
F.S. FLOOR SINK
B.V. BALL VALVE
G.V. GATE VALVE
W.H. WALL HYDRANT
HOT WTR. PIPE (125°)
BALL VALVE
L E G E N D
WASTE PIPE
VENT PIPE
COLD WATER PIPE
UNION
GATE VALVE
CHECK VALVE
H.D.
F.D.
C.O.
HUB DRAIN
FLOOR DRAIN
CLEANOUT
FLOOR CLEANOUT
FCO
ROOF DRAIN
DOWNSPOUT
D.S.
R.D.
HOT WTR. RECIRC. PIPE
INDICATES POINT OF
CONNECTION TO OUTSIDE
UTILITY. SEE CIVIL DWGS..
EXISTING
CONNECTION TO
INDICATES POINT OF
ACID RESIST. WASTE PIPE
ACID RESIST. VENT PIPE
AR
AR
GAS PIPE
STORM WATER PIPE
G
S
HANDICAPPED
H/C
C.I. CAST IRON
PIPINGPIPE INSULATION
WHERE SPECIFIED
THREADED ROD
SUSPEND FROM
STRUCTURE
WHERE REQUIRED
PIPE INSULATION
NO SCALE
SPECS
SHIELD. SEE
PROTECTIVE
PIPING
STRUCTURE
SUSPEND FROM
THREADED ROD
UNISTRUT
SEE SPECS. FOR
SPACING OF HANGERS.
PROVIDE PIPE
CLAMP AT EACH
STRUT - SIZE TO
FIT OVER PIPE
INSULATION
TYP. PIPE HANGER DETAIL
NO SCALE
TYP. PIPE HANGER DETAIL
PROTECTIVE SHIELD -
PIPING OVER 1 1/4"
REQUIRES INTEGRAL
SHIELD - SEE SPECS
PAINTED, POWDER
COATED OR OTHER
25/50 COMPLIANT
COATING AS
SPECIFIED
TYP. EXTERIOR CLEANOUT DETAIL
NO SCALE
WASTE PIPING
EXTERIOR CLEANOUT
CLEANOUT PLUG
FINISHED GRADE
PROVIDE TWO-WAY
CLEANOUT WHERE
REQUIRED.
TERMINATE W/
CLEANOUT PLUG
AT END OF RUN.
EXTERIOR CLEANOUT
COVER & FRAME.
6"THICK CONC.
PAD OR EXTERIOR
SLAB.
TYP. FLOOR CLEANOUT DETAIL
NO SCALE
SCORIATED TOP.
ADJUSTABLE BRONZE
AT END OF
CLEANOUT PLUG
TERMINATE W/
RUN.
WASTE PIPING
FLOOR CLEANOUT
FINISHED FLOOR
UNION TO FACILITATE ITS REMOVAL.
13. PROVIDE A BALL VALVE ON EACH SIDE OF EVERY DIELECTRIC
WATER PRESSURE REDUCING
VALVE - SET OUTLET PRESS AT
70 PSI MAY BE OMITTED IF WATER
PRESSURE IS BELOW 80 PSI
2" BELOW GRADE
2"
NOTE 1:
EXTEND 2" DOM. WATER LINE SERVING NON-STORM SHELTER AREAS OF THE
BUILDING DN. TO ADA HEIGHT A.F.F. WITH READY ACCESSIBLE BALL VALVE.
PROVIDE SIGN STATING THE FOLLOWING "CLOSE THIS VALVE IN THE EVENT
OF A TORNADO".
2" TO FIXTURES IN
STORM SHELTER
2" TO NON-STORM
SHELTER AREAS
C.W. LINE
WATER HEATER DETAIL
NO SCALE
VALVE W/COPPER
208V,1PH,60HZ.
4.5 KW HTG. ELEM.
30.0 GAL. STOR.
SUPPORT BY G.C..
WATER HEATER
BALL
VALVE
TO AUX. DRAIN
OVERFLOW LINE
PAN.
WALL
H.W. LINE
UNION
T.&P. RELIEF
BREAKER
VACUUM
AUX. DRAIN PAN W/
COPPER DR. LINE TO
MOP BASIN.
THERMOMETER
3/4"
3/4"
SEE ARCH. DETAIL.
WATER
HEATER
3 GAL. THERMAL
EXPANSION TANK
PROVIDE SUPPORT-SEE SPECS
CHECK
VALVE
3/4"
WTR. HTR. SCHED. WH-1
NEOPRENE PAD.
2"x2"x1" THICK
(4) REQ'D..
CIRC.
PUMP
STRAP-ON
AQUASTAT
RECIRC.
H.W.
WALL MTD.
