DATOS CABLES DE ALIMENTADORES SAN CARLOSCABLE No. CALIBRE DEL CONDUCTOR LONGITUD (m) TIPO DE CABLE
1 3F*350 MCM 65 TRIPOLAR2 3F*350 MCM 60 TRIPOLAR3 3F*1/0 AWG 70 MONOPOLAR4 2*3F*250 MCM 315 MONOPOLAR5 3*250 MCM 450 TRIPOLAR6 3*1/0 AWG 15 MONOPOLAR7 3*1/0 AWG 15 MONOPOLAR8 3*1/0 AWG 20 TRIPOLAR9 3*1/0 AWG 20 TRIPOLAR
10 3*250 MCM 200 MONOPOLAR11 3*250 MCM 180 MONOPOLAR12 3*2/0 AWG 5 MONOPOLAR13 3*2 AWG 15 MONOPOLAR14 3*2 AWG 10 MONOPOLAR15 3*2 AWG 20 MONOPOLAR16 3*2 AWG 20 MONOPOLAR17 3*2 AWG 20 TRIPOLAR18 3*2 AWG 20 TRIPOLAR19 3*2 AWG 20 TRIPOLAR20 3*2 AWG 20 MONOPOLAR21 3*2 AWG 20 MONOPOLAR22 3*2 AWG 20 TRIPOLAR23 3*2 AWG 20 TRIPOLAR24 3*2 AWG 20 TRIPOLAR25 3*250 MCM 70 TRIPOLAR26 3*2 AWG 20 TRIPOLAR27 3*1/0 AWG 40 TRIPOLAR28 3*1/0 AWG 40 TRIPOLAR29 3*1/0 AWG 40 TRIPOLAR30 3*1/0 AWG 200 TRIPOLAR31 5*3F*500 MCM 10 TRIPOLAR32 5*3F*500 MCM 50 TRIPOLAR33 3*2 AWG 30 MONOPOLAR34 3*2 AWG 8 MONOPOLAR35 3*3F*500 MCM 80 MONOPOLAR36 3*266 ACSR 800 MONOPOLAR
DATOS CABLES DE ALIMENTADORES SAN CARLOS I max (aire) I max (ducto) PARAMETROS DE LOS CABLESCONFIGURACION A A
Cables 1 y 2 juntos 40 m 445 370 0.100226458091 0.12779365678445 370 0.100226458091 0.12779365678
Independiente hasta la carga 220 170 0.3292880875264 0.419858484881
Cables 4 y 5 juntos 270 m 385 280 0.1399354620628 0.178424587188345 290 0.1400695144847 0.17859551061
Cables 6 y 7 juntos hasta la carga 220 170 0.3292880875264 0.419858484881220 170 0.3292880875264 0.419858484881
Cables 8 y 9 juntos hasta la carga 205 175 0.3293166207437 0.419894866135205 175 0.3293166207437 0.419894866135
Independiente hasta la carga 385 280 0.1399354620628 0.178424587188Independiente hasta la carga 385 280 0.1399354620628 0.178424587188Independiente hasta la carga 275 205 0.2613890304434 0.333283852176Independiente hasta la carga 185 145 0.5231637757939 0.667059509804Independiente hasta la carga 185 145 0.5231637757939 0.667059509804
Cables 15 al 19 juntos hasta la carga
185 145 0.5231637757939 0.667059509804185 145 0.5231637757939 0.667059509804170 150 0.5231752751842 0.667074172091170 150 0.5231752751842 0.667074172091170 150 0.5231752751842 0.667074172091
Independiente hasta la carga 185 145 0.5231637757939 0.667059509804Independiente hasta la carga 185 145 0.5231637757939 0.667059509804Independiente hasta la carga 170 150 0.5231752751842 0.667074172091Independiente hasta la carga 170 150 0.5231752751842 0.667074172091Independiente hasta la carga 170 150 0.5231752751842 0.667074172091Independiente hasta la carga 345 290 0.1400695144847 0.17859551061Independiente hasta la carga 170 150 0.5231752751842 0.667074172091
Cables 27, 28 y 29 juntos hasta la carga205 175 0.3293166207437 0.419894866135205 175 0.3293166207437 0.419894866135205 175 0.3293166207437 0.419894866135
Independiente hasta la carga 205 175 0.3293166207437 0.419894866135Independiente hasta la carga 525 425 0.0724478712318 0.092374594164Independiente hasta la carga 525 425 0.0724478712318 0.092374594164Independiente hasta la carga 185 145 0.5231637757939 0.667059509804Independiente hasta la carga 185 145 0.5231637757939 0.667059509804Independiente hasta la carga 590 415 0.0719579733252 0.091749950271
- 465 465 0.2117665205637 0.270012714825
R1 20º C Ω/km R1 90º C Ω/km
PARAMETROS DE LOS CABLESX1 Ω/km R0 Ω/km X0 Ω/km B uS/km
0.115530652 0.129821 0.882138948 79.798831920.115530652 0.129821 0.882138948 79.798831920.169944002 2.132215184 0.093955331 61.815996550.149504222 1.600970493 0.074580544 91.436161570.121653064 0.180836522 0.885260845 84.402610680.169944002 2.132215184 0.093955331 61.815996550.169944002 2.132215184 0.093955331 61.815996550.139210389 0.422597175 0.907591442 60.957441050.139210389 0.422597175 0.907591442 60.957441050.149504222 1.600970493 0.074580544 91.436161570.149504222 1.600970493 0.074580544 91.436161570.164120751 1.974500299 0.088391009 66.49902660.181557907 2.515634117 0.105077325 49.874269950.181557907 2.515634117 0.105077325 49.874269950.181557907 2.515634117 0.105077325 49.874269950.181557907 2.515634117 0.105077325 49.874269950.149712388 0.66998745 0.919823841 52.249235180.149712388 0.66998745 0.919823841 52.249235180.149712388 0.66998745 0.919823841 52.249235180.181557907 2.515634117 0.105077325 49.874269950.181557907 2.515634117 0.105077325 49.874269950.149712388 0.66998745 0.919823841 52.249235180.149712388 0.66998745 0.919823841 52.249235180.149712388 0.66998745 0.919823841 52.249235180.121653064 0.180836522 0.885260845 84.402610680.149712388 0.66998745 0.919823841 52.249235180.139210389 0.422597175 0.907591442 60.957441050.139210389 0.422597175 0.907591442 60.957441050.139210389 0.422597175 0.907591442 60.957441050.139210389 0.422597175 0.907591442 60.957441050.109550056 0.093802235 0.877933281 109.72339390.109550056 0.093802235 0.877933281 109.72339390.181557907 2.515634117 0.105077325 49.874269950.181557907 2.515634117 0.105077325 49.874269950.137213333 1.26154894 0.063246444 109.72339390.125780515 2.1204326 0.050046098 91.43616157
CALCULO DE RESISTENCIA
DATOSCABLE No. 1 350 MCM TRIPOLAR Frecuencia 60 HzRdc 20º C 0.0992 Ω/km
α234.5 Cu recocido con 100% de conductividad
228 Al recocido en frio241.5 Cu con 97,3% de conductividad
CORRECIÓN POR TEMPERATURA
Rdc 90º C = 0.1265 Ω/km
CORRECIÓN POR EFECTO PIEL
ks1.00 conductor redondo
0.435 conductor segmental
Xs 1.0919
Ys 0.0074
CORRECIÓN POR EFECTO ESPACIAMIENTO
kp 1.00 conductor redondo0.37 conductor segmental
S 28.26 distancia entre centros de conductoresdc 15.68 diametro del conductor
Xp 1.0919
dc/S 0.3079Xp^4/(192+0,8*Xp^4) 0.0074
Yp 0.00299
Rac 90º C 0.12779 Ω/km
REACTANCIA DE SECUENCIA POSITIVA Y NEGATIVA
f = 60 Hz f = 60 HzS = 28.26 mm S = 1.1125984252 pulgadasGMD-3C = 28.26 mm GMD-3C = 1.1125984252 pulgadasDc = 15.68 mm Dc = 0.6173228346 pulgadasGMR-1C = 6.10736 mm GMR-1C = 0.2404472441 pulgadas
x1 = x2 = 0.185890027 Ω/milla
x1 = x2 = 0.115530652 Ω/km
REACTANCIA DE SECUENCIA CERO
rc = resistencia AC del conductor (Ω/milla)re = resistencia AC debido al retorno por tierra (Ω/milla) Tabla.De = distancia equivalente (pulgadas) Tabla.
