MODULO BM-E8
Módulo AmbienteInstrucciones de Instalación,Montaje y Funcionamiento para elINSTALADOR y USUARIO
E
GB
Room ModuleInstallation, Assembly,and Operating Instructions for theINSTALLER and the USER
PT
Módulo AmbienteInstruções de Instalação,Montagem e Funcionamento para oINSTALADOR e UTILIZADOR
2
1. DESCRIPTION AND MAIN FEATURES Page 101.1 General Description Page 101.2 Delivery Page 101.3 Main Features Page 10
2. ASSEMBLY AND INSTALLATION Page 102.1 Wiring Diagrams Page 102.2 Installation Diagrams Page 102.3 Controller Installation via a BUS System Page 10
3. OPERATION Page 103.1 Operating Mode Page 103.2 Programming Mode Page 113.3 Programming Areas and Levels Page 113.4 GENERAL Area > DATE / TIME Page 113.5 GENERAL Area > SERVICE Page 123.6 DISPLAY Area Page 123.7 USER Area Page 133.8 TIME PROGRAM Area Page 143.9 EXPERT Area Page 153.10 System Protection Features Page 16
4. FAULT CODES Page 16
GB
PT
1. DESCRIÇÃO E CARACTERÍSTICAS PRINCIPAIS Pág. 171.1 Descrição geral Pág. 171.2 Forma de fornecimento Pág. 171.3 Características principais Pág. 17
2. MONTAGEM E INSTALAÇÃO Pág. 172.1 Esquemas de ligação eléctrica Pág. 172.2 Esquemas de instalação Pág. 172.3 Instalação de centrais via Bus Pág. 17
3. FUNCIONAMENTO Pág. 173.1 Modo de funcionamento Pág. 173.2 Modo de programação Pág. 183.3 Áreas e níveis de programação Pág. 183.4 Área GERAL > DATA /HORA Pág. 183.5 Área GERAL > SERVIÇO Pág. 193.6 Área VISUALIZAR Pág. 193.7 Área UTILIZADOR Pág. 203.8 Área PRO CRONOLOG Pág. 213.9 Área PERITO Pág. 223.10 Funções de protecção do sistema Pág. 23
4. ANOMALIAS Pág. 23
ES
1. DESCRIPCIÓN Y CARACTERÍSTICASPRINCIPALES Pág. 3
1.1 Descripción general Pág. 31.2 Forma de suministro Pág. 31.3 Características principales Pág. 3
2. MONTAJE E INSTALACIÓN Pág. 32.1 Esquemas de conexión eléctrica Pág. 32.2 Esquemas de instalación Pág. 32.3 Instalación centralitas vía Bus Pág. 3
3. FUNCIONAMIENTO Pág. 33.1 Modo funcionamiento Pág. 33.2 Modo programación Pág. 43.3 Areas y niveles de programación Pág. 43.4 Área GENERAL > FECHA / HORA Pág. 43.5 Área GENERAL > SERVICIO Pág. 53.6 Área INDICACIÓN Pág. 53.7 Área USUARIO Pág. 63.8 Área PROG TIEMPO Pág. 73.9 Área TÉCNICO Pág. 83.10 Funciones de protección del sistema Pág. 9
4. ANOMALIAS Pag. 9
3
1. DESCRIPCIÓN Y CARACTERÍSTICAS PRINCIPALES
1.1. Descripción general
BM-E8El módulo ambiente BM-E8 está destinado a la conexión vía BUS conuna centralita E8 ó E9, permitiendo el acceso a la visualización yprogramación de los parámetros del circuito regulados por la centralita.El módulo está equipado con una sonda de temperatura ambiente.
1.2. Forma de suministroEn un solo bulto
1.3. Características principalesTensión de alimentación: 12 V= +/- 15%Potencia absorbida: 1 W máximoTemperatura ambiente admisible en funcionamiento: 0 °C ÷ 50 °CTemperatura ambiente admisible en almacén: - 30°C ÷ 60 °CReserva cuerda del reloj: > 10 horasTipo de protección: IP40 según Norma EN 60 529Resistencia de sondas: PTC 1K
2. MONTAJE E INSTALACIÓN
Separar el frontal de la base de fijación mural según se indica en la figura.
Fijar la base a la pared (los orificios A están destinados a los tornillos defijación y los B al paso del cable de conexión)Efectuar la conexión mediante cable telefónico (4 hilos 2 x 0,8 mm2) en laregleta C, según:
- Borne 1: BUS H- Borne 2: BUS L- Borne 3: BUS –- Borne 4: BUS +
A una central E8 ó E9 se pueden conectar vía BUS tantos módulos BM-E8, como circuitos de calefacción se gestionen.
3. FUNCIONAMIENTO
3.1. Modo funcionamientoCorresponde al funcionamiento normal del módulo con la tapa cerrada.
E
Ajuste de la temperatura ambiente
Selector modo de funcionamiento
Desconexión temporal del circuito (ECO)
Prolongación periodo de calefacción
SELECCIÓN DEL MODO DE FUNCIONAMIENTO
Son seleccionables los siguientes modos de funcionamiento:
El cambio de un modo de funcionamiento a otro no es efectivo hastatranscurridos unos 5s.
DESCONEXIÓN TEMPORAL DEL CIRCUITO (ECO)
Función para ahorro energético. Permite la desconexión temporal de lainstalación cuando abandonamos la vivienda durante unas horas.
Pulsar la tecla . El display muestra el aspecto de la imagen.
Pulsar la tecla para aumentar en 1h el tiempo de desconexión delcircuito.
Pulsar la tecla para disminuir en 1h el tiempo de desconexión delcircuito.
Pulsar la tecla durante 3 seg. para que el circuito de calefacciónpase al modo reducido hasta el primer ciclo de funcionamientoconfort del día siguiente.
Nota: Durante el tiempo establecido como desconexión, el circuito decalefacción se regula a las temperaturas configuradas para elfuncionamiento reducido
PROLONGACIÓN PERIODO CALEFACCIÓN
Permite prolongar el funcionamiento del ciclo de calefacción un determinadoperiodo de tiempo.
Pulsar la tecla . El display muestra el aspecto de la imagen.
Pulsar la tecla para aumentar en 1h el tiempo de desconexión delcircuito.
Pulsar la tecla para disminuir en 1h el tiempo de desconexión delcircuito.
Pulsar la tecla durante 3 seg. para que el circuito de calefacciónpase al modo confort hasta el primer ciclo de funcionamientoconfort del día siguiente.
arepsE:sadalehitnanóicnufolóS.oicivresedareufSCAynóiccafelaCroiretxearutarepmetaleuqerpmeissotiucricsolnáratcenoces
.adanoiccelessadalehitnaedalaroirefniolaugiaes
ocitámotuA1
ysoirarohsolnúgesnalugeresnóiccafelacedsotiucricsoLoiporpusnúgesSCAedoicivreS.1amargorpledsarutarepmet
.amargorp
ocitámotuA2
ysoirarohsolnúgesnalugeresnóiccafelacedsotiucricsoLoiporpusnúgesSCAedoicivreS.2amargorpledsarutarepmet
.amargorp
SCASCAedotiucriclE.airatinaSetneilaCaugAednóicaraperpoloS
.odicelbatseamargorplenúgesalugeres
trofnoC)LOS(
alnúgessaroh42salnalugeresnóiccafelaCedsotiucricsoLotneimanoicnufarapadamargorp1etneibmaedarutarepmetodicelbatseamargorplenúgesalugeresSCAedotiucriclE."LOS"
odicudeR)ANUL(
alnúgessaroh42salnalugeresnóiccafelaCedsotiucricsoLotneimanoicnufarapadamargorpetneibmaedarutarepmetodicelbatseamargorplenúgesalugeresSCAedotiucriclE."ANUL"
4
AJUSTE TEMPERATURA AMBIENTE
En la posición intermedia latemperatura de consigna del ambiente es de 20°C:
Giro a derechas: en cada puntoaumenta 1°C la temperaturade consiganGiro a izquierdas: en cada puntodisminuye 1°C la temperaturade consigan
INFORMACIÓN DEL DISPLAY EN MODO FUNCIONAMIENTO
3.2. Modo programaciónSe accede al modo programación al abrir la tapa (1)
3.3. Areas y niveles de programaciónLa programación de las centrales se establerce en seis áreas, cuatrode las cuales subdividen en tres niveles:
La operativa general para visualizar / modificar parámetros dentro de unnivel es:
Seleccionar el nivel en el cual se encuentra el valor a visualizar /modificar mediante los botones + / -
Presionar la tecla de programación (se accede al nivelcorrespondiente)
Acceder al valor mediante los botones + / -
Presionar la tecla de programación ( selección de valor) El LED demodificación de parámetros se ilumina. El calor puede ahoramodificarse.
Modificar el valor mediante los botones + / -
Presionar la tecla de programación. El valor queda almadenado yel LED se apaga
3.4. Área GENERAL FECHA/HORA
En esta área se accede al ajuste de los parámetros de hora, fecha y
ajuste del periodo vacaciones.
A B C
IHGFED
LARENEGOICIVRES
AROH/AHCEF
NÓICACIDNI
OIRAUSU
OPMEITGORP
OCINCÉT
SELEVIN
NÓICALATSNIsodazilausivserolavysetsujA
alaorodareneglasetneidnopserroclarenegnóicalatsni
LACAUGAsodazilausivserolavysetsujA
SCAednóiccudorpalasetneidnopserroc
OTIUCRICsodazilausivserolavysetsujA
nóiccafelacedotiucriclasetneidnopserroc
(1)
Tecla de programación que permite: - Acceder al menú de programación. - seleccionar un valor a sustituir. - Validar valores nuevos introducidos
Botón + que permite: - Desplazarse por el menú. - Ajustar valores.
Botón - que permite: - Desplazarse por el menú. - Ajustar valores.
