8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 1/27
6*27MW REYG AS TURBINE POWER PLANT
Purpose of issue
For Approval ■
For Review
For Construction
For Information
For Procurement
For Quotation
For Use
DistributedExecutiveDeputy
Commercial/
Subcontracting
Client
Consultant ■
Commissioning
QC Dept.
Planning Dept.
Sub-Contractor
Eng. Manager
Civil
Electrical
Inst. &Control
Mechanical
Piping Process
Archive ■ ■
File Copy
Recipients
Document Name:Battery & Battery Charger Calculation
A 10 Jun. 09 Second Issue Z. Fakhri M. Khanmohammadi A. Shahintabe
0 3 Feb. 09 First Issue Z. Fakhri M. Khanmohammadi A. Shahintabe
Rev. Date Description Prepared Checked Approved
Sub-Contractor: Sub-ContractorDocument No.
Document No. SizeTotalPage
No. of Attachment
REY-MS-59ED-08-EFG-001Rev.A
A4 27 1
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 2/27
Document Name: Battery and Charger Calculation Page 2 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
Page Rev.0 Rev.A Rev.B Rev.C Rev.D
1
2 3
4
5
6
7
8
9
10
11 12
13
14
15
16
17
18
19
20 21
22
23
24
25
26
27
28
29 30
31
32
33
34
35
36
37
38
39 40
Page Rev.0 Rev.A Rev.B Rev.C Rev.D
41
42 43
44
45
46
47
48
49
50
51 52
53
54
55
56
57
58
59
60 61
62
63
64
65
66
67
68
69 70
71
72
73
74
75
76
77
78
79 80
TABULATION OF REVISED PAGES
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 3/27
Document Name: Battery and Charger Calculation Page 3 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
1. BPurpose
The purpose of this document is sizing of nickel-cadmium batteries with standardized technique for
stationary application.
2. B
Reference
The procedure of sizing nickel-cadmium batteries is based on the following standard:
IEEE Std 1115-2000, “IEEE Recommended Practice for Sizing Nickel-Cadmium Batteries for
Stationary Applications”
IEC 60623, fourth edition 2001, “Secondary cells and batteries containing alkaline or other noon-acid
electrolytes- vented nickel-cadmium prismatic rechargeable single cells”
3. BDefinitions
Available capacity: The capacity for a given discharge time and end-of-discharge voltage that can
be withdrawn from a cell under the specific conditions of operation.
Battery duty cycle: the loads a battery is expected to supply for a specified time periods.
Full float (constant potential) operation: Operation of a dc system with the battery, battery charger,
and load all connected in parallel and with the battery charger supplying the normal dc load plus any
self-discharge or charging current required by the battery. (The battery will deliver current only when
the load exceeds the charger output.)
Period: An interval of time in the battery duty cycle during which the load is assumed to be constant
for purposes of cell sizing calculations.
Rated capacity (nickel-cadmium cell): The capacity assigned to a nickel cadmium cell by its
manufacture for a specific constant current discharge voltage.
4. BGeneral considerations
The battery must supply the dc power requirement when the following conditions occur:
a) The load on the dc system exceeds the maximum output of the battery charger.
b) The output of the battery charger is interrupted.
c) The ac power is lost.
The most severe of these conditions, in terms of battery load and duration, should be used to
determine the battery sizing for the installation.
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 4/27
Document Name: Battery and Charger Calculation Page 4 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
5. BDetermining battery size
I. BNumber of cells
When the battery is allowed to exceed a given maximum system voltage, the number of cells will be
limited by the manufacture’s recommended cell voltage required for satisfactory charging. That is,
The minimum battery voltage equals the minimum system voltage plus any voltage drop between the
battery terminals and the load. The minimum battery voltage is then used to calculate the allowable
minimum cell voltage,
The DC system voltage limits are from 112.5 V to 137.5 V (125VDC±10%) and the manufacturer
recommends a cell voltage of 1.40 V for satisfactory charging, so:
Required Number of Cells = 137.5 V / 1.40 V per cell = 98.2, therefore 98 cells;
End-of-charging voltage = 112.5 V / 98 V = 1.14 V per cell
II. B
Additional considerations:
Temperature derating factor (Tt): The available capacity of a cell is affected by operating
temperature. The standard temperature for stating cell capacity is 25℃. If the lowest expected
electrolyte temperature is above 25℃, generally no noticeable increase in the available capacity.
Design Margin: Since the loads of this practice are not exposed to grow, there is no need to provide
such growth rate to the cell size calculation. Therefore, design margin of 1 is used.
Aging Factor: Capacity decreases gradually during the life of the battery, with no sudden capacity
loss being encountered under normal operating conditions. Since the rate of capacity is dependentupon such factors as operating temperature, electrolyte-specific gravity, and depth of frequency of
discharge, an aging factor should be chosen. The choice of aging factor is, therefore essentially an
economic consideration. In this practice an aging factor of 1.2 is used, meaning that the battery is
sized to carry the loads until its capacity has decreased approximately to 80% of its rated capacity.
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 5/27
Document Name: Battery and Charger Calculation Page 5 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
6. B
Duty cycle diagram
A duty cycle diagram showing total load at any time during the cycle is an aid in the analysis of the
duty cycle. Loads that have inception and shut down times that are known are plotted on the duty
cycle diagram as they would occur.
Table 1: DC Load List that shall be supplied by Batteries
N
o. Name
Quantity Rating Load Capacity (A)
Remarks
T o t a l Q ’ t y
N o
r . O p e . Q
’ t y
C
a p a c i t y
U n i t
C o
n t i n u o u s
I
n r u s h /
S
t a r t i n g
I
n r u s h /
S
t a r t i n g
T i
m e ( s e c )
1Emergency Lube Oil
Pump1 1 5.5 kW 43.6 132.5 10
2Hydraulic Ratchet
Pump1 1 0.75 kW 5.7 25.5 3
3 Generator Breaker 1 1 2.0 A 2.0 6.0 10.0
4
Emergency Lighting
for ACC.
Compartment
1 1 0.8 A 0.8 - -
5
Emergency Lighting
for Control
Compartment
1 1 0.8 A 0.8 - -
6Turbine Control
Panel1 1 8.0 A 8.0 - -
7Generator Protection
Panel1 1 4.0 A 4.0 - -
8 AVR cubicle 1 1 4.0 A 4.0 - -
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 6/27
Document Name: Battery and Charger Calculation Page 6 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
B
The Duty Cycle Diagram indicated by this DC load list is:
Fig.1 Duty Cycle Diagram
Time(min)
S123
S122
S3S2
S1
P123P3P2P1
120
3 sec
180 sec
180 sec
10 sec
156.1A
Ratchet Start
Rotor Stop
Black out after Trip
0 2017
COOL DOWNSHUT DOWNLoad (A)
≈
≈
19.6
200 sec
20 sec
10 sec
177.6A
68.9A
157.8A
63.2
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 7/27
Document Name: Battery and Charger Calculation Page 7 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
7. B
Cell Sizing Data
The following table summarizes the Cell Sizing Data for the given Duty Cycle Diagram.
Table 2: Cell Sizing Data
PeriodTotal
amperes
Duration Capacity Removed
(Ah)Remarks
Sec. Min.
1 156.1 10 0.1667 0.43361111
2 63.2 1010 16.83 17.7311111
3 19.6 180 3 0.98 *31 times
4 177.6 3 0.05 0.148 *30 times
5 157.8 7 0.116 0.30683333 *30 times
6 68.9 10 0.1667 0.19138889 *30 times
The periods remarked by * are repeated as per defined.
Total = 67.93 Ah
At the first step KPL70 selected to supply DC loads specified in Table1.