GMR-3C = 0.66767568682 pulgadasrc = 0.20561999376 Ω/millare = 0.286 Ω/milla
De = 7.44E+04 pulgadas
Zc = 0.305541826121371+2.62919458236753i Ω/km
rs = 0.001087613 Ω/millare = 0.286 Ω/millaDe = 7.44E+04 pulgadasro = 34.35 pulgadasri = 31.56 pulgadas
Zs = 0.179776854862365+1.74705563444574i Ω/km
re = 0.286 Ω/millaDe = 7.44E+04 pulgadasro = 34.35 pulgadasri = 31.56 pulgadas
Zm = 0.177749+1.74705563444574i Ω/km
Si I retorno lo hace por vaina y tierra:
Zo = 0.12982044131053+0.8821412770449i Ω/km
0.129820441 0.88214128
Si I retorno lo hace por vaina:
Zo = 0.129820680983736+0.88213894792179i Ω/km
0.129820681 0.88213895
Si I retorno lo hace por tierra:
Zo = 0.305541826121371+2.62919458236753i Ω/km
0.305541826 2.62919458
REACTANCIA CAPACITIVA
Aislamiento kVulcanel EP 2.6Vulcanel XLPEP 2.1SINTANEX 7Papel impregnado 3.9
k = 2.1Espesor Aisla. 4.45 mmT/d = 0.2838G = 0.55C1 = C2 = C0 = 0.34058182 uF/milla
C1 = C2 = C0 = 0.21167298 uF/km
B = 79.7988319 uS/km
DATOS re Y De a 60 Hz.De re xe
pulgadas pies Ω/milla Ω/milla1 3.36E+03 280 0.286 2.055 7.44E+03 620 0.286 2.34
10 1.06E+04 880 0.286 2.4750 2.40E+04 2000 0.286 2.76
100 3.36E+04 2800 0.286 2.89
Resistividad suelo Ω/m
500 7.44E+04 6200 0.286 3.181000 1.06E+05 8800 0.286 3.315000 2.40E+05 20000 0.286 3.6
10000 3.36E+05 28000 0.286 3.73
CALCULO DE RESISTENCIA
DATOSCABLE No. 5 y 25 250 MCM TRIPOLAR Frecuencia 60 HzRdc 20º C 0.139 Ω/km
α234.5 Cu recocido con 100% de conductividad
228 Al recocido en frio241.5 Cu con 97,3% de conductividad
CORRECIÓN POR TEMPERATURA
Rdc 90º C = 0.1772 Ω/km
CORRECIÓN POR EFECTO PIEL
ks1.00 conductor redondo
0.435 conductor segmental
Xs 0.9224
Ys 0.0038
CORRECIÓN POR EFECTO ESPACIAMIENTO
kp 1.00 conductor redondo0.37 conductor segmental
S 25.9 distancia entre centros de conductoresdc 13.25 diametro del conductor
Xp 0.9224
dc/S 0.2617Xp^4/(192+0,8*Xp^4) 0.0035
Yp 0.00394
Rac 90º C 0.17860 Ω/km
REACTANCIA DE SECUENCIA POSITIVA Y NEGATIVA
f = 60 Hz f = 60 HzS = 25.9 mm S = 1.0196850394 pulgadasGMD-3C = 25.9 mm GMD-3C = 1.0196850394 pulgadasrc = 6.625 mm rc = 0.2608267717 pulgadasGMR-1C = 5.160875 mm GMR-1C = 0.2031840551 pulgadas
x1 = x2 = 0.195741053 Ω/milla
x1 = x2 = 0.121653064 Ω/km
REACTANCIA DE SECUENCIA CERO
rc = resistencia AC del conductor (Ω/milla)re = resistencia AC debido al retorno por tierra (Ω/milla) Tabla.De = distancia equivalente (pulgadas) Tabla.