FECHA / HORA
AROH-AHCEF AROH ahcefyarohedsetsujA
OÑA
SEM
AID
SENOICACAV NARRAOÑA senoicacavodoirepsetsujAnóicalatsniallaucleetnarud
odomneárecenamrepAREPSEotneimanoicnuf
NARRASEM
NARRAAID
NIFOÑA
NIFSEM
NIFAID
ONAREVPMEIT NARRASEM sodoirepsoledsetsujAonreivni/onarev
NARRAAID
NIFSEM
NIFAID
SARTA SELECCIÓNPARÁMETRO
AJUSTEPARÁMETRO
ACCESO ÁREA FECHA / HORAA aroH
B yalpsidlenerazilausivalanoicpoarutarepmeT
C .)ognimoD=7,…,setraM=2,senuL=1(anamesaledaíD
D odatcenocSUBNAC
E .nóiccafelacotiucricledotneimanoicnufedsolcicsoledairarohnóicubirtsiD
F
:nóicalatsnialedodatsE
.otneimanoicnufnerodameuQ
.nóiccafelacedoicivreS
.S.C.AednóiccudorpedoicivreS
G odanoiccelesotneimanoicnufedodoM
Hetneibmaarutarepmetalnocnóiccafelacosacetsene(lautcaotneimanoicnuF
.)2angisnoced
I etneibmaarutarepmeT
5
3.5. Área GENERAL SERVICIO
En esta área se accede a los contadores horarios y rearmes de la central
(*) Para poner a cero presionar la tecla hasta que aparezca RESETen el display
(**) Seleccionar el valor 01 mediante y presionar
(***)
ACCESO ÁREA SERVICIO
SERVICIO
CODIGO
0000
INTRODUCCIÓN CÓDIGO DE ACCESOPARA LOS CUATRO DIGITOS
3.6. Área INDICACIÓN
En esta área se accede a la visualización, sin posibilidad de modificación,de los distintos valores de las sondas
ACCESO ÁREA INDICACIÓN
INDICACIÓN
NÓICALATSNI ROIRETXE-T roiretxearutarepmeT
ROETDLAC-T arutarepmetetsujAaredlac
AREDLAC-T aredlacarutarepmeT
NÓICALUDOM alednóicaludomedleviN.aredlac
isoloseceraparolavetsEnóixenocodautcefeahesaredlacanunocSUBaívatimsnarteuqetnaludom
alanóicamrofniatse.atilartnec
1ELER-T éleradnosarutarepmeTaled1nóicnufitlum
atilartnec
1TCELOC-T leneroirefniarutarepmeT.ralosaígreneedotisóped
SARTA
LACAUGA CLACSCA-T angisnocedarutarepmeTodicelbatseolnúgesSCA
edodomleropleyotneimanoicnuf
amargorp
SCA-T SCAarutarepmeT
ISCA-T SCAotisópedarutarepmeT.roirefnianozalne
leisecerapaolosrolavetsEOSAPAGRACortemáraplevinleneodavitcaátse
aledLACAUGA>OCINCETatilartnec
SARTA
OTIUCRIC TCABMA-T edetneibmaarutarepmeTnúgesotiucricledangisnocedodomyamargorp
.otneimanoicnuf
ETNEIBMA-T etneibmaarutarepmeTotiucricledlautca
DADEMUH avitalerdademuhaledrolaV.lautca
esisecerapaolosrolavetsErosnesnuodatcenocah.nóicnufatsearapocifícepse
ROETPMIT angisnocedarutarepmeTotiucriclednóislupmied
PMIED-T edlautcaarutarepmeTotiucriclednóislupmi
N-ITPO-EIT .nóicazimitpoedopmeiTanusenóicazimitpoaLneelbanoiccelesnóicnuf-ITPO>TIUCRIC>OIRAUSUetimrepeuqICAZIMotneimanoicnuflerapicitnaedniflenocnóicalatsnialedlacolleeuqrarugesa
arutarepmetalecnaclaleneadamargorpetneibma
olcicleraiciniedotnemom.oiraroh
SARTA
XX-XXXONWS erawtfosedoremúnlednóicacifitnedI)aírevaedosacneovitamrofni(
1MEUQMET ledotneimanoicnufedsarohedrodatnoC)*(1rodameuq
1MEUQNARRA ledseuqnarraedoremúnledrodatnoC)*(1rodameuq
2MEUQMET ledotneimanoicnufedsarohedrodatnoC)*(2rodameuq
2MEUQNARRA ledseuqnarraedoremúnledrodatnoC)*(2rodameuq
SUBRAPPA aívsodatcenocsotnemeleednóicazilausiVoludómlasuB
AUSUEMRAER soledacirbáfedsetsujasolarepuceRleotpecxe(OIRAUSUaeráledsortemárap
)**()AMOIDI
INCETEMRAERsoledacirbáfedsetsujasolarepuceR
)**(OCINCÉTaeráledsortemárapedogidócednóiccudortnialereiuqeR
)***(osecca
MRAERTGORP soledacirbáfedsetsujasolarepuceR)**(OPMEITGORPaeráledsortemárap
SARTA
SELECCIONARDIGITO
VALIDARAJUSTAR VALOR
6
ORTEMÁRAP OGNAR ROPROLAVOTCEFED
OTIUCRIC 1BMA-T C°04-5 C°02
2BMA-T C°04-5 C°02
3BMA-T C°04-5 C°02
ADICUDER-T C°04-5 C°01
SENOICACAV-T C°04-5 C°01
QSF-ROLAV K02-0 KO
AIDETIMIL-T C°04-)5-(,---- C°91
CONETIMIL-T C°04-)5-(,---- C°01
ETNEIDNEP 00.3-00.0 05.2
NOICATPADA 10,00 )FFO(00
BMAULFNI 02-00 01
BMA-T-BILAC K)0.5(-)0.5-( K0.0
ICAZIMITPO 20,10,00 00
XAM-ITPO-EIT h00:3-00:0 h00:2
CCUDER-TPO h00:3-00:0 h00:0
ODITIMDACP 9999-0000 0000
SARTA
ORTEMÁRAP OGNAR ROPROLAVOTCEFED
NÓICALATSNI LONAPSE LONAPSE
ETSARTSNOC )02(-)02-( 0
LPSIDCELES -T,AID.,ROIRETXE .. ROIRETXE-T
ODATSE 10/00 10
SARTA
3.7.1. Descripción de los parametros del área USUARIO
ESPANOLSelección de idiomaCONTRASTEAjuste de la intensidad del displaySELEC DISPLSelección del parámetro a visualizar en el display en modo funcionamiento:
3.7. Área USUARIO
En esta área pueden modificarse los parámetros a nivel USUARIO de loscuatro nivelesEn el apartado 3.7.1. se describen los parámetros del área usuario
ACCESO ÁREA USUARIO
USUARIO
ORTEMÁRAP OGNAR ROPROLAVOTCEFED
LACAUGA SCAX1 10-00 )FFO(00
1SCA-T C°07-01 C°06
2SCA-T C°07-01 C°06
3SCA-T C°07-01 C°06
NOIGELITNA 10,00 )FFO(00
SARTA
SELECCIÓNPARÁMETRO
AJUSTEPARÁMETRO
INSTALACIÓN
---- ortemárapnúgninrazilausivesoN
AID anamesaledaíD
ANRETXE-T roiretxearutarepmeT
1PMIEDT 1otiucricadiedarutarepmeT
SCA-T SCAotisópedarutarepmeT
1ETNEIBMA-T 1otiucricetneibmaarutarepmeT
ESTADOEste parámetro permite reducir la información mostrada en el display01= Muestra información estandar00= Desactiva algunos símbolos
1X ACSProducción de ACS fuera del tiempo programado. Si hay un descenso enla temperatura del depósito por debajo de la temperatura de consignafuera del periodo de producción de ACS (p.ej. una ducha en periodo noprogramado), el depósito recupera por una vez la temperatura de consigna.00=OFF 01=ONT-ACS 1Temperatura de consigna en el ciclo 1 del programa de producción ACS.T-ACS 2Temperatura de consigna en el ciclo 2 del programa de producción ACS.T-ACS 3Temperatura de consigna en el ciclo 3 del programa de producción ACS.ANTILEGIONFunción antilegionella.La temperatura del depósito se eleva a 70º C cada Domingo a la 1: 00 h.00=OFF 01=ON
AGUA CAL
T-AMB 1Temperatura de consigna para el ciclo 1 del programa SOL del circuito.T-AMB 2Temperatura de consigna para el ciclo 2 del programa SOL del circuito.T-AMB 3Temperatura de consigna para el ciclo 3 del programa SOL del circuito.T-REDUCIDATemperatura de consigna para el programa LUNA del circuito.T-VACACIONESTemperatura de consigna para el periodo de VACACIONES.VALOR-FSQParámetro aplicable en combinación con un depósito y sistema solar.Permite reducir la temperatura ambiente de consigna del circuitoautomáticamente antes de conectar la caldera, en el caso de que elsistema solar no aporte suficiente energía al depósitoT-LIMITE DIATemperatura límite día.El servicio de calefacción se desactiva si la temperatura exterior superaa lo largo del programa SOL la temperatura consignada en este parámetro.T-LIMITE NOCTemperatura límite noche.El servicio de calefacción se desactiva si la temperatura exterior superaa lo largo del programa LUNA la temperatura consignada en esteparámetro.PENDIENTEPendiente de la instalación.Los valores de máxima temperatura de ida y exterior fijados para eldimensionado de la instalación determinan la Pendiente a seleccionarpara mantener 20 °C de temperatura en el ambiente interior.
Pendiente = ∆T (ºC) / (T ambiente – T exterior)
CIRCUITO
7
∆T (ºC) = Diferencia entre la temperatura máxima de ida y la mínima parala emisión calorífica de un radiador (30 °C) o de suelo radiante (20º C)
T ambiente = Temperatura ambienteT exterior = Temperatura exterior
Ejemplo de selección:Valorar la Pendiente de una instalación dimensionada para:
Temperatura máxima del agua de ida = 80 °CTemperatura de ambiente = 20 °CTemperatura exterior = - 5 °C
Pendiente = ( 80 – 30 )/ ( 20 – (-5) ) = 50 / 25 = 2
Nota: En instalaciones de calefacción con suelo radiante, la pendienteoscila entre 0,5 y 1.En cualquier punto de la Pendiente se establece la relación entre latemperatura exterior y la del agua de ida.
La Pendiente de fábrica en cada circuito de calefacción es 2,5.
ADAPTACIÓNAdaptación automática de la pendiente.Permite que la central realice un ajuste automático de la pendiente de lainstalación según la evolución del funcionamiento de la misma.Esta función solo está activa si está conectada una sonda exterior AF.00=OFF 01=ONINFLU AMBInfluencia de la temperatura ambiente.La temperatura de la caldera se incrementa en el valor seleccionadocuando la temperatura ambiente cae por debajo del valor consignado en1 K.00: Actuación según temperatura exterior20: Actuación según temperatura ambienteCALIB-T-AMBCorrección de la sonda ambiente.La lectura de la sonda ambiente puede ser corregida en este parámetrosi esta no mide correctamente.OPTIMIZACIOptimización.00=OFF01=La central anticipa la entrada en funcionamiento del sistema alprograma establecido, en función de la temperatura exterior02= La central anticipa la entrada en funcionamiento del sistema alprograma establecido, en función de la temperatura ambiente.TIE-OPTI-MAXTiempo de optimización máximo.Esta función solo es operativa si el parámetro OPTIMIZACI estáconfigurado en 01 ó 02.La entrada en funcionamiento del sistema se anticipa como máximo en eltiempo establecido en este parámetro.OPT-REDUCCTiempo de optimización reducido.El apagado de la caldera se adelanta como máximo en el tiempo establecidoen este parámetro a lo establecido por el programa.PC ADMITIDOAcceso mediante PC.Código para habilitar el acceso desde un PC.