PROGRAM
CLOCK
2"
4
"
WASTE RISER R-1
P
9
C
O
C
O
P
8
P
9
P
2
P
1
C
O
P
6
P
5
C
O
P
5
C
O
C
O
P
5
C
O
P
5
P
1
P
6
C
O
P
1
P
1
P
2
S
E
E
W
A
S
T
E
R
I
S
E
R
R
-
1
F
O
R
C
O
N
T
I
N
U
A
T
I
O
N
S
E
E
W
A
S
T
E
R
I
S
E
R
R
-
3
F
O
R
C
O
N
T
I
N
U
A
T
I
O
N
P
9
C
O
P
9
C
O
P
9
P
7
2
"
H
U
B
D
R
A
I
N
W
/
T
R
A
P
P
R
I
M
E
R
4
"
4
"
4
"
3
"
4
"
2
"
2
"
2
"
4
"
V
S
T
R
2
"
V
S
2
"
V
S
2
"
V
S
2
"
2
"
2
"
3
"
3
"
2
"
2
"
V
S
3
"
S
E
E
W
A
S
T
E
R
I
S
E
R
R
-
1
F
O
R
C
O
N
T
I
N
U
A
T
I
O
N
WASTE RISER R-2
P
3
C
O
P
4
C
O
3
"
3
"
2
"
4
"
4
"
4
"
4
"
2
"
2
"
2
"
2
"
3
"
V
S
T
R
2
"
V
S
2
"
V
S
2
"
V
S
2
"
V
S
2
"
V
S
2
"
2
"
3
"
2
"
2
"
WASTE RISER R-3
C
O
P
6
P
2
C
O
P
6
P
2
4
"
4
"
2
"
3
"
3
"
3
"
3
"
C
O
P
9
S
E
E
W
A
S
T
E
R
I
S
E
R
R
-
2
F
O
R
C
O
N
T
I
N
U
A
T
I
O
N
4
"
C
O
P
9
2
"
2
"
C
O
P
8
4
"
2
"
2
"
H
U
B
D
R
A
I
N
W
/
T
R
A
P
P
R
I
M
E
R
S
E
E
W
A
S
T
E
R
I
S
E
R
R
-
2
F
O
R
C
O
N
T
I
N
U
A
T
I
O
N
3
"
V
S
T
R
2
"
V
S
2
"
V
S
2
"
V
S
2
"
V
S
2
"
V
S
2
"
V
S
2
"
2
"
2
"
2
"
E
X
T
E
N
D
2
"
V
E
N
T
P
I
P
I
N
G
T
O
F
I
X
P
8
4
"
3
"
F
D
F
D
3
"
4
"
3
"
P
6
C
O
P
2
3
"
2
"
V
S
LOCATE BALL VALVE
AT ADA HEIGHT W/
ACCESS & SIGNAGE
REVISED
09-07-18
18-134
08-31-18
SHEET TITLE :
MCKEE JOB # :
CHECKED BY :
DATE:
SHEET NO. :
M c K
E
E
a
n
d
A
S
S
O
C
I A
T
E
S
A R
C
H
I T
E
C
T
U
R
E
a
n
d
I N
T
E
R
I O
R
D
E
S
I G
N
63
1 S
OU
TH
H
UL
L S
TR
EE
T M
ON
TG
OM
ER
Y , A
LA
BA
MA
3
61
04
(3
34
) 8
34
-9
93
3
- F
riday, S
eptem
ber 07, 2018 10:01:53 A
M
- Z
:\M
ckee\18-213 B
ig S
pring Lake P
re-K
\H
VA
C &
P
LB
G P
lans.dw
g
REVISED DATE:
REVISED DATE:
REVISED DATE:
A N
ew
P
re-K
B
uilding
FO
R
BIG
S
PR
IN
G LA
KE
K
IN
DE
RG
AR
TE
N S
CH
OO
L
FO
R T
HE
ALB
ER
TV
ILLE
C
IT
Y B
OA
RD
of E
DU
CA
TIO
N
ALB
ER
TV
ILLE
, A
LA
BA
MA
H
C
R
E
R
E
T
A
E
T
O
E
R
S
I
S
G
T
A
FA
L
B
A
M
T
A
E
C
T
I
DA
No. 1082
WA
LT
ER
T
. M
cK
EE
, JR
.
MO
NT
GO
ME
RY
, A
LA
.
DRAWN BY :
MONTGOMERY, AL. 36104800 S McDONOUGH STREET
334.263.4406
ZGOUVAS, EIRING & ASSOCIATESCONSULTING ENGINEERS
THE INFORMATION CONTAINED IN THIS DRAWING IS COPYRIGHTED MATERIAL AND SHALL NOT BE REPRODUCED, DIGITIZED, OR REVISED, IN WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF ZGOUVAS, EIRING AND ASSOCIATESZEA PROJECT NUMBER 18-213