GMR-3C = 0.59558064105 pulgadasrc = 0.28736017657 Ω/millare = 0.286 Ω/milla
De = 7.44E+04 pulgadas
Zc = 0.356343349739287+2.65504628863894i Ω/km
rs = 0.00120256 Ω/millare = 0.286 Ω/millaDe = 7.44E+04 pulgadasro = 31.2 pulgadasri = 28.41 pulgadas
Zs = 0.179991172688785+1.76978544412757i Ω/km
re = 0.286 Ω/millaDe = 7.44E+04 pulgadasro = 31.2 pulgadasri = 28.41 pulgadas
Zm = 0.177749+1.76978544412757i Ω/km
Si I retorno lo hace por vaina y tierra:
Zo = 0.180836236485316+0.88526365607885i Ω/km
0.180836236 0.88526366
Si I retorno lo hace por vaina:
Zo = 0.180836522428072+0.88526084451137i Ω/km
0.180836522 0.88526084
Si I retorno lo hace por tierra:
Zo = 0.356343349739287+2.65504628863894i Ω/km
0.35634335 2.65504629
REACTANCIA CAPACITIVA
Aislamiento kVulcanel EP 2.6Vulcanel XLPEP 2.1SINTANEX 7Papel impregnado 3.9
k = 2.1Espesor Aisla. 4.45 mmT/d = 0.336G = 0.52C1 = C2 = C0 = 0.360 uF/milla
C1 = C2 = C0 = 0.22388488 uF/km
B = 84.4026107 uS/km
DATOS re Y De a 60 Hz.De re xe
pulgadas pies Ω/milla Ω/milla1 3.36E+03 280 0.286 2.055 7.44E+03 620 0.286 2.34
10 1.06E+04 880 0.286 2.4750 2.40E+04 2000 0.286 2.76
100 3.36E+04 2800 0.286 2.89
Resistividad suelo Ω/m
500 7.44E+04 6200 0.286 3.181000 1.06E+05 8800 0.286 3.315000 2.40E+05 20000 0.286 3.6
10000 3.36E+05 28000 0.286 3.73
CALCULO DE RESISTENCIA
DATOSCABLE No. 8,9,27-30 1/0 AWG TRIPOLAR Frecuencia 60 HzRdc 20º C 0.329 Ω/km
α234.5 Cu recocido con 100% de conductividad
228 Al recocido en frio241.5 Cu con 97,3% de conductividad
CORRECIÓN POR TEMPERATURA
Rdc 90º C = 0.4195 Ω/km
CORRECIÓN POR EFECTO PIEL
ks1.00 conductor redondo
0.435 conductor segmental
Xs 0.5996
Ys 0.0007
CORRECIÓN POR EFECTO ESPACIAMIENTO
kp 1.00 conductor redondo0.37 conductor segmental
S 21.02 distancia entre centros de conductoresdc 8.52 diametro del conductor
Xp 0.5996
dc/S 0.1643Xp^4/(192+0,8*Xp^4) 0.0004
Yp 0.00029
Rac 90º C 0.41989 Ω/km
REACTANCIA DE SECUENCIA POSITIVA Y NEGATIVA
f = 60 Hz f = 60 HzS = 21.02 mm S = 0.8275590551 pulgadasGMD-3C = 21.02 mm GMD-3C = 0.8275590551 pulgadasrc = 4.26 mm rc = 0.1677165354 pulgadasGMR-1C = 3.31854 mm GMR-1C = 0.1306511811 pulgadas
x1 = x2 = 0.223990972 Ω/milla
x1 = x2 = 0.139210389 Ω/km
REACTANCIA DE SECUENCIA CERO
rc = resistencia AC del conductor (Ω/milla)re = resistencia AC debido al retorno por tierra (Ω/milla) Tabla.De = distancia equivalente (pulgadas) Tabla.
GMR-3C = 0.4472706941 pulgadasrc = 0.6756108396 Ω/millare = 0.286 Ω/milla
De = 7.44E+04 pulgadas
Zc = 0.597641136818319+2.71983582554436i Ω/km
rs = 0.001450811 Ω/millare = 0.286 Ω/millaDe = 7.44E+04 pulgadasro = 26.1 pulgadasri = 23.31 pulgadas
Zs = 0.180454037724722+1.81224438342381i Ω/km
re = 0.286 Ω/millaDe = 7.44E+04 pulgadasro = 26.1 pulgadasri = 23.31 pulgadas
Zm = 0.177749+1.81224438342381i Ω/km
Si I retorno lo hace por vaina y tierra:
Zo = 0.4225967764406+0.90759544014088i Ω/km
0.422596776 0.90759544
Si I retorno lo hace por vaina:
Zo = 0.422597174543041+0.90759144212055i Ω/km
0.422597175 0.90759144
Si I retorno lo hace por tierra:
Zo = 0.597641136818319+2.71983582554436i Ω/km
0.597641137 2.71983583
REACTANCIA CAPACITIVA
Aislamiento kVulcanel EP 2.6Vulcanel XLPEP 2.1SINTANEX 7Papel impregnado 3.9
k = 2.1Espesor Aisla. 4.45 mmT/d = 0.522G = 0.72C1 = C2 = C0 = 0.26017 uF/milla
C1 = C2 = C0 = 0.16169463 uF/km
B = 60.957441 uS/km
DATOS re Y De a 60 Hz.De re xe
pulgadas pies Ω/milla Ω/milla1 3.36E+03 280 0.286 2.055 7.44E+03 620 0.286 2.34
10 1.06E+04 880 0.286 2.4750 2.40E+04 2000 0.286 2.76
100 3.36E+04 2800 0.286 2.89
Resistividad suelo Ω/m
500 7.44E+04 6200 0.286 3.181000 1.06E+05 8800 0.286 3.315000 2.40E+05 20000 0.286 3.6
10000 3.36E+05 28000 0.286 3.73
CALCULO DE RESISTENCIA
DATOSCABLE No. 17-19,22-24,26 2 AWG TRIPOLAR Frecuencia 60 HzRdc 20º C 0.523 Ω/km
α234.5 Cu recocido con 100% de conductividad
228 Al recocido en frio241.5 Cu con 97,3% de conductividad
CORRECIÓN POR TEMPERATURA
Rdc 90º C = 0.6669 Ω/km
CORRECIÓN POR EFECTO PIEL
ks1.00 conductor redondo
0.435 conductor segmental
Xs 0.4755
Ys 0.0003
CORRECIÓN POR EFECTO ESPACIAMIENTO
kp 1.00 conductor redondo0.37 conductor segmental
S 19.34 distancia entre centros de conductoresdc 6.82 diametro del conductor
Xp 0.4755
dc/S 0.1244Xp^4/(192+0,8*Xp^4) 0.0001
Yp 0.00007
Rac 90º C 0.66707 Ω/km
REACTANCIA DE SECUENCIA POSITIVA Y NEGATIVA
f = 60 Hz f = 60 HzS = 19.34 mm S = 0.7614173228 pulgadasGMD-3C = 19.34 mm GMD-3C = 0.7614173228 pulgadasrc = 3.41 mm rc = 0.1342519685 pulgadasGMR-1C = 2.65639 mm GMR-1C = 0.1045822835 pulgadas
x1 = x2 = 0.240888798 Ω/milla
x1 = x2 = 0.149712388 Ω/km
REACTANCIA DE SECUENCIA CERO
rc = resistencia AC del conductor (Ω/milla)re = resistencia AC debido al retorno por tierra (Ω/milla) Tabla.De = distancia equivalente (pulgadas) Tabla.