100
80
60
40
20
3 2,5
2
1,5
1,2
1
0,80,6
0,40,2
20 16 12 8 4 0 -4 -8 -12 -16Temperatura Exterior (°C )
Tem
pera
tura
de
ida
(°C
)
3.8. Área PROG TIEMPO
ACCESO ÁREA PROG TIEMPO
PROG TIEMPO
OPMEITGORP SCAGORP SCAotiucricledamargorP
1FELACGORP nóiccafelacedotiucricled1amargorP
2FELACGORP nóiccafelacedotiucricled2amargorP
SARTA
El equipo se suministra con una programación estándar de fábrica
NÓICCAFELAC
1OTIUCRIC
1FELACGORPREIV-UL 00:22a00:60
OD-AS 00:32a00:70
2FELACGORPREIV-UL 00:80a00:60
00:22a00:61
OD-AS 00:22a00:61
AIRATINASETNEILACAUGA
S.C.AREIV-UL 00:12a00:50
OD-AS 00:32a00:70
Información del display:
oicinI1olciC
niF1olciC
Cº02 olcicesearapangisnocedarutarepmeT
joleR nóicamargorpaletnemacifárgacidnI .nóiccafelaced
nóiccafelacedotiucricled1amargorP
nóiccafelacedotiucricled2amargorP
1olcicledoicinI 1olcicledniF
2olcicledoicinI 2olcicledniF
3olcicledoicinI 3olcicledniF
1
2
I
II
III III
II
I
Modificación de los ciclos de programación:
Acceder al PROG CALEF 1 del circuito de calefacción presionando
Seleccionar el día de la semana (LUNES a DOMINGO) o el bloque (LU-VIER ó LU-DO) con y presionar .
1 ABIERT 20°C:
Seleccionar la hora de inicio del ciclo 1 con y presionar
1 CERRAD 20°C:
Seleccionar la hora de fin del ciclo 1 con y presionar
2 ABIERT 20°C:
Seleccionar la hora de inicio del ciclo 2 con y presionar
2 CERRAD 20°C:
Seleccionar la hora de fin del ciclo 2 con y presionar
3 ABIERT 20°C:Seleccionar la hora de inicio del ciclo 3 con y presionar
3 CERRAD 20°C:
Seleccionar la hora de fin del ciclo 3 con y presionar
Seleccionar otro día de la semana (LUNES a DOMINGO) u otro bloque(SA-DO) con y presionar .
Repetir el proceso descrito anteriormente
8
ORTEMÁRAP OGNAR ROPROLAVOTCEFED
TIUCRIC TIUCRICOPIT 10,00 00
ABMOBCNUF 30-00 00
ALUVLAV s042-03 s021
XAMPMI-T C°011-02 C°08
NIMPMI-T C°011-01 C°01
OLEIHITNA C°)5(-)51-()----( C°0
TXE-T-RTER h00:42-00:0 00:0
LAC-PMI-FID K05-0 K5
OREDIMUS 10,00 00
LORTNOC-I -h00:30,FFOh51:00 FFO
SARTA
Notas importantes:
1. Hay que introducir todos los ciclos de calefacción de todos losdías de la semana o los bloques (LU-VIER y SA-DO ó LU-DO) paraque la información sea almacenada.
2. Si se desea eliminar un ciclo horario de programación, o no sedesea introducir datos para el ciclo 2 ó 3, hay que configurar ——que se encuentra al final del día (…, 23:45, 24:00, ——, 00:00,00:15, …).
3.9. Área TÉCNICO
En este área se accede al ajuste de párametros a nivel de experto concódigo de acceso (el código de acceso es necesario para entrar encualquiera de los cuatro niveles)En el apartado 3.9.1 se incluye una descripción de los parámetros delárea TECNICO El ajuste incorrecto de los parametros del area TÉCNICO puedecausar mal funcionamiento o daños en el sistema.
ACCESO ÁREA TÉCNICO
TÉCNICO
ORTEMÁRAP OGNAR ROPROLAVOTCEFED
NÓICALATSNI OGIDOC 9999-0000 ----
OGIDOC 9999-0000 0000
SUBCERID 51-10,)00( 10
OPMEITREFER 10,00 FFO=00
SARTA
ORTEMÁRAP OGNAR ROPROLAVOTCEFED
LACAUGA SCACSED 10,00 0=10
LELARAPCNUF 10,00 00
SARTA
SELECCIÓNPARÁMETRO
AJUSTEPARÁMETRO
CODIGOSu modificación permite modificar todos los parámetros del área TÉCNICO,incluso el número de código (primer parámetro)DIREC BUSIdentificador BUSLos circuitos de calefacción se numeran de forma secuencial partiendode 01.No se debe repetir el número identificativo de un circuito.Este parámetro es especialmente importante cuando se dispone de variascentrales E8 conectadas vía BUSREFER TIEMPOTiempo de referencia.Todos los equipos conectados a través del BUS toman el tiempo (hora,día, mes y año) a partir del de la central consignada como referencia detiempo.Solo se permite un tiempo de referencia en el sistema, por tanto, solo unacentral podrá tener activado este parámetro.En caso de que ninguna central tenga activado este parámetro, cadacentral gestionará sus circuitos en base a su propio tiempo.00 = NO REFERENCIA DE TIEMPO01 = CENTRAL ES REFERENCIA DE TIEMPO
INSTALACIÓN
3.9.1. Descripción de los parámetros del área TÉCNICO
AGUA CAL
DESC ACSEncendido del circulador de ACS.Si la función está activada (01), el circulador de ACS no se conecta hastaque la temperatura de caldera no supera en 5 K la temperatura del depósitode ACS; de este modo se evita que el depósito se enfríe en el periodotransitorio de calentamiento de la caldera.FUNC PARALELFuncionamiento en paralelo de los circuladores calefacción y ACS.00 = OFF01 = ON
CIRCUITO
TIPO CIRCUITSelección del tipo de circuito, según:
rolaV nóicpircseD
00 .radnátsenóiccafelacedotiucriC
10anuaesabnenóiccafelacedsolcicsoletnarudalugerlartnecaLedarutarepmetanuodneicelbatse,ajifnóislupmiedarutarepmetajifnóislupmiedarutarepmetanuyLOSolcicleetnarudajifnóislupmi
.ANULodoirepleetnarud)atnitsid(
rolaV nóicpircseD
00 .radnatseotneimanoicnufedodoM
10 )CONETIMIL-T,AIDETIMIL-T(setimílnúgesotneimanoicnufedodoM
20 nóiccafelacedamargorplaodreucaedotneimanoicnufedodoM
30 ounitnocotneimanoicnuF
FUNC BOMBAModo de funcionamiento de los circuladores.
VALVULAParámetro de control de la válvula mezcladora; corresponde al tiemporequerido para la apertura completa de la misma.T-IMP MAXTemperatura máxima de impulsión.Para el caso de circuitos directos (sin válvula mezcladora) existe undiferencial respecto al valor consignado de +8 K / - 5 K en la desconexióny conexión respectivamente.
CODIGO
0000
INTRODUCCIÓN CÓDIGO DE ACCESO PARA LOS CUATRO DIGITOS
SELECCIONARDIGITO
VALIDARAJUSTARVALOR
9
T-IMP MINTemperatura minima de impulsiónANTIHIELOTemperatura exterior de activación de la función antihielo.Si la temperatura exterior cae por debajo de la temperatura consignadaen este parámetro se activa la función antihielo.RETR-T-EXTRetraso en la consideración por parte de la centralita, de la lectura de lasonda exterior AF (solo para edificios muy aislados)DIF-IMP-CALDiferencia entre temperatura de caldera y de ida en circuitos mezcladores.El valor consignado compensa la perdidas y tolerancias de sondas en elvalor de la temperatura de caldera, sobre la temperatura necesaria enimpulsión del circuito mezclador.SUMIDEROEl circuito de calefacción puede emplearse como sumidero de calor decara a prevenir sobretemperaturas en la caldera. Se aplica únicamentecon calefacción activada y establece la máxima temperatura de impulsión.I-CONTROLSi existe una desviación de la temperatura ambiente de 1 K para el valorajustado en este parámetro, la temperatura de ida se incrementa en elvalor INFLU-AMB.
3.10 Funciones de protección del sistema
ANTIHIELOLa protección antihielo se establece en los siguientes supuestos:
•Temperatura exterior por debajo del límite establecido en el parámetroTECNICO>CIRCUITO >ANTIHIELO (conexión circuladores y caldera)
•Temperatura de caldera inferior a 5 ºC (conexión caldera a sutemperatura mínima establecida en T-MIN-CAL)
•Temperatura ambiente inferior a 5 ºC (conexión circuladores y caldera)
AUTOCHEQUEOCada 10 min, la central establece un autochequeo automático para verificarsi todos los parámetros de la misma están dentro de los límitesestablecidos. Caso de detectar un parámetro anómalo, el sistema sebloquea (código de error 81)
RETRASO PARO CIRCULADOREn la desconexión de un circulador, este continua funcionando durante 5min. si una de las calderas ha estado funcionando los últimos 5 min.
ANTIBLOQUEO CIRCULADORESLa central conecta aquellos circuladores que no han entrado enfuncionamiento durante las últimas 24 h, cada día a las 12:00 durante 3 s.
ANTIBLOQUEO VÁLVULAS MEZCLADORASSi la válvula mezcladora no ha funcionado en 24 h, esta es abierta totalmentea las 3:00 h. El circulador deja de funcionar durante esta operación y seestablece la temperatura de consigna máxima.
NÓICACINUMOCSERORRE
09E 1y0SUBedserodacifitnedisoremúnsoledoenatlumisosU
19E ametsisortoroposuneSUBednóicacifitnediedoremúN
ONRETNIRORRE
18E01adacatilartnecalaútcefeeuqlortnocotualeneodatcetedrorrE
rorreleecelbatseesognaredareufrolavnuatcetedatseiS.nim.sodicelbatsesetsujasolracifirevesodneibed,odacidni
ADNOSEDSERORRE
96E 2otiucricledFVadnosnerorrE
07E 1otiucricledFVadnosnerorrE
57E FAroiretxeadnosnerorrE
67E FPSotisópededadnosnerorrE
77E FKneadatcenocaredlacedadnosnerorrE
97E 1nóicnufitlumélerledadnosnerorrE
08E 1otiucricled1RBFetneibmaadnosnerorrE
38E otisópedroirefniadnoS/2otiucricled1RBFetneibmaadnosnerorrEanicsipadnoS/rodalumuca
4. ANOMALÍASEn caso de anomalía la pantalla muestra el símbolo parpadeante, y elcódigo de anomalía correspondiente según la siguiente tabla.
Una vez corregida la anomalía de funcionamiento es necesario realizarun RESET de la centralita, para ello presionar con un objeto punzante enRESET.Para cargar los ajustes de fábrica, presionar simultáneamente en RESETy
10
GB1. DESCRIPTION AND MAIN FEATURES
1.1 General Description
BM-E8The Room Module BM-E8 is intended to be linked to an E8 or E9 HeatingController via a BUS system, allowing access to the display andprogramming of system parameters monitored by the heating controller.The room module is fitted with a room temperature sensor.
1.2 DeliveryIn a single package.
1.3 Main FeaturesSupply Voltage: 12V=+/-15%Total power consumption: 1W maximumOperating ambient temperature limits: 0ºC to 50ºCShipping ambient temperature limits: -30ºC to 60ºCTimer battery back-up: > 10 hoursEnclosure IP40 to EN 60 529Sensor resistance: PTC 1K
2. ASSEMBLY AND INSTALLATION
Remove the front panel from the sub-base as shown.
Secure the sub-base onto the wall (‘A’ holes are for the fixing screws and‘B’ holes are for passing the connecting cable).Make the connection at the terminal strip ‘C’ using telephone line (4 wires2 x 0.8mm), as follows:
-Terminal 1: BUS H -Terminal 2: BUS L -Terminal 3: BUS - -Terminal 4: BUS +
An E8 or E9 heating controller can take as many BM-E8 modules (via aBUS system) as heating circuits being managed.
