TemBreak Plus For High Demand Applications
Ics=Icu=50kA & 85kA, Selectivity with 3:1 MCCB ratio
owerful interrupting Capacities
imitation of System Damage
nique Contact Structure
P
LU
electivity Enhanced Switchgear S
Innovators in Protection Technlogy
2
TemBreak PlusHigh Demand Applications
TemBreak Plus
TemBreak Plus meets this need, with frame sizes and accessories whichare completely compatible with the well established TemBreak range.Together TemBreak and TemBreak Plus offer a massive choice of ratings -one for every application!
Contact your local office for sales, service and application support.(Addresses on rear cover).
Marine systems with high demand loads and short cable runs, high faultservice rated switchboards, fully selective secure supplies.....
.....highly rated electrical installations need highly rated MCCB protection.
Innovators in Protection Technology
Innovators in Protection Technology
3
Section Contents Page
Product Features 5-10
Ratings and Specifications 11-16
Outline Dimensions 33-42
Optional Accessories 25-32
Thermal Magnetic Characteristics 17-20
Microprocessor Based Characteristics 21-24
N S
IEC
7 8 94 5 6
1 2 30 . X
=
–
+
ON
OFF
Selectivity Table 43-44
4
5
Product Features
Section
ON
OFF
6
Type XH125PJ XH160PJ XH250PJ XH400PJ XH400PE XH630PJ XH630PE XH800PJ XH800PE
No. of poles 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4
Ampere Frame 125 160 250 400 400 630 630 800 800
Rated Current In (Amp) 20,32,50,63 160 160,250 250,400 250,400 400,630 630 800 800
100,125
Rated AC breaking
capacity 690V 8/4 15/7.5 18/9 18/9 20/10 45/23 20/10 45/23 20/10IEC 60947-2 500V 25/13 25/13 42/21 42/21 42/21 65/33 42/21 65/33 42/21Icu/Ics kA 440V 42/35 42/35 65/50 65/50 65/50 85/43 65/50 85/43 65/50 415V 50/50 50/50 65/50 65/50 65/50 85/50 65/50 85/50 65/50 400V 50/50 50/50 65/50 65/50 65/50 100/50 65/50 100/50 65/50
Type TL-100NJ TL-250NJ TL-400NE TL-630NE TL-800NE TL-1250NE
No. of poles 3,4 3,4 3,4 3,4 3,4 3,4
Ampere Frame 100 250 400 630 800 1250
Rated Current In (Amp) 20,32,50, 160,250 400 630 800 1000
63,100 1250
Rated AC breaking
capacity 690V - - 25/25 25/25 45/34 45/34 45/34
IEC 60947-2 500V - - 70/70 70/70 75/57 75/57 75/57
Icu/Ics kA 440V 85/85 85/85 85/85 125/70 125/70 125/65
415V 85/85 85/85 85/85 125/70 125/70 125/65
400V 85/85 100/100 100/100 125/70 125/70 125/65
Type XS400SE XH400SE XS630SE XH630SE XS800SE XH800SE XS1250SE XH1250SE
No. of poles 3,4 3,4 3,4 3,4 3,4 3,4 3,4 3,4
Ampere Frame 400 400 630 630 800 800 1250 1600
Rated Current In (Amp) 250,400 250,400 630 630 800 800 1000 1600
1250
Rated AC breaking
capacity 690V 18/9 20/10 20/10 20/10 20/10 20/10 25/19 45/34
IEC 60947-2 500V 30/15 42/21 35/18 42/21 35/18 42/21 45/34 65/49
Icu/Ics kA 440V 42/21 65/33 50/25 65/33 50/25 65/33 65/49 85/64
415V 50/25 65/33 50/25 65/33 50/25 65/33 65/49 65/49
400V 50/25 65/33 50/25 65/33 50/25 65/33 85/64 100/75
PowerBreaker Series Ics = 50kA
LimitorBreaker Series Ics = 65~85kA
Selectivity Series 3:1 Selectivity
Product Features
TemBreak Plus
High Demand Applications
Thermal magnetic • • • • • •
Microprocessor • • •
Dimensions 4P 120x155x86 140x165x103 185x260x103 185x260x103 185x260x103 280x273x103 280x273x103 280x273x103 280x273x103
Dimensions 3P 90x155x86 105x165x103 140x260x103 140x260x103 140x260x103 210x273x103 210x273x103 210x273x103 210x273x103
Reference MCCB
for accessories XH125NJ XH250NJ XS400NJ XS400NJ XH400NE XS630NJ XH630NE XS800NJ XH800NE
Thermal magnetic • •
Microprocessor • • • •
Dimensions 4P 120x235x86 185x360X103 185x360x103 280X370X140 280X370X140 280x370x140
Dimensions 3P 90x235x86 140x360x103 140x360x103 210x370x140 210x370x140 210x370x140
Reference MCCB
for accessories XH125NJ XH400NJ XS400NE XS1600NE XS1600NE XS1600NE
Microprocessor • • • • • • • •
Dimensions 4P 185x260x103 185x260x103 280x273x103 280x273x103 280x273x103 280x370x120 280x370x120 280x370x140
Dimensions 3P 140x260x103 140x260x103 210x273x103 210x273x103 210x273x103 210x273x103 210x370x120 210x370x140
Reference MCCB
for accessories XS400NE XH400NE XS630NE XH630NE XS800NE XH800NE XS1250NE XS1600NE
7
Icu=o-co 2 Full Short CircuitsIcs=o-co-co 3 Full Short Circuits
During a fault condition, a circuit breaker withexcellent current limiting ability such as TemBreakPlus, can substantially reduce damage to the electricalsystem and thus minimise downtime.This current limiting feature reduces the peak letthrough current (Ipeak) and energy let through (I2t)during fault conditions.
Terasaki's TemBreak Plus MCCBs achieve thisexceptional current limiting performance by utilising aunique contact structure which we call the Fast BreakMechanism (FBM).The U-Shaped contact of this mechanism assists in theelectromagnetic repulsion of the contact tips for fastarc extinction.The 50kA PowerBreaker Series uses oneFBM per pole whilst the LimitorBreaker Series usestwo FBM per pole to achieve its rating of 85kA.
The need for a continuous and reliable power supplyplaces increased emphasis on selectivity requirementsin today's electrical distribution system.The Selectivity Series utilises microprocessor basedprotection, giving enhanced selectivity. This ensures3:1 ratio between the upstream and downstreamMCCBs. For further details please refer to theselectivity table on page 31 of this catalogue.
Powerful Interrupting Capacities Limitation of System Damage
Unique Contact Structure Selectivity Enhanced Switchgear
Icu = 50kAIcs = 25kA
XH125NJ
Icu = 50kAIcs = 50kA
XH125PJ Ics = 85kAIcu = 85kATL100NJ
Plus
Plus
kA
Conventional MCCB
TemBreak Plus
50
9
I peak
t
I t2
I t2
2
4
6
8
10
I2I1
0.1
0.2 0.3
0.4
IG
5
10
15
20
30
T1
0.1
0.150.2
0.25
0.3
SECT2
0.1
0.2
0.3
0.4
0.8
SECTG
LONG TIME SHORT TIME INSTANTANEOUS GROUND FAULT
TIMESETTING
PICK UP
SHORT TIME I2t
OFF ONTEST IN
SECat 6 x I1
RATED CUR. (A)
T
I
IG
I1
T1
I2 T2
I3TG
BASE CUR.
AIC
x In
0.63 0.8 1.0
0.8
0.85
0.9
0.95
1.0
CURR.SETTING
xI0 x I0X In
T2 SECat 10 x I0
12501250
3
6 9
12
x I0I3
CT RATED CURRENT
In A
The majority of distribution systems are designed to anultimate short circuit rating (Icu). An Icu rated MCCBprovides the optimum protection in terms of safe andeconomical selection.Certain applications may require protection which isdesigned to the more onerous service short circuitrating (Ics).Terasaki's TemBreak Plus range can provide a widechoice of MCCBs with superior Ics ratings up to 85kAat 440V AC.
Product Features
TemBreak Plus
High Demand Applications
8
Product Features
TemBreak Plus
High Demand Applications
Very often, MCCBs must grade with other protective devices that may not have adjustable characteristics.This could be either a downstream fuse or an upstream electricty authority relay. Each microprocessorbased TemBreak Plus can achieve as standard over 200,000 independant time current characteristics. Thisunique curve flexibility enables TemBreak Plus to achieve full selectivity even in the tightest of gradingsystems.
Microprocessor Time Current Characteristics
Microprocessor Adjustment Facia
4
3
2
15040
30
20
108
654
3
2
1504030
20
108
654
3
2
10.8
0.60.50.4
0.3
0.2
0.10.080.060.050.04
0.03
0.02
0.010.008
0.0060.005
8 9 10 15 20 25 30 40 50 60 70 80 90 100 60 70 80 90 100
125
150
200
250
300
400
500
600
700
800
900
1000
1500
2000
0.7
0.8
1.0
IP x I1
0.9
Pre-trip alarm(PTA) characteristics
Long time-delay (LTD) tripcharacteristic
Short time-delay (STD) tripcharacteristic
Instantaneous (INST)trip characteristic
Short time-delayI2t ramp selector switch
Ground fault trip(GFT) Characteristics
0.1
0.2 0.3
0.4
IG X In
0.1
0.2
0.3
0.4
0.8
SECTG
5
10
15
20
30
T1 SECat 6 x I1
I1
0.8
0.85
0.9
0.95
1.0
xI0
2
4
6
8
10
I2
0.1
0.150.2
0.25
0.3
SECT2x I0
OFF ON
T2 SECat 10 x I0
3
6 9
12
x I0I3
Tri
pp
ing
tim
e
Percent x[In] Percent x[Io]
ho
ur
min
ute
seco
nd
2
4
6
8
10
I2I1
0.1
0.2 0.3
0.4
IG
5
10
15
20
30
T1
0.1
0.150.2
0.25
0.3
SECT2
0.1
0.2
0.3
0.4
0.8
SECTG
LONG TIME SHORT TIME INSTANTANEOUS GROUND FAULT
TIMESETTING
PICK UP
SHORT TIME I2t
OFF ONTEST IN
Example XS1250SE
SECat 6 x I1
RATED CUR. (A)
T
I
IG
I1
T1
I2 T2
I3TG
PRE TRIP ALARM
0.7
0.8
1.0
IP x I1
0.9
BASE CUR.