GMR-3C = 0.3928570418 pulgadasrc = 1.0733223429 Ω/millare = 0.286 Ω/milla
De = 7.44E+04 pulgadas
Zc = 0.844818836109341+2.74918352322174i Ω/km
rs = 0.001564824 Ω/millare = 0.286 Ω/millaDe = 7.44E+04 pulgadasro = 24.3 pulgadasri = 21.51 pulgadas
Zs = 0.180666614363207+1.82935968172206i Ω/km
re = 0.286 Ω/millaDe = 7.44E+04 pulgadasro = 24.3 pulgadasri = 21.51 pulgadas
Zm = 0.177749+1.82935968172206i Ω/km
Si I retorno lo hace por vaina y tierra:
Zo = 0.669986995358609+0.91982844980594i Ω/km
0.669986995 0.91982845
Si I retorno lo hace por vaina:
Zo = 0.66998745047255+0.91982384149968i Ω/km
0.66998745 0.91982384
Si I retorno lo hace por tierra:
Zo = 0.844818836109341+2.74918352322174i Ω/km
0.844818836 2.74918352
REACTANCIA CAPACITIVA
Aislamiento kVulcanel EP 2.6Vulcanel XLPEP 2.1SINTANEX 7Papel impregnado 3.9
k = 2.1Espesor Aisla. 4.45 mmT/d = 0.652G = 0.84C1 = C2 = C0 = 0.223 uF/milla
C1 = C2 = C0 = 0.1385954 uF/km
B = 52.2492352 uS/km
DATOS re Y De a 60 Hz.De re xe
pulgadas pies Ω/milla Ω/milla1 3.36E+03 280 0.286 2.055 7.44E+03 620 0.286 2.34
10 1.06E+04 880 0.286 2.4750 2.40E+04 2000 0.286 2.76
100 3.36E+04 2800 0.286 2.89
Resistividad suelo Ω/m
500 7.44E+04 6200 0.286 3.181000 1.06E+05 8800 0.286 3.315000 2.40E+05 20000 0.286 3.6
10000 3.36E+05 28000 0.286 3.73
CALCULO DE RESISTENCIA
DATOSCABLE No. 31,32 500 MCM TRIPOLAR Frecuencia 60 HzRdc 20º C 0.0694 Ω/km
α234.5 Cu recocido con 100% de conductividad
228 Al recocido en frio241.5 Cu con 97,3% de conductividad
CORRECIÓN POR TEMPERATURA
Rdc 90º C = 0.0885 Ω/km
CORRECIÓN POR EFECTO PIEL
ks1.00 conductor redondo
0.435 conductor segmental
Xs 1.3054
Ys 0.0149
CORRECIÓN POR EFECTO ESPACIAMIENTO
kp 1.00 conductor redondo0.37 conductor segmental
S 31.2 distancia entre centros de conductoresdc 18.74 diametro del conductor
Xp 1.3054
dc/S 0.3608Xp^4/(192+0,8*Xp^4) 0.0195
Yp 0.02897
Rac 90º C 0.09237 Ω/km
REACTANCIA DE SECUENCIA POSITIVA Y NEGATIVA
f = 60 Hz f = 60 HzS = 31.2 mm S = 1.2283464567 pulgadasGMD-3C = 31.2 mm GMD-3C = 1.2283464567 pulgadasrc = 9.37 mm rc = 0.3688976378 pulgadasGMR-1C = 7.29923 mm GMR-1C = 0.2873712598 pulgadas
x1 = x2 = 0.176267186 Ω/milla
x1 = x2 = 0.109550056 Ω/km
REACTANCIA DE SECUENCIA CERO
DATOS re Y De a 60 Hz.rc = resistencia AC del conductor (Ω/milla)re = resistencia AC debido al retorno por tierra (Ω/milla) Tabla.De = distancia equivalente (pulgadas) Tabla. 1
5GMR-3C = 0.75688232 pulgadas 10rc = 0.14863072 Ω/milla 50re = 0.286 Ω/milla 100
Resistividad suelo Ω/m
De = 7.44E+04 pulgadas 5001000
Zc = 0.270122993729115+2.60082266032289i Ω/km 500010000
rs = 0.000766018 Ω/millare = 0.286 Ω/millaDe = 7.44E+04 pulgadasro = 38.45 pulgadasri = 34.89 pulgadas
Zs = 0.179177240946431+1.72288937904903i Ω/km
re = 0.286 Ω/millaDe = 7.44E+04 pulgadasro = 38.45 pulgadasri = 34.89 pulgadas
Zm = 0.177749+1.72288937904903i Ω/km
Si I retorno lo hace por vaina y tierra:
Zo = 0.09380211286102+0.87793445258865i Ω/km
0.093802113 0.87793445
Si I retorno lo hace por vaina:
Zo = 0.093802234675546+0.87793328127386i Ω/km
0.093802235 0.87793328
Si I retorno lo hace por tierra:
Zo = 0.270122993729115+2.60082266032289i Ω/km
0.270122994 2.60082266
REACTANCIA CAPACITIVA
Aislamiento kVulcanel EP 2.6Vulcanel XLPEP 2.1SINTANEX 7Papel impregnado 3.9
k = 2.1Espesor Aisla. 4.45 mmT/d = 0.237G = 0.4C1 = C2 = C0 0.4683 uF/milla
C1 = C2 = C0 0.29105034 uF/km
B = 109.723394 uS/km
DATOS re Y De a 60 Hz.De re xe
pulgadas pies Ω/milla Ω/milla3.36E+03 280 0.286 2.057.44E+03 620 0.286 2.341.06E+04 880 0.286 2.472.40E+04 2000 0.286 2.763.36E+04 2800 0.286 2.89
7.44E+04 6200 0.286 3.181.06E+05 8800 0.286 3.312.40E+05 20000 0.286 3.63.36E+05 28000 0.286 3.73
CALCULO DE RESISTENCIA
DATOSCABLE No. 3,6,7 1/0 AWG MONOPOLAR Frecuencia 60 HzRdc 20º C 0.329 Ω/km
α234.5 Cu recocido con 100% de conductividad
228 Al recocido en frio241.5 Cu con 97,3% de conductividad
CORRECIÓN POR TEMPERATURA
Rdc 90º C = 0.4195 Ω/km
CORRECIÓN POR EFECTO PIEL
ks1.00 conductor redondo
0.435 conductor segmental
Xs 0.5996
Ys 0.0007
CORRECIÓN POR EFECTO ESPACIAMIENTO
kp 1.00 conductor redondo0.37 conductor segmental
S 25.1 distancia entre centros de conductoresdc 8.52 diametro del conductor
Xp 0.5996
dc/S 0.1152Xp^4/(192+0,8*Xp^4) 0.0004
Yp 0.00020
Rac 90º C 0.41986 Ω/km 0.32928809
REACTANCIA DE SECUENCIA POSITIVA Y NEGATIVA
DONDE:
S = distancia entre centros de conductores en pulgadasro = radio externo de la vaina pulgadasri = radio interno de la vaina pulgadas
f = 60 Hz f = 60 HzS = 25.1 mm S = 0.9881889764 pulgadasSab = 25.1 mmSbc = 25.1 mmSca = 50.2 mmGMD-3C = 31.6240184 mm GMD-3C = 1.2450400926 pulgadasGMR-1C = 3.31854 mm GMR-1C = 0.1306511811 pulgadasro = 12.55 mm ro = 0.4940944882 pulgadasri = 10.52 mm ri = 0.4141732283 pulgadas
