All Island Home InspectionsProperty Inspection Report

Cover Page

Inspection prepared for: Sample Report Date of Inspection: 3/13/2017

Inspector: Jarrod BarlowPhone: Office : 808-330-5908

Email: [email protected]

Page 2: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 1 of 125

Report SummaryReport Summary

The summary below consists of potentially significant findings. These findings can be a safetyhazard, a deficiency requiring a major expense to correct or items I would like to draw extra attentionto. The summary is not a complete listing of all the findings in the report, and reflects the opinion ofthe inspector. Please review all pages of the report as the summary alone does not explain all of theissues. All repairs should be done by a licensed & bonded tradesman or qualified professional. Irecommend obtaining a copy of all receipts, warranties and permits for the work done.ElectricalPage 5 Item: 1 Electrical Panel • Double tapped breaker(s) inside panel box (more than one

electrical conductor attached). This is not standard practice,and may cause overheating or even an electrical fire.Recommend evaluation by an electrician. Double tapping andlugging can create hot spots on breakers and neutral barsbecause they are not tightened to the correct torque--especially if two different size conductors are used. Becausethe hot [black] and neutral [white]wires are both currentcarrying conductors, the chance is then greater for potentialhot spots. If the double tap or lug becomes loose, it begins toarc. As it arcs it builds up carbon. Carbon is then resistanceand with more carbon buildup the more difficult it is for theconductor to make contact, thus increasing the current. Theend result can be the breaker tripping because of the looseconnection [current exceeding the rating of the breaker], orsigns of overheating such as discolored wires, melted wires,etc, or even fire.• Bushings missing from around branch wire(s) entering panelbox.• Breaker #6(unnamed) appears to be overheating and shouldbe replaced and circuit checked for proper wiring by alicensed electrician,

GroundsPage 12 Item: 8 Main Gas Valve

Condition• There is a gas smell present at the main valve. Werecommend contacting the gas utility company to repair.

Page 13 Item: 9 Plumbing • Corrosion is noted. Consult with a licensed plumbingcontractor to determine and correct the cause of the issue.

Page 14 Item: 11 Pressure Regulator • The pressure regulator is missing proper support. Moveswhen water is turned on and off.

Page 16 Item: 16 Fence Condition • Retaining walls are leaning.Exterior AreasPage 17 Item: 2 Window Condition • Deteriorated frame(s) at window(s)GaragePage 27 Item: 10 Fire Door • Does Not Appear to be a Rated Fire Door

• No auto closure presentKitchenPage 48 Item: 23 Electrical • Reversed polarity, hot and neutral reversed and other terms

used for electric receptacles are usually easily corrected byminor wiring adjustments at the specified item. When theseconditions are noted in this report, a licensed electricianshould be consulted for repairs/replacement as needed toensure safety.

Definition
A double tap occurs when two conductors are connected under one screw inside a panelboard. Most circuit breakers do not support double tapping, although some manufacturers, such as like Cutler Hammer, make hardware specially designed for this purpose. Double tapping is a defect when it is used on incompatible devices. If the conductors come loose, they cause overheating and electrical arcing, and the risk of fire is also present. A double tap can be accommodated by installing a new circuit board compatible with double tapping. It is also possible to add another circuit breaker or install a tandem breaker to the existing breaker box.
Page 3: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 2 of 125

FoundationPage 62 Item: 3 Foundation Walls • Efflorescence observed; this is a mineral deposit left behind

from exterior water infiltration.Page 62 Item: 4 Cripple Walls • Support beam for cripple wall ends short, unprofessional

extention is sagging due to lack of support .Page 63 Item: 8 Post and Girders • Some beams are sitting directly in soil.

• Vegetation growing through floor joists (see pics)• Some blocking are loose between joists

Page 65 Item: 11 FoundationElectrical

• Open junction boxes were observed. Whenever an electricwire is cut and reconnected, the 'splice' should be encased ina covered junction box to prevent shocks and separation ofthe splice.

Page 65 Item: 12 FoundationPlumbing

• 1/4 water line leaking

Main house interior areasPage 91 Item: 16 Fireplace • The fireplace damper is damaged and not functional; The

lever will not open or close the damper correctly. Do notattempt to start a fire until corrected.