AIC
x In
0.63 0.8 1.0
0.8
0.85
0.9
0.95
1.0
CURR.SETTING
xI0 x I0X In
T2 SECat 10 x I0
12501250
3
6 9
12
x I0I3
CT RATED CURRENT
In A
TRIP INDICATORSRESET
9
Product Features
TemBreak Plus
High Demand Applications
Flexibility
In addition to TemBreak microprocessor MCCBsbeing the most flexible on the market, a number ofimportant features are available as STANDARD!Most other MCCB manufacturers offer theserelevant features at a premium price.
Provision of adjustable LTD T1 settings and STDT2 setting are important to match the protec-tive characteristic to the load requirement. Itis also extremely useful to provide flexible grad-ing with other devices.
When co-ordinating between MCCB and fuses,it can often be difficult to obtain the requiredselectivity due to the different shape of the timecurrent curves. With a flick of a switch the I2tramp can be enabled to make grading easier.
Inductive loads such as motors often producea transient inrush on initial switching. In thisapplication it is important to have anadjustable instantaneous trip to set above thisinrush current.
T1
T2
5 sec
30 sec
300 msec
100 msec
L.V.fusedownstream
I3
motorstartingcurve
300% 1200%
Adjustable Time Settings
Adjustable Inst. TripAdjustable I T Ramp2
10
Electronic office equipment is being increasingly usedin today's buildings and factories.The power demand at peak time can reach overloadlevels of the breakers installed in the system. If such asituation continued a sudden trip may be generatedby the long time-delay trip function of the breaker.The pre-trip alarm prevents this 'sudden trip' by trippingout non-essential loads thus ensuring an uninterruptedsupply to essential loads.
TemBreak Plus MCCBs from 125AF to 1600AF aresuitable for isolation as defined by IEC 947-2. PositiveContact Indication (PCI) is achieved via the togglemechanism.Padlocks can only be installed if the contacts are fullyopen.
As well as microprocessor MCCBs from 125A to 1600A,Terasaki is one of the few manufacturers who can stilloffer a complete range of Thermal Magnetic MCCBsup to 800AF. The thermal adjustment of the TemBreakPlus range, 63% to 100% of the nominal rating, is oneof the biggest on the market.This proven form of electromechanical technology stillrepresents by far the largest type of MCCBs sold onthe European Market.Wouldn't you prefer the choice?
Output contact (1a)of the pre-trip alarm
SHTSHT
Essential Load Non-essential Load Non-essential Load
TemBreak
Computer
400A
ONI
400A 400A
OFFO
Pre-Trip Alarm Function (Optional)
Suitable for Isolation Choice of Protection
Thermal Adjustment63% - 100% x In
Magnetic Adjustment500% - 1000% x In
Ir 0.8
0.63 1
xIn
Im
6
5
7.18.5
10
xIn
I (ON) TRIP O (OFF)
High Frequency Harmonics Detected
TemBreak MCCBs employ a True R.M.S. detectionthrough a process of sampling and integrating.Even those MCCBs that claim True R.M.S. may only doso up until the 3rd or 5th Harmonic. Ignoring higherfrequency harmonics can lead to 'under protection'of the conductor. By utilizing a high sampling rate of500 µsec TemBreak microprocessor MCCBs detect upuntil and including the 19th Harmonic.
Frequency spectrum
Conventional r.m.s.
detection can ignore
higher frequency
harmonics
%
3
50
5 7 9 11 13 15 17 19
Total
Harmonic
Distortion
Product Features
TemBreak Plus
High Demand Applications
11
Ratings and
Section
IEC
7 8 94 5 6
1 2 30 . X
=
–
+
Specifications
12
3
5
5
44 4 4 4
Notes:
•
• 5
4
3
2
1NRC : Nominal Rated Current : The application on IT systems on this voltage is not available.ASR : Adjustable Setting Range : Available on request, contact Terasaki for details.
: Standard. This configuration is used unless otherwise specified. : For AC UVT, a UVT controller is mounted externally : Optional. Specify when ordering. : Line side interpole bariers supplied as standard. : Yes or available. : Draw out leads horizontally.
– : No or not available.
Ampere FrameType
2 2 2
Number of polesRATED CURRENT (A). [In]Calibrated at 45°C
RATED IMPULSE WITHSTAND VOLTAGE Uimp [kV]AC RATED INSULATION VOLTAGE [Ui]AC RATED BREAKING CAPACITY sym. r.m.s. [kA]IEC 947-2 [Icu] IEC 947-2 [Ics]BS EN 60947-2 [Icu] BS EN 60947-2 [Ics]CEI EN 60947-2 [Icu] CEI EN 60947-2 [Ics]
Without Inst.DC RATED BREAKINGCAPACITY [kA]RATED SHORT TIME CURRENT r.m.s. [kA] [Icw]UTILIZATION CATEGORYOUTLINE DIMENSIONS (mm) w
hd1d2
Weight (kg) marked standard typeCONNECTIONS AND MOUNTINGSFront Terminal screw (FCS)connected (FC) Attached flat bar (BAR)
Solderless terminal (PWC)Rear Bolt stud (REB)connected (RC) Flat bar stud (REF)Plug-in (PM) For switchboard (PRC/PMB)
For distribution boardDraw-out (DO)STANDARD FEATURESON-OFF colour indicationTrip buttonPROTECTIVE FUNCTIONSElectronic type
Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)
Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic tripsAdjustable thermal and fixed magnetic tripsAdjustable thermal and magnetic trips
ACCESSORIES (option)Internally Auxiliary switchmounted Alarm switch
Shunt trip Undervoltage trip
Externally Motor operatormounted Handle Panel mounted type
operating Breaker mounted type mechanism Variable depth type Handle extension Mechanical Front type interlock Rear type Handle holder Handle lock Terminal Front conn. type cover Rear conn./ plug-in type Interpole barrier Accessory lead terminal
Door flange IP20 Protection (Plug-in type)
125 160 250 400 400XH125PJ XH160PJ XH250PJ XH400PJ XH400PE
Ratings and Specifications
TemBreak Plus
PowerBreaker Series
3 4 3 4 3 4 3 4 3 4NRC ASR NRC ASR NRC ASR NRC ASR NRC ASR min. max. min. max. min. max. min. max. min. max. 20 13 20 160 100 160 160 100 160 250 160 250 400 200 400 32 20 32 250 160 250 400 250 400 50 32 50 63 40 63100 63 100125 80 1258 8 8 8 8690 690 690 690 690
690V 8/4 15/7.5 18/9 18/9 20/10 500V 25/13 25/13 42/21 42/21 42/21 440V 42/35 42/35 65/50 65/50 65/50 415V 50/50 50/50 65/50 65/50 65/50 400V 50/50 50/50 65/50 65/50 65/50 380V 50/50 50/50 65/50 65/50 65/50 240V 85/50 85/50 85/50 85/50 100/50 240-690V – – – – 5 250V 40 40 40 40 – 125V 40 40 40 40 –
– – – – 5 (0.3 sec)A A A A B90 120 105 140 140 185 140 185 140 185155 165 260 260 26086 103 103 103 103104 124 131 145 131 145 131 1451.3 1.6 2.1 2.6 4.7 6.1 4.7 6.1 4.8 6.2
– O (BAR) O (BAR) O (BAR) O (BAR)O O O O OO – – – –– O O O OO O O O –O – – – –– O O O O
• • • • •• • • • •
– – – – •– – – – • (PTA only)– – – – –
– – – – –– – – – – –
• • – – –– – • • –
CODE AX,AXE •(AXE) •(AXE) •(AX) •(AX) •(AX) AL,ALE •(ALE) •(ALE) •(AL) •(AL) •(AL)
SHT • • • • •UVT • • • • •MOT • • • • •OHE • • • • •OHJ • • • • •OHH • • • • •EHA – – – – –MIF • • • • •MIB • • • • •HH • • • • •HL • • • • •TCF • • • • •TCR • • • • •TBA • • • • •LTF • • • • •LTS – – – – –D.F • • • • •IP20 • • • • •
2
1
1
1
1
1
1
1
1
1
1
• • • • •
13
3
5
Notes:
•
• 5
4
3
2
1NRC : Nominal Rated Current : The application on IT systems on this voltage is not available.ASR : Adjustable Setting Range : Available on request, contact Terasaki for details.
: Standard. This configuration is used unless otherwise specified. : For AC UVT, a UVT controller is mounted externally : Optional. Specify when ordering. : Line side interpole bariers supplied as standard. : Yes or available. : Draw out leads horizontally.
– : No or not available.
Ampere FrameType
2 2
• • •
Number of polesRATED CURRENT (A). [In]Calibrated at 45°C
RATED IMPULSE WITHSTAND VOLTAGE Uimp [kV]AC RATED INSULATION VOLTAGE [Ui]AC RATED BREAKING CAPACITY sym. r.m.s. [kA]IEC 947-2 [Icu] IEC 947-2 [Ics]BS EN 60947-2 [Icu] BS EN 60947-2 [Ics]CEI EN 60947-2 [Icu] CEI EN 60947-2 [Ics]
Without Inst.DC RATED BREAKINGCAPACITY [kA]RATED SHORT TIME CURRENT r.m.s. [kA] [Icw]UTILIZATION CATEGORYOUTLINE DIMENSIONS (mm) w
hd1d2
Weight (kg) marked standard typeCONNECTIONS AND MOUNTINGSFront Terminal screw (FCS)connected (FC) Attached flat bar (BAR)
Solderless terminal (PWC)Rear Bolt stud (REB)connected (RC) Flat bar stud (REF)Plug-in (PM) For switchboard (PRC/PMB)
For distribution boardDraw-out (DO)STANDARD FEATURESON-OFF colour indicationTrip buttonPROTECTIVE FUNCTIONSElectronic type
Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)
Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic tripsAdjustable thermal and fixed magnetic tripsAdjustable thermal and magnetic trips
ACCESSORIES (option)Internally Auxiliary switchmounted Alarm switch
Shunt trip Undervoltage trip
Externally Motor operatormounted Handle Panel mounted type
operating Breaker mounted type mechanism Variable depth type Handle extension Mechanical Front type interlock Rear type Handle holder Handle lock Terminal Front conn. type cover Rear conn./ plug-in type Interpole barrier Accessory lead terminal
Door flange IP20 Protection (Plug-in type)
630 630 800 800XH630PJ XH630PE XH800PJ XH800PE3 4 3 4 3 4 3 4NRC ASR NRC ASR NRC ASR NRC ASR min. max. min. max. min. max. min. max.400 250 400 630 315 630 800 500 800 800 400 800630 400 630
8 8 8 8690 690 690 690
690V 45/23 20/10 45/23 20/10 500V 65/33 42/21 65/33 42/21 440V 85/43 65/50 85/50 65/50 415V 85/50 65/50 85/50 65/50 400V 100/50 65/50 100/50 65/50 380V 100/50 65/50 100/50 65/50 240V 125/63 100/50 125/63 100/50 240-690V – 10 – 10 250V 40 – 40 – 125V 40 – 40 –
– 10 (0.3 sec) – 10 (0.3 sec)A B A B210 280 210 280 210 280 210 280273 273 273 273103 103 103 103145 145 145 1459.0 11.5 9.0 11.5 9.0 11.5 9.0 11.5
– – – –
O O O O– – – –O O O OO O O O– – – –• • • •
• • • •• • • •
– • – •– • – •– • – •
– – – –– – – – –
– – – –• – • –
CODE AX,AXE •(AX) •(AX) •(AX) •(AX) AL,ALE •(AL) •(AL) •(AL) •(AL)
SHT • • • •UVT • • • •MOT • • • •OHE • • • •OHJ • • • •OHH • • • •EHA • • • •MIF • • • •MIB • • • •HH • • • •HL • • • •TCF • • • •TCR • • • •TBA • • • •LTF • • • •LTS – – – –D.F • • • •IP20 • • • •
2
1
1
1
1
1
1
1
1
•
2
22
Ratings and Specifications
TemBreak Plus
PowerBreaker Series
14
3
5
4 4
Notes:
•
• 5
4
3
2
1NRC : Nominal Rated Current : The application on IT systems on this voltage is not available.ASR : Adjustable Setting Range : Available on request, contact Terasaki for details.