rs = 2.75520423 Ω/milla
Xm = 0.094341121 Ω/millax1 = x2 = 0.273441676 Ω/milla
x1 = x2 = 0.169944002 Ω/km
REACTANCIA DE SECUENCIA CERO
DATOS re Y De a 60 Hz.rc = resistencia AC del conductor (Ω/milla)re = resistencia AC debido al retorno por tierra (Ω/milla) Tabla.De = distancia equivalente (pulgadas) Tabla. 1GMR-1C = 0.13065118 pulgadas 5GMD-3C = 1.24504009 pulgadas 10GMR-3C= 0.58725493 pulgadas 50rc = 0.6755523 Ω/milla 100re = 0.286 Ω/milla 500De = 7.44E+04 pulgadas 1000
5000Zc = 0.59760475580126+2.65823127250919i Ω/km 10000
rs = 2.75520423 Ω/millare = 0.286 Ω/millaDe = 7.44E+04 pulgadasro = 0.494094488 pulgadasri = 0.414173228 pulgadasGMR-3S = 0.889576944 pulgadas
Zs = 1.89010842868246+2.56427594198125i Ω/km
re = 0.286 Ω/milla
Resistividad suelo Ω/m
De = 7.44E+04 pulgadasro = 0.494094488 pulgadasri = 0.414173228 pulgadasGMR-3C-ES = 0.889576944 pulgadas
Zm = 0.177749+2.56427594198125i Ω/km
Si I retorno lo hace por vaina y tierra:
Zo = 1.58608620623317+0.83487864418296i Ω/km
1.586086206 0.83487864
Si I retorno lo hace por vaina:
Zo = 2.13221518448372+0.0939553305279395iΩ/km
2.132215184 0.09395533
Si I retorno lo hace por tierra:
Zo = 0.59760475580126+2.65823127250919i Ω/km
0.597604756 2.65823127
REACTANCIA CAPACITIVA
Aislamiento kVulcanel EP 2.6Vulcanel XLPEP 2.1SINTANEX 7Papel impregnado 3.9
k = 2.1Espesor Aisla. 4.45 mmT/d = 0.522G = 0.71C1 = C2 = C0 0.263830986 uF/milla
C1 = C2 = C0 0.163972024 uF/km
B = 61.81599655 uS/km
DATOS re Y De a 60 Hz.De re xe
pulgadas pies Ω/milla Ω/milla3.36E+03 280 0.286 2.057.44E+03 620 0.286 2.341.06E+04 880 0.286 2.472.40E+04 2000 0.286 2.763.36E+04 2800 0.286 2.897.44E+04 6200 0.286 3.181.06E+05 8800 0.286 3.312.40E+05 20000 0.286 3.63.36E+05 28000 0.286 3.73
CALCULO DE RESISTENCIA
DATOSCABLE No. 4,10,11 250 MCM MONOPOLAR Frecuencia 60 HzRdc 20º C 0.139 Ω/km
α234.5 Cu recocido con 100% de conductividad
228 Al recocido en frio241.5 Cu con 97,3% de conductividad
CORRECIÓN POR TEMPERATURA
Rdc 90º C = 0.1772 Ω/km
CORRECIÓN POR EFECTO PIEL
ks1.00 conductor redondo
0.435 conductor segmental
Xs 0.9224
Ys 0.0038
CORRECIÓN POR EFECTO ESPACIAMIENTO
kp 1.00 conductor redondo0.37 conductor segmental
S 29.8 distancia entre centros de conductoresdc 13.26 diametro del conductor
Xp 0.9224
dc/S 0.1980Xp^4/(192+0,8*Xp^4) 0.0035
Yp 0.00297
Rac 90º C 0.17842 Ω/km
REACTANCIA DE SECUENCIA POSITIVA Y NEGATIVA
DONDE:
S = distancia entre centros de conductores en pulgadasro = radio externo de la vaina pulgadasri = radio interno de la vaina pulgadas
f = 60 Hz f = 60 HzS = 29.8 mm S = 1.1732283465 pulgadasSab = 29.8 mmSbc = 29.8 mmSca = 59.6 mmGMD-3C = 37.5456473 mm GMD-3C = 1.47817509 pulgadasGMR-1C = 5.16477 mm GMR-1C = 0.2033374016 pulgadasro = 14.9 mm ro = 0.5866141732 pulgadasri = 12.87 mm ri = 0.5066929134 pulgadas
rs = 2.288893107 Ω/milla
Xm = 0.092668704 Ω/millax1 = x2 = 0.240553858 Ω/milla
x1 = x2 = 0.149504222 Ω/km
REACTANCIA DE SECUENCIA CERO
DATOS re Y De a 60 Hz.rc = resistencia AC del conductor (Ω/milla)re = resistencia AC debido al retorno por tierra (Ω/milla) Tabla.De = distancia equivalente (pulgadas) Tabla. 1GMR-1C = 0.2033374 pulgadas 5GMD-3C = 1.47817509 pulgadas 10GMR-3C= 0.76305588 pulgadas 50rc = 0.28708516 Ω/milla 100re = 0.286 Ω/milla 500De = 7.44E+04 pulgadas 1000
5000Zc = 0.356172427428271+2.59898478959071i Ω/km 10000
rs = 2.288893107 Ω/millare = 0.286 Ω/millaDe = 7.44E+04 pulgadasro = 0.586614173 pulgadasri = 0.506692913 pulgadasGMR-3S = 1.061014475 pulgadas
Zs = 1.60029606588781+2.52440424608666i Ω/km
re = 0.286 Ω/milla
Resistividad suelo Ω/m
De = 7.44E+04 pulgadasro = 0.586614173 pulgadasri = 0.506692913 pulgadasGMR-3C-ES = 1.061014475 pulgadas
Zm = 0.177749+2.52440424608666i Ω/km
Si I retorno lo hace por vaina y tierra:
Zo = 1.23846978576781+0.64641118462769i Ω/km
1.238469786 0.64641118
Si I retorno lo hace por vaina:
Zo = 1.60097049331608+0.0745805435040499iΩ/km
1.600970493 0.07458054
Si I retorno lo hace por tierra:
Zo = 0.356172427428271+2.59898478959071i Ω/km
0.356172427 2.59898479
REACTANCIA CAPACITIVA
Aislamiento kVulcanel EP 2.6Vulcanel XLPEP 2.1SINTANEX 7Papel impregnado 3.9
k = 2.1Espesor Aisla. 4.45 mmT/d = 0.336G = 0.48C1 = C2 = C0 0.39025 uF/milla
C1 = C2 = C0 0.242541952 uF/km
B = 91.43616157 uS/km
DATOS re Y De a 60 Hz.De re xe
pulgadas pies Ω/milla Ω/milla3.36E+03 280 0.286 2.057.44E+03 620 0.286 2.341.06E+04 880 0.286 2.472.40E+04 2000 0.286 2.763.36E+04 2800 0.286 2.897.44E+04 6200 0.286 3.181.06E+05 8800 0.286 3.312.40E+05 20000 0.286 3.63.36E+05 28000 0.286 3.73
CALCULO DE RESISTENCIA
DATOSCABLE No. 12 2/0 AWG MONOPOLAR Frecuencia 60 HzRdc 20º C 0.261 Ω/km
α234.5 Cu recocido con 100% de conductividad
228 Al recocido en frio241.5 Cu con 97,3% de conductividad
CORRECIÓN POR TEMPERATURA.