08-31-18
PLUMBING
C. WARD
T. ZGOUVAS
P1
09-07-18
TOILET
A126
CORRIDOR
A101
BOYS
A122
GIRLS
A123
STG
A106
MECH
A124
JAN
A125
SECURE
VESTIBULE
A100
DIRECTOR
A103
OFFICE
A105
RECEPTION
A102
PE-CLASSROOM
A113
STORAGE
A114
ELECTRICAL
A115
CO
RR
ID
OR
A1
04
TOILET
A108
TOILET
A109
ELECTRICAL
A110
CLASSROOM
A107
CLASSROOM
A111
CORRIDOR
A112
CORRIDOR
A121
CLASSROOM
A116
CLASSROOM
A117
CLASSROOM
A118
CLASSROOM
A119
CLASSROOM
A120
T
HC
A
T
HC
T
HC
T
HC
T
HC
A A A A B
T
HC
A
THC
48 CU. FT.
DRYWELL
1-1/4" COND. DRAIN LINE
UNDERGROUND TO DRYWELL
48 CU. FT.
DRYWELL
1-1/4" COND. DRAIN LINE
UNDERGROUND TO DRYWELL
48 CU. FT.
DRYWELL
1-1/4" COND. DRAIN LINE
UNDERGROUND TO DRYWELL
A
27 CU. FT.
DRYWELL
27 CU. FT.
DRYWELL
1-1/4" COND. DRAIN LINE
UNDERGROUND TO DRYWELL
1-1/4" COND. DRAIN LINE
UNDERGROUND TO DRYWELL
34x14
HP-1
THC
EXH. FAN TYPE
EF-B (100 CFM)
DHP-A
EXH. FAN TYPE
EF-A (300 CFM)
12x12 EXH. UP THRU ROOF - PROVIDE
16x16 FEMA LVR. IN VERTICAL WHERE
PENETRATION OF STORM SHELTER
OCCURS
EXH. FAN TYPE
EF-A (300 CFM)
12x12 EXH. UP THRU ROOF - PROVIDE
16x16 FEMA LVR. IN VERTICAL WHERE
PENETRATION OF STORM SHELTER
OCCURS
4
12x12 O.A. DN. FROM INTAKE ON ROOF
- PROVIDE 16x16 FEMA LVR. IN VERTICAL
WHERE PENETRATION OF STORM SHELTER
OCCURS
PROVIDE MTR. DAMPER
IN VERTICAL DUCT WITHIN
STORM SHELTER - INTERLOCK
DAMPER WITH EF-A
PROVIDE MTR. DAMPER
IN VERTICAL DUCT WITHIN
STORM SHELTER - INTERLOCK
DAMPER WITH EF-A
12x12 FEMA LVR.
BY GEN. CONTR.
6"Ø
1" COND. DRAIN
LINE TO HUB DRAIN
IN CORNER
HP-1
DHP-A
SA
SA
SA
SA
SA
SA
EXH. FAN TYPE
EF-C (280 CFM)
DENOTES STORM
SHELTER LIMITS
DENOTES STORM
SHELTER LIMITS
18x12
22x22 RELIEF AIR DUCT
THRU ROOF W/ MTD.
DAMPER
18x14
14x12
10x10
10x10
6x10
6x10
7
30
x1
4
34
x1
4
3
20x12
2
150
150
150
150
150
150
150
150
175
180
50
265
2
2
2
2
3
2
2
2
2
2
2
8x10
8x10
2
2
12
x1
0
FOR WORK IN THIS AREA
SEE LARGE SCALE PLAN
THIS SHEET
12x6
2
12x6
12x6
12x8
3
3
3
3
10x10 RUN
BETWEEN
TRUSSES
10x10 RUN
BETWEEN
TRUSSES
12x10
12x10
24x16 LVR. BY
GEN. CONTR.
8x8
6"Ø
EF-D
(100 CFM)
FEMA LOUVER OVER
UNIT OA INTAKE AND
CONDENSER SECTION
COORDINATE SIZE AND
QUANTITY REQUIRED
WITH UNIT FURNISHED
FEMA LOUVER OVER
UNIT OA INTAKE AND
CONDENSER SECTION
COORDINATE SIZE AND
QUANTITY REQUIRED
WITH UNIT FURNISHED
T
TH
130
2
EXH. FAN TYPE
EF-B (70 CFM)
16-1/2" x 7-3/4" BRICK VENT
AND FULL SIZE PLENUM
6"Ø
REVISED
09-07-18
REVISED
09-07-18
REVISED
09-07-18
DUCT W/ RECTANGULAR SIZE
SMOKE DETECTOR
MOTORIZED DAMPER (MD)
MANUAL VOLUME DAMPER (MVD)
FIRE DAMPER
CONNECT OR CONNECTION
AD
LEGEND
CEILING DIFFUSER
RETURN AIR GRILLE/REGISTER
EXHAUST AIR GRILLE/REGISTER
CEILING DIFFUSER DESIGNATOR
RETURN AIR GRILLE/REGISTER
EXHAUST AIR GRILLE/REGISTER
4
4
4
DENOTES LOCATION OF VERTICAL
RECTANGULAR RETURN OR EXHAUST AIR DUCT
FLOOR OR ROOF PENETRATION
ACTION FIRE DAMPER
DENOTES LOCATION OF HORIZONTAL
ACTION FIRE DAMPER
BAROMETRIC DAMPER
B
12x12
12x12 DUCT W/ FLAT OVAL SIZE
AIR TRANSFER DUCTATD
THERMOSTATT
H HUMIDISTAT
ABOVE FINISH FLOORA.F.F.
CEILING DIFFUSERC.D.
CEILING EXHAUST REGISTERC.E.R.
O.A.
F.D.
GENERAL CONTRACTORG.C.
OUTSIDE AIR
S.A. SUPPLY AIR
R.A. RETURN AIR
CLG. CEILING OR COOLING
CONN.
AUXILIARY DRAIN
C CO2 SENSOR
RECTANGULAR SUPPLY AIR DUCT TURNING DOWN
RECTANGULAR RETURN AIR OR EXHAUST
RECTANGULAR SUPPLY DUCT TURNING UP
RECTANGULAR RETURN AIR OR EXHAUST
RECTANGULAR SUPPLY AIR DUCT
DUCT TURNING DOWN
FLOOR OR ROOF PENETRATION
DUCT TURNING UP
DENOTES LOCATION OF VERTICAL
ACTION FIRE DAMPER PENETRATING
SA
SAFE AREA
DENOTES LOCATION OF HORIZONTAL
ACTION FIRE DAMPER PENETRATING
SA
SAFE AREA
CORRIDOR
A101
BOYS
A122
MECH
A124
JAN
A125
22x22 RELIEF AIR DUCT
THRU ROOF W/ MTD.