: Standard. This configuration is used unless otherwise specified. : For AC UVT, a UVT controller is mounted externally : Optional. Specify when ordering. : Line and load side interpole bariers supplied as standard. : Yes or available. : Draw out leads horizontally.
– : No or not available.
Ampere FrameType
• • •
•
Number of polesRATED CURRENT (A). [In]Calibrated at 45°C
RATED IMPULSE WITHSTAND VOLTAGE Uimp [kV]AC RATED INSULATION VOLTAGE [Ui]AC RATED BREAKING CAPACITY sym. r.m.s. [kA]IEC 947-2 [Icu] IEC 947-2 [Ics]BS EN 60947-2 [Icu] BS EN 60947-2 [Ics]CEI EN 60947-2 [Icu] CEI EN 60947-2 [Ics]
Without Inst.DC RATED BREAKINGCAPACITY [kA]RATED SHORT TIME CURRENT r.m.s. [kA] [Icw]UTILIZATION CATEGORYOUTLINE DIMENSIONS (mm) w
hd1d2
Weight (kg) marked standard typeCONNECTIONS AND MOUNTINGSFront Terminal screw (FCS)connected (FC) Attached flat bar (BAR)
Solderless terminal (PWC)Rear Bolt stud (REB)connected (RC) Flat bar stud (REF)Plug-in (PM) For switchboard (PRC/PMB)
For distribution boardDraw-out (DO)STANDARD FEATURESON-OFF colour indicationTrip buttonPROTECTIVE FUNCTIONSElectronic type
Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)
Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic tripsAdjustable thermal and fixed magnetic tripsAdjustable thermal and magnetic trips
ACCESSORIES (option)Internally Auxiliary switchmounted Alarm switch
Shunt trip Undervoltage trip
Externally Motor operatormounted Handle Panel mounted type
operating Breaker mounted type mechanism Variable depth type Handle extension Mechanical Front type interlock Rear type Handle holder Handle lock Terminal Front conn. type cover Rear conn./ plug-in type Interpole barrier Accessory lead terminal
Door flange IP20 Protection (Plug-in type)
TL-100NJ TL-250NJ TL-400NE TL-630NE TL-800NE TL1250NE
Ratings and Specifications
TemBreak Plus
LimitorBreaker Series
1
1
1
1
1
1
1
1
1
1
• •
4
2 2
3 4 3 4 3 4 3 4 3 4 3 4NRC ASR NRC ASR NRC ASR NRC ASR NRC ASR NRC ASR min. max. min. max. min. max. min. max. min. max. min. max. 20 12.5 20 160 100 160 250 160 250 630 315 630 800 400 400 1000 500 1000 32 20 32 250 160 250 400 250 400 1250 630 1250 50 32 50 63 40 63100 63 100
8 8 8 8 8 8690 690 690 690 690 690
690V – – 25/25 25/25 45/34 45/34 45/34 500V – – 70/70 70/70 75/57 75/57 75/57 440V 85/85 85/85 85/85 125/70 125/70 125/65 415V 85/85 85/85 85/85 125/70 125/70 125/65 400V 85/85 100/100 100/100 125/70 125/70 125/65 380V 85/85 100/100 100/100 125/70 125/70 125/70 240V 100/100 130/130 130/130 150/113 150/113 150/113 240-690V – – 15 15 15 15 250V 40 40 – – – – 125V 40 40 – – –
– – 15 (0.3 sec) 15 (0.3 sec) 15 (0.3 sec) 15 (0.3 sec)A A B B B B90 120 140 185 140 185 210 280 210 280 210 280235 360 360 370 370 37086 103 103 140 140 140104 145 145 191 191 1912.2 2.7 7.1 9.1 7.1 9.1 25.8 33.5 25.8 33.5 26.0 33.7
– – ––
– –– – – –
–
– – – – – –– – – – – –
• • • • •• • • • •
– – • • • •– – • (PTA only) • • •– – – • • •
– – – – – –– – – – – – –
• – – – – –– • – – – –
CODE AX,AXE •(AXE) •(AX) •(AX) •(AX) •(AX) AL,ALE •(ALE) •(AL) •(AL) •(AL) •(AL)
SHT • • • • •UVT • • • • •MOT • • • • •OHE – – – • •OHJ • • • • •OHH • • • • •EHA – – – • •MIF • • • • •MIB • • • • •HH • • • • •HL • • • • •TCF • • • • •TCR • • • – –TBA • • • • •LTF • • • • •LTS – – – – –D.F • • • • •IP20 • • • • •
100 400 400 1600 1600 1600
15
NRC : Nominal Rated Current : Available on request, contact Terasaki for details.ASR : Adjustable Setting Range : For AC UVT, a UVT controller is mounted externally.
: Standard. This configuration is used unless otherwise specified. : Line side interpole barriers are supplied as standard. : Optional. Specify when ordering. : Draw-out leads, horizontally. : Yes or available.
– : No or not available.
2
5
•
Notes:
•
•
4
3
2
Ampere FrameType
44
5
Number of polesRATED CURRENT (A). [In]Calibrated at 45°C
RATED IMPULSE WITHSTAND VOLTAGE Uimp [kV]AC RATED INSULATION VOLTAGE [Ui]AC RATED BREAKING CAPACITY sym. r.m.s. [kA]IEC 947-2 [Icu] IEC 947-2 [Ics]BS EN 60947-2 [Icu] BS EN 60947-2 [Ics]CEI EN 60947-2 [Icu] CEI EN 60947-2 [Ics]
Without Inst.DC RATED BREAKINGCAPACITY [kA]RATED SHORT TIME CURRENT r.m.s. [kA] [Icw]UTILIZATION CATEGORYOUTLINE DIMENSIONS (mm)
whd1d2
Weight (kg) marked standard typeCONNECTIONS AND MOUNTINGSFront Terminal screw (FCS)connected (FC) Attached flat bar (BAR)
Solderless terminal (PWC)Rear Bolt stud (REB)connected (RC) Flat bar stud (REF)Plug-in (PM) For switchboard (PRC/PMB)
For distribution boardDraw-out (DO)STANDARD FEATURESON-OFF colour indicationTrip buttonPROTECTIVE FUNCTIONSElectronic type
Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)
Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic tripsAdjustable thermal and fixed magnetic tripsAdjustable thermal and magnetic trips
ACCESSORIES (option)Internally Auxiliary switchmounted Alarm switch
Shunt trip Undervoltage trip
Externally Motor operatormounted Handle Panel mounted type
operating Breaker mounted type mechanism Variable depth type Handle extension Mechanical Front type interlock Rear type Handle holder Handle lock Terminal Front conn. type cover Rear conn./ plug-in type Interpole barrier Accessory lead terminal
Door flange IP20 Protection (Plug-in type)
400 400 400 630 630XS400SE-C XS400SE XH400SE XS630SE-C XS630SE
•
4
2 2 2 2
3 4 3 4 3 4 3 4 3 4NRC ASR NRC ASR NRC ASR NRC ASR NRC ASR min. max. min. max. min. max. min. max. min. max.250 125 250 250 125 250 250 125 250 630 400 630 630 400 630400 250 400 400 250 400 400 200 4008 8 8 8 8690 690 690 690 690
690V 16/8 18/9 20/10 16/8 20/10 500V 22/11 30/15 42/21 25/13 35/18 440V 30/15 42/21 65/33 30/15 50/25 415V 35/18 50/25 65/33 35/18 50/25 400V 35/18 50/25 65/33 40/20 50/25 380V 35/18 50/25 65/33 40/20 50/25 240V 50/25 85/43 100/50 50/25 85/43 240-690V 5 5 5 10 10 250V – – – – – 125V – – – –
5 (0.3 sec) 5 (0.3 sec) 5 (0.3 sec) 10 (0.3 sec) 10 (0.3 sec)B B B B B
140 185 140 185 140 185 210 280 210 280260 260 260 273 273103 145 103 145 103 145 103 103131 131 131 145 1454.8 6.2 4.8 6.2 4.8 6.2 9.6 12 9.6 12
– –O (BAR) O (BAR) O (BAR)O O O O O– – – – –O O O O OO O O O O– – – – –
• • • • •• • • • •
• • • • •• (PTA only) • (PTA only) • (PTA only) • •• • • • •
– – – – –– – – – –– – – – –– – – – –
CODE AX,AXE •(AX) •(AX) •(AX) •(AX) •(AX) AL,ALE •(AL) •(AL) •(AL) •(AL) •(AL)
SHT • • • • •UVT • • • • •MOT • • • • •OHE • • • • •OHJ • • • • •OHH • • • • •EHA • • • • •MIF • • • • •MIB • • • • •HH • • • • •HL • • • • •TCF • • • • •TCR • • • • •TBA • • • • •LTF • • • • •LTS • • • • •D.F • • • • •IP20 • • • • •
2
Ratings and Specifications
TemBreak Plus
Selectivity Series
• • •
•
16
•
1
5
3
Notes:
Ampere FrameType
Number of polesRATED CURRENT (A). [In]Calibrated at 45°C
RATED IMPULSE WITHSTAND VOLTAGE Uimp [kV]AC RATED INSULATION VOLTAGE [Ui]AC RATED BREAKING CAPACITY sym. r.m.s. [kA]IEC 947-2 [Icu] IEC 947-2 [Ics]BS EN 60947-2 [Icu] BS EN 60947-2 [Ics]CEI EN 60947-2 [Icu] CEI EN 60947-2 [Ics]
Without Inst.DC RATED BREAKINGCAPACITY [kA]RATED SHORT TIME CURRENT r.m.s. [kA] [Icw]UTILIZATION CATEGORYOUTLINE DIMENSIONS (mm)
whd1d2
Weight (kg) marked standard typeCONNECTIONS AND MOUNTINGSFront Terminal screw (FCS)connected (FC) Attached flat bar (BAR)
Solderless terminal (PWC)Rear Bolt stud (REB)connected (RC) Flat bar stud (REF)Plug-in (PM) For switchboard (PRC/PMB)
For distribution boardDraw-out (DO)STANDARD FEATURESON-OFF colour indicationTrip buttonPROTECTIVE FUNCTIONSElectronic type
Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)
Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic tripsAdjustable thermal and fixed magnetic tripsAdjustable thermal and magnetic trips
ACCESSORIES (option)Internally Auxiliary switchmounted Alarm switch
Shunt trip Undervoltage trip
Externally Motor operatormounted Handle Panel mounted type
operating Breaker mounted type mechanism Variable depth type Handle extension Mechanical Front type interlock Rear type Handle holder Handle lock Terminal Front conn. type cover Rear conn./ plug-in type Interpole barrier Accessory lead terminal
Door flange IP20 Protection (Plug-in type)
•• • ••
2
2
22
222 2
630 800 800 1250 1600XH630SE XS800SE XH800SE XS1250SE XS1600SE
Ratings and Specifications
TemBreak Plus
Selectivity Series
3 4 3 4 3 4 3 4 3 4NRC ASR NRC ASR NRC ASR NRC ASR NRC ASR min. max. min. max. min.max. min.max. min.max.630 315 630 800 400 800 800 400 800 1000 500 1000 1600 800 1600
1250 630 12508 8 8 8 8690 690 690 690 690
690V 20/10 20/10 20/10 25/19 45/34 500V 42/21 35/18 42/21 45/34 65/49 440V 65/33 50/25 65/33 65/49 85/64 415V 65/33 50/25 65/33 65/49 85/64 400V 65/33 50/25 65/33 85/64 100/75 380V 65/33 50/25 65/33 85/64 100/75 240V 100/50 85/43 100/50 100/75 125/94 240-690V 10 10 10 15 20 250V – – – – – 125V – – – – –
10 (0.3 sec) 10 (0.3 sec) 10 (0.3 sec) 15 (0.3 sec) 20 (0.3 sec)B B B B B
210 280 210 280 210 280 210 280 210 280273 273 370 370 370103 103 103 120 140145 145 145 171 1919.6 12.0 9.7 12.5 9.7 12.5 22.0 28.0 27.0 35.0
– – – – –
O O O O –– – – – –O O O O OO O O O –– – – – –– – – – –
• • • • •• • • • •
• • • • •• • • • •• • • • •
– – – – –– – – – –– – – – –– – – – –
AX,AXE •(AX) •(AX) •(AX) •(AX) •(AX) AL,ALE •(AL) •(AL) •(AL) •(AL) •(AL)
SHT • • • • •UVT • • • • •MOT • • • • •OHE • • • • •OHJ • • • • •OHH • • • • •EHA • • • • •
MIF • • • • • •MIB • • • • •HH • • • • •HL • • • • •TCF • • • – –TCR • • • – –TBA • • • • •LTF • • • • •LTS – – – – –D.F • • • • •IP20 • • • • –
2NRC : Nominal Rated Current : Available on request, contact Terasaki for details.ASR : Adjustable Setting Range : For AC UVT, a UVT controller is mounted externally.
: Standard. This configuration is used unless otherwise specified. : Draw-out leads, horizontally. : Optional. Specify when ordering. : Yes or available.
– : No or not available.
3
5
•
•
2
17
Thermal Magnetic
Section
Characteristics
N S
18
Thermal Magnetic Characteristics
Time/Current Curves
XH125PJ, XH160PJ
Time/current characteristic curvesXH160PJ
Time/current characteristic curvesXH125PJ
Percent Rated Current
Trip
pin
g T
ime
43
2
15040
30
20
108
654
3
2
15040
30
20
108
654
3
2
10.80.6
0.50.4
0.3
0.2
0.10.08
0.060.050.04
0.03
0.02
0.010.008
0.0060.005
80
90
10
0
12
5
15
0
20
0
25
0
30
0
40
0
50
0
60
0
70
08
00
90
01
00
0
15
00
20
00
25
00
30
00
40
00
50
00
60
00
70
00
80
00
seco
nd
min
ute
ho
ur
125A
20, 32, 50, 63, 100A
Max.
Min.
Ambient compensating curvesAmbient compensating curves
130
120
110
100
900 10 20 30 40 50 60
Calibratedtemperature
5 15 25 35 45 55 6510 20 30 40 50 60 70
Calibrated at 40°C45°C50°C
Ambient temperature (°C)
Per
cent
cur
rent
rat
ing
160A(min.)
160A(max.)
Percent Rated Current
Trip
pin
g T
ime
43
2
15040
30
20
108
654
3
2
15040
30
20
108
654
3
2
10.80.6
0.50.4
0.3
0.2
0.10.08
0.060.050.04
0.03
0.02
0.010.008
0.0060.005
80
90
10
0
12
5
15
0
20
0
25
0
30
0
40
0
50
0
60
0
70
08
00
90
01
00
0
15
00
20
00
25
00
30
00
40
00
50
00
60
00
70
00
80
00
seco
nd
min
ute
ho
ur
Max.
Min.
Magnetic trip current
Rated curr.(A) Mag. trip curr.NRC (A)20 260±5232 420±8450 650±13063 820±164
100 1300±260 125 1550±310
Magnetic trip current
Rated curr.(A) Mag. trip curr.NRC (A)160 1760±176
150
140
130
120
110
100
90
800 10 20 30 40 50 60
Calibratedtemperature
50A, 20A(min.)
50, 20A(max.)
5 15 25 35 45 55 65Calibrated at 40°C
45°C 50°C
Ambient temperature (°C)
Per
cent
cur
rent
rat
ing
100, 32A(max.)
63A(min.)
100, 32A(min.)
125A(min.)
125A(max.)63A(max.)
10 20 30 40 50 60 70
19
Thermal Magnetic Characteristics
Time/Current Curves
XH250PJ, XH400PJ, XH630PJ, XH800PJ
Time/current characteristic curvesXH630PJ, XH800PJ
Time/current characteristic curvesXH250PJ, XH400PJ
Percent Rated Current
Trip
ping
Tim
e
43
2
15040
30
20
108
654
3
2
15040
30
20
108
654
3
2
10.80.6
0.50.4
0.3
0.2
0.10.08
0.060.050.04
0.03
0.02
0.010.008
0.0060.005
80 90 100
125
150
200
250
300
400
500
600
700
800
900
1000
1500
2000
2500
3000
4000
5000
6000
7000
8000
seco
ndm
inut
eho
ur
Min.
Max.
X5 X10
Percent Rated Current
Trip
ping
Tim
e
43
2
15040
30
20
108
654
3
2
15040
30
20
108
654
3
2
10.80.6
0.50.4
0.3
0.2
0.10.08
0.060.050.04
0.03
0.02
0.010.008
0.0060.005
80 90 100
125
150
200
250
300
400
500
600
700
800
900
1000
1500
2000
2500
3000
4000
5000
6000
7000
8000
seco
ndm
inut
eho
ur
Min.
Max.
X5 X10
Ambient compensating curvesAmbient compensating curves
130
120
110
100
900 10 20 30 40 50 60
Calibratedtemperature
800A (min)630A (min)400A (min)
Calibrated at 40°C45°C50°C
Ambient temperature (°C)
Per
cent
cur
rent
rat
ing
5 15 25 35 45 55 6510 20 30 40 50 60 70
800A (max)630A (max)400A (max)
Magnetic trip current
Rated curr.(A) Mag. trip curr.NRC (A)160 1660±160250 2500±250400 4000±400
Magnetic trip current
Rated curr.(A) Mag. trip curr.NRC (A)400 4000±160630 6300±250800 8000±400
130
120
110
100
90 0 10 20 30 40 50 60 5 15 25 35 45 55 6510 20 30 40 50 60 70
Calibratedtemperature
250A max.400A max.
Calibrated at 40°C45°C50°C
Ambient temperature (°C)
Per
cent
cur
rent
rat
ing
250A min.400A min.
20
Thermal Magnetic Characteristics
Time/Current Curves
TL-100NJ, TL-250NJ
Time/current characteristic curvesTL-250NJ
Time/current characteristic curvesTL-100NJ
Ambient compensating curvesAmbient compensating curves
Percent Rated Current
Trip
ping
Tim
e
43
2
15040
30
20
108
654
3
2
15040
30
20
108
654
3
2
10.80.6
0.50.4
0.3
0.2
0.10.08
0.060.050.04
0.03
0.02
0.010.008
0.0060.005
80 90 100
125
150
200
250
300
400
500
600
700
800
900
1000
1500
2000
2500
3000
4000
5000
6000
7000
8000
seco
ndm
inut
eho
ur
Percent Rated Current
Trip
ping
Tim
e
43
2
15040
30
20
108
654
3
2
15040
30
20
108
654
3
2
10.80.6
0.50.4
0.3
0.2
0.10.08
0.060.050.04
0.03
0.02
0.010.008
0.0060.005
80 90 100
125
150
200
250
300
400
500
600
700
800
900
1000
1500
2000
2500
3000
4000
5000
6000
7000
8000
seco
ndm
inut
eho
ur
x5 x10
80
90
100
110
120
130
140
150
160
10 20 30 40 505 15 25 35 45 55
Calibrated at 40 C45 C
Ambient temperature ( C)
Per
cent
cur
rent
rat
ing
0
Calibratedtemperature
o
o
32.50A min
100A min
63A min
20A min
100A max
32.50A max
20A max
63A max
90
100
110
120
130
140
150
10 20 30 40 505 15 25 35 45 5510 20 35 40 50 60
Calibrated at 40 C45 C50 C
Ambient temperature ( C)
Per
cent
cur
rent
rat
ing
0
Calibratedtemperature
250A min
160A max
250A max
160A min
o
o
o
Magnetic trip current
Rated curr.(A) Mag. trip curr.NRC (A)20 260±5232 420±8450 650±13063 820±164
100 1300±260
Magnetic trip current
Rated curr.(A) Mag. trip curr.NRC (A)160 1600±160250 2500±250
21
Section
Microprocessor BasedCharacteristics
Overcurrent tripping characteristics Overcurrent tripping characteristics
Time/current characteristic curvesXS630SE, XS630SE-C, XH630SE, XH630PE,XS800SE, XH800SE, XH800PE
Time/current characteristic curvesXS400SE, XS400SE-C, XH400SE, XH400PE,
CT rated current (A) (In) 250,400Base current setting (A): (Io) (In) x (0.63-0.8-1.0)Long time-delay pick-up current (A): (I1) (Io) x (0.8-0.85-0.9-0.95-1.0) Non-tripping at (I1)
setting x 105% and below. Tripping at 125% and above.Long time-delay time settings (S) (T1) (5–10–15–20–30) at (I1) x 600% current.