Rdc 90º C = 0.3328 Ω/km
CORRECIÓN POR EFECTO PIEL
ks1.00 conductor redondo
0.435 conductor segmental
Xs 0.6731
Ys 0.0011
CORRECIÓN POR EFECTO ESPACIAMIENTO
kp 1.00 conductor redondo0.37 conductor segmental
S 26.1 distancia entre centros de conductoresdc 9.57 diametro del conductor
Xp 0.6731
dc/S 0.1344Xp^4/(192+0,8*Xp^4) 0.0007
Yp 0.00042
Rac 90º C 0.33328 Ω/km
REACTANCIA DE SECUENCIA POSITIVA Y NEGATIVA
DONDE:
S = distancia entre centros de conductores en pulgadasro = radio externo de la vaina pulgadasri = radio interno de la vaina pulgadas
f = 60 Hz f = 60 HzS = 26.1 mm S = 1.0275590551 pulgadasSab = 26.1 mmSbc = 26.1 mmSca = 52.2 mmGMD-3C = 32.8839394 mm GMD-3C = 1.2946432836 pulgadasGMR-1C = 3.727515 mm GMR-1C = 0.1467525591 pulgadasro = 13.05 mm ro = 0.5137795276 pulgadasri = 11.02 mm ri = 0.4338582677 pulgadas
rs = 2.640737913 Ω/milla
Xm = 0.093932719 Ω/millax1 = x2 = 0.264072004 Ω/milla
x1 = x2 = 0.164120751 Ω/km
REACTANCIA DE SECUENCIA CERO
DATOS re Y De a 60 Hz.rc = resistencia AC del conductor (Ω/milla)re = resistencia AC debido al retorno por tierra (Ω/milla) Tabla.De = distancia equivalente (pulgadas) Tabla. 1GMR-1C = 0.14675256 pulgadas 5GMD-3C = 1.29464328 pulgadas 10GMR-3C= 0.62655901 pulgadas 50rc = 0.53625372 Ω/milla 100re = 0.286 Ω/milla 500De = 7.44E+04 pulgadas 1000
5000Zc = 0.511030685831354+2.64357443019441i Ω/km 10000
rs = 2.640737913 Ω/millare = 0.286 Ω/millaDe = 7.44E+04 pulgadasro = 0.513779528 pulgadasri = 0.433858268 pulgadasGMR-3S = 0.926056621 pulgadas
Zs = 1.81896761319919+2.55518342081536i Ω/km
re = 0.286 Ω/milla
Resistividad suelo Ω/m
De = 7.44E+04 pulgadasro = 0.513779528 pulgadasri = 0.433858268 pulgadasGMR-3C-ES = 0.926056621 pulgadas
Zm = 0.177749+2.55518342081536i Ω/km
Si I retorno lo hace por vaina y tierra:
Zo = 1.47645547454995+0.78801637329494i Ω/km
1.476455475 0.78801637
Si I retorno lo hace por vaina:
Zo = 1.97450029903054+0.0883910093790501iΩ/km
1.974500299 0.08839101
Si I retorno lo hace por tierra:
Zo = 0.511030685831354+2.64357443019441i Ω/km
0.511030686 2.64357443
REACTANCIA CAPACITIVA
Aislamiento kVulcanel EP 2.6Vulcanel XLPEP 2.1SINTANEX 7Papel impregnado 3.9
k = 2.1Espesor Aisla. 4.45 mmT/d = 0.465G = 0.66C1 = C2 = C0 0.283818182 uF/milla
C1 = C2 = C0 0.176394147 uF/km
B = 66.4990266 uS/km
DATOS re Y De a 60 Hz.De re xe
pulgadas pies Ω/milla Ω/milla3.36E+03 280 0.286 2.057.44E+03 620 0.286 2.341.06E+04 880 0.286 2.472.40E+04 2000 0.286 2.763.36E+04 2800 0.286 2.897.44E+04 6200 0.286 3.181.06E+05 8800 0.286 3.312.40E+05 20000 0.286 3.63.36E+05 28000 0.286 3.73
CALCULO DE RESISTENCIA
DATOSCABLE No. C13-C16,C20,2 AWG MONOPOLAR Frecuencia 60 HzRdc 20º C 0.523 Ω/km
α234.5 Cu recocido con 100% de conductividad
228 Al recocido en frio241.5 Cu con 97,3% de conductividad
CORRECIÓN POR TEMPERATURA.
Rdc 90º C = 0.6669 Ω/km
CORRECIÓN POR EFECTO PIEL
ks1.00 conductor redondo
0.435 conductor segmental
Xs 0.4755
Ys 0.0003
CORRECIÓN POR EFECTO ESPACIAMIENTO
kp 1.00 conductor redondo0.37 conductor segmental
S 23.4 distancia entre centros de conductoresdc 6.81 diametro del conductor
Xp 0.4755
dc/S 0.0847Xp^4/(192+0,8*Xp^4) 0.0001
Yp 0.00005
Rac 90º C 0.66706 Ω/km
REACTANCIA DE SECUENCIA POSITIVA Y NEGATIVA
DONDE:
S = distancia entre centros de conductores en pulgadasro = radio externo de la vaina pulgadasri = radio interno de la vaina pulgadas
f = 60 Hz f = 60 HzS = 23.4 mm S = 0.9212598425 pulgadasSab = 23.4 mmSbc = 23.4 mmSca = 46.8 mmGMD-3C = 29.4821526 mm GMD-3C = 1.160714668 pulgadasGMR-1C = 2.652495 mm GMR-1C = 0.104428937 pulgadasro = 11.7 mm ro = 0.4606299213 pulgadasri = 9.67 mm ri = 0.3807086614 pulgadas
rs = 2.974382853 Ω/milla
Xm = 0.095119308 Ω/millax1 = x2 = 0.292128571 Ω/milla
x1 = x2 = 0.181557907 Ω/km
REACTANCIA DE SECUENCIA CERO
DATOS re Y De a 60 Hz.rc = resistencia AC del conductor (Ω/milla)re = resistencia AC debido al retorno por tierra (Ω/milla) Tabla.De = distancia equivalente (pulgadas) Tabla. 1GMR-1C = 0.10442894 pulgadas 5GMD-3C = 1.16071467 pulgadas 10GMR-3C= 0.52010449 pulgadas 50rc = 1.07329875 Ω/milla 100re = 0.286 Ω/milla 500De = 7.44E+04 pulgadas 1000
5000Zc = 0.844804173917203+2.68570366954478i Ω/km 10000
rs = 2.974382853 Ω/millare = 0.286 Ω/millaDe = 7.44E+04 pulgadasro = 0.460629921 pulgadasri = 0.380708661 pulgadasGMR-3S = 0.827555733 pulgadas
Zs = 2.02632794336474+2.58062634462735i Ω/km
re = 0.286 Ω/milla
Resistividad suelo Ω/m
De = 7.44E+04 pulgadasro = 0.460629921 pulgadasri = 0.380708661 pulgadasGMR-3C-ES = 0.827555733 pulgadas
Zm = 0.177749+2.58062634462735i Ω/km
Si I retorno lo hace por vaina y tierra:
Zo = 1.87243417854439+0.92422346175281i Ω/km
1.872434179 0.92422346
Si I retorno lo hace por vaina:
Zo = 2.51563411728194+0.10507732491743i Ω/km
2.515634117 0.10507732
Si I retorno lo hace por tierra:
Zo = 0.844804173917203+2.68570366954478i Ω/km
0.844804174 2.68570367
REACTANCIA CAPACITIVA
Aislamiento kVulcanel EP 2.6Vulcanel XLPEP 2.1SINTANEX 7Papel impregnado 3.9
k = 2.1Espesor Aisla. 4.45 mmT/d = 0.653G = 0.88C1 = C2 = C0 0.212863636 uF/milla
C1 = C2 = C0 0.13229561 uF/km
B = 49.87426995 uS/km
DATOS re Y De a 60 Hz.De re xe
pulgadas pies Ω/milla Ω/milla3.36E+03 280 0.286 2.057.44E+03 620 0.286 2.341.06E+04 880 0.286 2.472.40E+04 2000 0.286 2.763.36E+04 2800 0.286 2.897.44E+04 6200 0.286 3.181.06E+05 8800 0.286 3.312.40E+05 20000 0.286 3.63.36E+05 28000 0.286 3.73
CALCULO DE RESISTENCIA
DATOSCABLE No. 35 500 MCM MONOPOLAR Frecuencia 60 HzRdc 20º C 0.0694 Ω/km
α234.5 Cu recocido con 100% de conductividad
228 Al recocido en frio241.5 Cu con 97,3% de conductividad
CORRECIÓN POR TEMPERATURA.