Main house 1/2 bathPage 122 Item: 5 GFCI • No GFCI protection present, suggest installing GFCI

protected receptacles for safety.

Definition
A special device that is intended for the protection of personnel by de-energizing a circuit, capable of opening the circuit when even a small amount of current is flowing through the grounding system.
Page 4: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 3 of 125

INTRODUCTION: We appreciate the opportunity to conduct this inspection for you!   Please carefully read your entireInspection Report.  Call us after you have reviewed your report, so we can go over any questionsyou may have.  Remember, when the inspection is completed and the report is delivered, we are stillavailable to you for any questions you may have, throughout the entire closing process. Properties being inspected do not "Pass" or "Fail.” -  The following report is based on an inspectionof the visible portion of the structure; inspection may be limited by vegetation and possessions. Depending upon the age of the property, some items like GFCI outlets may not be installed; thisreport will focus on safety and function, not current code. This report identifies specific non-code,non-cosmetic concerns that the inspector feels may need further investigation or repair. For your safety and liability purposes, we recommend that licensed contractors evaluate and repairany critical concerns and defects.  Note that this report is a snapshot in time. We recommend thatyou or your representative carry out a final walk-through inspection immediately before closing tocheck the condition of the property, using this report as a guide.

Page 5: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 4 of 125

Inspection Details 1. Attendance

In Attendance: Owner/Client present

2. Home TypeHome Type: Detached

3. OccupancyOccupancy: Occupied - Furnished

Page 6: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 5 of 125

Electrical 1. Electrical PanelGood Fair Poor N/A None

XLocation: Main Location: laundry roomLocation: Located in the garage.Observations:• Double tapped breaker(s) inside panel box (more than one electricalconductor attached). This is not standard practice, and may causeoverheating or even an electrical fire. Recommend evaluation by anelectrician. Double tapping and lugging can create hot spots on breakersand neutral bars because they are not tightened to the correct torque--especially if two different size conductors are used. Because the hot [black]and neutral [white]wires are both current carrying conductors, the chance isthen greater for potential hot spots. If the double tap or lug becomes loose, itbegins to arc. As it arcs it builds up carbon. Carbon is then resistance andwith more carbon buildup the more difficult it is for the conductor to makecontact, thus increasing the current. The end result can be the breakertripping because of the loose connection [current exceeding the rating of thebreaker], or signs of overheating such as discolored wires, melted wires, etc,or even fire.• Bushings missing from around branch wire(s) entering panel box.• Breaker #6(unnamed) appears to be overheating and should be replacedand circuit checked for proper wiring by a licensed electrician,

Definition
A double tap occurs when two conductors are connected under one screw inside a panelboard. Most circuit breakers do not support double tapping, although some manufacturers, such as like Cutler Hammer, make hardware specially designed for this purpose. Double tapping is a defect when it is used on incompatible devices. If the conductors come loose, they cause overheating and electrical arcing, and the risk of fire is also present. A double tap can be accommodated by installing a new circuit board compatible with double tapping. It is also possible to add another circuit breaker or install a tandem breaker to the existing breaker box.
Page 7: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 6 of 125

2. Main Amp BreakerGood Fair Poor N/A None

XObservations:• 100 amp• 125 amp

3. Breakers in off positionGood Fair Poor N/A None

XObservations:• 0

4. Cable FeedsGood Fair Poor N/A None

XObservations:• There is an underground service lateral noted.

5. BreakersGood Fair Poor N/A None

XMaterials: Copper non-metallic sheathed cable noted.

6. FusesGood Fair Poor N/A None

X

Page 8: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 7 of 125

Grounds 1. Driveway and Walkway ConditionGood Fair Poor N/A None

XMaterials: Concrete driveway noted.Observations:• Driveway improperly sloped towards the garage/Recommend slab jacking,repair or replacing the settled concrete.

2. GradingGood Fair Poor N/A None

XObservations:• Lot grading and drainage have a significant impact on the building, simplybecause of the direct and indirect damage that moisture can have on thefoundation. It is very important, therefore, that surface runoff water beadequately diverted away from the home. Lot grading should slope away andfall a minimum of one (1) inch every foot for a distance of six (6) feet aroundthe perimeter of the building.• The exterior grading is improperly sloped towards the foundation. Watercan intrude into the interior. Recommend creating the proper slope awayfrom the foundation to allow for proper drainage.• Retaining Wall shows signs of deterioration.