Setting tolerance ± 20%Short time-delay pick-up current (A): (I2) (Io) x (2-4-6-8-10) Setting tolerance ± 15%Short time-delay time settings (S) (T2) Opening time (0.1, 0.15, 0.2, 0.25, 0.3) in the definite
time-delay. Total clearing time is + 50 mS andresettable time -20mS for the time-delay setting
Instantaneous trip pick-up current (A) (I3) Continuously adjustable from (Io) x (3 to12)Setting tolerance ± 20%
* Pre-trip alarm pick-up current (A) (IP) (I1) x (0.7, 0.8, 0.9, 1.0) Setting tolerance ±10%* Pre-trip alarm time setting (S) (TP) 40 fixed definite time-delay.Setting tolerance ±10%Note: * OptionalNote: The underlined values will be applied as standard ratings unless otherwise specified when ordering.
Percent rated current of base current (I0)
Trippin
g T
ime
43
2
15040
30
20
108
654
3
2
15040
30
20
108
654
3
2
10.80.6
0.50.4
0.3
0.2
0.10.08
0.060.050.04
0.03
0.02
0.010.008
0.0060.005
80
90
10
0
12
5
15
0
20
0
25
0
30
0
40
0
50
0
60
0
70
08
00
90
01
00
0
15
00
20
00
25
00
30
00
seco
nd
min
ute
ho
ur
8 9
10
12
.5 15
20
40
50
Percent rated current ofCT rated current (In)
Microprocessor Based Characteristics
Time/Current Curves
PowerBreaker and Selectivity Series
T
I
IG
I1
T1
I2 T2
I3TG
IP
CT rated current (A) (In) 630,800Base current setting (A): (Io) (In) x (0.63-0.8-1.0)Long time-delay pick-up current (A): (I1) (Io) x (0.8-0.85-0.9-0.95-1.0) Non-tripping at (I1)
setting x 105% and below. Tripping at 125% & above.Long time-delay time settings (S) (T1) (5–10–15–20–30) at (I1) x 600% current.
Setting tolerance ± 20%Short time-delay pick-up current (A): (I2) (Io) x (2-4-6-8-10) Setting tolerance ± 15%Short time-delay time settings (S) (T2) Opening time (0.1, 0.15, 0.2, 0.25, 0.3) in the definite
time-delay. Total clearing time is + 50 mS andresettable time -20mS for the time-delay setting.
Instantaneous trip pick-up current (A) (I3) Continuously adjustable from (Io) x (3 to12)Setting tolerance ± 20%
* Pre-trip alarm pick-up current (A) (IP) (I1) x (0.7, 0.8, 0.9, 1.0) Setting tolerance ±10%* Pre-trip alarm time setting (S) (TP) 40 fixed definite time-delay.Setting tolerance ±10%* Ground fault trip pick-up current (A): (IG) Continiuously adjustable from (In) x (0.1 to 0.4)
Setting tolerance ± 15%* Ground fault trip time setting (S): (TG) Opening time (0.1-0.2-0.3-0.4-0.8) in the definite
time-delay. Total clearing time is + 50mS andresettable time is - 20mS for the time-delay settings
Note: * OptionalNote: The underlined values will be applied as standard ratings unless otherwise specified
when ordering.
Percent rated current of base current (I0)
Trip
ping
Tim
e
43
2
15040
30
20
108
654
3
2
15040
30
20
108
654
3
2
10.80.6
0.50.4
0.3
0.2
0.10.08
0.060.050.04
0.03
0.02
0.010.008
0.0060.005
80 90 100
125
150
200
250
300
400
500
600
700
800
900
1000
1500
2000
2500
3000
4000
5000
6000
7000
8000
seco
ndm
inut
eho
ur
T
I
IPI1
T1
I2 T2
I3
Curves based on standard settingscurves based on standard settings
Percent rated current of base current (I0)
Trip
pin
g T
ime
43
2
15040
30
20
108
654
3
2
15040
30
20
108
654
3
2
10.80.6
0.50.4
0.3
0.2
0.10.08
0.060.050.04
0.03
0.02
0.010.008
0.0060.005
80
90
100
125
150
200
250
300
400
500
600
700
800
900
1000
1500
2000
2500
3000
seco
nd
min
ute
hour
8 9
10
12.5 15
20
40
50
Percent rated current ofCT rated current (In)
T
I
IG
I1
T1
I2 T2
I3TG
IP
Microprocessor Based Characteristics
Time/Current Curves
LimitorBreaker Series
Time/current characteristic curvesTL-400NE
Percent rated current of base current (I0)
Trip
pin
g T
ime
43
2
15040
30
20
108
654
3
2
15040
30
20
108
654
3
2
10.80.6
0.50.4
0.3
0.2
0.10.08
0.060.050.04
0.03
0.02
0.010.008
0.0060.005
80
90
100
125
150
200
250
300
400
500
600
700
800
900
1000
1500
2000
2500
3000
4000
5000
6000
7000
8000
seco
nd
min
ute
hour
T
I
IPI1
T1
I2 T2
I3
Overcurrent tripping characteristics
Time/current characteristic curvesTL-630NE, TL-800NE, TL-1250NE
CT rated current (A) (In) 630, 800, 1000, 1250Base current setting (A): (Io) (In) x (0.63-0.8-1.0)Long time-delay pick-up current (A): (I1) (Io) x (0.8-0.85-0.9-0.95-1.0) Non-tripping at (I1)
setting x 105% and below. Tripping at 125% & above.Long time-delay time settings (S) (T1) (5–10–15–20–30) at (I1) x 600% current.
Setting tolerance ± 20%Short time-delay pick-up current (A): (I2) (Io) x (2-4-6-8-10) Setting tolerance ± 15%Short time-delay time settings (S) (T2) Opening time (0.1, 0.15, 0.2, 0.25, 0.3) in the definite
time-delay. Total clearing time is + 50 mS andresettable time -20mS for the time-delay setting.
Instantaneous trip pick-up current (A) (I3) Continuously adjustable from (Io) x (3 to 12)Setting tolerance ± 20%
* Pre-trip alarm pick-up current (A) (IP) (I1) x (0.7, 0.8, 0.9, 1.0) Setting tolerance ±10%* Pre-trip alarm time setting (S) (TP) 40 fixed definite time-delay.Setting tolerance ±10%* Ground fault trip pick-up current (A): (IG) Continiuously adjustable from (In) x (0.1 to 0.4)
Setting tolerance ± 15%* Ground fault trip time setting (S): (TG) Opening time (0.1-0.2-0.3-0.4-0.8) in the definite
time-delay. Total clearing time is + 50mS andresettable time is - 20mS for the time-delay settings
Note: * OptionalNote: The underlined values will be applied as standard ratings unless otherwise specified
when ordering.
Overcurrent tripping characteristics
CT rated current (A) (In) 400Base current setting (A): (Io) (In) x (0.63-0.8-1.0)Long time-delay pick-up current (A): (I1) (Io) x (0.8-0.85-0.9-0.95-1.0) Non-tripping at (I1)
setting x 105% and below. Tripping at 125% and above.Long time-delay time settings (S) (T1) (5–10–15–20–30) at (I1) x 600% current.
Setting tolerance ± 20%Short time-delay pick-up current (A): (I2) (Io) x (2-4-6-8-10) Setting tolerance ± 15%Short time-delay time settings (S) (T2) Opening time (0.1, 0.15, 0.2, 0.25, 0.3) in the definite
time-delay. Total clearing time is + 50 mS andresettable time -20mS for the time-delay setting
Instantaneous trip pick-up current (A) (I3) Continuously adjustable from (Io) x (3 to12)Setting tolerance ± 20%
* Pre-trip alarm pick-up current (A) (IP) (I1) x (0.7, 0.8, 0.9, 1.0) Setting tolerance ±10%* Pre-trip alarm time setting (S) (TP) 40 fixed definite time-delay.Setting tolerance ±10%Note: * OptionalNote: The underlined values will be applied as standard ratings unless otherwise specified when ordering.
Curves based on standard settings
Curves based on standard settings
24
Microprocessor Based Characteristics
Time/Current Curves
Selectivity Series
Overcurrent tripping characteristics
Time/current characteristic curvesXS1250SE, XS1600SE
CT rated current (A) (In) 1000, 1250, 1600Base current setting (A): (Io) (In) x (0.63-0.8-1.0)Long time-delay pick-up current (A): (I1) (Io) x (0.8-0.85-0.9-0.95-1.0) Non-tripping at (I1)
setting x 105% and below. Tripping at 125% & above.Long time-delay time settings (S) (T1) (5–10–15–20–30) at (I1) x 600% current.
Setting tolerance ± 20%Short time-delay pick-up current (A): (I2) (Io) x (2-4-6-8-10) Setting tolerance ± 15%Short time-delay time settings (S) (T2) Opening time (0.1, 0.15, 0.2, 0.25, 0.3) in the definite
time-delay. Total clearing time is + 50 mS andresettable time -20mS for the time-delay setting.
Instantaneous trip pick-up current (A) (I3) Continuously adjustable from (Io) x (3 to 12)Setting tolerance ± 20%
* Pre-trip alarm pick-up current (A) (IP) (I1) x (0.7, 0.8, 0.9, 1.0) Setting tolerance ±10%* Pre-trip alarm time setting (S) (TP) 40 fixed definite time-delay.Setting tolerance ±10%* Ground fault trip pick-up current (A): (IG) Continiuously adjustable from (In) x (0.1 to 0.4)
Setting tolerance ± 15%* Ground fault trip time setting (S): (TG) Opening time (0.1-0.2-0.3-0.4-0.8) in the definite
time-delay. Total clearing time is + 50mS andresettable time is - 20mS for the time-delay settings
Note: * OptionalNote: The underlined values will be applied as standard ratings unless otherwise specified
when ordering.