Table 3: Discharge Currents for KPL cell range manufactured by Interberg CompanyNICKEL-CADMIUM BATTERIES, DISCHARGE TABLESinterberg batteries
FINAL DISCHARGE VOLTAGE : 1,14 VOLTS / CELL
CELL TYPES
DISCHARGE TIME
10
h
8
h
5
h
3
h
2
h
90
min
60
min
45
min
30
min
20
min
15
min
10
min
5
min
60
sec
30
sec
5
sec
1
sec
KPL70 7.35 9.19 14.09 19.5 23 27 32.2 34.9 40.2 43.5 45 47.5 53.8 63.8 73 76.4 78.4
KPL80 8.40 10.50 16.10 22.3 26.3 30.9 36.8 39.9 45.9 49.7 51.4 54.3 61.5 72.9 83.4 87.3 89.6
KPL90 9.27 11.97 18.09 25.0 29.6 34.8 41.5 44.8 51.6 56.0 57.8 61.1 63.8 81.9 94.5 98.1 101
KPL100 10.30 13.30 20.10 27.8 32.9 38.7 46.1 49.8 57.3 62.2 64.2 67.9 70.9 91.0 105 109 112
KPL115 12.24 15.18 23.09 32.0 37.9 44.4 53.0 57.2 65.9 71.6 73.7 78.1 88.5 103 113 120 129
KPL135 14.67 17.91 27.09 37.5 44.5 43.1 62.1 67.2 77.3 84.0 86.5 90.9 104 124 142 147 151
KPL15016.30 19.90 30.10 41.7 49.4 47.9 69.0 74.7 85.9 93.3 96.1 101 115 138 158 163 168
KPL180 19.17 23.76 36.00 50.0 59.2 69.4 82.7 89.6 103 112 114 122 138 165 190 196 202
KPL200 21.30 26.40 40.00 55.6 65.8 77.1 91.9 99.5 114 124 127 135 153 183 211 218 224
KPL250 26.40 33.00 44.90 69.5 82.3 96.2 114 123 142 155 159 169 192 229 263 272 280
KPL280 29.40 36.87 55.91 77.7 92.1 107 128 138 160 174 178 189 215 258 289 305 308
KPL300 31.50 39.50 59.90 83.3 98.7 115 137 148 171 186 191 203 230 276 310 327 330
KPL330 34.7 43.37 65.91 91.6 108 126 151 163 189 205 210 223 254 303 347 359 370
KPL350 36.80 46.00 69.90 97.1 115 134 160 173 200 217 223 237 269 321 368 381 392
KPL400 42.10 52.50 79.70 110 131 153 183 198 228 248 255 271 307 366 419 436 448
KPL430 45.15 56.50 85.66 119 141 165 197 212 245 267 274 292 330 393 449 469 482
KPL450 47.25 59.13 89.64 124 148 173 206 222 257 279 287 305 346 411 470 491 504
KPL500 52.50 65.70 99.60 138 164 192 229 247 285 310 319 339 384 457 522 545 560
KPL600 62.50 78.70 119 165 197 230 275 297 342 372 383 407 461 549 627 654 672
KPL700 73.40 91.70 138 193 230 268 320 346 400 434 447 475 538 637 731 763 784
KPL800 83.90 104 158 221 263 307 366 396 457 496 511 543 615 729 845 873 896
KPL900 94.3 117 178 248 296 345 412 445 514 558 575 611 692 820 940 982 1008
KPL1000 105 130 198 276 329 383 458 495 571 621 639 679 769 911 1043 1091 1120
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 8/27
Document Name: Battery and Charger Calculation Page 8 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
8. Capacity Rating Factors ( K t)
The capacity rating factor, K t , is the ratio of rated ampere-hour capacity (at a standard time rate,
25℃, and to standard end-of-discharge voltage) of a cell, to the amperes that can be supplied by that
cell for t minutes at 25℃ and to a given end-of-discharge voltage.
The factor K t for time t is calculated in the following table by interpolation using the formula:
Table 4: Calculation of the Capacity Rating Factors (K t ) for KPL70 cell type:
t(min) t 1(min) t 2(min) Ampere
t1
Ampere
t2Kt1 Kt2 Kt
0.05 0.016667 0.083 78.4 76.4 0.893 0.916 0.905
0.1167 0.083333 0.500 76.4 73 0.916 0.959 0.920
0.1667 0.083333 0.500 76.4 73 0.916 0.959 0.925
0.2833 0.083 0.5 76.4 73 0.916 0.959 0.937
0.3333 0.083 0.5 76.4 73 0.916 0.959 0.942
3 1 5 63.8 53.8 1.097 1.301 1.199
3.05 1 5 63.8 53.8 1.097 1.301 1.202
3.1667 1 5 63.8 53.8 1.097 1.301 1.208
3.2167 1 5 63.8 53.8 1.097 1.301 1.210
3.2833 1 5 63.8 53.8 1.097 1.301 1.214
3.3333 1 5 63.8 53.8 1.097 1.301 1.216
3.3833 1 5 63.8 53.8 1.097 1.301 1.219
3.45 1 5 63.8 53.8 1.097 1.301 1.222
3.5 1 5 63.8 53.8 1.097 1.301 1.225
3.6167 1 5 63.8 53.8 1.097 1.301 1.231
3.6667 1 5 63.8 53.8 1.097 1.301 1.233
6.3333 5 10 53.8 47.5 1.301 1.474 1.347
6.3833 5 10 53.8 47.5 1.301 1.474 1.349
6.5 5 10 53.8 47.5 1.301 1.474 1.353
6.55 5 10 53.8 47.5 1.301 1.474 1.355
6.6167 5 10 53.8 47.5 1.301 1.474 1.3576.6667 5 10 53.8 47.5 1.301 1.474 1.359
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 9/27
Document Name: Battery and Charger Calculation Page 9 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
6.7167 5 10 53.8 47.5 1.301 1.474 1.360
6.7833 5 10 53.8 47.5 1.301 1.474 1.363
6.8333 5 10 53.8 47.5 1.301 1.474 1.364
6.95 5 10 53.8 47.5 1.301 1.474 1.368
7 5 10 53.8 47.5 1.301 1.474 1.370
9.6667 5 10 53.8 47.5 1.301 1.474 1.462
9.7167 5 10 53.8 47.5 1.301 1.474 1.464
9.8333 5 10 53.8 47.5 1.301 1.474 1.468
9.8833 5 10 53.8 47.5 1.301 1.474 1.470
9.95 5 10 53.8 47.5 1.301 1.474 1.472
10 10 - 47.5 - 1.474 - 1.474
10.05 10 15 47.5 45 1.474 1.556 1.475
10.1167 10 15 47.5 45 1.474 1.556 1.476
10.1667 10 15 47.5 45 1.474 1.556 1.476
10.2833 10 15 47.5 45 1.474 1.556 1.478
10.3333 10 15 47.5 45 1.474 1.556 1.479
13 10 15 47.5 45 1.474 1.556 1.523
13.05 10 15 47.5 45 1.474 1.556 1.524
13.1667 10 15 47.5 45 1.474 1.556 1.526
13.2167 10 15 47.5 45 1.474 1.556 1.526
13.2833 10 15 47.5 45 1.474 1.556 1.527
13.3333 10 15 47.5 45 1.474 1.556 1.528
13.3833 10 15 47.5 45 1.474 1.556 1.529
13.45 10 15 47.5 45 1.474 1.556 1.530
13.5 10 15 47.5 45 1.474 1.556 1.531
13.6167 10 15 47.5 45 1.474 1.556 1.533
13.6667 10 15 47.5 45 1.474 1.556 1.534
16.3333 15 20 45 43.5 1.556 1.609 1.570
16.3833 15 20 45 43.5 1.556 1.609 1.570
16.5 15 20 45 43.5 1.556 1.609 1.572
16.55 15 20 45 43.5 1.556 1.609 1.57216.6167 15 20 45 43.5 1.556 1.609 1.573
16.6667 15 20 45 43.5 1.556 1.609 1.573
16.7167 15 20 45 43.5 1.556 1.609 1.574
16.7833 15 20 45 43.5 1.556 1.609 1.575
16.8333 15 20 45 43.5 1.556 1.609 1.575
16.95 15 20 45 43.5 1.556 1.609 1.576
17 15 20 45 43.5 1.556 1.609 1.577
19.6667 15 20 45 43.5 1.556 1.609 1.606
19.7167 15 20 45 43.5 1.556 1.609 1.606
19.8333 15 20 45 43.5 1.556 1.609 1.607
19.8833 15 20 45 43.5 1.556 1.609 1.608
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 10/27
Document Name: Battery and Charger Calculation Page 10 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
19.95 15 20 45 43.5 1.556 1.609 1.609
20 20 - 43.5 - 1.609 - 1.609
20.05 20 30 43.5 40.2 1.609 1.741 1.610
20.1167 20 30 43.5 40.2 1.609 1.741 1.611
20.1667 20 30 43.5 40.2 1.609 1.741 1.611
20.2833 20 30 43.5 40.2 1.609 1.741 1.613
20.3333 20 30 43.5 40.2 1.609 1.741 1.614
23 20 30 43.5 40.2 1.609 1.741 1.649
23.05 20 30 43.5 40.2 1.609 1.741 1.649
23.1667 20 30 43.5 40.2 1.609 1.741 1.651
23.2167 20 30 43.5 40.2 1.609 1.741 1.652
23.2833 20 30 43.5 40.2 1.609 1.741 1.653
23.3333 20 30 43.5 40.2 1.609 1.741 1.653
23.3833 20 30 43.5 40.2 1.609 1.741 1.654
23.45 20 30 43.5 40.2 1.609 1.741 1.655
23.5 20 30 43.5 40.2 1.609 1.741 1.655
23.6167 20 30 43.5 40.2 1.609 1.741 1.657
23.6667 20 30 43.5 40.2 1.609 1.741 1.658
26.3333 20 30 43.5 40.2 1.609 1.741 1.693
26.3833 20 30 43.5 40.2 1.609 1.741 1.694
26.5 20 30 43.5 40.2 1.609 1.741 1.695
26.55 20 30 43.5 40.2 1.609 1.741 1.696
26.6167 20 30 43.5 40.2 1.609 1.741 1.697
26.6667 20 30 43.5 40.2 1.609 1.741 1.697
26.7167 20 30 43.5 40.2 1.609 1.741 1.698
26.7833 20 30 43.5 40.2 1.609 1.741 1.699
26.8333 20 30 43.5 40.2 1.609 1.741 1.699