DAMPER
34x14 R.A. DN. W/ MODULATING
MTR. DAMPER CONN. TO R.A.
PLATFORM
30x16 O.A. DN. FROM
INTAKE ON ROOF W/
MODULATING MTD.
DAMPER - CONN. TO
R.A. PLATFORM
30x14 S.A.
INDOOR SECTION OF
HEAT PUMP UNIT HP-1
30x14 S.A.
SMOKE DETECTORS
REVISED
09-07-18
FLEX. CONN.
AUX. RESIST. HEATER
REFRIG. HOT GAS
REHEAT COIL
INDOOR SECTION OF
HEAT PUMP HP-1
COOLING / HEATING COIL
FILTER FRAME
AND FILTER
VIB. ISOL. PAD1-1/4" COND. DRAIN
LINE TO DRAIN
R.A. PLATFORM - CONSTRUCT WITH
1-1/2" x 1-1/2" x 1/4" STEEL
ANGELS & 18 GA. SHEET METAL -
INSULATE ALL SIDES, TOP AND BOTTOM
WITH 2" THICK, 1.5 LB. DENSITY DUCT
LINER (TYP. ALL R.A. PLATFORMS) NO
COMBUSTIBLES ALLOWED IN THE R.A.
PLATFORM / PLENUM
22x22 RELIEF AIR DUCT
THRU ROOF W/ MTD.
DAMPER
14x34 R.A. DN. W/ MODULATING
MTR. DAMPER CONN. TO R.A.
PLATFORM
SMOKE DETECTOR
SMOKE DETECTOR
30x14 S.A.
16x30 O.A. DN. FROM INTAKE ON ROOF W/
MODULATING MTD. DAMPER - CONN. TO
R.A. PLATFORM
REVISED
09-07-18
HVAC FLOOR PLAN
SCALE: 1/8" = 1'-0"
N
18-134
08-31-18
SHEET TITLE :
MCKEE JOB # :
CHECKED BY :
DATE:
SHEET NO. :
M c K
E
E
a
n
d
A
S
S
O
C
I A
T
E
S
A R
C
H
I T
E
C
T
U
R
E
a
n
d
I N
T
E
R
I O
R
D
E
S
I G
N
63
1 S
OU
TH
H
UL
L S
TR
EE
T M
ON
TG
OM
ER
Y , A
LA
BA
MA
3
61
04
(3
34
) 8
34
-9
93
3
- F
riday, S
eptem
ber 07, 2018 10:01:56 A
M
- Z
:\M
ckee\18-213 B
ig S
pring Lake P
re-K
\H
VA
C &
P
LB
G P
lans.dw
g
REVISED DATE:
REVISED DATE:
REVISED DATE:
A N
ew
P
re-K
B
uilding
FO
R
BIG
S
PR
IN
G LA
KE
K
IN
DE
RG
AR
TE
N S
CH
OO
L
FO
R T
HE
ALB
ER
TV
ILLE
C
IT
Y B
OA
RD
of E
DU
CA
TIO
N
ALB
ER
TV
ILLE
, A
LA
BA
MA
H
C
R
E
R
E
T
A
E
T
O
E
R
S
I
S
G
T
A
FA
L
B
A
M
T
A
E
C
T
I
DA
No. 1082
WA
LT
ER
T
. M
cK
EE
, JR
.
MO
NT
GO
ME
RY
, A
LA
.
DRAWN BY :
MONTGOMERY, AL. 36104800 S McDONOUGH STREET
334.263.4406
ZGOUVAS, EIRING & ASSOCIATESCONSULTING ENGINEERS
THE INFORMATION CONTAINED IN THIS DRAWING IS COPYRIGHTED MATERIAL AND SHALL NOT BE REPRODUCED, DIGITIZED, OR REVISED, IN WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF ZGOUVAS, EIRING AND ASSOCIATESZEA PROJECT NUMBER 18-213
08-31-18
HVAC FLOOR PLAN
C. WARD
T. ZGOUVAS
M1
LARGE SCALE MECH. RM. A124
SCALE: 1/4" = 1'-0"
SECTION "A"
SCALE: 1/4" = 1'-0"
09-07-18
REVISED
09-07-18
LOW AMBIENT HEAD PRESS. CONTROL TO MIN. DEGREES F (COOLING ONLY)45
3.0 HP- 208 V., 3PH., 60HZ.APPROXIMATE INDOOR FAN MOTOR HP-POWER
14.0 SEER
4.5 - 208V., 1PH., 60HZ.
24.0 - 208 V., 3 PH., 60HZ.
208 V., 3 PH., 60HZ.
TWO
19.0
50,000
72,000
150
2400
HP-1
MINIMUM HSPF/COP
MINIMUM ENERGY EFFICIENCY RATING AT A.R.I. CONDITIONS
APPROXIMATE OUTDOOR SECTION FAN MOTOR(S) F.L.A. - POWER
APPROXIMATE COMPRESSOR MOTOR(S) F.L.A. - POWER
POWER
NUMBER OF CONTROL STEPS
MINIMUM AUXILIARY ELECTRIC RESISTANCE HEAT - KW
INDOOR TEMPERATURE AND 22°F OUTDOOR TEMPERATURE-BTU/HR
MINIMUM HEATING CAPACITY (COMPRESSOR ONLY) AT 70°F
MINIMUM TOTAL COOLING CAPACITY AT A.R.I. CONDITIONS-BTU/HR
MINIMUM OUTSIDE AIR SETPOINT/MAX. CO2 SETPOINT/MAX. O.A. (ECONOMIZER) CFM
MINIMUM TOTAL AIR CFM
UNIT NUMBER
SPLIT SYSTEM HEAT PUMP UNITS SCHEDULE
APPROXIMATE EXTERNAL STATIC PRESSURE - IN. WATER COLUMN 1.56
8.2 HSPF
NOTES: 1.) ALL INDOOR UNITS SHALL BE FACTORY WIRED FOR SINGLE POINT POWER CONNECTIONS (FAN AND HEATER).