Page 9: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 8 of 125

Page 10: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 9 of 125

3. Vegetation ObservationsGood Fair Poor N/A None

XObservations:• Prune or remove any plants that are in contact or proximity to home toeliminate pathways of wood destroying insects.• Tree limbs within 10 feet of roof should be trimmed away to provide air andsunlight to roof, while minimizing debris & dampness.

Page 11: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 10 of 125

4. Patio and Porch DeckGood Fair Poor N/A None

XObservations:• Appeared functional at time of inspection.

Page 12: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 11 of 125

5. Stairs & HandrailGood Fair Poor N/A None

XObservations:• Appeared functional at time of inspection.

Page 13: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 12 of 125

6. Grounds ElectricalGood Fair Poor N/A None

XObservations:• Interior grade Romex should be replaced with exterior-rated Romex andenclosed in conduit.

7. GFCIGood Fair Poor N/A None

XObservations:• None visible.

8. Main Gas Valve ConditionGood Fair Poor N/A None

XMaterials: Exterior of structure. • LP Gas shutoff located at the gas manifold -labeled and client made aware.Observations:• There is a gas smell present at the main valve. We recommend contactingthe gas utility company to repair.

Page 14: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 13 of 125

9. PlumbingGood Fair Poor N/A None

XMaterials: Copper piping noted.Observations:• Corrosion is noted. Consult with a licensed plumbing contractor todetermine and correct the cause of the issue.

Page 15: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 14 of 125

10. Water PressureGood Fair Poor N/A None

XObservations:• 60

11. Pressure RegulatorGood Fair Poor N/A None

XObservations:• Pressure regulator noted.• The pressure regulator is missing proper support. Moves when water isturned on and off.

12. Exterior Faucet ConditionGood Fair Poor N/A None

X XLocation: Front of structure.Observations:• Hose bib at north side of house leaks.

Page 16: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 15 of 125

13. BalconyGood Fair Poor N/A None

X

14. Lanai EnclosureGood Fair Poor N/A None

XObservations:• Appears in satisfactory and functional condition with normal wear for itsage. Appears to be sound structure.• Improve: Typical cracking was observed at the concrete surfaces.Recommend sealing the cracks to prolong the life of the concrete.

15. Lanai ConditionGood Fair Poor N/A None

XMaterials: The Lanai roof is the same as main structure.Observations:• No major system safety or function concerns noted at time of inspection.

16. Fence ConditionGood Fair Poor N/A None

XMaterials: StoneObservations:• Retaining walls are leaning.

Page 17: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 16 of 125

Page 18: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 17 of 125

Exterior Areas 1. DoorsGood Fair Poor N/A None

X

2. Window ConditionGood Fair Poor N/A None

XObservations:• Deteriorated frame(s) at window(s)

Page 19: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 18 of 125

3. Siding ConditionGood Fair Poor N/A None

X

4. Eaves & FaciaGood Fair Poor N/A None

XObservations:• Soffits at the home appeared to be in serviceable condition at the time ofthe inspection.• Suggest sealing/caulking as part of routine maintenance to prevent furtherdeterioration.

Page 20: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 19 of 125

Page 21: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 20 of 125

5. Exterior PaintGood Fair Poor N/A None

XObservations:• Suggest sealing/caulking as part of routine maintenance to prevent furtherdeterioration.• Peeling paint observed, suggest scraping and painting as necessary.• Exposed wood surfaces observed. Wood rot & deterioration can occur.Prep, prime and paint wood trim surface where paint is peeling or missing.• All exterior painted wood trim surfaces should be annually examined andsealed, re-caulked and re-painted as needed.

Page 22: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 21 of 125

6. StuccoGood Fair Poor N/A None

XObservations:• We recommend sealing holes & gaps in the stucco to keep water infiltrationfrom causing further damage.