26.95 20 30 43.5 40.2 1.609 1.741 1.701
27 20 30 43.5 40.2 1.609 1.741 1.702
29.6667 20 30 43.5 40.2 1.609 1.741 1.737
29.7167 20 30 43.5 40.2 1.609 1.741 1.73829.8333 20 30 43.5 40.2 1.609 1.741 1.739
29.8833 20 30 43.5 40.2 1.609 1.741 1.740
29.95 20 30 43.5 40.2 1.609 1.741 1.741
30 30 - 40.2 - 1.741 - 1.741
30.05 30 45 40.2 34.9 1.741 2.006 1.742
30.1167 30 45 40.2 34.9 1.741 2.006 1.743
30.1667 30 45 40.2 34.9 1.741 2.006 1.744
30.2833 30 45 40.2 34.9 1.741 2.006 1.746
30.3333 30 45 40.2 34.9 1.741 2.006 1.747
33 30 45 40.2 34.9 1.741 2.006 1.794
33.05 30 45 40.2 34.9 1.741 2.006 1.795
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 11/27
Document Name: Battery and Charger Calculation Page 11 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
33.1667 30 45 40.2 34.9 1.741 2.006 1.797
33.2167 30 45 40.2 34.9 1.741 2.006 1.798
33.2833 30 45 40.2 34.9 1.741 2.006 1.799
33.3333 30 45 40.2 34.9 1.741 2.006 1.800
33.3833 30 45 40.2 34.9 1.741 2.006 1.801
33.45 30 45 40.2 34.9 1.741 2.006 1.802
33.5 30 45 40.2 34.9 1.741 2.006 1.803
33.6167 30 45 40.2 34.9 1.741 2.006 1.805
33.6667 30 45 40.2 34.9 1.741 2.006 1.806
36.3333 30 45 40.2 34.9 1.741 2.006 1.853
36.3833 30 45 40.2 34.9 1.741 2.006 1.854
36.5 30 45 40.2 34.9 1.741 2.006 1.856
36.55 30 45 40.2 34.9 1.741 2.006 1.857
36.6167 30 45 40.2 34.9 1.741 2.006 1.858
36.6667 30 45 40.2 34.9 1.741 2.006 1.859
36.7167 30 45 40.2 34.9 1.741 2.006 1.860
36.7833 30 45 40.2 34.9 1.741 2.006 1.861
36.8333 30 45 40.2 34.9 1.741 2.006 1.862
36.95 30 45 40.2 34.9 1.741 2.006 1.864
37 30 45 40.2 34.9 1.741 2.006 1.865
39.6667 30 45 40.2 34.9 1.741 2.006 1.912
39.7167 30 45 40.2 34.9 1.741 2.006 1.913
39.8333 30 45 40.2 34.9 1.741 2.006 1.915
39.8833 30 45 40.2 34.9 1.741 2.006 1.916
39.95 30 45 40.2 34.9 1.741 2.006 1.917
40 30 45 40.2 34.9 1.741 2.006 1.918
40.05 30 45 40.2 34.9 1.741 2.006 1.918
40.1167 30 45 40.2 34.9 1.741 2.006 1.920
40.1667 30 45 40.2 34.9 1.741 2.006 1.921
40.2833 30 45 40.2 34.9 1.741 2.006 1.923
40.3333 30 45 40.2 34.9 1.741 2.006 1.92343 30 45 40.2 34.9 1.741 2.006 1.970
43.05 30 45 40.2 34.9 1.741 2.006 1.971
43.1667 30 45 40.2 34.9 1.741 2.006 1.973
43.2167 30 45 40.2 34.9 1.741 2.006 1.974
43.2833 30 45 40.2 34.9 1.741 2.006 1.975
43.3333 30 45 40.2 34.9 1.741 2.006 1.976
43.3833 30 45 40.2 34.9 1.741 2.006 1.977
43.45 30 45 40.2 34.9 1.741 2.006 1.978
43.5 30 45 40.2 34.9 1.741 2.006 1.979
43.6167 30 45 40.2 34.9 1.741 2.006 1.981
43.6667 30 45 40.2 34.9 1.741 2.006 1.982
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 12/27
Document Name: Battery and Charger Calculation Page 12 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
46.3333 45 60 34.9 32.2 2.006 2.174 2.021
46.3833 45 60 34.9 32.2 2.006 2.174 2.021
46.5 45 60 34.9 32.2 2.006 2.174 2.023
46.55 45 60 34.9 32.2 2.006 2.174 2.023
46.6167 45 60 34.9 32.2 2.006 2.174 2.024
46.6667 45 60 34.9 32.2 2.006 2.174 2.024
46.7167 45 60 34.9 32.2 2.006 2.174 2.025
46.7833 45 60 34.9 32.2 2.006 2.174 2.026
46.8333 45 60 34.9 32.2 2.006 2.174 2.026
46.95 45 60 34.9 32.2 2.006 2.174 2.028
47 45 60 34.9 32.2 2.006 2.174 2.028
49.6667 45 60 34.9 32.2 2.006 2.174 2.058
49.7167 45 60 34.9 32.2 2.006 2.174 2.059
49.8333 45 60 34.9 32.2 2.006 2.174 2.060
49.8833 45 60 34.9 32.2 2.006 2.174 2.060
49.95 45 60 34.9 32.2 2.006 2.174 2.061
50 45 60 34.9 32.2 2.006 2.174 2.062
50.05 45 60 34.9 32.2 2.006 2.174 2.062
50.1167 45 60 34.9 32.2 2.006 2.174 2.063
50.1667 45 60 34.9 32.2 2.006 2.174 2.064
50.2833 45 60 34.9 32.2 2.006 2.174 2.065
50.3333 45 60 34.9 32.2 2.006 2.174 2.066
53 45 60 34.9 32.2 2.006 2.174 2.095
53.05 45 60 34.9 32.2 2.006 2.174 2.096
53.1667 45 60 34.9 32.2 2.006 2.174 2.097
53.2167 45 60 34.9 32.2 2.006 2.174 2.098
53.2833 45 60 34.9 32.2 2.006 2.174 2.099
53.3333 45 60 34.9 32.2 2.006 2.174 2.099
53.3833 45 60 34.9 32.2 2.006 2.174 2.100
53.45 45 60 34.9 32.2 2.006 2.174 2.100
53.5 45 60 34.9 32.2 2.006 2.174 2.10153.6167 45 60 34.9 32.2 2.006 2.174 2.102
53.6667 45 60 34.9 32.2 2.006 2.174 2.103
56.3333 45 60 34.9 32.2 2.006 2.174 2.133
56.3833 45 60 34.9 32.2 2.006 2.174 2.133
56.5 45 60 34.9 32.2 2.006 2.174 2.135
56.55 45 60 34.9 32.2 2.006 2.174 2.135
56.6167 45 60 34.9 32.2 2.006 2.174 2.136
56.6667 45 60 34.9 32.2 2.006 2.174 2.137
56.7167 45 60 34.9 32.2 2.006 2.174 2.137
56.7833 45 60 34.9 32.2 2.006 2.174 2.138
56.8333 45 60 34.9 32.2 2.006 2.174 2.138
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 13/27
Document Name: Battery and Charger Calculation Page 13 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
56.95 45 60 34.9 32.2 2.006 2.174 2.140
57 45 60 34.9 32.2 2.006 2.174 2.140
59.6667 45 60 34.9 32.2 2.006 2.174 2.170
59.7167 45 60 34.9 32.2 2.006 2.174 2.171
59.8333 45 60 34.9 32.2 2.006 2.174 2.172
59.8833 45 60 34.9 32.2 2.006 2.174 2.173
59.95 45 60 34.9 32.2 2.006 2.174 2.173
60 60 - 32.2 - 2.174 - 2.174
60.05 60 90 32.2 27 2.174 2.593 2.175
60.1167 60 90 32.2 27 2.174 2.593 2.176
60.1667 60 90 32.2 27 2.174 2.593 2.176
60.2833 60 90 32.2 27 2.174 2.593 2.178
60.3333 60 90 32.2 27 2.174 2.593 2.179
63 60 90 32.2 27 2.174 2.593 2.216
63.05 60 90 32.2 27 2.174 2.593 2.216
63.1667 60 90 32.2 27 2.174 2.593 2.218
63.2167 60 90 32.2 27 2.174 2.593 2.219
63.2833 60 90 32.2 27 2.174 2.593 2.220
63.3333 60 90 32.2 27 2.174 2.593 2.220
63.3833 60 90 32.2 27 2.174 2.593 2.221
63.45 60 90 32.2 27 2.174 2.593 2.222
63.5 60 90 32.2 27 2.174 2.593 2.223
63.6167 60 90 32.2 27 2.174 2.593 2.224
63.6667 60 90 32.2 27 2.174 2.593 2.225
66.3333 60 90 32.2 27 2.174 2.593 2.262
66.3833 60 90 32.2 27 2.174 2.593 2.263
66.5 60 90 32.2 27 2.174 2.593 2.265
66.55 60 90 32.2 27 2.174 2.593 2.265
66.6167 60 90 32.2 27 2.174 2.593 2.266
66.6667 60 90 32.2 27 2.174 2.593 2.267
66.7167 60 90 32.2 27 2.174 2.593 2.26866.7833 60 90 32.2 27 2.174 2.593 2.269
66.8333 60 90 32.2 27 2.174 2.593 2.269
66.95 60 90 32.2 27 2.174 2.593 2.271
67 60 90 32.2 27 2.174 2.593 2.272
69.6667 60 90 32.2 27 2.174 2.593 2.309
69.7167 60 90 32.2 27 2.174 2.593 2.310
69.8333 60 90 32.2 27 2.174 2.593 2.311
69.8833 60 90 32.2 27 2.174 2.593 2.312
69.95 60 90 32.2 27 2.174 2.593 2.313
70 60 90 32.2 27 2.174 2.593 2.313
70.05 60 90 32.2 27 2.174 2.593 2.314
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 14/27
Document Name: Battery and Charger Calculation Page 14 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
70.1167 60 90 32.2 27 2.174 2.593 2.315
70.1667 60 90 32.2 27 2.174 2.593 2.316
70.2833 60 90 32.2 27 2.174 2.593 2.317
70.3333 60 90 32.2 27 2.174 2.593 2.318
73 60 90 32.2 27 2.174 2.593 2.355
73.05 60 90 32.2 27 2.174 2.593 2.356
73.1667 60 90 32.2 27 2.174 2.593 2.358
73.2167 60 90 32.2 27 2.174 2.593 2.358
73.2833 60 90 32.2 27 2.174 2.593 2.359
73.3333 60 90 32.2 27 2.174 2.593 2.360
73.3833 60 90 32.2 27 2.174 2.593 2.361
73.45 60 90 32.2 27 2.174 2.593 2.362
73.5 60 90 32.2 27 2.174 2.593 2.362
73.6167 60 90 32.2 27 2.174 2.593 2.364
