ansi/ashrae/ashe standard 170 -2013 - cdn.ymaws.com · nomenclature: room name, type & function...

11
ANSI/ASHRAE/ASHE Standard 170 - 2013

Upload: nguyendang

Post on 26-Jun-2018

252 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: ANSI/ASHRAE/ASHE Standard 170 -2013 - cdn.ymaws.com · NOMENCLATURE: Room Name, Type & Function ASHRAE Standard 170 Table 7.1 provides room names, required pressure relationships,

ANSI/ASHRAE/ASHEStandard170-2013

Page 2: ANSI/ASHRAE/ASHE Standard 170 -2013 - cdn.ymaws.com · NOMENCLATURE: Room Name, Type & Function ASHRAE Standard 170 Table 7.1 provides room names, required pressure relationships,

CDC2003VentilationRequirementsTableB2

Page 3: ANSI/ASHRAE/ASHE Standard 170 -2013 - cdn.ymaws.com · NOMENCLATURE: Room Name, Type & Function ASHRAE Standard 170 Table 7.1 provides room names, required pressure relationships,

TexasAdministrativeCode:25TAC133.169(c)

Page 4: ANSI/ASHRAE/ASHE Standard 170 -2013 - cdn.ymaws.com · NOMENCLATURE: Room Name, Type & Function ASHRAE Standard 170 Table 7.1 provides room names, required pressure relationships,

NOMENCLATURE:RoomName,Type&FunctionASHRAEStandard170Table7.1providesroomnames,requiredpressurerelationships,minimumoutdoorACH,minimumtotalACH,requirementtoexhausttotheoutsideorabilitytorecirculateair,humidityandtemperature.TherequirementsarelinkedtotheroomnameHowdoyoudeterminetheroomname?YouneedtounderstandthefunctionoftheroomandpossibleproceduresperformedintheroomsASHRAEStandard170outlinesadditionalRoom-SpecificRequirements

7.2.1AirborneInfectionIsolationRooms7.2.2ProtectiveEnvironment(PE)Rooms7.2.3CombinationAirborneInfectiousIsolationandPERooms7.3.1WoundIntensive-CareUnits(BurnUnits)7.4.1OperatingRooms7.4.2SterilizationRooms7.4.3ImagingProcedureRooms7.5.1MorgueandAutopsyRooms7.5.2Bronchoscopy7.6PsychiatricPatientAreas

Page 5: ANSI/ASHRAE/ASHE Standard 170 -2013 - cdn.ymaws.com · NOMENCLATURE: Room Name, Type & Function ASHRAE Standard 170 Table 7.1 provides room names, required pressure relationships,

TexasChildren’sHospitalPolicy:AdoptTAC133.169(c)

Page 6: ANSI/ASHRAE/ASHE Standard 170 -2013 - cdn.ymaws.com · NOMENCLATURE: Room Name, Type & Function ASHRAE Standard 170 Table 7.1 provides room names, required pressure relationships,

THEPLANAdoptanationallyrecognizedstandardandcreateapolicy.CreateaninventoryofPressureDependentSpacesUpdatetheSpaceManagementPolicytoinclude:

AuditingroomsReportingnon-complianceofroomusage(currentfunction)vs.roomdesignintent

AllpressuredependentspacestobedefinedbynomenclatureinthestandardEnsureroomsignagematchesthestandard(ensurecurrentroomnamescorrelatetocurrentroomfunctionality)EnsuredesignatedpressuredependentspacesmeettherequirementsoftheadoptedstandardDevelopaprocesstoreviewspaceusageagainstrequirementsonaperiodicbasisDeterminehowspaceswillbemonitoredandinsuremonitoringsolutionalsoaccountsfortemperatureandhumidityrequirementsDeterminehowoftenspaceswillbetestedDevelopatrainingprogram:

HowtorecognizeaspacehasapressurerequirementOwnership:EnduserresponsibilitiestomonitorspaceutilizationandstandardizationRoomsymbolforpressuredependentspaces

Page 7: ANSI/ASHRAE/ASHE Standard 170 -2013 - cdn.ymaws.com · NOMENCLATURE: Room Name, Type & Function ASHRAE Standard 170 Table 7.1 provides room names, required pressure relationships,

HOW?FormmultidisciplinaryWorkingGroupComparenationallyrecognizedstandardsAdoptthemoststringentrequirementsPerformariskassignmentforconflictingstandardsInsurespacepolicymandatesstandardizedroomnamesandsignageForvisibility,createasymbolforroomsignageInsurespacepolicyprovidesprocessforrepurposingspaceorrequestingnewspacethatwillhavepressuredependentrequirementsDefinestandardsforthemonitoringofspaces.Wesetupfourtiers:

Tier I: Most critical spaces. These spaces are monitored for pressure, temperature, humidity, and air exchanges. Local display and linked to BAS for critical monitoring by engineering and archiving of data.Tier II: Monitoring pressure only. Local display and linked to BAS for monitoring by engineering and archiving of data.Tier III: Monitoring pressure only locally, however, not remotely via BAS.Tier IV: Monitoring of construction projects