Page 23: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 22 of 125

Roof 1. Roof ConditionGood Fair Poor N/A None

X

Page 24: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 23 of 125

2. FlashingGood Fair Poor N/A None

X

3. ChimneyGood Fair Poor N/A None

X

4. Sky LightsGood Fair Poor N/A None

X

5. Spark ArrestorGood Fair Poor N/A None

X

Page 25: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 24 of 125

6. Vent CapsGood Fair Poor N/A None

X

7. GutterGood Fair Poor N/A None

X

Page 26: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 25 of 125

Page 27: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 26 of 125

Garage 1. Roof ConditionGood Fair Poor N/A None

XMaterials: Roofing is the same as main structure.

2. WallsGood Fair Poor N/A None

XObservations:• Appeared satisfactory, at time of inspection.

3. Anchor BoltsGood Fair Poor N/A None

XObservations:• The anchor bolts were not visible, obscured by drywall.

4. Floor ConditionGood Fair Poor N/A None

XMaterials: Bare concrete floors noted.

Page 28: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 27 of 125

5. Rafters & CeilingGood Fair Poor N/A None

XObservations:• Garage has drywall ceiling.

6. ElectricalGood Fair Poor N/A None

XObservations:• Some outlets not accessible due to furniture and or stored personal items.

7. GFCIGood Fair Poor N/A None

XObservations:• GFCI in place and operational

8. 240 VoltGood Fair Poor N/A None

XObservations:• The 240 volt outlet for dryer

9. Exterior DoorGood Fair Poor N/A None

X

10. Fire DoorGood Fair Poor N/A None

XObservations:• Does Not Appear to be a Rated Fire Door• No auto closure present

Definition
A special device that is intended for the protection of personnel by de-energizing a circuit, capable of opening the circuit when even a small amount of current is flowing through the grounding system.
Page 29: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 28 of 125

11. Garage Door ConditionGood Fair Poor N/A None

XMaterials: Sectional door noted.Observations:• Door bottom weatherstripping is missing or damaged. Recommend repairor replacement.

12. Garage Door PartsGood Fair Poor N/A None

XObservations:• The garage door appeared functional during the inspection.

Page 30: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 29 of 125

13. Garage Opener StatusGood Fair Poor N/A None

XObservations:• Chain drive opener noted.

14. Garage Door's Reverse StatusGood Fair Poor N/A None

XObservations:• Eye beam system present and operating.

15. VentilationGood Fair Poor N/A None

X

16. Vent ScreensGood Fair Poor N/A None

X

17. CabinetsGood Fair Poor N/A None

X

Page 31: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 30 of 125

18. CountersGood Fair Poor N/A None

XObservations:• No discrepancies noted.

19. Wash BasinGood Fair Poor N/A None

X

Page 32: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 31 of 125

Interior Areas The Interior section covers areas of the house that are not considered part of the Bathrooms,Bedrooms, Kitchen or areas covered elsewhere in the report. Interior areas usually consist ofhallways, foyer, and other open areas. Within these areas the inspector is performing a visualinspection and will report visible damage, wear and tear, and moisture problems if seen. Personalitems in the structure may prevent the inspector from viewing all areas on the interior. The inspector does not usually test for mold or other hazardous materials. A qualified expert shouldbe consulted if you would like further testing.

1. BarGood Fair Poor N/A None

X

2. CabinetsGood Fair Poor N/A None

XObservations:• No deficiencies observed.

3. Ceiling FansGood Fair Poor N/A None

X

4. ClosetsGood Fair Poor N/A None

X

Page 33: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 32 of 125

5. Door BellGood Fair Poor N/A None

XObservations:• The inspector was not able to operate the doorbell.

6. DoorsGood Fair Poor N/A None

X

7. ElectricalGood Fair Poor N/A None

XObservations:• Some outlets not accessible due to furniture and or stored personal items.

8. Security BarsGood Fair Poor N/A None

X

9. Smoke DetectorsGood Fair Poor N/A None

XObservations:• The smoke alarm(s) did not operate when tested.

Page 34: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 33 of 125

10. Stairs & HandrailGood Fair Poor N/A None

X

11. Window-Wall AC or HeatGood Fair Poor N/A None

X

12. Ceiling ConditionGood Fair Poor N/A None

XMaterials: There are drywall ceilings noted.

13. Patio DoorsGood Fair Poor N/A None

X

14. Screen DoorsGood Fair Poor N/A None

X

15. Wall ConditionGood Fair Poor N/A None

XMaterials: Drywall walls noted. • Plaster walls noted.