73.6667 60 90 32.2 27 2.174 2.593 2.365
76.3333 60 90 32.2 27 2.174 2.593 2.402
76.3833 60 90 32.2 27 2.174 2.593 2.403
76.5 60 90 32.2 27 2.174 2.593 2.404
76.55 60 90 32.2 27 2.174 2.593 2.405
76.6167 60 90 32.2 27 2.174 2.593 2.406
76.6667 60 90 32.2 27 2.174 2.593 2.407
76.7167 60 90 32.2 27 2.174 2.593 2.407
76.7833 60 90 32.2 27 2.174 2.593 2.408
76.8333 60 90 32.2 27 2.174 2.593 2.409
76.95 60 90 32.2 27 2.174 2.593 2.410
77 60 90 32.2 27 2.174 2.593 2.411
79.6667 60 90 32.2 27 2.174 2.593 2.448
79.7167 60 90 32.2 27 2.174 2.593 2.449
79.8333 60 90 32.2 27 2.174 2.593 2.451
79.8833 60 90 32.2 27 2.174 2.593 2.451
79.95 60 90 32.2 27 2.174 2.593 2.45280 60 90 32.2 27 2.174 2.593 2.453
80.05 60 90 32.2 27 2.174 2.593 2.454
80.1167 60 90 32.2 27 2.174 2.593 2.455
80.1667 60 90 32.2 27 2.174 2.593 2.455
80.2833 60 90 32.2 27 2.174 2.593 2.457
80.3333 60 90 32.2 27 2.174 2.593 2.458
83 60 90 32.2 27 2.174 2.593 2.495
83.05 60 90 32.2 27 2.174 2.593 2.496
83.1667 60 90 32.2 27 2.174 2.593 2.497
83.2167 60 90 32.2 27 2.174 2.593 2.498
83.2833 60 90 32.2 27 2.174 2.593 2.499
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 15/27
Document Name: Battery and Charger Calculation Page 15 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
83.3333 60 90 32.2 27 2.174 2.593 2.500
83.3833 60 90 32.2 27 2.174 2.593 2.500
83.45 60 90 32.2 27 2.174 2.593 2.501
83.5 60 90 32.2 27 2.174 2.593 2.502
83.6167 60 90 32.2 27 2.174 2.593 2.504
83.6667 60 90 32.2 27 2.174 2.593 2.504
86.3333 60 90 32.2 27 2.174 2.593 2.541
86.3833 60 90 32.2 27 2.174 2.593 2.542
86.5 60 90 32.2 27 2.174 2.593 2.544
86.55 60 90 32.2 27 2.174 2.593 2.544
86.6167 60 90 32.2 27 2.174 2.593 2.545
86.6667 60 90 32.2 27 2.174 2.593 2.546
86.7167 60 90 32.2 27 2.174 2.593 2.547
86.7833 60 90 32.2 27 2.174 2.593 2.548
86.8333 60 90 32.2 27 2.174 2.593 2.548
86.95 60 90 32.2 27 2.174 2.593 2.550
87 60 90 32.2 27 2.174 2.593 2.551
89.6667 60 90 32.2 27 2.174 2.593 2.588
89.7167 60 90 32.2 27 2.174 2.593 2.589
89.8333 60 90 32.2 27 2.174 2.593 2.590
89.8833 60 90 32.2 27 2.174 2.593 2.591
89.95 60 90 32.2 27 2.174 2.593 2.592
90 90 - 27 - 2.593 - 2.593
90.05 90 120 27 23 2.593 3.043 2.593
90.1167 90 120 27 23 2.593 3.043 2.594
90.1667 90 120 27 23 2.593 3.043 2.595
90.2833 90 120 27 23 2.593 3.043 2.597
90.3333 90 120 27 23 2.593 3.043 2.598
93 90 120 27 23 2.593 3.043 2.638
93.05 90 120 27 23 2.593 3.043 2.638
93.1667 90 120 27 23 2.593 3.043 2.64093.2167 90 120 27 23 2.593 3.043 2.641
93.2833 90 120 27 23 2.593 3.043 2.642
93.3333 90 120 27 23 2.593 3.043 2.643
93.3833 90 120 27 23 2.593 3.043 2.643
93.45 90 120 27 23 2.593 3.043 2.644
93.5 90 120 27 23 2.593 3.043 2.645
93.6167 90 120 27 23 2.593 3.043 2.647
93.6667 90 120 27 23 2.593 3.043 2.648
96.3333 90 120 27 23 2.593 3.043 2.688
96.3833 90 120 27 23 2.593 3.043 2.689
96.5 90 120 27 23 2.593 3.043 2.690
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 16/27
Document Name: Battery and Charger Calculation Page 16 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
96.55 90 120 27 23 2.593 3.043 2.691
96.6167 90 120 27 23 2.593 3.043 2.692
96.6667 90 120 27 23 2.593 3.043 2.693
96.7167 90 120 27 23 2.593 3.043 2.694
96.7833 90 120 27 23 2.593 3.043 2.695
96.8333 90 120 27 23 2.593 3.043 2.695
96.95 90 120 27 23 2.593 3.043 2.697
97 90 120 27 23 2.593 3.043 2.698
99.6667 90 120 27 23 2.593 3.043 2.738
99.7167 90 120 27 23 2.593 3.043 2.739
99.8333 90 120 27 23 2.593 3.043 2.740
99.8833 90 120 27 23 2.593 3.043 2.741
99.95 90 120 27 23 2.593 3.043 2.742
100 90 120 27 23 2.593 3.043 2.743
100.05 90 120 27 23 2.593 3.043 2.744
100.1667 90 120 27 23 2.593 3.043 2.745
100.3333 90 120 27 23 2.593 3.043 2.748
103 90 120 27 23 2.593 3.043 2.788
103.1667 90 120 27 23 2.593 3.043 2.790
103.2167 90 120 27 23 2.593 3.043 2.791
103.3333 90 120 27 23 2.593 3.043 2.793
103.3833 90 120 27 23 2.593 3.043 2.794
103.5 90 120 27 23 2.593 3.043 2.795
103.6667 90 120 27 23 2.593 3.043 2.798
106.5 90 120 27 23 2.593 3.043 2.841
106.55 90 120 27 23 2.593 3.043 2.841
106.6667 90 120 27 23 2.593 3.043 2.843
106.7167 90 120 27 23 2.593 3.043 2.844
106.8333 90 120 27 23 2.593 3.043 2.846
107 90 120 27 23 2.593 3.043 2.848
109.8333 90 120 27 23 2.593 3.043 2.891109.8833 90 120 27 23 2.593 3.043 2.891
110 90 120 27 23 2.593 3.043 2.893
110.05 90 120 27 23 2.593 3.043 2.894
110.1667 90 120 27 23 2.593 3.043 2.896
110.3333 90 120 27 23 2.593 3.043 2.898
113.1667 90 120 27 23 2.593 3.043 2.941
113.2167 90 120 27 23 2.593 3.043 2.942
113.3333 90 120 27 23 2.593 3.043 2.943
113.3833 90 120 27 23 2.593 3.043 2.944
113.5 90 120 27 23 2.593 3.043 2.946
113.6667 90 120 27 23 2.593 3.043 2.948
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 17/27
Document Name: Battery and Charger Calculation Page 17 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
116.5 90 120 27 23 2.593 3.043 2.991
116.55 90 120 27 23 2.593 3.043 2.992
116.6667 90 120 27 23 2.593 3.043 2.993
116.7167 90 120 27 23 2.593 3.043 2.994
116.8333 90 120 27 23 2.593 3.043 2.996
117 90 120 27 23 2.593 3.043 2.998
119.8333 90 120 27 23 2.593 3.043 3.041
120 120 - 23 - 3.043 - 3.043
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 18/27
Document Name: Battery and Charger Calculation Page 18 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
9. The worksheet table
To determine the required cell size, it is necessary to calculate, from an analysis of each section of
the duty cycle, the maximum capacity required by the combined load demands (current versus time)
of the various sections.
The calculation of the capacity F S required by each section S , when S can be integer from 1 to N, can
be expressed as follows:
Where
S is the section of the duty cycle being analyzed. Section S contains the first S periods of the
duty cycle.
N is the number of periods in the duty cycle
P is the period being analysed
AP is the amperes required for period P
t is the time in minutes from the beginning of period P through the end of section S
K t is the capacity rating factor for a given cell type, at the t minute discharge rate, at 25℃, to a
definite end-of-discharge voltage
T t is the temperature derating factor at t minutes, based on electrolyte temperature at start of
the duty cycle
F S is the capacity required by each section S
If the current for period P+1 is greater than the current for period P, then section S=P+1 will require
larger cell than section S=P. consequently, the calculations for section S=P can be omitted. The
maximum capacity (max F S ) calculated determines the cell size.
According to Table 2 there exist 123 sections that which sections 3, 4, 5 and 6 are repeated in
sequence, in which section 4 has the greatest cell size. Table 5 shows the increase of cell capacity
according to increase number of periods. It can be concluded that section 120 will result in the
greatest cell size among 123 sections.