Percent rated current of base current (I0)
Trip
ping
Tim
e
43
2
15040
30
20
108
654
3
2
15040
30
20
108
654
3
2
10.80.6
0.50.4
0.3
0.2
0.10.08
0.060.050.04
0.03
0.02
0.010.008
0.0060.005
80 90 100
125
150
200
250
300
400
500
600
700
800
900
1000
1500
2000
2500
3000
seco
ndm
inut
eho
ur
8 9 10
12.5 15 20 40 50
Percent rated current ofCT rated current (In)
Curves based on standard settings
T
I
IG
I1
T1
I2 T2
I3TG
IP
25
Section
Optional Accessories
26
Auxiliary Trip (AX, AXE)
Electrically indicates On/Off statusof the breaker.
Alarm Switch (AL,ALE)
Electrically indicates when thebreaker is in the “Tripped” state.
Shunt Trip (SHT)
Remote tripping of the breaker
Undervoltage Trip (UVT)
Automatically trips the breakerwhen the circuit breaker fallsbelow pre-set value. Remotetripping of the breaker is alsopossible.Note: The UVT controller isinstalled externally, when providedwith AC UVT. (Refer to page 23)
Note: The SHT and UVT cannotbe mounted in the same breaker.
Operation of AX, AXE and AL, ALE
Auxiliary switches (AX,AXE) and alarm switches (AL,ALE) ratingsApplicable breakers 250AF or smaller 400AF or larger
(including:XH250PJ and TL250NJ)
Switch type *AV39052(AXE, ALE) *V-10(AX, AL)AC Voltage (V) 480 250 125 480 250 125
Current (A) Resistive load 0.4 3 3 3 5 5Lamp load 0.05 0.3 0.5 0.3 1.5 2Inductive load 0.25 2 2 2 5 5Motor load 0.1 0.5 0.7 0.4 2 3
DC Voltage (V) 250 125 30 250 125 30Current (A) Resistive load 0.2 0.4 3 0.3 0.6 5
Lamp load 0.03 0.05 1 0.05 0.1 3Inductive load 0.03 0.05 2 0.3 0.6 4Motor load 0.03 0.05 2 0.05 0.1 3
Note:* For use in the micro current (mA) range. Contact Terasaki for details.
Switch type Breaker 'ON' Breaker 'OFF' Breaker 'TRIP' Switch type Breaker 'ON' Breaker 'OFF' Breaker 'TRIP'
AX, AXE AL, ALE
AXc1
AXb1 AXa1 ALb1 ALa1
ALc1AXc1
AXb1 AXa1
AXc1
AXb1 AXa1 ALb1 ALa1
ALc1
ALb1 ALa1
ALc1
Ratings
Optional Accessories
Internally Mounted Accessories
Overview
27
Optional Accessories
Internally Mounted Accessories
Ratings
Undervoltage trip (UVT) ratings
UVT controllerIf the UVT is for AC use a UVT controller must be installed. Standard installation of the UVTcontroller is on the left side of the breaker. However, this may be installed in a separate location(please specify). Separate installation is standard for breakers fitted with Mechanical Interlocks.A time-delay UVT controller is available with the same outside configurations (please contactTerasaki for details). For the UVT controller mounting position and accessory lead terminal blockarrangement refer to pages 74-75 of catalogue ‘98-I20E.
XH125PJ 3.4 0.83 1.6 0.71 0.4 -XH160PJXH250PJ 1.1 0.93 2.52 1.55 0.67 0.35
Shunt trip (SHT) rating
PowerBreaker
Note: Special voltages available on request. Contact Terasaki for details.Note: Shunt trip is provided with anti-burnout switch.
Controller Designations
Frame size
Instantaneous type
Time delay type
50A-250A
XCU IS
XCU ID
400A-2500A
XCU 4JS
XCU 4JD
* Configuration is for simultaneous mounting with OCRcontroller, for details on OCR controller refer to page 38of catalogue ‘98-I20E.
50A to 250A frame 400A to 2500A frame
XH400PJ, XH400PEXH630PJ, XH630PEXH800PJ, XH800PETL-100NJ 3.4 0.83 1.6 0.71 0.4 -TL-250NJ 1.1 0.93 2.52 1.55 0.67 0.35TL-400NETL-630NETL-800NETL-1250NEXS400SE, XS400SE-C, XH400SE 1.1 0.93 2.52 1.55 0.67 0.35XS630SE, XS630SE-C, XH630SEXS800SE, XH800SEXS1250SEXS1600SE
LimitorBreaker
Selectivity
Series Breaker Rated Exciting coil current [ peak value (A)] Values at the highest voltage (60Hz for AC use)voltage:110-115VAC 200-480VAC 24VDC 48VDC 100-115VDC 200-230VDC
Note: AC rated, permissible operating voltage range is 85 to 110%. DC 75 to 125%.Note: *Applicable to 200V and 400V class only.
XH125PJ 5VA 5VA 5VA 18.2 4.8 *-XH160PJ
Undervoltage trip (UVT) ratings
TL-100NJ 5VA 5VA 5VA 18.2 4.8 *-TL-250NJ 2VA 2VA 2VA 86.5 21.2 12.1TL-400NETL-630NETL-800NETL-1250NEXS400SE, XS400SE-C, XH400SE 2VA 2VA 2VA 86.5 21.2 12.1XS630SE, XS630SE-C, XH630SEXS800SE, XH800SEXS1250SEXS1600SE
LimitorBreaker
Selectivity
Series Breaker Rated Power supply, VA (with UVT controller) Exciting coil current (MA)voltage:100-120VAC 200-480VAC 300-450VAS 24DC 110-115VDC 200-230VDC
XH250PJ 2VA 2VA 2VA 86.5 21.2 12.1XH400PJ, XH400PEXH630PJ, XH630PEXH800PJ, XH800PE
PowerBreaker
Note: Tripping voltage is 35-70% of the rated voltage. Resettable voltage is 85% or less, of the rated voltage.Note: *200V DC application available on request as a special specification and equipped with resistor. Contact Terasaki for details.Note: Special voltages available on request. Contact Terasaki for details
UVT controller
688 10
0
61010
80
16
22 6
25
1518
1516
7.8
*1OCR21
9
support
59
45
57.5
Terminal screw 9
support
83
69
81.5
Terminal screw
ON
OFFUC2UC1
Small type of breakeror fuse
ON
OFF
P2P1
UVTcontroller
UVTcontroller
Small type of breakeror fuse
NOTE: Terminals UC1 andUC2 are already connected
UC2UC1
P2P1
28
Designation
FCSPWCBARREFREBPRCPFBLTPLTFLTSPMBTCFTCRTBAXCUELBEHAHLMOTOMMOHEOHJMIFMIBMIW
Description
Front connect screwSolderless terminalAttach barRear connection flat barRear connection bolt studPlug-in rear connectionPlug-in attach barPlug-in lead terminalAccessory lead terminalAccessory lead terminal (angled entry)Plug-in mounting baseTerminal cover (front connected)Terminal cover (rear connected)Interpole barrierUVT controllerEarth leakage block *Extension handleHandle lockMotor operatorOperating handle, variable depthOperating handle, panel mountedOperating handle, breaker mountedFront mechanical interlockRear mechanical interlockWire mechanical interlock
REB
MIW
REF
PFB
PMB
LTP
MIB
MIF
REB
REF
ON
OFF
ON
OFF
PRC
PRC
Optional Accessories
Externally Mounted Accessories
Overview
* Available for MCCB types XH125PJ and XH160PJ only
29
Optional Accessories
Externally Mounted Accessories
Overview
OHJ
PWC
BAR
HL
FCS
LTF/LTS
XCU
TCR
TCF
TBA
LTP
ON
OFF
ON
OFF
DF MOT
UNLOCK
LOCK
OHH
EHA
BAR
PWC
ELB
I
0
TRIP.
LOADTemBreak
T
MANUAL OPERATION
ONI
TemBreak
XH400NE
In 400A
CONTACT
INDICATION
ON
TRIPPED
OFF
MOTOR
OPERATOR
Type
XMD4
Serial
CAUTION
Connections
NOTE
OnOff
P1P2
E
OnOff
P1P2
E
PUSH TO
TRIP
source
OHE
CAUTIONARY NOTESIf the motor operator is turned ON with thebreaker OFF and the UVT de-energised,apply the power and complete one ON-OFFoperation. (The breaker cannot be turnedON). Then complete one ON operation again(The breaker can be turned ON)
When the breaker is ON and is then tripped,the ON/OFF indicator on the motor operatorwill be indicating ON until the breaker is reset.Note: The breaker’s condition may differ.Note: Allow several minutes to cool when athermal-magnetic breaker is tripped by athermal overload trip, then reset the breaker.
Reference NotesPermissible operating voltage range asfollows:AC rated, 85 to 110% of the rated voltageDC rated, 75 to 110% of the rated voltageNote: AC rated operating voltage 380V or 400-460V a power transformer is available(optional)
Requires breaker’s auxiliary switch (1b-contact). This will be wired at the factory (onrequest) when the breaker/motor operatorassemblies are ordered. However, when allthe auxiliary switch contacts are specified forother purposes, an external auxiliary relay (notsupplied) is required to be controlled by theauxiliary a-contact of the breaker and use therelay’s normally closed contact (b-contact) forautomatic reset.
Time values at the rated operating voltage.Allow a longer time for the motor operator tocomplete the operation, at lower operatingvoltage.
The motor operator is of a short time duty. Donot subject it to more than 10 continuous ON-OFF operations. If this occurs, allow the motoroperator to cool for at least 15 minutes.
Maximum values at 110V ACMaximum values at 220V ACSpecial specification, available on request.