2.) 208 VOLT, 3 PHASE POWER IS BEING PROVIDED BY ELECTRICAL TO THE INDOOR HEAT PUMP UNIT SECTIONS. UNIT MANUFACTURER SHALL PROVIDE
FACTORY INSTALLED RELAYS, TRANSFORMERS, ETC., AS REQUIRED TO OPERATE EQUIPMENT AT POWER REQUIREMENTS SPECIFIED ABOVE.
3.) EER RATINGS BASED ON ARI 340/360
4.) COP RATING BASED ON ARI 340/360 AT 47°F DB/43°F WB
5.) PROVIDE A REFRIGERANT HOT GAS REHEAT COIL COMPLETE WITH REFRIGERANT PIPING,
AND LIQUID LINES - FURNISH FOR APPROVAL DETAILED REFRIGERANT PIPING CONN. DIAGRAM AND CONTROL WIRING DIAGRAM - PRIOR TO
PIPE INSULATION, VALVES, CONTROLS, ETC. REQUIRED FOR HUMIDITY CONTROL - PROVIDE MANUAL REFRIGERANT ISOLATION VALVES FOR HOT GAS
SUBMITTING THE DIAGRAM OBTAIN EQUIPMENT MANUFACTURER'S APPROVAL
6.) MINIMUM OF 8°F TEMPERATURE RISE (REHEAT) REQUIRED ON ALL REFRIGERANT HOT GAS REHEAT COILS
3.0
1,650
520
54,500
33,700
15.0
TWO
17.5 - 208 V., 3 PH., 60HZ.
3.8 - 208 V., 1 PH., 60HZ.
10.0 EER
45LOW AMBIENT HEAD PRESS. CONTROL TO DEGREES F (COOLING ONLY)
45
1/2 HP - 208 V., 3 PH., 60HZ.APPROXIMATE INDOOR FAN MOTOR HP-POWER
10.0 EER
2.5 - 208 V., 1 PH., 60HZ.
7.5 - 208 V., 3 PH., 60HZ.
208 V., 3 PH., 60HZ.
TWO
10.0
22,400
34,000
300
1,200
MINIMUM COP
MINIMUM EFFICIENCY RATING
APPROXIMATE CONDENSER SECTION FAN MOTOR(S) F.L.A. - POWER
APPROXIMATE COMPRESSOR MOTOR(S) F.L.A. - POWER
POWER
NUMBER OF CONTROL STEPS
MINIMUM AUXILIARY ELECTRIC RESISTANCE HEAT - KW
INDOOR TEMPERATURE AND 17°F OUTDOOR TEMPERATURE-BTU/HR
MINIMUM HEATING CAPACITY (COMPRESSOR ONLY) AT 70°F
MINIMUM TOTAL COOLING CAPACITY AT 95° F AMBIENT AND A.R.I. CONDITIONS-BTU/HR
MINIMUM OUTSIDE AIR CFM
MINIMUM TOTAL AIR CFM AT .20" STATIC PRESSURE
UNIT TYPE
PACKAGED WALL MOUNTED HEAT PUMP UNITS SCHEDULE
3.0
3/4 HP - 208 V., 3 PH., 60HZ.
208 V., 3 PH., 60HZ.
A B
NOTES:
1.) ALL UNITS SHALL BE FACTORY WIRED FOR SINGLE POINT POWER CONNECTIONS 208V., 3PH., 60HZ. (FAN AND HEATER).
3.) EER RATINGS BASED ON ARI 390
4.) COP RATINGS BASED ON ARI 210/240
77.0MINIMUM CIRCUIT AMPACITY (MCA)
49.8
80.0MAXIMUM FUSE SIZE (MFS) AMPS
50.0
2.) ALL UNITS SHALL BE PROVIDED WITH REFRIGERANT HOT GAS REHEAT COIL FOR HUMIDITY CONTROL AND AUTOMATIC RELIEF AIR ASSEMBLY - SEE SPECS.
20
20
20
20
20
2015" ROUND
14" ROUND
12" ROUND
10" ROUND
8" ROUND
15"Ø
14"Ø
12"Ø
10"Ø
8"Ø
6"Ø
24x24
24x24
24x24
24x24
24x24
535 - 615
405 - 530
275 - 400
185 - 270
100 - 180
24x246" ROUND10 - 95
CEILING DIFFUSER SCHEDULE
1
2
3
4
5
6
TITUS TMS
TITUS TMS
TITUS TMS
TITUS TMS
TITUS TMS
TITUS TMS
NOTES
1.) RUNOUTS/BRANCH DUCTS SHALL BE AS SCHEDULED ABOVE UNLESS NOTED OTHERWISE ON THE PLANS
2.) CONTRACTOR SHALL INSULATE THE EXTERIOR (BACK SIDE OF DIFFUSER PANEL) WITH 2" THICKNESS
EXTERNAL DUCT INSULATION WITH CHARACTERISTICS SPECIFIED FOR EXTERNAL DUCT INSULATION.