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 19/27
Document Name: Battery and Charger Calculation Page 19 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
Table 5: Worksheet Table
Lowest Expected electrolyte Temp: 25⁰C
Minimum Cell
Voltage:
1.14V/cell
Cell Mfg: Interberg Cell Type: KPL 70
( 1 ) P e r i o d
(2)
Load (A)
(3)
Change in Load (A)
(4)
Duration of Period
(min)
(5)
Time to End of
Section (min)
(6)
Kt
(7)
Tt
Required Section Size =
(3)*(6)*(7) Ah
Positive Negative
Section 1– First Period Only
1 A1 = 156 A1 - A0 = 156 M1 = 0.1667 t = 0.1667 0.9248 1 144.36
144.36 0.00Sub-
total
144.36 total
Section 2– First Two Period Only
1 A1 = 156 A1 - A0 = 156 M1 = 0.1667 t = 17 1.5770 1 246.17
2 A2 = 63.2 A2 - A1 = -92.9 M2 = 16.8333 t = 16.8333 1.5752 1 146.34
246.17 146.34Sub-
total
99.83 total
Section 3– First Three Period Only
1 A1 = 156 A1 - A0 =
2 A2 = 63.2 A2 - A1 =
3 A3 = 19.6 A3 - A2 =
Since A4 is greater than A3, go to section 4
Sub-
total
total
Section 4– First Four Period Only
1 A1 = 156 A1 - A0 = 156 M1 = 0.1667 t = 20.05 1.6099 1 251.302 A2 = 63.2 A2 - A1 = -92.9 M2 = 16.8333 t = 19.8833 1.6079 1 149.38
3 A3 = 19.6 A3 - A2 = -43.6 M3 = 3.0000 t = 3.05 1.2017 1 52.39
4 A4 = 178 A4 - A3 = 158 M4 = 0.0500 t = 0.05 0.9045 1 142.92
394.22 201.77Sub-
total
192.44 total
Section 5– First Five Period Only
1 A1 = 156 A1 - A0 = 156 M1 = 0.1667 t = 20.1667 1.6114 1 251.54
2 A2 = 63.2 A2 - A1 = -92.9 M2 = 16.8333 t = 20 1.6092 1 149.49
3 A3 = 19.6 A3 - A2 = -43.6 M3 = 3.0000 t = 3.1667 1.2076 1 52.65
4 A4 = 178 A4 - A3 = 158 M4 = 0.0500 t = 0.1667 0.9248 1 146.11
5 A5 = 158 A5 - A4 = -19.8 M5 = 0.1167 t = 0.1167 0.9196 1 18.21
397.65 220.36Sub-
total
177.30 total
Section 6– First Six Period Only
1 A1 = 156 A1 - A0 = 156 M1 = 0.1667 t = 20.3333 1.6136 1 251.88
2 A2 = 63.2 A2 - A1 = -92.9 M2 = 16.8333 t = 20.1667 1.6114 1 149.70
3 A3 = 19.6 A3 - A2 = -43.6 M3 = 3.0000 t = 3.3333 1.2161 1 53.02
4 A4 = 178 A4 - A3 = 158 M4 = 0.0500 t = 0.3333 0.9418 1 148.81
5 A5 = 158 A5 - A4 = -19.8 M5 = 0.1167 t = 0.2833 0.9367 1 18.55
6 A6 = 68.9 A6 - A5 = -88.9 M6 = 0.1667 t = 0.1667 0.9248 1 82.21
400.69 303.48Sub-
total
97.21 total
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 20/27
Document Name: Battery and Charger Calculation Page 20 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
Lowest Expected electrolyte Temp: 25⁰C
Minimum Cell
Voltage:1.14V/cell
Cell Mfg: Interberg Cell Type: KPL 70
( 1 ) P e r i o d
(2)
Load (A)
(3)
Change in Load (A)
(4)
Duration of Period
(min)
(5)
Time to End of
Section (min)
(6)
Kt
(7)
Tt
Required Section Size =
(3)*(6)*(7) Ah
Positive Negative
Section 7– First Seven Period Only
1 A1 = 156 A1 - A0 =
2 A2 = 63.2 A2 - A1 =3 A3 = 19.6 A3 - A2 =
4 A4 = 178 A4 - A3 =
5 A5 = 158 A5 - A4 =
6 A6 = 68.9 A6 - A5 =
7 A7 = 19.6 A7 - A6 =
Since A8 is greater than A7, go to section 8
Sub-
total
total
Section 8– First Eight Period Only
1 A1 = 156 A1 - A0 = 156 M1 = 0.1667 t = 23.3833 1.6539 1 258.17
2 A2 = 63.2 A2 - A1 = -92.9 M2 = 16.8333 t = 23.2167 1.6517 1 153.44
3 A3 = 19.6 A3 - A2 = -43.6 M3 = 3.0000 t = 6.3833 1.3489 1 58.81
4 A4 = 178 A4 - A3 = 158 M4 = 0.0500 t = 3.3833 1.2187 1 192.55
5 A5 = 158 A5 - A4 = -19.8 M5 = 0.1167 t = 3.3333 1.2161 1 24.08
6 A6 = 68.9 A6 - A5 = -88.9 M6 = 0.1667 t = 3.2167 1.2102 1 107.59
7 A7 = 19.6 A7 - A6 = -49.3 M7 = 3.0000 t = 3.05 1.2017 1 59.24
8 A8 = 178 A8 - A7 = 158 M8 = 0.0500 t = 0.05 0.9045 1 142.92
593.64 403.16 Sub-total
190.48 total
Section 9– First Nine Period Only
1 A1 = 156 A1 - A0 = 156 M1 = 0.1667 t = 23.5 1.6554 1 258.41
2 A2 = 63.2 A2 - A1 = -92.9 M2 = 16.8333 t = 23.3333 1.6532 1 153.58
3 A3 = 19.6 A3 - A2 = -43.6 M3 = 3.0000 t = 6.5 1.3529 1 58.99
4 A4 = 178 A4 - A3 = 158 M4 = 0.0500 t = 3.5 1.2246 1 193.49
5 A5 = 158 A5 - A4 = -19.8 M5 = 0.1167 t = 3.45 1.2221 1 24.20
6 A6 = 68.9 A6 - A5 = -88.9 M6 = 0.1667 t = 3.3333 1.2161 1 108.11
7 A7 = 19.6 A7 - A6 = -49.3 M7 = 3.0000 t = 3.1667 1.2076 1 59.54
8 A8 = 178 A8 - A7 = 158 M8 = 0.0500 t = 0.1667 0.9248 1 146.11
9 A9 = 158 A9 - A8 = -19.8 M9 = 0.1167 t = 0.1167 0.9196 1 18.21598.02 422.63 Sub-total
175.39 total
Section 10– First Ten Period Only
1 A1 = 156 A1 - A0 = 156 M1 = 0.1667 t = 23.6667 1.6576 1 258.76
2 A2 = 63.2 A2 - A1 = -92.9 M2 = 16.8333 t = 23.5 1.6554 1 153.79
3 A3 = 19.6 A3 - A2 = -43.6 M3 = 3.0000 t = 6.6667 1.3586 1 59.24
4 A4 = 178 A4 - A3 = 158 M4 = 0.0500 t = 3.6667 1.2331 1 194.84
5 A5 = 158 A5 - A4 = -19.8 M5 = 0.1167 t = 3.6167 1.2306 1 24.37
6 A6 = 68.9 A6 - A5 = -88.9 M6 = 0.1667 t = 3.5 1.2246 1 108.87
7 A7 = 19.6 A7 - A6 = -49.3 M7 = 3.0000 t = 3.3333 1.2161 1 59.96
8 A8 = 178 A8 - A7 = 158 M8 = 0.0500 t = 0.3333 0.9418 1 148.81
9 A9 = 158 A9 - A8 = -19.8 M9 = 0.1167 t = 0.2833 0.9367 1 18.55
10 A10 = 68.9 A10 - A9 = -88.9 M10 = 0.1667 t = 0.1667 0.9248 1 82.21
602.40 506.98 Sub-total
95.42 total
Section 11–
1 A1 = 156 A1 - A0 = 156 M1 = 0.1667 t = 26.6667 1.6973 1 264.94
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 21/27
Document Name: Battery and Charger Calculation Page 21 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
2 A2 = 63.2 A2 - A1 = -92.9 M2 = 16.8333 t = 26.5 1.6951 1 157.47
3 A3 = 19.6 A3 - A2 = -43.6 M3 = 3.0000 t = 9.6667 1.4622 1 63.75
4 A4 = 178 A4 - A3 = 158 M4 = 0.0500 t = 6.6667 1.3586 1 214.67
5 A5 = 158 A5 - A4 = -19.8 M5 = 0.1167 t = 6.6167 1.3569 1 26.87
6 A6 = 68.9 A6 - A5 = -88.9 M6 = 0.1667 t = 6.5 1.3529 1 120.27
