A quick review of SDG&E’s AL-TOU Rate
IceBank Energy Storage
Terry AndrewsCALMAC Manufacturing Corp.tandrews@calmac.com(714)585-6121
SDG&E’S AL-TOU RATE:
WHY IT IS A FANTASTIC RATE FOR ENERGY STORAGE DUE TO HIGH DEMAND CHARGES
Energy Storage for a Cooler Future ™
CALMAC Mfg.Corp.2012©
SDG&E’s AL-TOU Rate, Secondary Service
• There are 2 rate sheets to pull the actual rates from:– The AL-TOU rate….PLUS– The EECC rate sheet, commodity costs. AL-TOU tariff states:
• Utility Distribution Company (UDC) Total Rate shown above excludes any applicable commodity charges associated with Schedule EECC
UCSDTORREY PINES
CALMAC Mfg.Corp.2012©
SDG&E’s AL-TOU Rate, Secondary Service
• Demand charges are additive– (Summer peak period is 11am to 6pm, May thru Sept.)
• Summer demand is + $ 10.37/kW on peak
+ $ 10.95/kW from the EECC sheet+ $ 24.43 /kW for non-coincident demand
• The “non-coincident” demand charge is $24.43/kW
• What the heck is a non-coincident demand charge?– It’s a facilities penalty charge for high peak demand that occurs during the utilities
peak based on the highest electrical peak over the last month, defined in the rate sheet as:
“The non-coincident demand charge shall be based on the higher of the monthly maximum demand or 50% of the maximum annual demand.”
$45.75/kW
CALMAC Mfg.Corp.2012©
Base Load
LightingFans
Pumps
Cooling
0
200
400
600
800
1000
1200
1400
1600
1800
2000
k
W
On Peak Demand – $10.37/kWEECC Demand - $10.95/kWNon-Coincident - $24.43/kWEffective Total Demand:
$45.75/kW
SDG&E AL-TOU Rate – Effective Demand Charges
Over $65,000 per monthin demand charges!
CALMAC Mfg.Corp.2012©
Base Load
LightingFans
Pumps
0200400600800
100012001400160018002000
k
W
Charging Storage
600 kW Shed
SDG&E AL-TOU Rate – Effective Demand Charges
On Peak Demand – $10.37/kWEECC Demand - $10.95/kWNon-Coincident - $24.43/kWEffective Total Demand:
$45.75/kW
Save!!!!$27,000/month
CALMAC Mfg.Corp.2012©
Summer “Blended” Costs – Day vs. Night29.4 cents vs. 8 cents per kWh
CALMAC Mfg.Corp.2012©
SDG&E’s AL-TOU Rate, Secondary Service
• In the winter (November thru April) the peak period is defined as 5pm to 8pm.
• If we assume the building is an office or a building with a similar cooling load profile the peak is likely to occur between 2pm and 5pm.
• Thus, at this time the demand savings will be derived from reducing the size of the non-coincident demand peak ……but this is a significant charge:
$24.43/kW
CALMAC Mfg.Corp.2012©
Winter “Blended” Costs, Day vs. Night18.6 cents verses 7.2 cents per kWh
CALMAC Mfg.Corp.2012©
SDG&E’s AL-TOU Rate, Summary
• The demand charges are significantly large.
• There are potentially large savings when shifting load in a daytime peaking building.
• Electricity in the summer is approximately 72% cheaper at night
• Electricity in the winter is approximately 61% cheaper at night
CALMAC Mfg.Corp.2012©
Recent Projects
Edwards AFBCA
Encinitas Civic CenterEncinitas, CA
Nordstrom Dept. StoreHawaii
Los PositasLivermore, CA
CALMAC Mfg.Corp.2012©
Recent Projects
Irvine Presbyterian ChurchIrvine, CA
Los Angeles Community College,Los Angeles, CA
Chabot College Hayward ,CA
California State Lottery Sacramento, CA
CALMAC Mfg.Corp.2012©
College Campus
University of ArizonaTucson, AZ
Production22 Chillers – 34,350 tons205 CALMAC IceBank™ tanks at two sites
30,750 ton hours of storage
Distribution7 miles of underground pipes5,500,000 gallons of water in the loop11 Pumps – 3255 HP (0.095 HP / ton of refrigeration)There are no pumps outside of the chiller plants62,260 gpm circulation capacity (1.8 gpm / ton)12 psi - total campus pressure drop16 degrees – average yearly temperature rise of the chilled waterLoads
176 buildings11,750,000 square feet (342 tons / ft².)
Notable Results
Distributes the chilled water at an average of 0.683 KW/ton. Includes everything, chillers, pumps, towers.
Thermal storage is saving $423,000/year ($2,063/tank/yr)
CALMAC Mfg.Corp.2012©
Get Started with Pre-engineered Hybrid Storage Systems
You don’t have to start from scratch.
Air Cooled Hybrid Cooling with pre-selected equipment combinations:• A/C Chillers• IceBank™ Tanks and Plate Frame HX’s• Factory Assembled Smart Pumping Skid• Pre-packaged controls • Dashboards that document savings
Saves time and MONEY• Design and Installation phase• Commissioning phase• Operation & Maintenance phase
CALMAC Mfg.Corp.2012©
Jefferson County Community College StagingJefferson County Community College Running
$ 84,000 REBATE!......IF IN CA