Rdc 90º C = 0.0885 Ω/km
CORRECIÓN POR EFECTO PIEL
ks1.00 conductor redondo
0.435 conductor segmental
Xs 1.3054
Ys 0.0149
CORRECIÓN POR EFECTO ESPACIAMIENTO
kp 1.00 conductor redondo0.37 conductor segmental
S 35.8 distancia entre centros de conductoresdc 18.74 diametro del conductor
Xp 1.3054
dc/S 0.2740Xp^4/(192+0,8*Xp^4) 0.0195
Yp 0.02191
Rac 90º C 0.09175 Ω/km
REACTANCIA DE SECUENCIA POSITIVA Y NEGATIVA
DONDE:
S = distancia entre centros de conductores en pulgadasro = radio externo de la vaina pulgadasri = radio interno de la vaina pulgadas
f = 60 Hz f = 60 HzS = 35.8 mm S = 1.4094488189 pulgadasSab = 35.8 mmSbc = 35.8 mmSca = 71.6 mmGMD-3C = 45.1051736 mm GMD-3C = 1.7757942357 pulgadasGMR-1C = 7.29923 mm GMR-1C = 0.2873712598 pulgadasro = 17.9 mm ro = 0.7047244094 pulgadasri = 15.87 mm ri = 0.6248031496 pulgadas
rs = 1.882219768 Ω/milla
Xm = 0.09119112 Ω/millax1 = x2 = 0.220777688 Ω/milla
x1 = x2 = 0.137213333 Ω/km
REACTANCIA DE SECUENCIA CERO
DATOS re Y De a 60 Hz.rc = resistencia AC del conductor (Ω/milla)re = resistencia AC debido al retorno por tierra (Ω/milla) Tabla.De = distancia equivalente (pulgadas) Tabla. 1GMR-1C = 0.28737126 pulgadas 5GMD-3C = 1.77579424 pulgadas 10GMR-3C= 0.96770475 pulgadas 50rc = 0.14762567 Ω/milla 100re = 0.286 Ω/milla 500De = 7.44E+04 pulgadas 1000
5000Zc = 0.269498353896613+2.54523066492361i Ω/km 10000
rs = 1.882219768 Ω/millare = 0.286 Ω/millaDe = 7.44E+04 pulgadasro = 0.704724409 pulgadasri = 0.62480315 pulgadasGMR-3S = 1.279825849 pulgadas
Zs = 1.34754858601435+2.48198422072347i Ω/km
re = 0.286 Ω/milla
Resistividad suelo Ω/m
De = 7.44E+04 pulgadasro = 0.704724409 pulgadasri = 0.62480315 pulgadasGMR-3C-ES = 1.279825849 pulgadas
Zm = 0.177749+2.48198422072347i Ω/km
Si I retorno lo hace por vaina y tierra:
Zo = 1.0303557806553+0.48906988327104i Ω/km
1.030355781 0.48906988
Si I retorno lo hace por vaina:
Zo = 1.26154893991096+0.0632464442001401iΩ/km
1.26154894 0.06324644
Si I retorno lo hace por tierra:
Zo = 0.269498353896613+2.54523066492361i Ω/km
0.269498354 2.54523066
REACTANCIA CAPACITIVA
Aislamiento kVulcanel EP 2.6Vulcanel XLPEP 2.1SINTANEX 7Papel impregnado 3.9
k = 2.1Espesor Aisla. 4.45 mmT/d = 0.237G = 0.4C1 = C2 = C0 0.4683 uF/milla
C1 = C2 = C0 0.291050342 uF/km
B = 109.7233939 uS/km
DATOS re Y De a 60 Hz.De re xe
pulgadas pies Ω/milla Ω/milla3.36E+03 280 0.286 2.057.44E+03 620 0.286 2.341.06E+04 880 0.286 2.472.40E+04 2000 0.286 2.763.36E+04 2800 0.286 2.897.44E+04 6200 0.286 3.181.06E+05 8800 0.286 3.312.40E+05 20000 0.286 3.63.36E+05 28000 0.286 3.73
CALCULO DE RESISTENCIA
DATOSCABLE No. 36 266.8 MCM ACSR MONOPOLAR Frecuencia 60 HzRdc 20º C 0.211 Ω/km
α234.5 Cu recocido con 100% de conductividad
228 Al recocido en frio241.5 Cu con 97,3% de conductividad
CORRECIÓN POR TEMPERATURA.