7 A7 = 19.6 A7 - A6 = -49.3 M7 = 3.0000 t = 6.3333 1.3471 1 66.41
8 A8 = 178 A8 - A7 = 158 M8 = 0.0500 t = 3.3333 1.2161 1 192.15
9 A9 = 158 A9 - A8 = -19.8 M9 = 0.1167 t = 3.2833 1.2136 1 24.03
10 A10 = 68.9 A10 - A9 = -88.9 M10 = 0.1667 t = 3.1667 1.2076 1 107.36
11 A11 = 19.6 A11 - A10 = -49.3 M11 = 3.0000 t = 3 1.1991 1 59.12
Since A12 is greater than A11, go to section 12
671.76 625.28 Sub-total
46.48 total
Continuing this worksheet shows the growth of cell size up to section 120, so:
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 22/27
Document Name: Battery and Charger Calculation Page 22 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
Lowest Expected electrolyte Temp: 25 ⁰C Minimum Cell
Voltage: 1.14V/cellCell Mfg: Interberg Cell Type: KPL 70
( 1 ) P e r i o
d (2)
Load (A)
(3)
Change in Load (A)
(4)
Duration of Period
(min)
(5)
Time to End of
Section (min)
(6)
Kt
(7)
Tt
Required Section Size = (3)*(6)*(7)
Ah
Positive Negative
Section 120–
1 A1 = 156 A1 - A0 = 156 M1 = 0.1667 t = 116.7167 2.9941 1 467.38
2 A2 = 63.2 A2 - A1 = -92.9 M2 = 16.8333 t = 116.55 2.9916 1 277.92
3 A3 = 19.6 A3 - A2 = -43.6 M3 = 3.0000 t = 99.7167 2.7386 1 119.40
4 A4 = 178 A4 - A3 = 158 M4 = 0.0500 t = 96.7167 2.6935 1 425.58
5 A5 = 158 A5 - A4 = -19.8 M5 = 0.1167 t = 96.6667 2.6928 1 53.32
6 A6 = 68.9 A6 - A5 = -88.9 M6 = 0.1667 t = 96.55 2.6910 1 239.23
7 A7 = 19.6 A7 - A6 = -49.3 M7 = 3.0000 t = 96.3833 2.6885 1 132.54
8 A8 = 178 A8 - A7 = 158 M8 = 0.0500 t = 93.3833 2.6434 1 417.66
9 A9 = 158 A9 - A8 = -19.8 M9 = 0.1167 t = 93.3333 2.6427 1 52.33
10 A10 = 68.9 A10 - A9 = -88.9 M10 = 0.1667 t = 93.2167 2.6409 1 234.78
11 A11 = 19.6 A11 - A10 = -49.3 M11 = 3.0000 t = 93.05 2.6384 1 130.07
12 A12 = 178 A12 - A11 = 158 M12 = 0.0500 t = 90.05 2.5933 1 409.7513 A13 = 158 A13 - A12 = -19.8 M13 = 0.1167 t = 90 2.5926 1 51.33
14 A14 = 68.9 A14 - A13 = -88.9 M14 = 0.1667 t = 89.8833 2.5910 1 230.34
15 A15 = 19.6 A15 - A14 = -49.3 M15 = 3.0000 t = 89.7167 2.5886 1 127.62
16 A16 = 178 A16 - A15 = 158 M16 = 0.0500 t = 86.7167 2.5468 1 402.39
17 A17 = 158 A17 - A16 = -19.8 M17 = 0.1167 t = 86.6667 2.5461 1 50.41
18 A18 = 68.9 A18 - A17 = -88.9 M18 = 0.1667 t = 86.55 2.5444 1 226.20
19 A19 = 19.6 A19 - A18 = -49.3 M19 = 3.0000 t = 86.3833 2.5421 1 125.33
20 A20 = 178 A20 - A19 = 158 M20 = 0.0500 t = 83.3833 2.5003 1 395.04
21 A21 = 158 A21 - A20 = -19.8 M21 = 0.1167 t = 83.3333 2.4996 1 49.49
22 A22 = 68.9 A22 - A21 = -88.9 M22 = 0.1667 t = 83.2167 2.4979 1 222.07
23 A23 = 19.6 A23 - A22 = -49.3 M23 = 3.0000 t = 83.05 2.4956 1 123.03
24 A24 = 178 A24 - A23 = 158 M24 = 0.0500 t = 80.05 2.4537 1 387.69
25 A25 = 158 A25 - A24 = -19.8 M25 = 0.1167 t = 80 2.4530 1 48.57
26 A26 = 68.9 A26 - A25 = -88.9 M26 = 0.1667 t = 79.8833 2.4514 1 217.93
27 A27 = 19.6 A27 - A26 = -49.3 M27 = 3.0000 t = 79.7167 2.4491 1 120.7428 A28 = 178 A28 - A27 = 158 M28 = 0.0500 t = 76.7167 2.4072 1 380.34
29 A29 = 158 A29 - A28 = -19.8 M29 = 0.1167 t = 76.6667 2.4065 1 47.65
30 A30 = 68.9 A30 - A29 = -88.9 M30 = 0.1667 t = 76.55 2.4049 1 213.79
31 A31 = 19.6 A31 - A30 = -49.3 M31 = 3.0000 t = 76.3833 2.4026 1 118.45
32 A32 = 178 A32 - A31 = 158 M32 = 0.0500 t = 73.3833 2.3607 1 372.99
33 A33 = 158 A33 - A32 = -19.8 M33 = 0.1167 t = 73.3333 2.3600 1 46.73
34 A34 = 68.9 A34 - A33 = -88.9 M34 = 0.1667 t = 73.2167 2.3584 1 209.66
35 A35 = 19.6 A35 - A34 = -49.3 M35 = 3.0000 t = 73.05 2.3560 1 116.15
36 A36 = 178 A36 - A35 = 158 M36 = 0.0500 t = 70.05 2.3142 1 365.64
37 A37 = 158 A37 - A36 = -19.8 M37 = 0.1167 t = 70 2.3135 1 45.81
38 A38 = 68.9 A38 - A37 = -88.9 M38 = 0.1667 t = 69.8833 2.3118 1 205.52
39 A39 = 19.6 A39 - A38 = -49.3 M39 = 3.0000 t = 69.7167 2.3095 1 113.86
40 A40 = 178 A40 - A39 = 158 M40 = 0.0500 t = 66.7167 2.2677 1 358.29
41 A41 = 158 A41 - A40 = -19.8 M41 = 0.1167 t = 66.6667 2.2670 1 44.89
42 A42 = 68.9 A42 - A41 = -88.9 M42 = 0.1667 t = 66.55 2.2653 1 201.39
43 A43 = 19.6 A43 - A42 = -49.3 M43 = 3.0000 t = 66.3833 2.2630 1 111.57
44 A44 = 178 A44 - A43 = 158 M44 = 0.0500 t = 63.3833 2.2211 1 350.94
45 A45 = 158 A45 - A44 = -19.8 M45 = 0.1167 t = 63.3333 2.2204 1 43.96
46 A46 = 68.9 A46 - A45 = -88.9 M46 = 0.1667 t = 63.2167 2.2188 1 197.25
47 A47 = 19.6 A47 - A46 = -49.3 M47 = 3.0000 t = 63.05 2.2165 1 109.27
48 A48 = 178 A48 - A47 = 158 M48 = 0.0500 t = 60.05 2.1746 1 343.59
49 A49 = 158 A49 - A48 = -19.8 M49 = 0.1167 t = 60 2.1739 1 43.04
50 A50 = 68.9 A50 - A49 = -88.9 M50 = 0.1667 t = 59.8833 2.1726 1 193.14
51 A51 = 19.6 A51 - A50 = -49.3 M51 = 3.0000 t = 59.7167 2.1707 1 107.02
52 A52 = 178 A52 - A51 = 158 M52 = 0.0500 t = 56.7167 2.1371 1 337.66
53 A53 = 158 A53 - A52 = -19.8 M53 = 0.1167 t = 56.6667 2.1365 1 42.30
54 A54 = 68.9 A54 - A53 = -88.9 M54 = 0.1667 t = 56.55 2.1352 1 189.82
55 A55 = 19.6 A55 - A54 = -49.3 M55 = 3.0000 t = 56.3833 2.1334 1 105.17
56 A56 = 178 A56 - A55 = 158 M56 = 0.0500 t = 53.3833 2.0997 1 331.76
57 A57 = 158 A57 - A56 = -19.8 M57 = 0.1167 t = 53.3333 2.0992 1 41.56
58 A58 = 68.9 A58 - A57 = -88.9 M58 = 0.1667 t = 53.2167 2.0979 1 186.5059 A59 = 19.6 A59 - A58 = -49.3 M59 = 3.0000 t = 53.05 2.0960 1 103.33
60 A60 = 178 A60 - A59 = 158 M60 = 0.0500 t = 50.05 2.0624 1 325.85
61 A61 = 158 A61 - A60 = -19.8 M61 = 0.1167 t = 50 2.0618 1 40.82
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 23/27
Document Name: Battery and Charger Calculation Page 23 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
62 A62 = 68.9 A62 - A61 = -88.9 M62 = 0.1667 t = 49.8833 2.0605 1 183.18