Page 35: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 34 of 125

16. FireplaceGood Fair Poor N/A None

X

17. Window ConditionGood Fair Poor N/A None

XMaterials: Wood framed sliding window noted.

Page 36: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 35 of 125

Bedrooms The main area of inspection in the bedrooms is the structural system. This means that all walls,ceilings and floors will be inspected. Doors and windows will also be investigated for damage andnormal operation. Personal items in the bedroom may prevent all areas to be inspected as theinspector will not move personal items.

1. LocationsLocations: Master#1

2. CabinetsGood Fair Poor N/A None

X

3. Ceiling FansGood Fair Poor N/A None

X

4. ClosetsGood Fair Poor N/A None

X

5. DoorsGood Fair Poor N/A None

X

Page 37: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 36 of 125

6. ElectricalGood Fair Poor N/A None

X

7. FireplaceGood Fair Poor N/A None

X

8. Floor ConditionGood Fair Poor N/A None

XFlooring Types: Carpet is noted.

9. Security BarsGood Fair Poor N/A None

X

10. Smoke DetectorsGood Fair Poor N/A None

XObservations:• The smoke detectors operated during the inspection.

Page 38: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 37 of 125

11. Wall ConditionGood Fair Poor N/A None

XMaterials: Drywall walls noted.

12. Window-Wall AC or HeatGood Fair Poor N/A None

X

13. Window ConditionGood Fair Poor N/A None

XMaterials: Wood framed sliding window noted.

14. Ceiling ConditionGood Fair Poor N/A None

XMaterials: There are drywall ceilings noted.

15. Patio DoorsGood Fair Poor N/A None

X

Page 39: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 38 of 125

16. Screen DoorsGood Fair Poor N/A None

X

Page 40: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 39 of 125

Bathroom Bathrooms can consist of many features from jacuzzi tubs and showers to toilets and bidets.Because of all the plumbing involved it is an important area of the house to look over. Moisture in theair and leaks can cause mildew, wallpaper and paint to peel, and other problems. The homeinspector will identify as many issues as possible but some problems may be undetectable due toproblems within the walls or under the flooring..

1. LocationsLocations: Master Bathroom

2. CabinetsGood Fair Poor N/A None

X

3. Ceiling ConditionGood Fair Poor N/A None

XMaterials: There are drywall ceilings noted.

4. CountersGood Fair Poor N/A None

XObservations:• Granite tops noted.

Page 41: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 40 of 125

5. DoorsGood Fair Poor N/A None

XObservations:• No major system safety or function concerns noted at time of inspection.

6. ElectricalGood Fair Poor N/A None

X

7. GFCIGood Fair Poor N/A None

XObservations:• GFCI in place and operational

8. Exhaust FanGood Fair Poor N/A None

XObservations:• Exhaust fan is noisy.

9. Floor ConditionGood Fair Poor N/A None

XMaterials: Ceramic tile is noted.

Page 42: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 41 of 125

10. HeatingGood Fair Poor N/A None

X

11. MirrorsGood Fair Poor N/A None

X

12. PlumbingGood Fair Poor N/A None

XObservations:• Older style metal traps noted. Buyer is cautioned that these traps can leakat any time due to corrosion.

13. Security BarsGood Fair Poor N/A None

X

14. ShowersGood Fair Poor N/A None

XObservations:• functional

Page 43: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 42 of 125

15. Shower WallsGood Fair Poor N/A None

XObservations:• Ceramic tile noted.

16. Bath TubsGood Fair Poor N/A None

X

17. EnclosureGood Fair Poor N/A None

XObservations:• The shower enclosure was functional at the time of the inspection.

Page 44: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 43 of 125

18. SinksGood Fair Poor N/A None

X

19. ToiletsGood Fair Poor N/A None

XObservations:• Toilet continues to run after flushing; have contractor evaluate and repair.• Mechanism in tank sticking, requires adjustment for proper flushing.

Page 45: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 44 of 125

20. Window ConditionGood Fair Poor N/A None

XMaterials: Glass blocks noted in window openings.

Page 46: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 45 of 125

Kitchen The kitchen is used for food preparation and often for entertainment. Kitchens typically include astove, dishwasher, sink and other appliances.