Rdc 90º C = 0.2690 Ω/km
CORRECIÓN POR EFECTO PIEL
ks1.00 conductor redondo
0.435 conductor segmental
Xs 0.7487
Ys 0.0016
CORRECIÓN POR EFECTO ESPACIAMIENTO
kp 1.00 conductor redondo0.37 conductor segmental
S 24.6 distancia entre centros de conductoresdc 15 diametro del conductor
Xp 0.7487
dc/S 0.3718Xp^4/(192+0,8*Xp^4) 0.0012
Yp 0.00200
Rac 90º C 0.27001 Ω/km
REACTANCIA DE SECUENCIA POSITIVA Y NEGATIVA
DONDE:
S = distancia entre centros de conductores en pulgadasro = radio externo de la vaina pulgadasri = radio interno de la vaina pulgadas
f = 60 Hz f = 60 HzS = 24.6 mm S = 0.968503937 pulgadasSab = 24.6 mmSbc = 24.6 mmSca = 49.2 mmGMD-3C = 30.9940578 mm GMD-3C = 1.2202384971 pulgadasGMR-1C = 5.8425 mm GMR-1C = 0.230019685 pulgadasro = 12.3 mm ro = 0.4842519685 pulgadasri = 10.39 mm ri = 0.4090551181 pulgadas
rs = 2.977347772 Ω/milla
Xm = 0.093914892 Ω/millax1 = x2 = 0.202382164 Ω/milla
x1 = x2 = 0.125780515 Ω/km
REACTANCIA DE SECUENCIA CERO
DATOS re Y De a 60 Hz.rc = resistencia AC del conductor (Ω/milla)re = resistencia AC debido al retorno por tierra (Ω/milla) Tabla.De = distancia equivalente (pulgadas) Tabla. 1GMR-1C = 0.23001969 pulgadas 5GMD-3C = 1.2202385 pulgadas 10GMR-3C= 0.69965641 pulgadas 50rc = 0.43445046 Ω/milla 100re = 0.286 Ω/milla 500De = 7.44E+04 pulgadas 1000
5000Zc = 0.447759959742232+2.61860944348463i Ω/km 10000
rs = 2.977347772 Ω/millare = 0.286 Ω/millaDe = 7.44E+04 pulgadasro = 0.484251969 pulgadasri = 0.409055118 pulgadasGMR-3S = 0.872877722 pulgadas
Zs = 2.028170640181+2.56856334573083i Ω/km
re = 0.286 Ω/milla
Resistividad suelo Ω/m
De = 7.44E+04 pulgadasro = 0.484251969 pulgadasri = 0.409055118 pulgadasGMR-3C-ES = 0.872877722 pulgadas
Zm = 0.177749+2.56856334573083i Ω/km
Si I retorno lo hace por vaina y tierra:
Zo = 1.4720727383293+0.87115717309441i Ω/km
1.472072738 0.87115717
Si I retorno lo hace por vaina:
Zo = 2.12043259992323+0.0500460977538006iΩ/km
2.1204326 0.0500461
Si I retorno lo hace por tierra:
Zo = 0.447759959742232+2.61860944348463i Ω/km
0.44775996 2.61860944
REACTANCIA CAPACITIVA
Aislamiento kVulcanel EP 2.6Vulcanel XLPEP 2.1SINTANEX 7Papel impregnado 3.9
k = 2.1Espesor Aisla. 4.45 mmT/d = 0.297G = 0.48C1 = C2 = C0 0.39025 uF/milla
C1 = C2 = C0 0.242541952 uF/km
B = 91.43616157 uS/km
DATOS re Y De a 60 Hz.De re xe
pulgadas pies Ω/milla Ω/milla3.36E+03 280 0.286 2.057.44E+03 620 0.286 2.341.06E+04 880 0.286 2.472.40E+04 2000 0.286 2.763.36E+04 2800 0.286 2.897.44E+04 6200 0.286 3.181.06E+05 8800 0.286 3.312.40E+05 20000 0.286 3.63.36E+05 28000 0.286 3.73
CALCULO DE RESISTENCIA
DATOSCABLE No. 35 500 MCM MONOPOLAR Frecuencia 60 HzRdc 20º C 0.0694 Ω/km
α234.5 Cu recocido con 100% de conductividad
228 Al recocido en frio241.5 Cu con 97,3% de conductividad
CORRECIÓN POR TEMPERATURA.
Rdc 90º C = 0.0885 Ω/km
CORRECIÓN POR EFECTO PIEL
ks1.00 conductor redondo
0.435 conductor segmental
Xs 1.3054
Ys 0.0149
CORRECIÓN POR EFECTO ESPACIAMIENTO
kp 1.00 conductor redondo0.37 conductor segmental
S 35.8 distancia entre centros de conductoresdc 18.74 diametro del conductor
Xp 1.3054
dc/S 0.2740Xp^4/(192+0,8*Xp^4) 0.0195
Yp 0.02191
Rac 90º C 0.09175 Ω/km
REACTANCIA DE SECUENCIA POSITIVA Y NEGATIVA
DONDE:
S = distancia entre centros de conductores en pulgadasro = radio externo de la vaina pulgadasri = radio interno de la vaina pulgadas
f = 60 Hz f = 60 HzS = 35.8 mm S = 1.4094488189 pulgadasSab = 35.8 mmSbc = 35.8 mmSca = 71.6 mmGMD-3C = 45.1051736 mm GMD-3C = 1.7757942357 pulgadasGMR-1C = 7.29923 mm GMR-1C = 0.2873712598 pulgadasro = 17.9 mm ro = 0.7047244094 pulgadasri = 15.87 mm ri = 0.6248031496 pulgadas
rs = 1.882219768 Ω/milla
Xm = 0.09119112 Ω/millax1 = x2 = 0.220777688 Ω/milla
x1 = x2 = 0.137213333 Ω/km
REACTANCIA DE SECUENCIA CERO
DATOS re Y De a 60 Hz.rc = resistencia AC del conductor (Ω/milla)re = resistencia AC debido al retorno por tierra (Ω/milla) Tabla.De = distancia equivalente (pulgadas) Tabla. 1GMR-1C = 0.28737126 pulgadas 5GMD-3C = 1.77579424 pulgadas 10GMR-3C= 0.96770475 pulgadas 50rc = 0.14762567 Ω/milla 100re = 0.286 Ω/milla 500De = 7.44E+04 pulgadas 1000
5000Zc = 0.269498353896613+2.54523066492361i Ω/km 10000
rs = 1.882219768 Ω/millare = 0.286 Ω/millaDe = 7.44E+04 pulgadasro = 0.704724409 pulgadasri = 0.62480315 pulgadasGMR-3S = 1.279825849 pulgadas
Zs = 1.34754858601435+2.48198422072347i Ω/km
re = 0.286 Ω/milla
Resistividad suelo Ω/m
De = 7.44E+04 pulgadasro = 0.704724409 pulgadasri = 0.62480315 pulgadasGMR-3C-ES = 1.279825849 pulgadas
Zm = 0.177749+2.48198422072347i Ω/km
Si I retorno lo hace por vaina y tierra:
Zo = 1.0303557806553+0.48906988327104i Ω/km
1.030355781 0.48906988
Si I retorno lo hace por vaina:
Zo = 1.26154893991096+0.0632464442001401iΩ/km
1.26154894 0.06324644
Si I retorno lo hace por tierra:
Zo = 0.269498353896613+2.54523066492361i Ω/km
0.269498354 2.54523066
REACTANCIA CAPACITIVA
Aislamiento kVulcanel EP 2.6Vulcanel XLPEP 2.1SINTANEX 7Papel impregnado 3.9
k = 2.1Espesor Aisla. 4.45 mmT/d = 0.237G = 0.4C1 = C2 = C0 0.4683 uF/milla
C1 = C2 = C0 0.291050342 uF/km
B = 109.7233939 uS/km
DATOS re Y De a 60 Hz.De re xe
pulgadas pies Ω/milla Ω/milla3.36E+03 280 0.286 2.057.44E+03 620 0.286 2.341.06E+04 880 0.286 2.472.40E+04 2000 0.286 2.763.36E+04 2800 0.286 2.897.44E+04 6200 0.286 3.181.06E+05 8800 0.286 3.312.40E+05 20000 0.286 3.63.36E+05 28000 0.286 3.73