63 A63 = 19.6 A63 - A62 = -49.3 M63 = 3.0000 t = 49.7167 2.0586 1 101.49
64 A64 = 178 A64 - A63 = 158 M64 = 0.0500 t = 46.7167 2.0250 1 319.95
65 A65 = 158 A65 - A64 = -19.8 M65 = 0.1167 t = 46.6667 2.0244 1 40.08
66 A66 = 68.9 A66 - A65 = -88.9 M66 = 0.1667 t = 46.55 2.0231 1 179.85
67 A67 = 19.6 A67 - A66 = -49.3 M67 = 3.0000 t = 46.3833 2.0212 1 99.65
68 A68 = 178 A68 - A67 = 158 M68 = 0.0500 t = 43.3833 1.9772 1 312.40
69 A69 = 158 A69 - A68 = -19.8 M69 = 0.1167 t = 43.3333 1.9763 1 39.13
70 A70 = 68.9 A70 - A69 = -88.9 M70 = 0.1667 t = 43.2167 1.9743 1 175.51
71 A71 = 19.6 A71 - A70 = -49.3 M71 = 3.0000 t = 43.05 1.9714 1 97.19
72 A72 = 178 A72 - A71 = 158 M72 = 0.0500 t = 40.05 1.9185 1 303.12
73 A73 = 158 A73 - A72 = -19.8 M73 = 0.1167 t = 40 1.9176 1 37.97
74 A74 = 68.9 A74 - A73 = -88.9 M74 = 0.1667 t = 39.8833 1.9155 1 170.29
75 A75 = 19.6 A75 - A74 = -49.3 M75 = 3.0000 t = 39.7167 1.9126 1 94.29
76 A76 = 178 A76 - A75 = 158 M76 = 0.0500 t = 36.7167 1.8597 1 293.83
77 A77 = 158 A77 - A76 = -19.8 M77 = 0.1167 t = 36.6667 1.8588 1 36.80
78 A78 = 68.9 A78 - A77 = -88.9 M78 = 0.1667 t = 36.55 1.8568 1 165.07
79 A79 = 19.6 A79 - A78 = -49.3 M79 = 3.0000 t = 36.3833 1.8538 1 91.39
80 A80 = 178 A80 - A79 = 158 M80 = 0.0500 t = 33.3833 1.8009 1 284.55
81 A81 = 158 A81 - A80 = -19.8 M81 = 0.1167 t = 33.3333 1.8001 1 35.6482 A82 = 68.9 A82 - A81 = -88.9 M82 = 0.1667 t = 33.2167 1.7980 1 159.84
83 A83 = 19.6 A83 - A82 = -49.3 M83 = 3.0000 t = 33.05 1.7951 1 88.50
84 A84 = 178 A84 - A83 = 158 M84 = 0.0500 t = 30.05 1.7422 1 275.26
85 A85 = 158 A85 - A84 = -19.8 M85 = 0.1167 t = 30 1.7413 1 34.48
86 A86 = 68.9 A86 - A85 = -88.9 M86 = 0.1667 t = 29.8833 1.7398 1 154.66
87 A87 = 19.6 A87 - A86 = -49.3 M87 = 3.0000 t = 29.7167 1.7376 1 85.66
88 A88 = 178 A88 - A87 = 158 M88 = 0.0500 t = 26.7167 1.6979 1 268.27
89 A89 = 158 A89 - A88 = -19.8 M89 = 0.1167 t = 26.6667 1.6973 1 33.61
90 A90 = 68.9 A90 - A89 = -88.9 M90 = 0.1667 t = 26.55 1.6957 1 150.75
91 A91 = 19.6 A91 - A90 = -49.3 M91 = 3.0000 t = 26.3833 1.6935 1 83.49
92 A92 = 178 A92 - A91 = 158 M92 = 0.0500 t = 23.3833 1.6539 1 261.31
93 A93 = 158 A93 - A92 = -19.8 M93 = 0.1167 t = 23.3333 1.6532 1 32.73
94 A94 = 68.9 A94 - A93 = -88.9 M94 = 0.1667 t = 23.2167 1.6517 1 146.84
95 A95 = 19.6 A95 - A94 = -49.3 M95 = 3.0000 t = 23.05 1.6495 1 81.32
96 A96 = 178 A96 - A95 = 158 M96 = 0.0500 t = 20.05 1.6099 1 254.36
97 A97 = 158 A97 - A96 = -19.8 M97 = 0.1167 t = 20 1.6092 1 31.86
98 A98 = 68.9 A98 - A97 = -88.9 M98 = 0.1667 t = 19.8833 1.6079 1 142.95
99 A99 = 19.6 A99 - A98 = -49.3 M99 = 3.0000 t = 19.7167 1.6062 1 79.18
100 A100 = 178 A100 - A99 = 158 M100 = 0.0500 t = 16.7167 1.5740 1 248.69
101 A101 = 158 A101 - A100 = -19.8 M101 = 0.1167 t = 16.6667 1.5734 1 31.15
102 A102 = 68.9 A102 - A101 = -88.9 M102 = 0.1667 t = 16.55 1.5722 1 139.77
103 A103 = 19.6 A103 - A102 = -49.3 M103 = 3.0000 t = 16.3833 1.5704 1 77.42
104 A104 = 178 A104 - A103 = 158 M104 = 0.0500 t = 13.3833 1.5291 1 241.60
105 A105 = 158 A105 - A104 = -19.8 M105 = 0.1167 t = 13.3333 1.5283 1 30.26
106 A106 = 68.9 A106 - A105 = -88.9 M106 = 0.1667 t = 13.2167 1.5264 1 135.69
107 A107 = 19.6 A107 - A106 = -49.3 M107 = 3.0000 t = 13.05 1.5236 1 75.11
108 A108 = 178 A108 - A107 = 158 M108 = 0.0500 t = 10.05 1.4745 1 232.97
109 A109 = 158 A109 - A108 = -19.8 M109 = 0.1167 t = 10 1.4737 1 29.18
110 A110 = 68.9 A110 - A109 = -88.9 M110 = 0.1667 t = 9.8833 1.4697 1 130.65
111 A111 = 19.6 A111 - A110 = -49.3 M111 = 3.0000 t = 9.7167 1.4639 1 72.17
112 A112 = 178 A112 - A111 = 158 M112 = 0.0500 t = 6.7167 1.3604 1 214.94113 A113 = 158 A113 - A112 = -19.8 M113 = 0.1167 t = 6.6667 1.3586 1 26.90
114 A114 = 68.9 A114 - A113 = -88.9 M114 = 0.1667 t = 6.55 1.3546 1 120.42
115 A115 = 19.6 A115 - A114 = -49.3 M115 = 3.0000 t = 6.3833 1.3489 1 66.50
116 A116 = 178 A116 - A115 = 158 M116 = 0.0500 t = 3.3833 1.2187 1 192.55
117 A117 = 158 A117 - A116 = -19.8 M117 = 0.1167 t = 3.3333 1.2161 1 24.08
118 A118 = 68.9 A118 - A117 = -88.9 M118 = 0.1667 t = 3.2167 1.2102 1 107.59
119 A119 = 19.6 A119 - A118 = -49.3 M119 = 3.0000 t = 3.05 1.2017 1 59.24
120 A120 = 178 A120 - A119 = 158 M120 = 0.0500 t = 0.05 0.9045 1 142.92
9919.27 9690.88 Sub-total
228.38 Total
Maximum Section Size × Aging Factor(1.2) = Required Cell Size (Ah)
228.38 1.2 = 274.059
KPL 280 whould be suitable for this practice.
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 24/27
Document Name: Battery and Charger Calculation Page 24 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
According to Table 3 the nearest cell size is KPL 280. Since the ratio of discharge current between
KPL70 and KPL280 for the Discharge Time up to 2 hours is the same, there is no need to calculate
the worksheet for KPL280 because it would result the same value of cell size.
Therefore,U
98 cells of KPL280 with end-of-discharge-voltage=1.14U
shall be selected to supply DC
loads specified in Table 1. See attachment 1 for more characteristics data of this Battery.
Battery Charger Capacity shall be calculated based on the summation of continuous loads indicated
in Table 1 plus Battery charging current.
According to charging procedure introduced in IEC 60623 for the duration of charge 7h to 8h the
constant current of 0.2 I t A is required, in which:
Charging Current = 19.6 + 0.2×280 = 75.6 A
Therefore, charger with nominal output voltage of 125 VDC and output current of 76 A is needed.
