ansi/ashrae/ashe standard 170 -2013 - cdn.ymaws.com · nomenclature: room name, type & function...
TRANSCRIPT
ANSI/ASHRAE/ASHEStandard170-2013
CDC2003VentilationRequirementsTableB2
TexasAdministrativeCode:25TAC133.169(c)
NOMENCLATURE:RoomName,Type&FunctionASHRAEStandard170Table7.1providesroomnames,requiredpressurerelationships,minimumoutdoorACH,minimumtotalACH,requirementtoexhausttotheoutsideorabilitytorecirculateair,humidityandtemperature.TherequirementsarelinkedtotheroomnameHowdoyoudeterminetheroomname?YouneedtounderstandthefunctionoftheroomandpossibleproceduresperformedintheroomsASHRAEStandard170outlinesadditionalRoom-SpecificRequirements
7.2.1AirborneInfectionIsolationRooms7.2.2ProtectiveEnvironment(PE)Rooms7.2.3CombinationAirborneInfectiousIsolationandPERooms7.3.1WoundIntensive-CareUnits(BurnUnits)7.4.1OperatingRooms7.4.2SterilizationRooms7.4.3ImagingProcedureRooms7.5.1MorgueandAutopsyRooms7.5.2Bronchoscopy7.6PsychiatricPatientAreas
TexasChildren’sHospitalPolicy:AdoptTAC133.169(c)
THEPLANAdoptanationallyrecognizedstandardandcreateapolicy.CreateaninventoryofPressureDependentSpacesUpdatetheSpaceManagementPolicytoinclude:
AuditingroomsReportingnon-complianceofroomusage(currentfunction)vs.roomdesignintent
AllpressuredependentspacestobedefinedbynomenclatureinthestandardEnsureroomsignagematchesthestandard(ensurecurrentroomnamescorrelatetocurrentroomfunctionality)EnsuredesignatedpressuredependentspacesmeettherequirementsoftheadoptedstandardDevelopaprocesstoreviewspaceusageagainstrequirementsonaperiodicbasisDeterminehowspaceswillbemonitoredandinsuremonitoringsolutionalsoaccountsfortemperatureandhumidityrequirementsDeterminehowoftenspaceswillbetestedDevelopatrainingprogram:
HowtorecognizeaspacehasapressurerequirementOwnership:EnduserresponsibilitiestomonitorspaceutilizationandstandardizationRoomsymbolforpressuredependentspaces
HOW?FormmultidisciplinaryWorkingGroupComparenationallyrecognizedstandardsAdoptthemoststringentrequirementsPerformariskassignmentforconflictingstandardsInsurespacepolicymandatesstandardizedroomnamesandsignageForvisibility,createasymbolforroomsignageInsurespacepolicyprovidesprocessforrepurposingspaceorrequestingnewspacethatwillhavepressuredependentrequirementsDefinestandardsforthemonitoringofspaces.Wesetupfourtiers:
Tier I: Most critical spaces. These spaces are monitored for pressure, temperature, humidity, and air exchanges. Local display and linked to BAS for critical monitoring by engineering and archiving of data.Tier II: Monitoring pressure only. Local display and linked to BAS for monitoring by engineering and archiving of data.Tier III: Monitoring pressure only locally, however, not remotely via BAS.Tier IV: Monitoring of construction projects
Createapilotproject(i.e.,anAmbulatorySurgeryarea)CreatepolicyfortestingthesespacesCreateatrainingprogram
MonitoringatRoomBallinthewall:PressureLamiflow:PressurePresura:PressurePrimex:Temp,Humidity&PressureSureFlow:Temp,Humidity&PressureL-VISPanels:Temp,Humidity&Pressure
MonitoringthroughBASMonthlySensorReport(example)Group:MedicalCenterCampusLocation:WTOR#6SerialNo:001EB38F4E41
Date TimeCurrent
Temperature
MinimumTemperature
MaximumTemperatur
e
AverageTemperatur
e
CurrentHumidity
MinimumHumidity
MaximumHumidity
AverageHumidity
CurrentPressur
e
Minimum
Pressure
Maximum
Pressure
AveragePressure
5/1/201612:34:00
AM 64.2 64 70 68.545% 29.00% 50.00% 40.50% 0.02 0.005 0.025 0.015
5/2/201612:46:00
AM 69.1 66 72 6944% 42.00% 49.00% 45.50% 0.02 0.020 0.030 0.025
5/3/201612:14:00
AM 73 69 74 71.543% 41.00% 51.00% 46.00% 0.02 0.020 0.030 0.025
5/4/201612:49:00
AM 72.3 70 75 72.542% 41.00% 49.00% 45.00% 0.02 0.020 0.030 0.025
5/5/201612:52:00
AM 71.6 64 73 68.541% 43.00% 50.00% 46.50% 0.02 0.020 0.030 0.025
5/6/201612:54:00
AM 72.3 66 72 6945% 42.00% 49.00% 45.50% 0.02 0.020 0.030 0.025
5/7/201612:57:00
AM 71.8 69 74 71.544% 41.00% 51.00% 46.00% 0.02 0.020 0.030 0.025
5/8/201612:41:00
AM 67.6 70 75 72.543% 41.00% 49.00% 45.00% 0.02 0.020 0.030 0.025
5/9/201612:39:00
AM 68.2 64 73 68.542% 43.00% 50.00% 46.50% 0.02 0.020 0.030 0.025
5/10/2016
12:38:00AM 72.1 66 72 69
41% 42.00% 49.00% 45.50% 0.02 0.020 0.030 0.0255/11/201
612:42:00
AM 75.7 69 76 72.545% 41.00% 51.00% 46.00% 0.02 0.020 0.030 0.025
5/12/2016
12:45:00AM 68.7 70 75 72.5
44% 41.00% 49.00% 45.00% 0.02 0.020 0.030 0.0255/13/201
612:33:00
AM 74.8 64 75 69.543% 43.00% 50.00% 46.50% 0.02 0.020 0.030 0.025
5/14/2016
12:35:00AM 72.5 66 72 69
42% 42.00% 49.00% 45.50% 0.02 0.020 0.030 0.0255/15/201
612:18:00
AM 67.6 69 74 71.541% 41.00% 51.00% 46.00% 0.02 0.020 0.030 0.025
5/16/2016
12:06:00AM 68.2 70 75 72.5
45% 41.00% 49.00% 45.00% 0.02 0.020 0.030 0.0255/17/201
612:08:00
AM 67.8 64 73 68.544% 43.00% 50.00% 46.50% 0.02 0.020 0.030 0.025
5/18/201 12:20:00
ServiceResponseCenter:Mustreceivecriticalalarms24/7Musthaveaccesstoreports
Nursing:MusthaveaccesstographicaldisplayMusthaveaccesstoreports
HOW?LocalmonitoringdevicesthatstaffcaneasilyunderstandAlarmsforcriticalspacestiedtoyourBASRoundingonspacesforfunctionalityvs.design(i.e.,EOCrounds)AnnualauditsofspacesCalibrationofdevicesTestingofroomsviainstrumentation(in-houseoroutsourced)VerificationofpressureusingthetissueorsmoketestTraining:
Whatarethespaces?HowdoIknowtheproperpressure,temperature,humidity,etc.?WhatdoIdoiftheyarenotcorrect?WhatdoIdoifIneedtouseanisolationroom?SpacepolicesandproceduresEOCroundsMonitoringandtesting
DidWeCoveritAll?
Questions?