The Peak Demand TM Advantage Current transformer accuracy that exceeds the IEEE C57.13-2016 0.15S class Accuracy of 0.15% from 1% of nominal current through rating factor Stocking available for just in time delivery 90% of orders ship within 24 hours Designed and engineered to meet customer specifications Fast turn-around time for custom quotations. Friendly team of industry veterans with decades of experience serving Utility and OEM customers Online ordering, inventory checking, and order status updates at mypeakdemand.com Applications High accuracy metering current transformers have been proven in independent utility studies to increase the revenue received by utilities. By extending the range and improving the accuracy of current flow to the meter, the utility can more accurately bill customers, especially during periods of low energy consumption. High Accuracy, Extended Range The Alta Series current transformers exceed the IEEE 0.15S accuracy standard with metering accuracy of 0.15% from 1% of nominal current through rating factor. Benefits Increases revenue with higher accuracy at lower loads Consolidates number of CT ratios Reduces inventory items Standardizes meter multipliers Lessens the risk of incorrect CT sizing PEAK DEMAND INC. www.peakdemand.com 1.844.PEAK.247 | 1.844.732.5247 605 Tarboro Street Annex SW Wilson, NC 27893 USA Alta Series TM High Accuracy Metering CT Specifications Insulation: 600V, 10kV BIL Frequency: 60 Hz Environment: Indoor/outdoor Standards: IEEE C57.13 RUS: All Peak Demand 600V metering CTs are RUS Listed

Upload: others

Post on 15-Mar-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Alta SeriesTM High Accuracy Metering CT - Peak Demand · • Consolidates number of CT ratios • Reduces inventory items • Standardizes meter multipliers • Lessens the risk of

The Peak DemandTM Advantage

• Current transformer accuracy that exceeds the IEEE C57.13-2016 0.15S class

• Accuracy of 0.15% from 1% of nominal current through rating factor

• Stocking available for just in time delivery

• 90% of orders ship within 24 hours

• Designed and engineered to meet customer specifications

• Fast turn-around time for custom quotations.

• Friendly team of industry veterans with decades of experience serving Utility and OEM customers

• Online ordering, inventory checking, and order status updates at mypeakdemand.com

ApplicationsHigh accuracy metering current transformers have been proven in independent utility studies to increase the revenue received by utilities. By extending the range and improving the accuracy of current flow to the meter, the utility can more accurately bill customers, especially during periods of low energy consumption.

High Accuracy, Extended RangeThe Alta Series current transformers exceed the IEEE 0.15S accuracy standard with metering accuracy of 0.15% from 1% of nominal current through rating factor.

Benefits• Increases revenue with higher accuracy at lower loads• Consolidates number of CT ratios • Reduces inventory items• Standardizes meter multipliers• Lessens the risk of incorrect CT sizing

PEAK DEMAND INC.www.peakdemand.com1.844.PEAK.247 | 1.844.732.5247605 Tarboro Street Annex SW Wilson, NC 27893 USA

Alta SeriesTM High Accuracy Metering CT

SpecificationsInsulation: 600V, 10kV BILFrequency: 60 HzEnvironment: Indoor/outdoorStandards: IEEE C57.13

RUS: All Peak Demand 600V metering CTs are RUS Listed

Page 2: Alta SeriesTM High Accuracy Metering CT - Peak Demand · • Consolidates number of CT ratios • Reduces inventory items • Standardizes meter multipliers • Lessens the risk of

Peak Demand Inc. strives to keep the information in this document current and accurate.  Please contact Peak Demand if there is any question as to the accuracy or completeness of the information contained in this document. Proper product selection and product application is the sole responsibility of the purchaser. Peak Demand reserves the right to discontinue any product or service at any time. © Peak Demand Inc. All Rights Reserved.

Selection GuideAlta Series High Accuracy Primary Rating IEEE Metering Accuracy Rating Factor

COS-6 30°C 55°C

COS0300ABN 300A 0.15SB-0.1 3.0 2.2

COS0600ABN 600A 0.15SB-0.2 2.0 1.5

COM-6 30°C 55°C

COM0500ABN 500A 0.15SB-0.2 2.0 1.5

COM0500ABN-X 500A 0.15SB-0.1 3.0 2.2

COM0500ABN-H 500A 0.15SB-0.2 4.0 3.0

COM0600ABN 600A 0.15SB-0.5 2.0 1.5

COM0600ABN-X 600A 0.15SB-0.2 3.0 2.0

COM1000ABN 1000A 0.15SB-0.5 2.0 1.5

COV-6 30°C 55°C 85°C

COV0500ANN 500A 0.15SB-0.5 2.0 2.0 2.0

COV0500ANN-R 500A 0.15SB-0.5 4.0 3.0 2.0

COV0500ANN-H 500A 0.15SB-0.2 3.0 3.0 3.0

COV0600ANN 600A 0.15SB-0.5 2.0 2.0 2.0

COV0600ANN-X 600A 0.15SB-0.2 3.0 3.0 3.0

COV1000ANN 1000A 0.15SB-0.5 2.0 2.0 2.0

COV2000ANN 2000A 0.15SB-0.5 2.0 2.0 2.0

COL-6 30°C 55°C

COL1200ANN 1200A 0.15SB-0.9 2.0 1.5

COL1500ANN 1500A 0.15SB-0.9 3.0 2.5

COL2000ANN 2000A 0.15SB-0.9 2.5 1.75

NotesMost CTs are available with or without a primary bar and with or without a base.

Docu

men

t: 1A

LT19