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 25/27
Document Name: Battery and Charger Calculation Page 25 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
ATTACHMENT 1:
Interberg Battery Characteristics and Data
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 26/27
Document Name: Battery and Charger Calculation Page 26 of 27 Document NO. : REY-MS-59ED-08-EFG-001 Rev.A
6*27MW REY
G AS TURBINE POWER PLANT
NICKEL-CADMIUM BATTERIES, DISCHARGE TABLES interberg batteries
FINAL DISCHARGE VOLTAGE = 1.14 VOLTS/CELL
CellTypes
Cell dimensions(mm)
10h
8h
5h
3h
2h
90min
60min
45min
30min
20min
15min
10min
5min
60sec
30sec
5sec
1sec
L W H
KPL10 38 84 128 1.00 1.30 2.00 2.80 3.29 3.90 4.60 5.00 5.80 6.30 6.40 6.80 7.70 9.10 10.5 10.9 11.2
KPL17 32 113 217 1.55 2.24 3.40 4.71 5.56 6.57 7.96 8.65 9.74 10.6 11.1 11.5 13.1 15.3 16.8 18.6 19.0
KPL22 32 113 217 2.00 2.90 4.40 6.10 7.20 8.50 10.3 11.2 12.6 13.7 14.3 14.9 16.9 19.8 21.7 24.1 24.6
KPL30 68 134 240 3.20 3.90 6.00 8.30 9.87 11.8 13.9 15.0 17.2 18.7 19.3 20.3 23.0 27.5 31.5 32.7 33.6
KPL40 68 134 240 4.00 5.30 8.00 11.3 13.2 15.6 18.5 20.0 23.0 24.9 25.8 27.1 30.7 36.5 41.9 43.6 44.8
KPL45 68 134 240 5.00 5.90 9.10 12.6 14.8 17.6 20.8 22.5 25.9 28.0 28.9 30.5 34.6 40.6 44.3 49.1 50.4
KPL50 70 134 280 5.20 6.50 10.10 14.0 16.5 19.5 23.1 25.0 28.7 31.1 32.1 33.9 38.4 45.7 52.2 54.5 56.1
KPL60 70 134 280 6.10 7.80 12.10 16.9 19.7 23.3 27.7 29.9 34.4 37.3 38.6 40.7 46.1 54.7 62.9 64.4 67.2
KPL70 79 140 360 7.35 9.19 14.09 19.5 23.0 27.0 32.2 34.9 40.2 43.5 45.0 47.5 53.8 63.8 73.0 76.4 78.4
KPL80 79 140 360 8.40 10.50 16.10 22.3 26.3 30.9 36.8 39.9 45.9 49.7 51.4 54.3 61.5 72.9 83.4 87.3 89.6KPL90 79 140 360 9.27 11.97 18.09 25.0 29.6 34.8 41.5 44.8 51.6 56.0 57.8 61.1 63.8 81.9 94.5 98.1 101
KPL100 79 140 360 10.30 13.30 20.10 27.8 32.9 38.7 46.1 49.8 57.3 62.2 64.2 67.9 70.9 91.0 105 109 112
KPL115 79 140 360 12.24 15.18 23.09 32.0 37.9 44.4 53.0 57.2 65.9 71.6 73.7 78.1 88.5 103 113 120 129
KPL125 79 140 360 13.30 16.50 25.10 34.8 41.2 48.3 57.6 62.2 71.6 77.8 80.1 84.9 96.2 112 123 130 140
KPL135 106 164 343 14.67 17.91 27.09 37.5 44.5 43.1 62.1 67.2 77.3 84.0 86.5 90.9 104 124 142 147 151
KPL150 106 164 343 16.30 19.90 30.10 41.7 49.4 47.9 69.0 74.7 85.9 93.3 96.1 101 115 138 158 163 168
KPL165 106 164 343 17.57 21.78 33.00 45.9 54.3 63.6 75.8 82.1 94.1 102 105 111 126 151 174 180 185
KPL180 106 164 343 19.17 23.76 36.00 50.0 59.2 69.4 82.7 89.6 103 112 114 122 138 165 190 196 202
KPL200 106 164 343 21.30 26.40 40.00 55.6 65.8 77.1 91.9 99.5 114 124 127 135 153 183 211 218 224
KPL230 138 276 418 24.29 30.36 41.31 63.9 75.7 88.5 105 113 131 143 146 155 177 211 242 250 258
KPL250 138 276 418 26.40 33.00 44.90 69.5 82.3 96.2 114 123 142 155 159 169 192 229 263 272 280
KPL265 138 276 448 27.83 34.89 52.91 73.6 87.2 102 121 131 151 164 169 179 203 244 274 289 292
KPL280 138 276 448 29.40 36.87 55.91 77.7 92.1 107 128 138 160 174 178 189 215 258 289 305 308
KPL300 138 276 448 31.50 39.50 59.90 83.3 98.7 115 137 148 171 186 191 203 230 276 310 327 330
KPL330 138 276 450 34.70 43.37 65.91 91.6 108 126 151 163 189 205 210 223 254 303 347 359 370
KPL350 138 276 450 36.80 46.00 69.90 97.1 115 134 160 173 200 217 223 237 269 321 368 381 392
KPL365 138 276 450 38.42 47.91 72.73 100 120 140 167 181 208 226 233 247 280 334 382 398 409
KPL400 138 276 450 42.10 52.50 79.70 110 131 153 183 198 228 248 255 271 307 366 419 436 448
KPL430 138 276 450 45.15 56.50 85.66 119 141 165 197 212 245 267 274 292 330 393 449 469 482
KPL450 138 276 450 47.25 59.13 89.64 124 148 173 206 222 257 279 287 305 346 411 470 491 504
KPL500 138 276 450 52.50 65.70 99.60 138 164 192 229 247 285 310 319 339 384 457 522 545 560
KPL600 174 290 505 62.50 78.70 119 165 197 230 275 297 342 372 383 407 461 549 627 654 672
KPL700 185 398 570 73.40 91.70 138 193 230 268 320 346 400 434 447 475 538 637 731 763 784
KPL800 285 398 570 83.90 104 158 221 263 307 366 396 457 496 511 543 615 729 845 873 896
KPL900 185 398 570 94.30 117 178 248 296 345 412 445 514 558 575 611 692 820 940 982 1008
KPL1000 185 398 570 105 130 198 276 329 383 458 495 571 621 639 679 769 911 1043 1091 1120
8/9/2019 Battery & Battery Charger Calculation RevA
http://slidepdf.com/reader/full/battery-battery-charger-calculation-reva 27/27
6*27MW REY
G AS TURBINE POWER PLANT
interberg batteriesNICKEL-CADMIUM BATTERIES, CELL RANGES AND BASIC PHYSICAL AND ELECTRICAL DATA
Celltypes
Cell dimensions(mm) No. of the
terminalsSize of theterminals
Size ofthe nut(mm)
Cellweightfilled(kg)
Cellweightempty(kg)
Quantityof
electrolyte(liters)
Required solidelectrolyte
Electrolyte reserveShort-circuit
current (A)
Internalresistance(mOhm)
Above the plates Below the plates
L W HGrams/liter
Grams/liter
Height(mm)
Quantity(mm)
Height(mm)
Quantity(mm)
KPL10 38 84 128 2 M6 10 0,66 0,48 0,15 45 4,5 10 20 5 10 200 6,3
KPL17 32 113 217 2 M6 10 1,5 1,2 0,25 75 7,5 20 50 5 12 220 6
KPL22 32 113 217 2 M6 10 1,78 1,42 0,30 90 9 20 50 5 12 240 5,5
KPL30 70 134 245 2 M16 24 2,5 2 0,40 120 12 30 210 10 75 260 5
KPL40 70 134 285 2 M16 24 3,65 2,45 1,00 300 30 50 350 10 75 300 4,3
KPL45 70 134 285 2 M16 24 3,85 2,9 0,80 240 24 50 350 10 75 330 4
KPL50 70 134 285 2 M16 24 4 3,16 0,70 210 21 50 350 10 75 360 3,6
KPL60 70 134 285 2 M16 24 4,2 3,6 0,50 150 15 50 350 10 75 400 3,2
KPL70 80 140 375 2 M10 16 6 4,2 1,50 450 45 80 700 10 90 460 2,8
KPL80 80 140 375 2 M10 16 6,2 4,52 1,40 420 42 20 200 10 90 520 2,5
KPL90 80 140 375 2 M10 16 6,3 4,7 1,35 405 40,5 20 200 10 90 590 2,2
KPL100 80 140 375 2 M10 16 6,5 5 1,30 390 39 20 200 10 90 650 2
KPL115 80 140 375 2 M10 16 6,8 5,5 1,10 330 33 20 200 10 90 720 1,8
KPL125 80 140 375 2 M10 16 7 5,8 1,00 300 30 20 200 10 90 760 1,7
KPL135 106 164 345 2 M20 30 10,5 6,7 3,50 1050 105 40 570 15 220 820 1,6
KPL150 106 164 345 2 M20 30 10,9 7,2 3,00 900 90 40 570 15 220 930 1,4
KPL165 106 164 345 2 M20 30 11,2 8 2,50 750 75 40 570 15 220 1000 1,3
KPL180 106 164 345 2 M20 30 12 9 2,00 600 60 40 570 15 220 1000 1,3
KPL200 106 164 345 2 M20 30 12,5 10,3 1,80 540 54 40 570 15 220 1050 1,2
KPL230 138 276 420 4 M16 24 18 10,2 6,50 1950 195 50 1400 25 690 1200 1,1
KPL250 138 276 420 4 M16 24 20 11,3 5,80 1740 174 50 1400 25 690 1200 1,1
KPL265 138 276 420 4 M16 24 21 13 5,30 1590 159 40 1150 25 690 1200 1,1
KPL280 138 276 450 4 M16 24 22,5 14,5 6,20 1860 186 60 1700 25 690 1200 1,1
KPL300 138 276 450 4 M16 24 23 16 6,00 1800 180 60 1700 25 690 1300 1
KPL330 138 276 450 4 M16 24 23,5 17 5,80 1740 174 60 1700 25 690 1450 0,9
KPL350 138 276 450 4 M16 24 24,5 18 5,20 1560 156 60 1700 25 690 1500 0,85
KPL365 138 276 450 4 M16 24 25 19 5,00 1500 150 50 1400 25 690 1500 0,85
KPL400 138 276 450 4 M16 24 26 21 4,50 1350 135 50 1400 25 690 1600 0,8
KPL430 138 276 450 4 M16 24 28 22 4,00 1200 120 40 1150 25 690 1750 0,75
KPL450 138 276 450 4 M16 24 30 24 3,50 1050 105 40 1150 25 690 1750 0,75
KPL500 174 291 510 4 M20 30 38 25 8,50 2550 255 120 5000 35 1400 1850 0,7
KPL600 174 291 510 4 M20 30 40 28 7,50 2250 225 100 4200 35 1400 2000 0,65
KPL700 174 291 510 4 M20 30 45 30 7,00 2100 210 100 3500 35 2050 2200 0,6
KPL800 185 398 570 6 M20 30 58 39 16,00 4800 480 90 5600 35 2050 2400 0,55
KPL900 185 398 570 6 M20 30 60 42 15,00 4500 450 70 4300 35 2050 2600 0,5
KPL1000 185 398 570 6 M20 30 63 46 14,00 4200 420 40 2500 35 2050 3250 0,4