3. OPERATION
3.1 Operating ModeDuring normal operation of the module, the cover will remain closed.
SELECTING THE OPERATING MODEThe following operating modes can be selected:
Shifting from one operating mode to another will take place after 5 seconds.
TEMPORARY DISCONNECTION OF THE HEATING CIRCUIT(ECO)
Energy-saving feature. It allows for the system to be temporarily OFFwhen the dwelling is unoccupied for a few hours.
Press the key. This symbol will be displayed on the screen.
Press the key to increase the circuit ‘disconnection’ time by 1 hour.
Press the key to decrease the circuit ‘disconnection’ time by 1 hour.
Press the key for 3 seconds to shift from the heating circuit to theNight
Set-back mode until the first operating Comfort cycle of the following
day.
Operating mode selector switch
Temporary disconnection of the heating circuit (ECO)
Extension of the heating period
Room temperature adjustment
yb-dnatSedoM
eht:ylnoerutaefnoitcetorptsorF.FFOeraWHDdnagnitaeHsierutarepmetedistuoehtrevenehwdezigreneeblliwstiucric.detceleserutarepmetnoitcetorptsorfehtnahtrewolrootlauqe
citamotuA1edoM
dnaseludehcsehtotgnidroccaetarepostiucricgnitaehehTlliwecivresWHDehT.1emmargorprednutesserutarepmet
.emmargorpnwostiotgnidroccaetarepo
citamotuA2edoM
dnaseludehcsehtotgnidroccaetarepostiucricgnitaehehTlliwecivresWHDehT.2emmargorprednutesserutarepmet
.emmargorpnwostiotgnidroccaetarepo
edoMWHDlliwtiucricWHDehT.ylnoretaWtoHcitsemoDfonoitcudorP
.emmargorptes-erpehtotgnidroccaetarepo
trofmoCedoM)NUS(
otgnidroccadetsujda)h42(yltnenamreperastiucricgnitaehehTehT.noitarepo"NUS"rof1erutarepmetmoordemmargorpeht
.emmargorptes-erpehtotgnidroccaetarepolliwtiucricWHD
-teSthgiNedoMkcab
)NOOM(
otgnidroccadetsujda)h42(yltnenamreperastiucricgnitaehehTehT.noitarepo"NOOM"rof1erutarepmetmoordemmargorpeht
.emmargorptes-erpehtotgnidroccaetarepolliwtiucricWHD
Note: During the ‘disconnection’ time, the heating circuit will adjust itself tomatch the temperature set for the Night Set-back mode .
EXTENSION OF THE HEATING PERIOD
It allows for operation of the heating cycle to be extended for a certainperiod of time.
Press the key. This symbol will be displayed on the screen.
Press the key to increase the circuit ‘disconnection’ time by 1 hour.
Press the key to decrease the circuit ‘disconnection’ time by 1 hour.
Press the key for 3 seconds to shift from the heating circuit to the
Comfort mode until the first operating Comfort cycle of the followingday.
11
ROOM TEMPERATURE ADJUSTMENT
In mid position, the room temperature setting is 20ºC:
- Turn switch to the right: each dot means a 1ºC increase of thesetpoint temperature.- Turn switch to the left: each dotmeans a 1ºC decrease of the setpoint temperature.
A B C
IHGFED
DISPLAY INFORMATION IN OPERATING MODE
3.2 Programming ModeAccess to the Programming Mode is gained by opening the cover (1).
Programming key to:- Access the programming menu.- Select a value to be altered.- Confirm newly entered values.
Plus + key to:- Scroll through the menu.- Adjust values.
Minus + key to:- Scroll through the menu.
- Adjust values. (1)
3.3 Programming Areas and LevelsThe programming of heating controllers is divided into six different areas,four of which are in turn subdivided into three levels:
LARENEGECIVRES
EMIT/ETAD
YALPSID
RESU
GORPEMIT
TREPXE
SLEVEL
NOITALLATSNIehtrofseulavdnastnemtsujdayalpsiD
.metsyslarenegrorotarenegtaeh
RETAWTOHehtrofseulavdnastnemtsujdayalpsiD
.WHDfonoitcudorp
TIUCRICGTHehtrofseulavdnastnemtsujdayalpsiD
.tiucricgnitaeh
The standard procedure to view and/or alter the parameters within a levelis as follows:
Using the +/- keys, select the level where the value to be displayedor altered can be found.
Press the programming key (to access the relevant level)
Search the value using the +/- keys.
Press the programming key (to select the value). The parameterchange LED will light up. The value can now be changed.
Change the value using the +/- keys.
Press the programming key. The value is stored and the LEDgoes out.
3.4 GENERAL Area > Date/Time
From this area you may access the time, date and holiday parameters.
DATE / TIME
ACCESS TO THE DATE / TIME AREA
YADILOH TRATSRAEY gniruddoirepyadilohehtteSeblliwnoitallatsniehthcihw
.edomYB-DNATSnoTRATSHTNOM
TRATSYAD
POTSRAEY
POTSHTNOM
POTSYAD
EMIT-ETAD EMIT etaddnaemitteS
RAEY
HTNOM
YAD
EGNAHCKCOLC TRATSHTNOM retniw/remmusehtteS.sdoirep
TRATSYAD
POTSHTNOM
POTSYAD
NRUTER SELECT PARAMETER
SETPARÁMETER
A emiTtnerruC
B yalpsidehtnodaereboterutarepmetlanoitpO
C )yadnuS=7,...,yadseuT=2,yadnoM=1(keewehtfoyaD
D detcennocSUBNAC
E selcycgnitarepotiucricgnitaehehtfoeludehcsemiT
F
:sutatsmetsyS
.NOrenruB
.gnitaeHrofdnameD
.WHDrofdnameD
G .edomgnitarepodetceleS
H )2erutarepmetmoortniopteshtiwgnitaeh:esacsihtni(edomgnitarepotnerruC
I erutarepmetmooR
12
3.5 General Area > Service
From this area you may access the burner hours run/starts counters andcontroller resets.
XX-XXXONWSrebmunerawtfosehtgniyfitnedI
)noitcnuflamfoesacnilufesu(
1EMITRENRUB )*(1renrubforetnuocnursruoH
1TRATSRENRUB )*(1renrubforetnuocstratS
2EMITRENRUB )*(2renrubforetnuocnursruoH
2TRATSRENRUB )*(2renrubforetnuocstratS
SECIVEDSUBotdetcennocstnemelefoyalpsiD
.metsysSUBaaiveludomeht
RESUTESERRESUtes-yrotcafehtseveirtertI
ehttpecxe(sretemarapaera)**()egaugnal
TREPXETESERTREPXEtes-yrotcafehtseveirtertIedocsseccA.)**(sretemarapaera
)***(deriuqer
GRP-TTESEREMITtes-yrotcafehtseveirtertI
)**(sretemarapaeraMARGORP
NRUTER
(*) To reset it, press the key until the word RESET is displayed onthe screen.
(**) Select the value 01 using and press .
(***)
CODE-NO
0000
ENTERING ACCESS CODE (4 DIGITS)
SELECTDIGIT
ADJUSTVALUE
CONFIRM
In this area we can view -but not alter- the values relating to the sensors.
3.6 DISPLAY Area
ACCESS TO THE DISPLAY AREA
DISPLAY
ACCESS TO THE SERVICE AREA
SERVICE
NOITALLATSNI EDISTUO-T erutarepmetedistuO
SEDRELIOB-T erutarepmetrelioBtnemtsujda
RELIOB-T erutarepmetrelioB
NOITALUDOM .levelnoitaludomrelioBebylnolliweulavsihT
gnitaludomafideyalpsiddetcennocneebsahreliobgnidnes,metsysSUBaaiv
siht ehtotnoitamrofni.rellortnocgnitaeh
1YALER-T noitcnufitlumfoerutarepmeTrellortnocnirosnes1yaler
LREFFUB-T noitcesrewoltaerutarepmeT.rednilycWHDfo
NRUTER
RETAWTOH DETARWHD-T erutarepmettnioptesWHDehtybdehsilbatsesa
gnitaehdnaedomgnitarepo.emmargorp
WHD-T erutarepmetWHD
1WHD-T noitcesrewoltaerutarepmeT.rednilycWHDfo
ebylnolliweulavsihTDAOLehtfideyalpsid
sahretemarapHGUORHTehttadelbaneneeb
.levelRETAWTOH>TREPXE
NRUTER
2/1TIUCRICGTH ASEDMOOR-T moortnioptestiucriCdehsilbatsesaerutarepmetdnaedomgnitarepoehtyb
.emmargorpgnitaeh
MOOR-T moortiucrictnerruCerutarepmet
YTIDIMUH ytidimuhevitalertnerruC.oitar
ebylnolliweulavsihTrosnescificepsafielbaliava
sihtrofdellatsnineebsah.esoprup
DETARWOLF-T wolftnioptestiucriC.erutarepmet
WOLF-T wolftnioptestiucrictnerruC.erutarepmet
EMIT-TPO-N .emitnoitazimitpOnoitcnufelbatcelesasisihT
>aerARESUehtnihtiwNOITAZIMITPO>TIUCRIC
gnignirbstimrephcihwotnoitarepometsysdrawrof
lliwsesimerpehterussamoordemmargorpehthcaer
emitehtnehwerutarepmet.stratseludehcs
NRUTER
13
RETEMARAP EGNAR TLUAFEDEULAV
2/1TIUCRICGTH 1MOOR-T 04-5 C° C°02
2MOOR-T 04-5 C° C°02
3MOOR-T 04-5 C° C°02
DECUDER-T 04-5 C° C°01
ECNESBA-T 04-5 C° C°01
EULAV-BOB K02-0 KO
YADTIMIL-T C°04-)5-(,---- C°91
NTIMIL-T C°04-)5-(,---- C°01
EPOLSTAEH 00.3-00.0 05.2
NOITATPADA 10,00 )FFO(00
LFNISMOOR 02-00 01
T-MOORPADA K)0.5(-)0.5-( K0.0
TAEHMITPO 20,10,00 00
EMIT-TPOXAM h00:3-00:0 h00:2
ITPOONOCE h00:3-00:0 h00:0
ELBANE-CP 9999-0000 0000
NRUTER
RETEMARAP EGNAR TLUAFEDEULAV
NOITALLATSNI HSINAPS HSINAPS
TSARTNOC )02(-)02-( 0
LESYALPSID -T,YAD...,EDISTUO EDISTUO-T
SUTATS 10/00 10
NRUTER
In this area, the USER level parameters of the four levels can be altered.Section 3.7.1 includes a description of the various parameters in this area.