Ratings and specifications
Padlocking Device
ON/OFF indicator
Motor driven type 1
Optional Accessories
Externally Mounted Accessories
Motor Operators (MOT)
Power Supply
OFFRESET
AUTO RESETSW
(OPTION)
LIMITSW
X2 X1
X
ON
ABCD
E
Control circuit AC and DC
Type of Motor OperatorsApplicable Breakers
Rated OperatingVoltage
Automatic Reset
Steady-state r.m.s.Amp/inrush Amp (A)
Type of operationOperating Time(s)
Control Switch RatingsPower Source Capacity (VA)Dielectric withstand voltageWeight (kg)
XH125PJXH160PJTL-100NJ••–••2.0/4.52.0/4.51.0/2.01.0/2.0––Motor driven type10.85250V, 5A100AC100V1.8
PowerBreaker Series
Limitor SeriesAC 100-110V 200-220VDC 100-110VYesNoAC100 50Hz-110V 60HzAC200 50Hz-220V 60HzDC 100V
110V
ON OFF, RESET
1
2
3
4
5
6
7
1
2
5
6
7
7
7
Note: • Yes or available,
– No or not available
Note : Resistor is fitted for AC200-220V motor•• • • : Relay : MotorXY
Colour coding indicates the true position ofthe contacts clearly: ON (red), OFF (green),TRIP (white).
Positive contact indication
Lever pumping is no longer required.
Manual ON/OFF operationwith one stroke
Closing in 60ms or less. The closing timeremains constant over repeated operations.
Ratings and Specifications
NOTE• : Yes or available : Maximum values at AC115V, 50Hz : Maximum values at AC230V, 50Hz : Maximum values at DC110V : Maximum values at the rated operating voltages
1
2
3
4
ø5.5 mm
padlock
Lock Plate
Breaker mounting, removal, and even settingchanges can be done without removing themotor operator.
Easy maintenance Fast closing operation
Manualoperatinghandle
Indicator
Control circuitterminals
Indicator
Lock plate
Control circuitterminalsTrip button
Manualoperatinghandle
Type XMD4 Type XMD6, XMD9Trip button
Lock plate
The breaker can be padlocked in the “OFF”position by pulling out the lock plate, and locking itwith a padlock.When the breaker is “ON”, the lock plate cannot bepulled out.Up to three locks can be used.Padlocks not supplied.
__+ +
Type of Motor OperatorsApplicable Breakers
Rated OperatingVoltage (V)
Lock in "OFF" position (standard) Manual Trip ButtonSteady-state r.m.s.Amp/inrush Amp (A)
Type of operationOperating Time(s)
Control Switch RatingsPower Source Capacity (VA)Dielectric withstand voltageThe value in brackets for 24V DCWeight (kg)
XMD4
XH400SE••••••–/3.11.2/5.7–/1.20.7/3.0–/0.81.0/4.0–/4.54.0/12.0Spring Charged0.063250V, 5A300VAAC1500V (AC500V)
4.7
XMD6XH630PJ, XH800PJXH630PE,XH800PE - TL-630NE, TL800NE
TL-1250NEXS630SE,XS630SE-C XS1250SEXH630SE,XH800SE
•••••* *–/3.11.8/6.0–/1.21.0/3.2–/0.81.1/4.2–/4.54.0/12.0Spring Charged0.063250V, 5A300VAAC1500V (AC500V)5.6
XMD9
XS1600SE–•••••
–/3.11.8/6.0–/1.21.0/3.2–/0.81.1/4.2–/4.54.0/12.0Spring Charged0.063250V, 5A300VAAC1500V (AC500V)6.4
PowerBreaker Series XH250PJ, XH400PJXH400PE
LimitorBreaker Series TL-250NJTL-400NE
Selectivity Series XS400SE,XS400SE-C
AC 100-115V 50/60Hz 200-230V 50/60HzDC 100-110V 24V
AC100 ON-115V OFF, RESETAC200 ON-230V OFF, RESETDC100 ON-110V OFF, RESETDC24V ON OFF, RESET
ON (Maximium values)OFF, RESET
Optional Accessories
Externally Mounted Accessories
Motor Operators (MOT)
Control circuit AC and DC
32
33
Section
Outline Dimensions
34
Plug-in
Front connected
Rear connected with motor operator
ASL: Arrangement Standard LineH : Handle Frame Centre LineL
Drilling plan
Drilling plan Panel cutout
Preparation of conductor
M8 Screw
Mounting holeInterpole barrier(removable)
Mounting block
Panel cutout dimen-sions shown give anallowance of 1.0 mmaround the handleescutcheon
for accessory wiring when necessary
M4 x 0.7 Tapped hole
Insulated stud block
Mounting plate
M8Screw
R1M6 Mounting screw
Conductor
M5 x 0.8Mounting screw
Preparation of conductor
Drilling plan
M4 x 0.7 Mountingscrew M4 x 0.7
Tappedhole
Details of connection
Outline dimensions (mm)
TemBreak Plus
XH125PJ
2518
.5
90
134
154530
90
3060
18.5
107
194
25
121
35 22 2 11989
4P3P
60
120
90
30
3P 4P
155
134
N
24
4 86
104
79
27 6 30 30
1530 30 30
18
90 1515
60
30
134
13231
.5
21.5
15 60
30
29
31.5
51.5
66.5
3P
4P
134
3P 4P
29
67
102
132
15
86.5
86
207.
8
9
17(max.)
8.5(
max
.)
57.5
54.5
ø6.5
10(m
ax.)
15(max.)
3P 4P
4P
3P
24
52
13
ø6
100
75
60
3P 4P
24
3
3028 15
86
27
86
HLHL
ASL ASL ASL
HL HL
ASL
operating handle
ASL ASLASL
ASL
HL
HL
HL
HL
HL
HL
HLHL
13
121
90
padlockfacility
35
Plug-in
Front connected
Rear connected with motor operator
Drilling plan
M8 Screw
M4 x 0.7Mountingscrew
Drilling plan
Note: Breakers with terminal bars available on request
Conductoroverlap max.
Panel cutout dimensionsshown give an allowanceof 1.0 mm around thehandle escutcheon
R1
Panel cutout
Mounting block Drilling plan
Details of connection
Preparation ofconductor
With terminal bars (optional)Interpole barrier(removable)
M5 x 0.8 Mounting
Screw
M8 Screw
25 Max.conductor width
Accessory connection block
Mounting plate
for accessory wiring when necessary
M4 x 0.7 Tapped hole
Stud can be turned 90º
Mounting plate max. 5t
Conductoroverlap max.
M4 x 0.7Tappedhole
Outline dimensions (mm)
TemBreak Plus
XH160PJ
Mounting plate
ASL: Arrangement Standard LineH : Handle Frame Centre LineL
36
Outline dimensions (mm)
TemBreak Plus
TL-100NJ
80
30M4x0.7
80
28
157.
577
.5
30
90
147
67
120
90
67
7960
4 86
8.5
17
30
132
143.
551
52
4P
24
3P
177
97
89 119
6030
90
30
60
27
75
86
180
15
10
6
ø9
6730 45 15
214
24
R 1
13
2235 2
3
15
ø6
37.5
37.5
104
86
66
27
121
147
67
24
ASL ASLASL
4PLH LH
3P 4P
3P
LH
ASL
LH M8
(max
.)
(max.)
ASL
4P3P
LHLH
(max
.)
(max.)4P3P
LHLH
Interpole barrier(removable)
Mounting holescrew
Mounting screw
Preparation of Pan head screw
Conductor
Tapped hole
Drilling plan
Panel cutout
Panel cutout dimensions should give anallowance of 1.0mm around the handle escutcheon.
Note: Panel cutout shown for MCCBwithout motor operator.
ASL
Mounting screw
Mounting block
Preparation ofConductor
ø6.5 Drilling plan
M5X0.8
M4x0.7
Mounting plate
(XDM2LS)
ASL
LH
M6 mounting screwConductor
Detailsforconnection
25
274
18.5
133.
553
.525
18.5
86.5
66.5
30
51.5
30
31.5
30
ASL
LHMounting plate
Bolt stud:type XRD2
Insulated stud block
M8 screw
54.5
57.5
86
3P
4P
188
29
15
30 30
90 1515
60
29
21413
280
31.5
21.5
60 M4x0.7
ø18
66
15
66
4P3PLHLH
ø15 for accessory wiring when necessaryTapped hole
ASL
157.
577
.5
147
67
ASL: Arrangement Standard LineH : Handle Frame Centre LineL
Front connected
Rear connected with motor operator
Plug-in
37
Outline dimensions (mm)
TemBreak Plus
TL-250NJ, TL-400NE
33
8
45
214
100
30
29
45
115
45
110
103
4P
830
328
45
8
45
33
45
257015
90
107
3P
360
337
345
214.5
ø13ø13
15
25
33 45 33
45
Mounting plate
Flat bar stud : type XRP4
Stud can be turned 90
ASL ASL
LH LH
M6 tappedhole
ø15 for accessory wiring when necessary
ø36
Drilling planPanel cutout
Panel cutout dimensions showngive an allowance of 1.0mm
the line side and the load side are in a horizontal direction.
NOTE: In the standard shipment made, both terminals on
Conductoroverlap,max.
3P 4P
around the handle escutcheon.
4.5max.11
114
214
230
130
714
.5
ø11
23
M6 tapped hole
44.5
23.5
28
10
107
3P
3P
4P
4P
214
114
47
10
60
72 119
45
4P
234
4545
241
141
35
90
148
3P
60
2514
225
12118 47
20
35
20
90
140
185
70 115
45 45 45
214
114
230
130
360
110
103
145
5646
7.5
14.728
12.5
(max
.)
25(max.)
60 60 60
52.5
120
14.5
45
214
100
69
44.5
20
28
ø14
ø9
18
74
11.5
54
20
167
67
20
2727
11.5
382
Drilling plan
M10 screw
Preparation of
Hexagon socket head screw
Conductor
With Terminal Bars
(Optional) t=8
Interpole barrier(removable)
4P
ASLASLASLASL
HL
LH
LH
Values for conductors or optional terminal bars
ASL
Auxiliarycircuitterminal
ASL
LH LH
LH4P
ASL
Drilling planMounting block
Mounting angle
hole
3P
3P
M6 mounting screw
mounting hole
M8 Mountingscrew
(XDM4LS)
HL
Detailsforconnection
Conductor width, 35 max.
M10 screw
42
Note: Panel cutout shown for MCCBwithout motor operator.
4P
64
R6.5
3P
92
HL
ASL
Front connected
Rear connected with motor operator
Plug-in
ASL: Arrangement Standard LineH : Handle Frame Centre LineL
38
52.5
2010
3P 4P
N
On side 31Off side 30
3P
4P
90
140
45 4545
70 115
185
45
214
8
39
8
38
228
260
110
28 14.769
145
1037.5
28
120
44.5
14.5
56
ø14 28
23
60 6060
23.5 7 44
.5
14.5
25(max.)
12.5
(max
.)
11
46
74119
60
121
4P3P
3P 4P
15
103
ø13
334 max
228
203
214.