SYMBOL CFM RANGE NECK SIZE
INCHES
FACE SIZE
INCHES
BRANCH
DUCT SIZE
MAXIMUM
NC VALUE
BASIS OF
DESIGN
941 - 1200
1201 - 1400
8
9
9
8
36x24
30x24CEILING EXH. OR RETURN REG.
CEILING EXH. OR RETURN REG.
20
20 28x14
24x14
EXHAUST/RETURN AIR REGISTER SCHEDULE
1
9x90 - 140
1
761 - 940
601 - 760
461 - 600
341 - 460
241 - 340
141 - 240
7
6
5
7
6
5
4
3
2
4
3
2
16x16
24x24
20x20
18x18
14x14
12x12
RANGE
R.A.
SYMBOL
EXH.
CFM
IN. x IN.
SIZE -
CEILING EXH. OR RETURN REG.
CEILING EXH. OR RETURN REG.
CEILING EXH. OR RETURN REG.
CEILING EXH. OR RETURN REG.
CEILING EXH. OR RETURN REG.
CEILING EXH. OR RETURN REG.
CEILING EXH. OR RETURN REG.
DESCRIPTION
20 9x6
20
20
20
20
20
20
16x9
24x12
20x12
18x10
14x7
12x7
MAXIMUM
NC
RATING
DUCT
SIZE
BRANCH
988 9
NOTES
1.) RUNOUTS/BRANCH DUCTS SHALL BE AS SCHEDULED ABOVE UNLESS NOTED OTHERWISE ON THE
PLANS.
2.) & SHALL BE IN INTEGRAL 48x24 METAL CEILING PANEL AS SPECIFIED. ALL OTHERS
SHALL BE IN INTEGRAL 24x14 METAL CEILING PANEL AS SPECIFIED.
INTO THE AIRSTREAM, ANY POINT WHERE LINED DUCT IS PRECEDED BY
CONNECT TO FAN SECTION, ANYWHERE BARE DUCT LINER PROTRUDES
THIS DETAIL APPLIES TO FIRE DAMPER INSTALLATION, WHERE DUCTSNOTE !!
DUCT
NOT TO SCALE
TYPICAL DUCT LINER INTERRUPTION DETAIL
NOSING
DUCT INSULATION
METAL
FLEX. CONN.
FAN
UNLINED DUCT, BARE DUCT INSULATION EDGES ARE EXPOSED IN THE
RETURN AIR PLENUM, ETC. - SEE SPECS FOR ADDITIONAL REQUIREMENTS
NO SCALE
CEILING MOUNTED EXHAUST FAN CONN. DETAIL
FAN MOTOR
DIRECT DRIVE
AT FAN DISCHARGE
PROVIDE FLEX. CONN.
FURNISHED ALUMINUM
FAN MANUFACTURER
CEILING
CEILING FAN
BACKDRAFT DAMPER
ALLOW WEIGHT TO BE CARRIED
STRUCTURE ABOVE - DO NOT
BY CEILING GRID
SUPPORT FAN HOUSING FROM
1/4" THREADED RODS
WITH RUBBER IN SHEAR
MOUNTS
FURNISHED BRACKET
MANUFACTURER
FOR HANGER RODS
GRILLE
METAL CLG. PANEL
24x24 OR 24x48
BRASS BUSHING
NYLON END BEARING
MAIN S.A.
DUCT
MAKE AIR-TIGHT
CONNECTION
EXTERNAL
INSULATION
MANUAL VOLUME
DAMPER WITH
EXTENDED
OPERATOR
ROUND METAL DUCT
GALVANIZED
DAMPER ROD
ROUND BRANCH DUCT TAKE-OFF DETAIL
NOT TO SCALE
MIN. 2" STAND-
OFF BRACKET
TAKE-OFF FITTING MIN. GA.
THICKNESS SHALL BE AS
SPECIFIED
RECTANGULAR RUNOUTS SAME EXCEPT WITH RECTANGULAR DUCT
NOT TO SCALE
CONDENSATE DRAIN DETAIL
B
TYPICAL AIR HANDLING UNIT
DRAIN PAN
FULL SIZE OF DRAIN
CONNECTION (MIN.)
EXTEND TO FLOOR
DRAIN.
P-TRAP
A
UNIT TYPE
DRAW-THRU
BLOW-THRU
2" PLUS "X"
1" MINIMUM
"X" PLUS 1"
2X PLUS 1"
A B
WHERE "X" = AHU STATIC PRESSURE
NOTES:
1. CONTRACTOR SHALL PROVIDE DRAIN AS REQUIRED BY
THE AIR HANDLING UNIT MANUFACTURER. IN ABSENCE OF
THOSE REQUIREMENTS, CONTRACTOR SHALL PROVED
DRAIN AS DETAILED ABOVE
2. CONTRACTOR SHALL RAISE AIR HANDLING AS REQUIRED
TO ALLOW FOR INSTALLATION OF THE DRAIN AS DETAILED
ABOVE
3. PROVIDE AN ELECTRIC SWITCH IN THE CONDENSATE
DRAIN LINE, THAT CONFORMS TO UL 508, TO SHUT DOWN
THE UNIT AND ALARM TO THE BUILDING ENERGY
MANAGEMENT SYSTEM OPERATOR CONSOLE (IF
APPLICABLE) SHOULD THE LINE BECOME OBSTRUCTED
THREADED PLUG
(TYPICAL)
UNION
UNIT CASING
60
60
100
280
112077.251050N/A8.0100
HERTZPH.