3.7 USER Area
ACCESS TO THE USER AREA
USER
RETEMARAP EGNAR TLUAFEDEULAV
RETAWTOH WHDX1 10-00 )FFO(00
1WHD-T C°07-01 06 C°
2WHD-T C°07-01 C°06
3WHD-T C°07-01 C°06
NOIGELITNA 10,00 )FFO(00
NRUTER
SELECTPARÁMETER
SETPARÁMETER
3.7.1 Description of parameters in the USER Area
SPANISHSelect languageCONTRASTAdjust intensity of displayDISPLAY SELSelect parameter to be displayed in operating mode:
INSTALLATION
---- yalpsidnosretemarapoN
YAD keewehtfoyaD
EDISTUO-T erutarepmetedistuO
1WOLF-T erutarepmetwolF,1tiucriC
WHD-T erutarepmetrednilycWHD
1MOOR-T erutarepmetmooR,1tiucriC
STATUSThis parameter permits reducing the information displayed on the screen01= Displays standard data00= Disables some symbols
1X DHWDHW production beyond the programmed time. Should the cylindertemperature drop below the setpoint temperature beyond the DHWproduction time (e.g. a shower at a non-programmed time), the DHWcylinder recovers the setpoint temperature once.00=OFF 01=ONT-DHW 1Setpoint temperature in cycle 1 of the DHW production programme.T-DHW 2Setpoint temperature in cycle 2 of the DHW production programme.T-DHW 3Setpoint temperature in cycle 3 of the DHW production programme.ANTILEGIONAntilegionella feature.The DHW cylinder temperature rises to 70ºC every Sunday at 1:00h.00=OFF 01=ON
T-ROOM 1Setpoint temperature for cycle 1 in the circuit’s SUN programme.T-ROOM 2Setpoint temperature for cycle 2 in the circuit’s SUN programme.T-ROOM 3Setpoint temperature for cycle 3 in the circuit’s SUN programme.T-REDUCEDSetpoint temperature for the circuit’s MOON programme.T-ABSENCESetpoint temperature for ABSENCE (unoccupied) periods.BOB-VALUEThis parameter is applicable to a combined cylinder and solar system. Itpermits reducing the circuit’s setpoint room temperature automaticallybefore starting up the boiler, in case the solar system fails to supplyenough energy to the cylinder.T-LIMIT DÍADay limit temperature.The heating service is switched off if the outside temperature exceeds thetemperature set under this parameter throughout the SUN programme.T-LIMIT NOCNight limit temperature.The heating service is switched off if the outside temperature exceeds thetemperature set under this parameter throughout the MOON programme.HEATSLOPESystem slope.The maximum flow and outside temperature values set for the size of thesystem determine the Heating Slope to be selected in order to maintain aroom temperature of 20ºC.
Slope = ∆T (ºC) / (room T - outside T)
HOT WATER
CIRCUIT
14
∆T (ºC) = Difference between the maximum flow temperature and theminimum temperature for a radiator’s heat emission (30ºC) or underfloorheating (20ºC)
Room T = Room temperature
Outside T = Outside temperature
Selection example:Evaluate the Slope for an installation based on:
Maximum water flow temperature = 80ºCRoom temperature = 20ºCOutside temperature = -5ºC
Slope = (80 - 30) / (20 - (-5)) = 50 / 25 = 2
Note: In underfloor heating systems, the slope ranges between 0.5 and 1.The relationship between the outside temperature and the water flowtemperature can be established at any point in the slope.
100
80
60
40
20
3 2,5
2
1,5
1,2
1
0,80,6
0,40,2
20 16 12 8 4 0 -4 -8 -12 -16Outside temperature (°C )
Flo
w t
empe
ratu
re (
°C )
The factory-set slope in each heating circuit is 2.5
ADAPTATIONAutomatic slope adaptation.It enables the heating controller to automatically adjust the system slope inaccordance with its operating development.This feature is active only if an outdoor sensor AF has been connected.00=OFF 01=ONROOMS INFLRoom temperature influence.The boiler temperature increases up to the selected value when the roomtemperature drops below the value set in 1 K.00: Operation according to the outside temperature20: Operation according to the room temperatureCALIB T-AMBCorrection of room sensor.The room sensor reading can be changed under this parameter if thesensor is not measuring correctly.OPTIM HEATOptimization.00=OFF01= The heating controller brings forward system operation ahead of thepre-set programme according to the outside temperature.02= The heating controller brings forward system operation ahead of thepre-set programme according to the room temperature.MAX OPT-TIMEMaximum optimization time.This feature will not operate if the OPTIMIZATION parameter has beenconfigured under 01 or 02.System operation is brought forward the time set under this parameter atthe most.ECONO OPTIReduced optimization time.Boiler switch-off is brought forward the time set under this parameter atthe most in relation to the time set by the programme.PC-ENABLEAccess via a PC link.Password to allow access from a PC.
The unit is delivered with standard factory settings.
3.8 TIME PROGRAM Area
ACCESS TO THE TIME PROGRAM AREA
TIME PROGRAM
MARGORPEMIT GORP-WTOH emmargorptiucricWHD
1GORP-GTH 1emmargorp,tiucricgnitaeH
2GORP-GTH 2emmargorp,tiucricgnitaeH
NRUTER
GNITAEH
1TIUCRIC
1GORP-GTHIRF-NOM 00:22ot00:60
NUS-TAS 00:32ot00:70
2GORP-GTHIRF-NOM
00:80ot00:6000:22ot00:61
NUS-TAS 00:22ot00:61
RETAWTOHCITSEMOD
WHDIRF-NOM 00:12ot00:50
NUS-TAS 00:32ot00:70
The information shown on the display is as follows:
tratS1elcyC
potS1elcyC
Cº02 elcyctahtroferutarepmettniopteS
kcolC emmargorpgnitaehfonoitacidnicihparG
1emmargorp,tiucricgnitaeH
2emmargorp,tiucricgnitaeH
tratS1elcyC potS1elcyC
tratS2elcyC potS2elcyC
tratS3elcyC potS3elcyC
1
2
I
II
III
I
II
III
Changing the programming cycles:
Access the HTG-PROG 1 of the heating circuit by pressing the key.Select the day of the week (MONDAY to SUNDAY) or the block (MON-FRI or MON-SUN) with and press .- 1 OPEN 20ºC:Select the starting time (ON) for cycle 1 with and press .- 1 CLOSE 20ºC:Select the stopping time (OFF) for cycle 1 with and press .- 2 OPEN 20ºC:Select the starting time (ON) for cycle 2 with and press .- 2 CLOSE 20ºC:Select the stopping time (OFF) for cycle 2 with and press .- 3 OPEN 20ºC:Select the starting time (ON) for cycle 3 with and press .- 3 CLOSE 20ºC:Select the stopping time (OFF) for cycle 3 with and press .- Select another day of the week (MONDAY to SUNDAY) or another block(SAT-SUN) with and press .
15
RETEMARAP EGNAR TLUAFEDEULAV
TIUCRIC NOITCNUFCH 10,00 00
EDOMPMUP 30-00 00
MANYDREXIM s042-03 s021
WOLF-TXAM C°011-02 C°08
WOLF-TNIM C°011-01 C°01
TORPTSORF-T C°)5(-)51-()----( C°0
LED-PMET-TUO h00:42-00:0 00:0
TESFFOEPOLS K05-0 K5
KNISTAEH-B 10,00 00
LORTNOC-I -h00:30,FFOh51:00 FFO
NRUTER
- Repeat the procedure described above.
N.B.:1. All heating cycles for each day of the week, or the blocks (MON-FRIand SAT-SUN or MON-SUN), have to be entered for data to be stored.2. Should you wish to cancel a time schedule, or you do not want to enterdata for cycle 2 or 3, then you will have to configure ____ which is at theend of the day (..., 23:45, 24:00, ____, 00:00, 00:15, ...).
3.9 EXPERT Area
ACCESS TO THE EXPERT AREA
EXPERT
CODE-NO
0000
ENTERING THE ACCESS CODE (FOUR DIGITS)
SELECTDIGIT
CONFIRMADJUST VALUE
RETEMARAP EGNAR TLUAFEDEULAV
NOITALLATSNI ON-EDOC 9999-0000 ----
ON-EDOC 9999-0000 0000
DISUB 51-10,)00( 10
RETSAMEMIT 10,00 FFO=00
NRUTER
RETEMARAP EGNAR TLUAFEDEULAV
RETAWTOH FEILERWHD 10,00 0=10
LELLARAP 10,00 00
NRUTER
SELECTPARÁMETER
SETPARÁMETER
3.9.1 Description of parameters in the EXPERT Area
CODE-NOEntering the code number allows all of the EXPERT parameters to bealtered, even the code number itself (first parameter).BUS IDBus identifierThe heating circuits are sequentially numbered, starting with 01.The number identifying a heating circuit must not be used twice.This parameter is especially important when several E8 units have beenconnected via BUS.TIME MASTERReference time.All pieces of equipment that are connected through the BUS take the time(time, date, month, year) from the controller designated as time reference.One time reference only is allowed in the system and so this parametercan be enabled by one heating controller only.If none of the controllers has this parameter enabled, each controller willmanage its circuits based on its own time.00= NO TIME MASTER01= CONTROLLER IS TIME MASTER
DHW RELIEFDHW pump switching.If this feature has been enabled (01), the DHW pump will not be switchedon until the boiler temperature exceeds the DHW cylinder temperature by5K; this prevents the cylinder water from cooling down during the transitionalboiler heating period.FUNC PARALELParallel running of heating & DHW pumps.00= OFF01= ON
HC FUNCTIONSelection of circuit type as described below:
INSTALLATION
HOT WATER
CIRCUIT
eulaV noitpircseD
00 .tiucricgnitaehdradnatS
10
ehtnosetareporellortnoceht,selcycgnitaehehtgniruDwolfdexifagnihsilbatse,erutarepmetwolfdexifafosisabdexif)tnereffid(adna,elcycNUSehtgniruderutarepmet
.doirepNOOMehtgniruderutarepmetwolf
PUMP MODEPump operating mode
eulaV noitpircseD
00 .edomgnitarepodradnatS
10 )NTIMIL-TdnaYADTIMIL-T(stimilot.ccaedomgnitarepO
20 .emmargorpgnitaehehtot.ccaedomgnitarepO
30 .noitareposuounitnoC
MIXER DYNAMControl parameter for the mixing valve; it refers to the time required for thevalve to open fully.MAX T-FLOWMaximum flow temperature.In case of direct heating circuits (without mixing valve), there is a differenceregarding the set value of +8K / -5K in the switching off and switching on,respectively.
In this area you can access the password-protected parameter settingsat technician level, (the password is necessary to access any of the fourlevels).Section 3.9.1 includes a description of the various parameters in this area. The wrong setting of parameters in the EXPERT area may causemalfunctioning or damage the system.
16
MIN T-FLOWMinimum circuit flow temperature.T-FROST PROTOutside temperature triggering frost protection.If the outside temperature drops below the temperature set for thisparameter, the frost protection feature is then initiated.OUT-TEMP-DELDelay from the heating controller in reading the outdoor sensor AF (forwell-insulated buildings only).SLOPE OFFSETDifference between the boiler temperature and the flow temperature inmixer circuits.The set value offsets the heat losses and sensor tolerances up to theboiler temperature value, over the required temperature at the mixer circuitflow side.B-HEAT SINKThe heating circuit can be used as heat sink to prevent boiler overheating.This is only used with the heating ON and establishes the maximum flowtemperature.I-CONTROLIf there is a temperature deviation of 1K in the value set under this parameter,the flow temperature is increased up to the ROOMS-INFL value.