511
0
70
15 30
454545
25
2515
13
29
33 90 33
ø36
ø3645 45
33 3345 45 45
214
228
8
72
228
282
10
90
148
HL
122
4PMotor operatorPanel Cutout 3P
45 4545
54
134
2054
104
20
282
11.5
11.5
8
8
4P
3P
64
92
844P
9
18
20
35
47
60
134
2525
3P
HL
HL HL
HL
HLHL
HLHL
ASL
ASL
ASL ASL ASL ASL
ASL
ASL
ASL ASLASL ASL
30
28.5
28.5
HLHL HL
ASL
214.54.5max.11
345
R3
ASL
3P
4P
Front connected
Rear connected with motor operator
Plug-in
With terminal bars (optional) Drilling plan
Preparation ofconductor
On side
Note: Breakers with terminal bars available on request
M6 Mountingscrew
M10 Screw
M6Tappedhole
Off side
Stud can be turned 90º
Mounting plate
Conductor overlapmax. for accessory wiring when necessary
R6.5
M6 Tapped hole
Panel cutoutdimensions showngive an allowance of1.0 mm around thehandle escutcheon
Note: In the normal shipment mode, both terminals on the lineside and the load side are in the horizontal direction.
M8 Mountingscrew
Accessory connection block
35 max. conductor width
M10 Screw
Details of connection
Mountingangle
Conductoroverlap max.
Interpole barrier(removable)
Drilling plan
Panel cutout
Drilling plan
Mounting block
On side
Off side
Outline dimensions (mm)
TemBreak Plus
XH250PJ, XH400PJ, XH400PE, XS400SE, XS400SE-C, XH400SE
Lock plate
ASL: Arrangement Standard LineH : Handle Frame Centre LineL
39
90
280
105
13
1540
121
4P3P
3P 4P
N
3P
4P
3P
4P
3P 4P
15
7.5
13
273
141
132
13
13
140
210 280
175105
70 7070
80
258
32
70
A 32
6
BA
28 14
103
80.5 145
126
117
7
70
14043 43
48
55
126
117
136
127
5570
43 70 70 70 43
1042
117
126
141
132
70 70 70
122
214.
5
820
62 45
156
147
126
117 90
70 7070
175
6218
1862
6776
303
57
253285
456
210
140
173.
575
.524
4P
3P
64
92
67
4P
11
18
60
47
90
76
2525
3P
HL HL
HL
ASLASL
ASL
Lock plate
ASL ASLASL
ASL
ASL
ASL ASL
HL
HLHL
HL
HL HL
HL
ASL
21
8
80
13
4010
231
.5
Max. 310
214.5max 11 4.5
HL
168
4PMotor operatorPanel Cutout 3P
86.5
17.5
R3
ASL
ASL: Arrangement Standard LineH : Handle Frame Centre Line
Outline dimensions (mm)
TemBreak Plus
XH630PJ, XH630PE, XS630SE, XS630SE-C, XH630SE, XH800PJ, XH800PE, XS800SE, XH800SE
Front connected
L
Note:In the normal shipment mode, both terminals on the lineside and the load side are in the horizontal direction.
Panel cutout dimensionsshown give an allowanceof 1.0 mm around thehandle escutcheon
Details of connection
Extension handle(removable)
M8 Mountingscrew
Drilling plan
M8 Tappedhole
(Neutral: N)
Mounting plate
Stud can be turned 90º
for accessory wiring when necessary
M8 Tapped hole
Mounting block
Conductor overlap max.
R6.5
M10 Mountingscrew
Accessory connectionblock
Mountingangle
Drilling plan
40 max. conductor width
M16 Screw
Panel cutout
Drilling plan
Conductoroverlapmax.
Note: Breakers with terminal bars available on request
Rear connected with motor operator
Plug-in
Breaker type A B N
XH630PJ 8 34 36
XH630PE, XS/XH630SE, XS630SE-C 8 36 36
XH800PJ 10 35 36
XH800PE, XS800SE, XH800SE 10 36 36
40
Front connected
ASL: Arrangement Standard LineH : Handle Frame Centre LineL
Rear connected with motor operator
Plug-in
Outline dimensions (mm)
TemBreak Plus
XS1250SE
Panel Cutout
41
Outline dimensions (mm)
TemBreak Plus
TL-630NE, TL-800NE, TL-1250NE, XS1600SE
Front connected
ASL: Arrangement Standard LineH : Handle Frame Centre LineL
Rear connected with motor operator
Draw-out
Motor operatorpanel cutout (*)
* Panel cutout dimensions shown givean allowance of 1mm around thehandle escutcheon or 1.5mm aroundthe motor operator frame
42
43
Section
Selectivity Table
XE100NS
XS125CJ
XS125NJ
XH125NJ
XH125PJ
XS160NJ
XH160NJ
XH160PJ
XE225NS
XS250NJ
XS250PJ
XH250NJ
XH250PJ
XH250PE
XE400NS
XS400CJ
XS400NJ
XH400PJ
XS400SE-C
XS400SE
XH400SE
XH400PE
XE600NS
XS630CJ
XS630NJ
XH630PJ
XS630SE-C
XS630SE
XH630SE
XH630PE
T
T
T
35
35
15
35
25
15
15
15
25
**
**
**
**
**
**
**
**
**
**
**
**
**
**
**
**
**
**
T
T
T
T
T
T
T
T
T
T
T
T
25
25
T
25
25
25
25
25
25
25
**
**
**
**
**
**
**
**
T
T
T
T
T
T
T
T
T
T
T
T
50
50
T
T
T
50
T
T
50
50
20
30
30
30
30
30
30
30
T
T
T
T
T
T
T
T
T
T
T
T
50
50
T
T
T
50
T
T
50
50
20
30
30
30
30
30
30
30
UpstreamIcu @
415 400 50 50 65 65 50 50 65 65 50 50 65 65 65 85 85 100
XS400SE XH400SE XS630SE XH630SE XS800SE XH800SE XS1250SE XS1600SE
Notes: 1. The letter 'T' denotes Total Selectivity up to the breaking capacity of lower rated Icu MCCB. 2. The symbol '**' denotes that selectivity is only obtained up to the level of the upstream instantaneous trip 3. All pick-up current and time delay settings are to be set at maximum for upstream MCCBs
10 15
14 18
25 30
50 50
50 50
25
35
50
50
50 50
15 18
25 35
35 35
50 50
65 65
65 65
25 25
35 35
50 50
65 65
35 35
50 50
65 65
65 65
25 25
35 45
50 65
85 100
35 40
50 50
65 65
65 65
T
T
T
T
T
T
T
T
T
T
T
T
10
10
10
10
10
10
10
10
10
10
**
**
**
**
**
**
**
**
T
T
T
T
T
T
T
T
T
T
T
T
10
10
10
10
10
10
10
10
10
10
**
**
**
**
**
**
**
**
T
T
T
T
T
T
T
T
T
T
T
T
25
25
T
25
25
25
25
25
25
25
**
**
**
**
**
**
**
**
T
T
T
T
T
T
T
T
T
T
T
T
50
50
T
T
T
50
T
T
50
50
20
30
30
30
30
30
30
30
T
T
T
T
T
T
T
T
T
T
T
T
50
50
T
T
T
50
T
T
50
50
20
30
30
30
30
30
30
30
T
T
T
T
T
T
T
T
T
T
T
T
25
25
T
25
25
25
25
25
25
25
**
**
**
**
**
**
**
**
T
T
T
T
T
T
T
T
T
T
T
T
25
25
T
25
25
25
25
25
25
25
**
**
**
**
**
**
**
**
T
T
T
35
35
15
35
25
T
15
15
25
**
**
**
**
**
**
**
**
**
**
**
**
**
**
**
**
**
**
T
T
T
35
35
15
35
25
15
15
15
25
**
**
**
**
**
**
**
**
**
**
**
**
**
**
**
**
**
**
T
T
T
35
35
15
35
25
T
15
15
25
**
**
**
**
**
**
**
**
**
**
**
**
**
**
**
**
**
**
T
T
T
T
T
T
T
T
T
T
T
T
10
10
10
10
10
10
10
10
10
10
**
**
**
**
**
**
**
**
T
T
T
T
T
T
T
T
T
T
T
T
10
10
10
10
10
10
10
10
10
10
**
**
**
**
**
**
**
**
Downstream
Notes: 4. The above table is in accordance with IEC-947-2 Appendix A 5. Figures are shown with 415v information in white and 400v information in black 6. Selectivity figures for the XH-PE series are the same as the
XS-SE. Please contact Terasaki for further details.
Application
TemBreak Plus
Selectivity Table for 415V and 400V
PlusOVERSEAS NETWORK
TERASAKI (EUROPE) LTD.80 Beardmore Way, Clydebank Industrial Estate, Clydebank, G81 4HT. SCOTLAND (U.K.)Telephone: 44-141-941-1940 / Fax: 44-141-952-9246web: www.terasaki.com
TERASAKI ITALIA s.r.l.Via Campania 4/6, 20090 Segrate, Milano, ITALYTelephone: + 39-02-2137574 / Fax: + 39-02-26922931web: www.terasaki.it
TERASAKI ESPAÑA, S.A.Roma Street, s/n 08400 Granollers, Barcelona, SPAINTelephone: +34-93-8796050 / Fax: +34-93-870-3905web: www.terasaki.es
TERASAKI CIRCUIT BREAKERS (S) PTE. LTD.51 Tannery Lane #10-02, Sharely Warehouse, Singapore 1334, SINGAPORETelephone: +65-7449752 / Fax: +65-7487592
TERASAKI ELECTRIC (M) SDN. BHD.Lot 3 Jalan 16/13-D, 40000 Shah Alam,Selangor, MALAYSIATelephone: +60-3-5510-3820 / Fax: +60-3-55103763
TERASAKI DO BRASIL S.A.Rua Campo Grande No. 3700, Campo Grande, Rio de Janeiro, BRAZILTelephone: 021-413 4222 / Telex: 2123178 TBRJ BR / Fax: 21-3941875
ELECTRIC CO., LTD.Head Office: 7-2-10 Hannancho, Abenoku, Osaka, JAPANTelephone: 81-6-692-1131 / Telex: 526-7749 TTSAKI / Cable: TERASAKI OSAKACircuit Breaker Division: 7-2-10 Kamihigashi, Hiranoku, Osaka, JAPANTelephone: 81-6-692-1134 / Telex: 526-7769 TSKNFB / Fax: 81-6-695-2296web: www.terasaki.jp
JUNE 2000 CATALOGUE No. '00 - I26ERatings and specifications covered in this catalogue may be subject to change without notice.
top related