FAN RUNS UPON LOSS OF POWER TO THE BUILDING1120234.401050N/A10.0CEILING MOUNTED, CENTRIFUGAL, DIRECT DRIVE300
INTERLOCK
CONTROL
VOLTS
POWER
H.P./
MIN.
IN. WTR. COL.
STATIC PRESS.
APPROX. EXT. FAN MOTOR
RPM
FAN SPEED
MAXIMUM
-INCHES
OPENING
ROOF
WALL/
APPROX.
INCHES
FAN SIZE
MINIMUMDESCRIPTIONFAN CFMFAN TYPE
FANS SCHEDULE
EF-A
EF-B
EF-C
EF-D
WATTS
CEILING MOUNTED, CENTRIFUGAL, DIRECT DRIVE
CEILING MOUNTED, CENTRIFUGAL, DIRECT DRIVE
CEILING MOUNTED, CENTRIFUGAL, DIRECT DRIVE
60 LIGHTING CIRCUIT1120234.301050N/A10.0
60112077.301050N/A8.0
LIGHTING CIRCUIT
LIGHTING CIRCUIT
5.) ALL UNITS TO HAVE ECM MOTORS
6.) TYPE B UNIT TO BE PROVIDED WITH FACTORY INSTALLED 100% OUTSIDE AIR ECONOMIZER POWERED RELIEF AIR
8.) INDOOR UNIT SHALL BE PROVIDED WITH 100% OUTDOOR AIR ECONOMIZER CYCLE. SEE CONTROLS FOR SEQUENCE OF OPERATION
5.) BASIS OF DESIGN IS MARVAIR SCHOLAR III
WALL MOUNTED DUCTLESS HEAT PUMP UNIT SCHEDULE
INDOOR UNIT MCA - POWER
INDOOR FAN CFM AT HIGH SPEED
MINIMUM AUX. ELECTRIC RESISTANCE HEAT - KW
MINIMUM HEATING CAP. (COMPRESSOR ONLY) AT 70°F INDOOR & 17°F AMBIENT - BTU/HR
MINIMUM TOTAL COOLING CAP. AT A.R.I. CONDITIONS - BTU/HR
MINIMUM HSPF AT ARI 210/240 CONDS.
OUTDOOR UNIT MOP
OUTSIDE AIR CFM
UNIT TYPE
8.2
1.5 - 208V, 1 PH. , 60 HZ.
18,000
N/A
0
400
13,000
DHP-A
OUTDOOR UNIT MCA (COMPRESSOR AND COND. FAN) - POWER 13.0A - 208V, 1 PH., 60 HZ.
MINIMUM S.E.E.R. AT ARI 210/240 CONDS 15.0
20.0A - 208V., - 1PH., 60HZ.
REVISED
09-07-18
18-134
08-31-18
SHEET TITLE :
MCKEE JOB # :
CHECKED BY :
DATE:
SHEET NO. :
M c K
E
E
a
n
d
A
S
S
O
C
I A
T
E
S
A R
C
H
I T
E
C
T
U
R
E
a
n
d
I N
T
E
R
I O
R
D
E
S
I G
N
63
1 S
OU
TH
H
UL
L S
TR
EE
T M
ON
TG
OM
ER
Y , A
LA
BA
MA
3
61
04
(3
34
) 8
34
-9
93
3
- F
riday, S
eptem
ber 07, 2018 10:01:57 A
M
- Z
:\M
ckee\18-213 B
ig S
pring Lake P
re-K
\H
VA
C &
P
LB
G P
lans.dw
g
REVISED DATE:
REVISED DATE:
REVISED DATE:
A N
ew
P
re-K
B
uilding
FO
R
BIG
S
PR
IN
G LA
KE
K
IN
DE
RG
AR
TE
N S
CH
OO
L
FO
R T
HE
ALB
ER
TV
ILLE
C
IT
Y B
OA
RD
of E
DU
CA
TIO
N
ALB
ER
TV
ILLE
, A
LA
BA
MA
H
C
R
E
R
E
T
A
E
T
O
E
R
S
I
S
G
T
A
FA
L
B
A
M
T
A
E
C
T
I
DA
No. 1082
WA
LT
ER
T
. M
cK
EE
, JR
.
MO
NT
GO
ME
RY
, A
LA
.