1. CabinetsGood Fair Poor N/A None

XObservations:• Some cabinet drawers need hardware repair/adjustment (to stay shut).Repair as needed.lazy Susan door

2. CountersGood Fair Poor N/A None

XObservations:• Granite tops noted.

3. DishwasherGood Fair Poor N/A None

XObservations:• Operated.

4. DoorsGood Fair Poor N/A None

X

Page 47: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 46 of 125

5. Garbage DisposalGood Fair Poor N/A None

XObservations:• Operated - appeared functional at time of inspection.

6. MicrowaveGood Fair Poor N/A None

X

7. Cook top conditionGood Fair Poor N/A None

XObservations:• Electric cook top noted.

8. Oven & RangeGood Fair Poor N/A None

XObservations:• Oven: Electric radiant heating coils or infrared halogen.

9. SinksGood Fair Poor N/A None

X

10. Drinking FountainGood Fair Poor N/A None

X

11. Spray WandGood Fair Poor N/A None

X

12. Hot Water DispenserGood Fair Poor N/A None

X

Page 48: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 47 of 125

13. Soap DispenserGood Fair Poor N/A None

X

14. Trash CompactorGood Fair Poor N/A None

X

15. Vent ConditionGood Fair Poor N/A None

X

16. Window ConditionGood Fair Poor N/A None

XMaterials: Wood framed sliding window noted.

17. Floor ConditionGood Fair Poor N/A None

XMaterials: Ceramic tile is noted.

18. PlumbingGood Fair Poor N/A None

X

19. Ceiling ConditionGood Fair Poor N/A None

XMaterials: There are drywall ceilings noted.

20. Security BarsGood Fair Poor N/A None

X

Page 49: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 48 of 125

21. Patio DoorsGood Fair Poor N/A None

X

22. Screen DoorsGood Fair Poor N/A None

X

23. ElectricalGood Fair Poor N/A None

XObservations:• Reversed polarity, hot and neutral reversed and other terms used forelectric receptacles are usually easily corrected by minor wiring adjustmentsat the specified item. When these conditions are noted in this report, alicensed electrician should be consulted for repairs/replacement as neededto ensure safety.

24. GFCIGood Fair Poor N/A None

XObservations:• GFCI in place and operational.

25. Wall ConditionGood Fair Poor N/A None

XMaterials: Drywall walls noted.

Page 50: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 49 of 125

Laundry 1. Locations

Locations: 1sr floor

2. CabinetsGood Fair Poor N/A None

X

3. CountersGood Fair Poor N/A None

X

4. Dryer VentGood Fair Poor N/A None

XObservations:• The dryer vent terminates under structure.

5. ElectricalGood Fair Poor N/A None

X

6. GFCIGood Fair Poor N/A None

XObservations:• No GFCI protection present, suggest installing GFCI protected receptaclesfor safety.

7. Exhaust FanGood Fair Poor N/A None

X

8. Gas ValvesGood Fair Poor N/A None

X

Page 51: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 50 of 125

9. Wash BasinGood Fair Poor N/A None

X

10. Floor ConditionGood Fair Poor N/A None

XMaterials: Ceramic tile is noted.

11. PlumbingGood Fair Poor N/A None

X

12. Wall ConditionGood Fair Poor N/A None

XMaterials: Drywall walls noted.

13. Ceiling ConditionGood Fair Poor N/A None

X

14. Security BarsGood Fair Poor N/A None

X

15. DoorsGood Fair Poor N/A None

X

16. Window ConditionGood Fair Poor N/A None

XMaterials: Wood framed sliding window noted.

Page 52: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 51 of 125

Page 53: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 52 of 125

A/C The heating, ventilation, and air conditioning and cooling system (often referred to as HVAC) is theclimate control system for the structure. The goal of these systems is to keep the occupants at acomfortable level while maintaining indoor air quality, ventilation while keeping maintenance costs ata minimum. The HVAC system is usually powered by electricity and natural gas, but can also bepowered by other sources such as butane, oil, propane, solar panels, or wood. The inspector will usually test the heating and air conditioner using the thermostat or other controls.For a more thorough investigation of the system please contact a licensed HVAC service person.

