an200.en003 setting reverse power 32r pick up value for vamp 230 255 257 259

2
[ Application note ] Setting reverse power 32R pick-up value 1 AN200.EN003 Setting reverse power 32R pick-up value for VAMP 230/255/257/259 The relay will show the pick-up value in input kilowatts, but the setting is done in percent of the nominal apparent power S N . 3 Pr Pr imary Rated imary Rated N VT CT S Example Let us say that the pick-up target value for reverse power stage P< 32R is 5 % of the rated active input power of the motor. Motor data: Rated current I MOT = 385 A Rated voltage U MOT = 6000 V Power factor cos = 0.8 Current and voltage transformers: CT = 400/5 VT = 6600/120 First we calculate the nominal apparent power kVA S N 6 . 4572 3 6600 400 and then the rated active input power kW U I P MOT MOT Input 8 . 3200 cos 3 The -5 % pick-up setting will be in input kilowatts . 04 . 160 8 . 3200 05 . 0 % 5 Re kW kW P P Input verse Input The pick-up setting for the relay will be

Upload: ari-catur-pamungkas

Post on 28-Jan-2016

3 views

Category:

Documents


0 download

DESCRIPTION

3rfefer

TRANSCRIPT

Page 1: AN200.EN003 Setting Reverse Power 32R Pick Up Value for VAMP 230 255 257 259

[ Application note ] Setting reverse power 32R pick-up value

1

AN200.EN003

Setting reverse power 32R pick-up value for VAMP 230/255/257/259

The relay will show the pick-up value in input kilowatts, but the setting is done in percent of

the nominal apparent power SN.

3PrPr imaryRatedimaryRatedN VTCTS

Example

Let us say that the pick-up target value for reverse power stage P< 32R is 5 % of the

rated active input power of the motor.

Motor data:

Rated current IMOT = 385 A

Rated voltage UMOT = 6000 V

Power factor cos = 0.8

Current and voltage transformers:

CT = 400/5

VT = 6600/120

First we calculate the nominal apparent power

kVASN 6.457236600400

and then the rated active input power

kWUIP MOTMOTInput 8.3200cos3

The -5 % pick-up setting will be in input kilowatts

.04.160

8.320005.0%5Re

kW

kWPP InputverseInput

The pick-up setting for the relay will be

Page 2: AN200.EN003 Setting Reverse Power 32R Pick Up Value for VAMP 230 255 257 259

Setting reverse power 32R pick-up value [ Application note ]

AN200.EN003

2

%.5.3

035.06.4572

04.160Re

N

verseInput

SettingS

PP

Schneider Electric

35 rue Joseph Monier 92506 Rueil-Malmaison FRANCE Phone: +33 (0) 1 41 29 70 00 Fax: +33 (0) 1 41 29 71 00

www.schneider-electric.com

Publishing: 4/2013

© 2012 Schneider Electric Industries SAS - All rights reserved. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.