3.10 System protection features
FROST PROTECTIONThe frost protection feature is established in the following assumptions:
Outside temperature below the limit set under the EXPERT>CIRCUIT >T-FROST PROT parameter (pumps and boiler power-up).Boiler temperature below 5ºC (boiler switches ON at its minimumtemperature established under MIN T-BOILER).Room temperature below 5ºC (pumps and boiler switch on).
SELF-CHECKEvery 10 minutes, the heating controller carries out an automatic self-check to ascertain whether all the parameters are within the specifiedlimits. If a an anomalous parameter is found, the system locks out (faultcode 81).
DELAYED PUMP SWITCH-OFFIn the case of a pump switch-off, this will continue running for 5 minutes ifone of the boilers has been operating for the last 5 minutes.
PUMP SEIZURE PROTECTIONThe heating controller will switch on those pumps that have been idle forthe past 24 hours, every day at 12:00h for 3 seconds.
MIXING VALVE SEIZURE PROTECTIONIf the mixing valve has not operated for 24 hours, it is fully open at 3:00h.The pump will stop running during this operation and the maximum setpointtemperature is established.
4. FAULT CODES
If a fault or error occurs, a flashing symbol will be displayed along withthe associated fault code, according to the table below.
SRORRENOITACINUMMOC
09E .1dna0srebmunnoitacifitnediSUBehtfoesusuoenatlumiS
19E .ecivedrehtonaybdesugniebrebmunnoitacifitnediSUB
RORRELANRETNI
18E .nim01yrevesnurrellortnocehtkcehc-flesehtnidetcetedrorrEdehsilbatsesirorrenwohseht,eulavegnar-fo-tuonastcetedtifI
.dekcehc-elbuodebdluohssgnittesderotsehtosdna
RORREROSNES
96E 2tiucricgnitaeh,FVrosneswolF
07E 1tiucricgnitaeh,FVrosneswolF
57E FArosnesroodtuO
67E FPSrosnesrednilyC
77E FKtadetcennocrosnesrelioB
97E 1yalernoitcnufitlumrosneS
08E 1tiucricgnitaeh,1RBFrosnesmooR
38E /rosnesrewolrednilyC/2tiucricgnitaeh,1RBFrosnesmooRrosneslooP
Once the fault has been rectified, the heating controller must be RESET.To do that, press on RESET with a sharp-pointed object.To load the factory settings, press on RESET and at the same time.
17
1. DESCRIÇÃO E CARACTERÍSTICAS PRINCIPAIS1.1 Descrição geralBM-8O módulo ambiente BM-E8 está destinado à ligação via BUS com umacentral E8 ou E9, permitindo o acesso à visualização e programação dosparâmetros do circuito regulados pela central.O módulo está equipado com uma sonda de temperatura ambiente.
1.2 Forma de fornecimentoNum só volume
1.3 Características principais- Corrente de alimentação: 12V = +/- 15%.- Potência absorvida: 1W máximo- Temperatura ambiente admissível em funcionamento: 0ºC ÷ 50ºC.- Temperatura ambiente admissível de armazenamento: -30ºC ÷ 60ºC- Reserva da corda do relógio: > 10 horas.- Tipo de protecção: IP40 conforme a Norma EN 60 529.- Resistência das sondas: PTC 1K
2. MONTAGEM E INSTALAÇÃO
Separar a parte frontal da base de fixação na parede, conforme indica afigura.
Fixar a base na parede (os orifícios A estão destinados aos parafusos defixação e os B para a passagem do cabo de ligação)Efectuar a ligação através de um cabo telefónico (4 condutores 2 x 0,8mm2) na régua C, da seguinte forma:- Borne 1: BUS H- Borne 2: BUS L- Borne 3: BUS –- Borne 4: BUS +Numa central E8 ou E9 podem ligar-se via BUS tantos módulos BM-E8como os circuitos de aquecimento central que se tenham de gerir.
3. FUNCIONAMENTO
3.1 Modo de funcionamento
Corresponde ao funcionamento normal do módulo com a tampa fechada.
PT
Ajuste da temperatura ambiente
Selector do modo de funcionamento
Corte temporário do circuito (ECO)
Prolongamento do período de aquecimento
SELECÇÃO DO MODO DE FUNCIONAMENTO
Podem ser seleccionados os seguintes modos de funcionamento
A alteração de um modo de funcionamento para outro só se torna efectivaapós 5 seg.
CORTE TEMPORÁRIO DO CIRCUITO (ECO)Função destinada a poupar energia. Permite o corte temporário dainstalação quando abandonamos a habitação durante umas horas.
Pressionar a tecla O ecrã mostra o aspecto da imagem.
Pressionar a tecla para aumentar numa hora o tempo de corte do
circuito.
Pressionar a tecla para diminuir numa hora o tempo de corte do
circuito.
Pressionar a tecla durante 3 seg. para que o circuito de aquecimento
passe para o modo reduzido até ao primeiro ciclo de funcionamentoz em conforto do dia seguinte.
Nota: Durante o tempo estabelecido para o corte, o circuito de aquecimentoregula-se pelas temperaturas configuradas para o funcionamento zreduzido.
PROLOGAMENTO DO PERÍODO DE AQUECIMENTO CENTRALPermite prolongar o funcionamento do ciclo de aquecimento central por
um determinado período de tempo.
Pressionar a tecla . O ecrã mostra o aspecto da imagem.
Pressionar a tecla para aumentar numa hora o tempo de corte
do circuito.
Pressionar a tecla para diminuir numa hora o tempo de corte do
circuito.
Pressionar a tecla durante 3 seg. para que o circuito de aquecimento
passe para o modo de conforto até ao primeiro ciclo de funcionamento
z em conforto do dia seguinte.
arepsE-itnaoãçnufetnemoS.oçivresedarofSQAeotnemiceuqAarutarepmetaeuqerpmesoã-es-ragilsotiucricso:oãçalegnoc.adanoiccelesoãçalegnoc-itnaedàroirefniuolaugiajesroiretxe
ocitámotuA1
esoirárohsoemrofnoces-malugerotnemiceuqaedsotiucricsOuesoemrofnocSQAedoçivreS.1amargorpodsarutarepmetsa
.amargorpoirpórp
ocitámotuA2
esoirárohsoemrofnoces-malugerotnemiceuqaedsotiucricsOuesoemrofnocSQAedoçivreS.2amargorpodsarutarepmetsa
.amargorpoirpórp
SQAedotiucricO.airátinaSetneuQaugÁedoãçaraperpetnemoS
.odicelebatseamargorpoemrofnoces-alugerSQA
otrofnoC)LOS(
aemrofnocsaroh42saes-malugerotnemiceuqAedsotiucricsOotnemanoicnufoarapadamargorp1etneibmaedarutarepmet
."LOS".odicelebatseamargorpoemrofnoces-alugerSQAedotiucricO
odizudeR)AUL(
aemrofnocsaroh42saes-malugerotnemiceuqAedsotiucricsO."AUL"otnemanoicnufoarapadamargorpetneibmaedarutarepmet
.odicelebatseamargorpoemrofnoces-alugerSQAedotiucricO
18
OÃREVEDAROH SÊM ADITRAP- sodoírepsodsetsujA.onrevnI/oãreV
ADITRAP-AID
SÊM MEGARAP-
MEGARAP-AID
SAIRÉF ADITRAP-ONA edodoírepodetsujAalauqoetnarudsairéf
árecenamrepoãçalatsniedodomon
meotnemanoicnuf.AREPSE
ADITRAP-SÊM
ADITRAP-AID
MEGARAP-ONA
SÊM MEGARAP-
MEGARAP-AID
AROH-ATAD AROH .atadadearohadsetsujA
ONA
SÊM
AID
AJUSTE DA TEMPERATURA AMBIENTE
A posição intermédia da temperatura ambiente programada é de 20ºC:
- Rodar para a direita: por cada ponto aumenta 1ºC a temperatura programada.- Rodar para a esquerda: por cada ponto diminui 1ºC a temperatura programada.
INFORMAÇÃO NO ECRÃ NO MODO DE FUNCIONAMENTO
3.2. Modo programaciónSe accede al modo programación al abrir la tapa (1)
3.3 Áreas e níveis de programaçãoA programação das centrais é estabelecida em seis áreas, quatro dasquais subdividem-se em três níveis.
O modo de operação geral para visualizar / modificar parâmetros dentrode um nível é:
Seleccionar o nível no qual se encontra o valor a visualizar/alteraratravés dos botões +/-.
Pressionar a tecla de programação (acede-se ao nívelcorrespondente)
Aceder ao valor através dos botões +/ -.
Pressionar a tecla de programação (selecção do valor). O LED dealteração de parâmetros acende-se. O valor pode agora seralterado.
Alterar o valor através dos botões +/-.
Pressionar a tecla de programação. O valor fica armazenado e oLED apaga-se.
3.4 Área Geral > Data /Hora
Nesta área acede-se ao ajuste dos parâmetros: hora, data e período de
férias.
A B C
IHGFED
(1)
A tecla de programação permite:- Aceder ao menu de programação.- Seleccionar um valor a substituir.- Validar os novos valores introduzidos
O Botão + permite:- Deslocar-se pelo menu.- Ajustar valores
O Botão - permite:- Deslocar-se pelo menu.- Ajustar valores
DATA / HORA
SELECÇÃO DOPARÂMETRO
AJUSTE DOPARÂMETRO
ACESO ÁREA DATA / HORAA aroH
B )ãrceonrazilausiva(lanoicpoarutarepmeT
C )ognimoD=7,…,açreT=2,adnugeS=1(anamesadaiD
D odagilSUBNAC
E onemiceuqaedotiucricodotnemanoicnufedsolcicsodairárohoãçiubirtsiD
F
:oãçalatsniadodatsE
.otnemanoicnufmerodamieuQ
otnemiceuqaedoçivreS
.S.Q.AedoãçudorpedoçivreS
G odanoiccelesotnemanoicnufedodoM
Hetneibmaarutarepmetamocotnemiceuqa,osacetsen(lautcaotnemanoicnuF
)2adamargorp
I etneibmaarutarepmeT
LAREGOÇIVRES
AROH/ATAD
RAZILAUSIV
RODAZILITU
GOLONORCORP
OTIREP
SIEVÍN
OTNEMAPIUQEsodazilausivserolavesetsujA
àuorodaregoasetnednopserroc.laregoãçalatsni
ETNEUQAUGÁsodazilausivserolavesetsujA
edoãçudorpàsetnednopserroc.SQA
OTIUCRICsodazilausivserolavesetsujAedotiucricoasetnednopserroc
.otnemiceuqa
SÁRTARAP
19
2/1OTIUCRIC CACEROETT etneibmaarutarepmeTotiucricodadamargorp
oeamargorpoemrofnocotnemanoicnufedodom
OTNICER-T lautcaetneibmaarutarepmeTotiucricod
EDADIMUH avitaleredadimuhadrolaV.lautca
esecerapaósrolavetsErosnesmuodagilrevitse
.oãçnufatsearapocifícepse
ROETOXULF-T edadamargorparutarepmeT.otiucricodoãslupmi
OXULF-T edlautcaarutarepmeT.otiucricodoãslupmi
-ERPTECEUQA
.oãçazimitpoedopmeToãçnufamuéoãçazimitpoA
melevánoicceles>OTIUCRIC>RODAZILITU
euqTPOEUQA-ERPorapicetnaetimrep
oãçalatsniadotnemanoicnufededadilanifamoc
ajnitalacoloeuqrarugessaetneibmaarutarepmeta
edotnemomonadamargorp.oirároholcicoraicini
SÁRTARAP
ETNEUQAUGÁ QAROET-T edadamargorparutarepmeToemrofnocSQA
edodomolepodicelebatseolepeotnemanoicnuf
.amargorp
QA-T SQAarutarepmeT
ISQA-T otisópedodarutarepmeT.roirefnietrapanSQA
oosacecerapaósrolavetsELARGETNIUQAortemârap
levínonovitcaajetseETNEUQAUGA>OTIREP
.lartnecad
SÁRTARAP
OTNEMAPIUQE ANRETXE-T roiretxearutarepmeT
EDLACROET-T adarutarepmetadetsujAariedlac
ARIEDLAC-T ariedlacadarutarepmeT
OÃÇALUDOM adoãçaludomedlevíN.ariedlac
onóseceraparolavetsEahneteseuqmeosac
SUBaivoãçagilaodautcefeetnaludomariedlacamumoc
atseatimsnarteuq.lartnecàoãçamrofni
1ÉLER-T odadnosadarutarepmeTad1seõçnuf-itluméler
lartnec
1TCELOC-T roirefnietrapadarutarepmeT.ralosaigreneedotisópedod
SÁRTARAP
3.5. Área GERAL SERVIÇO
Nesta área acede-se aos contadores horários e aos rearmes da central.