1. Heater ConditionGood Fair Poor N/A None

X

2. Heater BaseGood Fair Poor N/A None

X

3. EnclosureGood Fair Poor N/A None

4. VentingGood Fair Poor N/A None

5. Gas ValvesGood Fair Poor N/A None

X

6. Refrigerant LinesGood Fair Poor N/A None

XObservations:• Missing insulation in areas.

Page 54: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 53 of 125

7. AC Compress ConditionGood Fair Poor N/A None

XCompressor Type: ElectricLocation: The compressor is located on the exterior north.Observations:• Annual HVAC service contract is recommended.

Page 55: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 54 of 125

8. Air SupplyGood Fair Poor N/A None

X

9. RegistersGood Fair Poor N/A None

10. FiltersGood Fair Poor N/A None

11. ThermostatsGood Fair Poor N/A None

Page 56: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 55 of 125

Water Heater 1. BaseGood Fair Poor N/A None

XObservations:• The water heater base is functional.

2. Heater EnclosureGood Fair Poor N/A None

XObservations:• The water heater enclosure is functional.

Page 57: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 56 of 125

3. CombusionGood Fair Poor N/A None

X

4. VentingGood Fair Poor N/A None

X

5. Water Heater ConditionGood Fair Poor N/A None

XHeater Type: ElectricLocation: The heater is located under the structure.Observations:• Water heater is reaching the end of its typical service life. Highlyrecommend replacement.

6. TPRVGood Fair Poor N/A None

XObservations:• Appears to be in satisfactory condition -- no concerns.

Page 58: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 57 of 125

7. Number Of GallonsGood Fair Poor N/A None

XObservations:• 80 gallons

8. Gas ValveGood Fair Poor N/A None

X

9. PlumbingGood Fair Poor N/A None

XMaterials: CopperObservations:• No deficiencies observed at the visible portions of the supply piping.

Page 59: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 58 of 125

10. Overflow ConditionGood Fair Poor N/A None

XMaterials: None

11. StrappingGood Fair Poor N/A None

X

Page 60: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 59 of 125

Attic 1. AccessGood Fair Poor N/A None

XObservations:• Garage bathroom• Access at hallway ceiling.

2. StructureGood Fair Poor N/A None

X

3. VentilationGood Fair Poor N/A None

XObservations:• Under eave soffit inlet vents noted.

4. Vent ScreensGood Fair Poor N/A None

XObservations:• Vent screens noted as functional.

Page 61: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 60 of 125

5. Duct WorkGood Fair Poor N/A None

XObservations:• Old ducting was left in attic when replaced.

6. ElectricalGood Fair Poor N/A None

XObservations:• Electrical Box Covers missing or damaged, which is a potential shock orelectrocution hazard.

7. Attic PlumbingGood Fair Poor N/A None

X

8. Insulation ConditionGood Fair Poor N/A None

XMaterials: Unfinished fiberglass batts noted.

9. ChimneyGood Fair Poor N/A None

X

Page 62: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 61 of 125

10. Exhaust VentGood Fair Poor N/A None

XObservations:• Functional.

Page 63: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 62 of 125

Foundation 1. Slab FoundationGood Fair Poor N/A None

XObservations:• Concrete slab foundation under garage only

2. Foundation PerimeterGood Fair Poor N/A None

X

3. Foundation WallsGood Fair Poor N/A None

XObservations:• Normal settlement.• Efflorescence observed; this is a mineral deposit left behind from exteriorwater infiltration.

4. Cripple WallsGood Fair Poor N/A None

XObservations:• Support beam for cripple wall ends short, unprofessional extention issagging due to lack of support .

Page 64: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 63 of 125

5. VentilationGood Fair Poor N/A None

X

6. Vent ScreensGood Fair Poor N/A None

X

7. Access PanelGood Fair Poor N/A None

X

8. Post and GirdersGood Fair Poor N/A None

XObservations:• Support Material: concrete block piers• Support Material: Block Pillars• Beam Material: Wood• No deficiencies were observed at the visible portions of the structuralcomponents of the home.other than those noted• Some beams are sitting directly in soil.• Vegetation growing through floor joists (see pics)• Some blocking are loose between joists

Page 65: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 64 of 125

9. Sub FlooringGood Fair Poor N/A None

XObservations:• Plywood sheathing sub floor.