DRAWN BY :
MONTGOMERY, AL. 36104800 S McDONOUGH STREET
334.263.4406
ZGOUVAS, EIRING & ASSOCIATESCONSULTING ENGINEERS
THE INFORMATION CONTAINED IN THIS DRAWING IS COPYRIGHTED MATERIAL AND SHALL NOT BE REPRODUCED, DIGITIZED, OR REVISED, IN WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF ZGOUVAS, EIRING AND ASSOCIATESZEA PROJECT NUMBER 18-213
08-31-18
HVAC SCHED. AND
DETAILS
C. WARD
T. ZGOUVAS
M2
09-07-18
SCALE: 1/8"=1'-0" FLOOR PLAN - POWER1
E3.1
E3.1
FLOOR PLAN - POWER
8'
1/8" = 1'-0
0 8 16 FT
GRAPHIC SCALE
18-134
08-31-18
SHEET TITLE :
MCKEE JOB # :
DRAWN BY :
DATE:
SHEET NO. :
M c K
E
E
a
n
d
A
S
S
O
C
I A
T
E
S
A R
C
H
I T
E
C
T
U
R
E
a n d I N
T
E
R
I O
R
D
E
S
I G
N
63
1 S
OU
TH
H
UL
L S
TR
EE
T M
ON
TG
OM
ER
Y , A
LA
BA
MA
36
10
4 (33
4) 8
34
-99
33
- T
hu
rsd
ay, S
ep
te
mb
er 0
6, 2
01
8 1
1:3
2:4
9 A
M
- N
:\2
01
8\1
8-2
35
\D
ra
win
gs\e
le
c\E
3.1
.d
wg
J. TILLERY
REVISED DATE:
REVISED DATE:
REVISED DATE:
A N
ew
P
re-K
B
uilding
FO
R
BIG
S
PR
IN
G LA
KE
K
IN
DE
RG
AR
TE
N S
CH
OO
L
FO
R T
HE
ALB
ER
TV
ILLE
C
IT
Y B
OA
RD
of E
DU
CA
TIO
N
AL
BE
RT
VIL
LE
, A
LA
BA
MA
H
C
R
E
R
E
T
A
E
T
O
E
R
S
I
S
G
T
A
FA
L
B
A
M
T
A
E
C
T
I
DA
No
. 1
08
2
WA
LT
ER
T
. M
cK
EE
, JR
.
MO
NT
GO
ME
RY
, A
LA
.
3102 Highway 14
Gunn & Associates, P.C.Consulting Engineers
Millbrook, AL 36054500 Southland Drive Suite 250
Hoover, AL 35226GA#18-235Tel: 334.285.1273
08-31-18
ENTRY
PORCH
PORCH
PORCH
CORRIDOR
A101
BOYS
A122
GIRLS
A123
MECH
A124
JAN
A125
SECURE
VESTIBULE
A100
DIRECTOR
A103
RECEPTION
A102
PE-CLASSROOM
A113
STORAGE
A114
ELECTRICAL
A115
CO
RR
ID
OR
A1
04
TOILET
A108
TOILET
A109
ELECTRICAL
A110
CLASSROOM
A107
CLASSROOM
A111
CORRIDOR
A112
CORRIDOR
A121
CLASSROOM
A116
CLASSROOM
A117
CLASSROOM
A118
CLASSROOM
A119
CLASSROOM
A120
GENERAL NOTES:
SHEET NOTES:
STG
A106
OFFICE
A105
TOILET
A126
B L
S
SCALE: 1/4"=1'-0" ENLARGED FLOOR PLAN - POWER2
E3.1
09-06-18
SCALE: 1/8"=1'-0" FLOOR PLAN - AUXILIARY1
E4.1 E4.1
FLOOR PLAN - AUXILIARY
8'
1/8" = 1'-0
0 8 16 FT
GRAPHIC SCALE
18-134
08-31-18
SHEET TITLE :
MCKEE JOB # :
DRAWN BY :
DATE:
SHEET NO. :
M c K
E
E
a
n
d
A
S
S
O
C
I A
T
E
S
A R
C
H
I T
E
C
T
U
R
E
a n d I N
T
E
R
I O
R
D
E
S
I G
N
63
1 S
OU
TH
H
UL
L S
TR
EE
T M
ON
TG
OM
ER
Y , A
LA
BA
MA
36
10
4 (33
4) 8
34
-99
33
- T
hu
rsd
ay, S
ep
te
mb
er 0
6, 2
01
8 1
1:3
2:2
8 A
M
- N
:\2
01
8\1
8-2
35
\D
ra
win
gs\e
le
c\E
4.1
.d
wg
J. TILLERY
REVISED DATE:
REVISED DATE:
REVISED DATE:
A N
ew
P
re-K
B
uilding
FO
R
BIG
S
PR
IN
G LA
KE
K
IN
DE
RG
AR
TE
N S
CH
OO
L
FO
R T
HE
ALB
ER
TV
ILLE
C
IT
Y B
OA
RD
of E
DU
CA
TIO
N
AL
BE
RT
VIL
LE
, A
LA
BA
MA
H
C
R
E
R
E
T
A
E
T
O
E
R
S
I
S
G
T
A
FA
L
B
A
M
T
A
E
C
T
I
DA
No
. 1
08
2
WA
LT
ER
T
. M
cK
EE
, JR
.
MO
NT
GO
ME
RY
, A
LA
.
3102 Highway 14
Gunn & Associates, P.C.Consulting Engineers
Millbrook, AL 36054500 Southland Drive Suite 250
Hoover, AL 35226GA#18-235Tel: 334.285.1273
08-31-18
ENTRY
PORCH
PORCH
PORCH
CORRIDOR
A101
BOYS
A122
GIRLS
A123
MECH
A124
JAN
A125
SECURE
VESTIBULE
A100
DIRECTOR
A103
RECEPTION
A102
STORAGE
A114
ELECTRICAL
A115
CO
RR
ID
OR
A1
04
TOILET
A108
TOILET
A109
ELECTRICAL
A110
CLASSROOM
A107
CLASSROOM
A111
CORRIDOR
A112
CORRIDOR
A121
CLASSROOM
A116
CLASSROOM
A117
CLASSROOM
A118
CLASSROOM
A119
CLASSROOM
A120
GENERAL NOTES:
SHEET NOTES:
PE-CLASSROOM
A113
NO SCALE DOOR SECURITY SYSTEM 2
E4.1
STG
A106
OFFICE
A105
TOILET
A126