(*) Para colocar a zero, pressionar a tecla , até que apareça RESETno ecrã.
(**) Seleccionar o valor 01 através de e pressionar .
(***)
ACESSO ÁREA SERVIÇO
SERVIÇO
CÓDIGO
0000
INTRODUÇÃO DO CÓDIGO DE ACESSO
PARA OS QUATRO DÍGITOS
3.6. Área INDICAÇÃO
Nesta área podem visualizar-se, sem poderem ser alterados, os diferentesvalores das sondas.
ACESSO ÁREA VISUALIZAR
VISUALIZAR
SELECCIONARDIGITO
VALIDARAJUSTAR VALOR
XX-XXXONWSerawtfosedoremúnodoãçacifitnedI
)airavaedosacmeovitamrofni(
1IEUQCNUFSHedsarohsadrodatnoC
.)*(1rodamieuqodotnemanoicnuf
1DAMIEUQTRAPseuqnarraedoremúnodrodatnoC
.)*(1rodamieuqod
2IEUQCNUFSHedsarohsadrodatnoC
.)*(2rodamieuqodotnemanoicnuf
2DAMIEUQTRAPseuqnarraedoremúnodrodatnoC
.)*(2rodamieuqod
SUBTISOPSIDsodagilsotnemelesodoãçazilausiV
.oludómoasuBaiv
LITURUATSERsodacirbáfedsetsujasoarepuceR
RODAZILITUaeráadsortemârap.)**()AMOIDIootpecxe(
BATSERTIREP
sodacirbáfedsetsujasoarepuceR.)**(OTIREPaeráadsortemârapogidócodoãçudortniadatisseceN
)***(ossecaed
ORCORPTSERsodacirbáfedsetsujasoarepuceR
ORPaeráadsortemârap.)3(GOLONORC
SÁRTARAP
20
ORTEMÂRAP OLAVRETNI ROPROLAVOTIEFED
2/1OTIUCRIC 1CERROET-T Cº04-5 Cº02
2CERROET-T Cº04-5 Cº02
3CERROET-T Cº04-5 Cº02
NEMAXIABA-T Cº04-5 Cº01
TNETSIXENI-T Cº04-5 Cº01
QSOROLAV k02-0 K0
DCEUQAMIL Cº04-)5-(,-Ñ Cº91
NCEUQAMIL Cº04-)5-(,-Ñ Cº01
CEUQAAVRUC 00.3-00.0 05.2
UQARICPADA 10,00 )FFO(00
TNICER.ULFNI 02-00 01
SNESADABMA K)0.5(-)0.5-( K0.0
EUQA-ERPTPO 20,10,00 00
QATPOXAMT h00:3-00:0 h00:2
IMITPOXIABA h00:3-00:0 h00:0
OACAREBILPC 9999-0000 0000
SÁRTARAP
ORTEMÂRAP OLAVRETNI ROPROLAVOTIEFED
OÃÇALATSNI SEUGUTROP SEUGUTROP
ETSARTNOC )02(-)02-( 0
LOCSELAUSIV -T,AID…ROIRETXE ROIRETXE-T
ODATSE 10/00 10
SÁRTARAP
ORTEMÂRAP OLAVRETNI ROPROLAVOTIEFED
ETNEUQAUGÁ AUGAX1NEUQ 10-00 )FFO(00
1QA-T º07-01 Cº06
2QA-T º07-01 Cº06
3SQA-T º07-01 Cº06
EL-TNAGART 10,00 )FFO(00
SÁRTARAP
3.7.1 Descrição dos parâmetros da área de UTILIZADOR
PORTUGUÊSSelecção do idioma
CONTRASTEAjuste da intensidade do ecrã.
VISUAL ESCOLSelecção do parâmetro a visualizar no ecrã no modo de funcionamento:
3.7. Área UTILIZADOR
Nesta área podem alterar-se os parâmetros, ao nível do UTILIZADOR,dos quatro níveis.Na alínea 3.7.1 é feita uma descrição dos parâmetros da área utilizador.
ACESSO ÁREA UTILIZADOR
UTILIZADOR
SELECÇÃOPARÂMETRO
AJUSTE DOPARÂMETRO
EQUIPAMENTO
ESTADOEste parâmetro permite reduzir a informação mostrada no ecrã01 = Mostra a informação standard00 = Desactiva alguns símbolos
1X AGUA QUENProdução de AQS fora do tempo programado. Se ocorrer uma descidada temperatura no depósito, e se este valor estiver abaixo da temperaturaprogramada fora do período de produção de AQS (por ex. um duche emperíodo não programado), o depósito recupera por uma só vez atemperatura de programada.00 = OFF 01 = ONT-AQ 1Temperatura programada no ciclo 1 do programa de produção de AQS.T-AQ 2Temperatura programada no ciclo 2 do programa de produção de AQS.T-AQS 3Temperatura programada no ciclo 3 do programa de produção de AQS.TR AG ANT-LEFunção anti-legionela.A temperatura do depósito sobe até aos 70ºC todos os Domingos à 1:00h.00 = OFF 01 = ON
ÁGUA QUENTE
T-TEOR REC 1Temperatura programada para o ciclo 1 do programa SOL do circuito.T-TEOR REC 2Temperatura programada para o ciclo 2 do programa SOL do circuito.T-TEOR REC 3Temperatura programada para o ciclo 3 do programa SOL do circuito.T-ABAIXAMENTemperatura programada para o programa LUA do circuito.T-INEXISTENTTemperatura programada para o período de FÉRIAS.VALOR OSQParâmetro aplicável em combinação com um depósito e um sistemasolar. Permite reduzir a temperatura ambiente programada do circuitoautomaticamente antes de ligar a caldeira, no caso de que o sistemasolar não debite energia suficiente ao depósito.LIM AQUEC DTemperatura limite para o dia.O serviço de aquecimento desactiva-se caso a temperatura exteriorultrapasse, ao longo do programa SOL, a temperatura programada paraeste parâmetro.LIM AQUEC NTemperatura limite para a noite.O serviço de aquecimento desactiva-se caso a temperatura exteriorultrapasse, ao longo do programa LUA, a temperatura programada paraeste parâmetro.CURVA AQUECPendente da instalação.Os valores máximos para a temperatura de ida e de exterior, fixadospara as dimensões da instalação determinam a pendente a seleccionar,para manter a temperatura de 20ºC no ambiente interior.
Inclinação = ∆T (ºC) /(T ambiente - T exterior)
CIRCUITO
---- muhnenortemârapazilausivesoãN
AID anamesadaiD
ANRETXE-T roiretxearutarepmeT
1PMIEDT 1otiucricadiedarutarepmeT
QA-T SQAotisópedodarutarepmeT
1OTNICER-T 1otiucricetneibmaarutarepmeT
21
∆T (ºC) = Diferença entre a temperatura máxima de ida e a mínima paraa emissão calorífica de um radiador (30ºC) ou de pavimento radiante(20ºC)
T ambiente = Temperatura ambienteT exterior = Temperatura exterior
Exemplo de selecção:Avaliar a Pendente de uma instalação dimensionada para:
Temperatura máxima da água de ida = 80ºCTemperatura ambiente = 20ºCTemperatura exterior = - 5ºC
Pendente = (80 – 30) / (20 – (-5) ) = 50 /25 = 2
Nota: Nas instalações de aquecimento com pavimento radiante, a pendenteoscila entre 0,5 e 1.Em qualquer ponto da pendente é estabelecida a relação entre atemperatura exterior e a da água de ida.
A Pendente de fábrica em cada circuito de aquecimento é de 2,5.
ADAP CIR AQUAdaptação automática da pendente.Permite que a central efectue um ajuste automático da pendente dainstalação conforme a evolução do funcionamento da mesma.Esta função só está activa se estiver ligada uma sonda exterior AF.00 = OFF 01 = 0NINFLU. RECINTInfluência da temperatura ambiente.A temperatura da caldeira aumenta no valor seleccionado quando atemperatura ambiente desce abaixo do valor programado em 1 K.00: Actua conforme a temperatura exterior.20: Actua conforme a temperatura ambiente.ADA SENS AMBCorrecção da sonda ambiente.A leitura da sonda ambiente pode ser corrigida neste parâmetro seesta não medir correctamente.PRE-AQUE OPTOptimização.00 = OFF.01 = A central antecipa a entrada em funcionamento do sistema noprograma estabelecido, em função da temperatura exterior.02 = A central antecipa a entrada em funcionamento do sistema noprograma estabelecido, em função da temperatura ambiente.T MAX OPT AQTempo de optimização máximo.Esta função só está operativa se o parâmetro OPTIMIZAÇÃO estáconfigurado em 01 ou 02.A entrada em funcionamento do sistema antecipa-se, no máximo, otempo estabelecido neste parâmetro.ABAIX OPTIMITempo de optimização reduzido.A paragem da caldeira antecipa-se no máximo, o tempo estabelecidoneste parâmetro ao estabelecido pelo programa.LIBERACAO CPAcesso através dum PC.Código para permitir o acesso a partir de um PC.
100
80
60
40
20
3 2,5
2
1,5
1,2
1
0,80,6
0,40,2
20 16 12 8 4 0 -4 -8 -12 -16Temperatura Exterior (°C )
Tem
pera
tura
de
ida
(°C
)
3.8. Área PRO CRONOLOG
ACESSO ÁREA PRO CRONOLOG
PRO CRONOLOG
O equipamento é fornecido com uma programação standard de fábrica.