Createapilotproject(i.e.,anAmbulatorySurgeryarea)CreatepolicyfortestingthesespacesCreateatrainingprogram

Page 8: ANSI/ASHRAE/ASHE Standard 170 -2013 - cdn.ymaws.com · NOMENCLATURE: Room Name, Type & Function ASHRAE Standard 170 Table 7.1 provides room names, required pressure relationships,

MonitoringatRoomBallinthewall:PressureLamiflow:PressurePresura:PressurePrimex:Temp,Humidity&PressureSureFlow:Temp,Humidity&PressureL-VISPanels:Temp,Humidity&Pressure

Page 9: ANSI/ASHRAE/ASHE Standard 170 -2013 - cdn.ymaws.com · NOMENCLATURE: Room Name, Type & Function ASHRAE Standard 170 Table 7.1 provides room names, required pressure relationships,

MonitoringthroughBASMonthlySensorReport(example)Group:MedicalCenterCampusLocation:WTOR#6SerialNo:001EB38F4E41

Date TimeCurrent

Temperature

MinimumTemperature

MaximumTemperatur

e

AverageTemperatur

e

CurrentHumidity

MinimumHumidity

MaximumHumidity

AverageHumidity

CurrentPressur

e

Minimum

Pressure

Maximum

Pressure

AveragePressure

5/1/201612:34:00

AM 64.2 64 70 68.545% 29.00% 50.00% 40.50% 0.02 0.005 0.025 0.015

5/2/201612:46:00

AM 69.1 66 72 6944% 42.00% 49.00% 45.50% 0.02 0.020 0.030 0.025

5/3/201612:14:00

AM 73 69 74 71.543% 41.00% 51.00% 46.00% 0.02 0.020 0.030 0.025

5/4/201612:49:00

AM 72.3 70 75 72.542% 41.00% 49.00% 45.00% 0.02 0.020 0.030 0.025

5/5/201612:52:00

AM 71.6 64 73 68.541% 43.00% 50.00% 46.50% 0.02 0.020 0.030 0.025

5/6/201612:54:00

AM 72.3 66 72 6945% 42.00% 49.00% 45.50% 0.02 0.020 0.030 0.025

5/7/201612:57:00

AM 71.8 69 74 71.544% 41.00% 51.00% 46.00% 0.02 0.020 0.030 0.025

5/8/201612:41:00

AM 67.6 70 75 72.543% 41.00% 49.00% 45.00% 0.02 0.020 0.030 0.025

5/9/201612:39:00

AM 68.2 64 73 68.542% 43.00% 50.00% 46.50% 0.02 0.020 0.030 0.025

5/10/2016

12:38:00AM 72.1 66 72 69

41% 42.00% 49.00% 45.50% 0.02 0.020 0.030 0.0255/11/201

612:42:00

AM 75.7 69 76 72.545% 41.00% 51.00% 46.00% 0.02 0.020 0.030 0.025

5/12/2016

12:45:00AM 68.7 70 75 72.5

44% 41.00% 49.00% 45.00% 0.02 0.020 0.030 0.0255/13/201

612:33:00

AM 74.8 64 75 69.543% 43.00% 50.00% 46.50% 0.02 0.020 0.030 0.025

5/14/2016

12:35:00AM 72.5 66 72 69

42% 42.00% 49.00% 45.50% 0.02 0.020 0.030 0.0255/15/201

612:18:00

AM 67.6 69 74 71.541% 41.00% 51.00% 46.00% 0.02 0.020 0.030 0.025

5/16/2016

12:06:00AM 68.2 70 75 72.5

45% 41.00% 49.00% 45.00% 0.02 0.020 0.030 0.0255/17/201

612:08:00

AM 67.8 64 73 68.544% 43.00% 50.00% 46.50% 0.02 0.020 0.030 0.025

5/18/201 12:20:00

ServiceResponseCenter:Mustreceivecriticalalarms24/7Musthaveaccesstoreports

Nursing:MusthaveaccesstographicaldisplayMusthaveaccesstoreports

Page 10: ANSI/ASHRAE/ASHE Standard 170 -2013 - cdn.ymaws.com · NOMENCLATURE: Room Name, Type & Function ASHRAE Standard 170 Table 7.1 provides room names, required pressure relationships,

HOW?LocalmonitoringdevicesthatstaffcaneasilyunderstandAlarmsforcriticalspacestiedtoyourBASRoundingonspacesforfunctionalityvs.design(i.e.,EOCrounds)AnnualauditsofspacesCalibrationofdevicesTestingofroomsviainstrumentation(in-houseoroutsourced)VerificationofpressureusingthetissueorsmoketestTraining:

Whatarethespaces?HowdoIknowtheproperpressure,temperature,humidity,etc.?WhatdoIdoiftheyarenotcorrect?WhatdoIdoifIneedtouseanisolationroom?SpacepolicesandproceduresEOCroundsMonitoringandtesting

Page 11: ANSI/ASHRAE/ASHE Standard 170 -2013 - cdn.ymaws.com · NOMENCLATURE: Room Name, Type & Function ASHRAE Standard 170 Table 7.1 provides room names, required pressure relationships,

DidWeCoveritAll?

Questions?