A informação que aparece no ecrã é a seguinte:
1
2
I
II
III III
II
I
GOLONORCORP UQAUGAGORP SQAotiucricodamargorP
1CEUQAGORP edotiucricod1amargorPotnemiceuqa
2CEUQAGORP edotiucricod2amargorPotnemiceuqa
SÁRTARAP
oicínI1olciC
miF1olciC
Cº02 olcicessearapadamargorparutarepmeT
oigóleR .otnemiceuqaedoãçamargorpaetnemacifargacidnI
otnemiceuqaedotiucricod1amargorP
otnemiceuqaedotiucricod2amargorP
1olcicodoicínI 1olcicodmiF
2olcicodoicínI 2olcicodmiF
3olcicodoicínI 3olcicodmiF
AIRÁTINASETNEUQAUGA
.S.Q.A.XES-.GES 00:12sà00:50.MOD-.BAS 00:32sà00:70
OTNEMICEUQA
1OTIUCRIC
1CEUQAGORP.XES-.GES 00:22sà00:60
MOD-.BAS 00:32sà00:70
2CEUQAGORPXES-.GES 00:80sà00:60
00:22sà00:61.MOD-.BAS 00:22sà00:61
Alteração dos ciclos de programação:
Aceder ao PROG AQUEC 1 do c i rcui to de aquecimento,pressionando .
Seleccionar o dia da semana (SEGUNDA a DOMINGO) ou o bloco (SEG.-SEX. ou SEG.-DOM) com e pressionar .
1 LIGAR 20ºC:Seleccionar a hora de início do ciclo 1 com e pressionar .
1 DESLIG 20ºC:Seleccionar a hora do fim do ciclo 1 com e pressionar .
2 LIGAR 20ºC:Seleccionar a hora de início do ciclo 2 com e pressionar .
2 DESLIG 20ºC:Seleccionar a hora do fim do ciclo 2 com e pressionar .
3 LIGAR 20ºC:Seleccionar a hora de início do ciclo 3 com e pressionar .
3 DESLIG 20ºC:Seleccionar a hora do fim do ciclo 3 com e pressionar .
Seleccionar outro dia da semana (SEGUNDA a DOMINGO) ou outrobloco (SÁB-DOM) com e pressionar .
Repetir o processo anteriormente descrito.
22
ORTEMÂRAP OLAVRETNI ROPROLAVOTIEFED
OTIUCRIC ACOACNUF 10,00 00
UQACRICMOB 30-00 00
MANIDUTSIM s042-03 s021
XAMOXULF-T Cº011-02 Cº08
NIMOXULF-T Cº011-01 Cº01
OLEG-T Cº)5(-)51-()----( Cº0
TXETDRATER h00:42-00:0 00:0
ILCNIOIVSED K05-0 K5
AGIRBOPECER 10,00 00
OLORTNOC-I -h00:30,FFOh51:00 FFO
SÁRTARAP
ORTEMÂRAP OLAVRETNI ROPROLAVOTIEFED
ETNEUQAUGÁ CBOIEUQOLB 10,00 0=10
BPF 10,00 00
SÁRTARAP
ORTEMÂRAP OLAVRETNI ROPROLAVOTIEFED
OTNEMAPIUQE OGIDÓC 9999-0000 ----
OGIDÓC 9999-0000 0000
SUBFITNEDI 51-10,)00( 10
RETSAMTIEZ 10,00 FFO=00
SÁRTARAP
Notas importantes:
1. Têm que ser introduzidos todos os ciclos de aquecimento de todos osdias da semana ou os blocos (SEG-SÁB e SÁB-DOM ou SEG-DOM)para que a informação seja armazenada.2. Caso se pretenda eliminar um ciclo horário de programação, ou não sedeseje introduzir dados para o ciclo 2 ou 3, terá que se configurar — —que se encontra no final do dia (…, 23:45, 24:00, ———, 00:00, 00:15,…).
3.9. Área PERITO
Nesta área acede-se ao ajuste dos parâmetros ao nível de perito comcódigo de acesso (o código de acesso é necessário para entrar emqualquer dos quatro níveis).Na alínea 3.9.1. são descritos os diferentes parâmetros da área PERITO.
O ajuste incorrecto dos parâmetros da área PERITO pode causaro mau funcionamento ou danos no sistema.
ACESSO ÁREA `PERITO
PERITO
SELECÇÃO DOPARÂMETRO
AJUSTEPARÂMETRO
CÓDIGOA sua alteração permite alterar todos os parâmetros da área PERITO,inclusive o número de código (primeiro parâmetro).IDENTIF BUSIdentificador BUSOs circuitos de aquecimento central numeram-se de forma sequencialpartindo de 01.Não se deve repetir o número identificativo de um circuito.Este parâmetro é especialmente importante quando se dispõe de váriascentrais E8 ligadas via BUS.ZEITMASTERTempo de referência.Todos os equipamentos ligados através do BUS recolhem informaçõesrelativas ao tempo (hora, dia, mês e ano) a partir do da central programadacomo referência de tempo.Só é permitido um tempo de referência no sistema, portanto, só umacentral poderá ter activado este parâmetro.No caso de que nenhuma central tenha activado este parâmetro, cadacentral gere os seus circuitos com base no seu próprio tempo.
00 = NÃO REFERÊNCIA DE TEMPO01 = CENTRAL É REFERÊNCIA DE TEMPO
EQUIPAMENTO
3.9.1 Descrição dos parâmetros da área PERITO
ÁGUA QUENTE
BLOQUEIO BCArranque do circulador de AQS.Se a função estiver activa (01), o circulador de AQS não se liga até quea temperatura da caldeira não ultrapassar em 5K a temperatura dodepósito de AQS; deste modo evita-se que o depósito arrefeça no períodotransitório de aquecimento da caldeira.FPBFuncionamento em paralelo dos circuladores de aquecimento central eAQS.00 = OF
01 = ON
CIRCUITO
FUNCAO CA
Selecção do tipo de circuito, conforme:
BOM CIRC AQU
Modo de funcionamento dos circuladores
MISTU DINAMParâmetro de controlo da válvula misturadora; corresponde ao temponecessário para a abertura completa da mesma.T-FLUXO MAXTemperatura máxima de impulsão.Para o caso de circuitos directos (sem válvula misturadora) existe umdiferencial em relação ao valor programado de + 8 K / - 5 K no corte e naligação respectivamente.
CÓDIGO
0000
INTRODUÇÃO DO CÓDIGO DE ACESSO PARA OS QUATRO DÍGITOS
SELECCIONARDIGITO
VALIDARAJUSTARVALOR
rolaV oãçircseD
00 .dradnatsotnemiceuqaedotiucriC
10
mocotnemiceuqaedsolcicsoetnarudalugerlartnecAodnecelebatse,axifoãslupmiedarutarepmetanesab
eLOSolcicoetnarudaxifoãslupmiedarutarepmetamuoetnarud)etnerefid(axifoãslupmiedarutarepmetamu
.AULodoírep
rolaV oãçircseD
00 .dradnatsotnemanoicnufedodoM
10DCEUQAMIL(setimilsoemrofnocotnemanoicnufedodoM
)NCEUQAMILe
20edamargorpomocodrocaedotnemanoicnufedodoM
.lartnecotnemiceuqa
30 ounítnocotnemanoicnuF
23
T-FLUXO MINTemperatura mínima de impulsão.T-GELOTemperatura exterior de activação da função anti-congelação.Se a temperatura exterior descer abaixo da temperatura programadapara este parâmetro, a função anti-congelação activa-se.RETR-T-EXTAtraso na reflexão por parte da central, da leitura da sonda exterior AF(só para edifícios muito isolados)DESVIO INCLIDiferença entre a temperatura da caldeira e a de ida em circuitosmisturadores. O valor programado compensa as perdas e tolerânciasdas sondas no valor da temperatura da caldeira, sobre a temperaturanecessária de impulsão do circuito misturador.RECEP OBRIGAO circuito de aquecimento pode utilizar-se como dissipador de calor, como objectivo de prevenir sobreaquecimentos na caldeira. Aplica-seunicamente com o aquecimento activado e estabelece a temperaturamáxima de impulsão.I-CONTROLSe existir um desvio na temperatura ambiente de 1 K para o valor ajustadoneste parâmetro, a temperatura de ida aumenta no valor de INFLU RECINT.
3.10 Funções de protecção do sistema
ANTI-CONGELAÇÃOA protecção anti-congelação estabelece-se nos seguintes pressupostos:
· Temperatura exterior abaixo do limite estabelecido no parâmetroPERITO>CIRCUITO>T-GELO (ligação circuladores e caldeira)
· Temperatura da caldeira inferior a 5ºC (ligação da caldeira à suatemperatura mínima estabelecida em T-CALD MIN)
· Temperatura ambiente inferior a 5ºC (ligação dos circuladores e dacaldeira)
AUTO-ANÁLISEA cada 10 min., a central estabelece uma auto-análise automática paraverificar se todos os parâmetros da mesma estão dentro dos limitesestabelecidos. Caso se detecte um parâmetro anómalo, o sistemabloqueia-se (código de erro 81).
ATRASO NA PARAGEM DO CIRCULADORNo corte de um circulador, este continua a funcionar durante 5 min. seuma das caldeiras esteve a funcionar nos últimos 5 min.
ANTI-BLOQUEIO DOS CIRCULADORESA central liga os circuladores que não tenham estado em funcionamentodurante as últimas 24 h, todos os dias às 12:00 durante 3 s.
ANTI-BLOQUEIO DAS VÁLVULAS MISTURADORASSe a válvula misturadora não funcionou nas últimas 24h, esta é totalmenteaberta às 3:00h. O circulador deixa de funcionar durante esta operação
e estabelece-se a temperatura máxima programada.
Uma vez corrigida a anomalia de funcionamento é necessário efectuarum RESET da central, para tal deverá pressionar com um objectopontiagudo no RESET.Para carregar os ajustes de fábrica, pressionar em simultâneo no RESETe no .
4. ANOMALIASEm caso de anomalia o ecrã mostra o símbolo intermitente, e ocorrespondente código de anomalia conforme a seguinte tabela:
OÃÇACINUMOCEDSORRE
09E 1e0SUBedserodacifitnedisoremúnsodoenâtlumisosU
19E .ametsisortuoropoãçazilitumeSUBodoãçacifitnediedoremúN
ONRETNIORRE
18E 01adacaautcefelartnecaeuqolortnoc-otuaonodatcetedorrEoodacidniéolavretniodarofrolavmuatcetedatseeS..nim
.sodicelebatsesetsujasoracifireves-odneved,orre
ADNOSADSORRE
96E 2otiucricodFVadnosanorrE
07E 1otiucricodFVadnosanorrE
57E FAroiretxeadnosanorrE
67E FPSotisópedodadnosanorrE
77E FKmeadagilariedlacadadnosanorrE
97E 1oãçnuf-itlumélerodadnosanorrE
08E 1otiucricod1RBFetneibmaadnosanorrE
38E odroirefniadnoS/2otiucricod1RBFetneibmaadnosanorrEanicsipadadnoS/rodalumucaotisóped
N-6
034-
0-03
06-C
E©
Ba
xi R
oca
Ca
lefa
cció
n, S
.L.U
. L’
Ho
spita
let d
e L
lob
reg
at
20
05
6
.67
01
.66
0
top related