Page 66: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 65 of 125

10. Anchor BoltsGood Fair Poor N/A None

XObservations:• The anchor bolts were not visible.

11. Foundation ElectricalGood Fair Poor N/A None

XObservations:• All wiring should be properly secured to the framing.• Exposed electrical wiring observed. This is a safety concern if used where itcould be subject to "Physical Damage". Exposed electrical wires are normallyencased in conduit to ensure safety. Client should consult with a licensedelectrician prior to closing for repairs/replacement as needed to ensuresafety.• Open junction boxes were observed. Whenever an electric wire is cut andreconnected, the 'splice' should be encased in a covered junction box toprevent shocks and separation of the splice.

12. Foundation PlumbingGood Fair Poor N/A None

Observations:• 3/4 inch copper• Acrylonitrile-Butadiene-Stryrene "ABS" waste and vent pipes noted.• Appears Functional at time of inspection.• 1/4 water line leaking

Definition
Acronym for acrylonitrile butadiene styrene; rigid black plastic pipe used only for drain lines.
Page 67: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 66 of 125

13. Sump PumpGood Fair Poor N/A None

XObservations:• Unable to determine location of discharge.

Page 68: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 67 of 125

14. DuctingGood Fair Poor N/A None

Page 69: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 68 of 125

Basement/Crawlspace 1. WallsGood Fair Poor N/A None

2. InsulationGood Fair Poor N/A None

3. WindowsGood Fair Poor N/A None

4. Plumbing MaterialsGood Fair Poor N/A None

5. Basement ElectricGood Fair Poor N/A None

6. GFCIGood Fair Poor N/A None

7. AccessGood Fair Poor N/A None

8. StairsGood Fair Poor N/A None

9. RailingsGood Fair Poor N/A None

10. Slab FloorGood Fair Poor N/A None

11. Finished FloorGood Fair Poor N/A None

12. DrainageGood Fair Poor N/A None

Page 70: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 69 of 125

13. Sump PumpGood Fair Poor N/A None

14. FramingGood Fair Poor N/A None

15. SubfloorGood Fair Poor N/A None

16. ColumnsGood Fair Poor N/A None

17. PiersGood Fair Poor N/A None

18. Basement/Crawlspace DuctworkGood Fair Poor N/A None

Page 71: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 70 of 125

Master bedroom 1. Locations

2. CabinetsGood Fair Poor N/A None

3. Ceiling FansGood Fair Poor N/A None

4. ClosetsGood Fair Poor N/A None

5. DoorsGood Fair Poor N/A None

6. ElectricalGood Fair Poor N/A None

7. FireplaceGood Fair Poor N/A None

8. Floor ConditionGood Fair Poor N/A None

9. Security BarsGood Fair Poor N/A None

10. Smoke DetectorsGood Fair Poor N/A None

11. Wall ConditionGood Fair Poor N/A None

12. Window-Wall AC or HeatGood Fair Poor N/A None

Page 72: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 71 of 125

13. Window ConditionGood Fair Poor N/A None

14. Ceiling ConditionGood Fair Poor N/A None

15. Patio DoorsGood Fair Poor N/A None

16. Screen DoorsGood Fair Poor N/A None

Page 73: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 72 of 125

Master bathroom 1. Locations

2. CabinetsGood Fair Poor N/A None

3. Ceiling FansGood Fair Poor N/A None

4. ClosetsGood Fair Poor N/A None

5. DoorsGood Fair Poor N/A None

6. ElectricalGood Fair Poor N/A None

7. FireplaceGood Fair Poor N/A None

8. Floor ConditionGood Fair Poor N/A None

9. Security BarsGood Fair Poor N/A None

10. Smoke DetectorsGood Fair Poor N/A None

11. Wall ConditionGood Fair Poor N/A None

12. Window-Wall AC or HeatGood Fair Poor N/A None

Page 74: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 73 of 125

13. Window ConditionGood Fair Poor N/A None

14. Ceiling ConditionGood Fair Poor N/A None

15. Patio DoorsGood Fair Poor N/A None

16. Screen DoorsGood Fair Poor N/A None

Page 75: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 74 of 125

Main house kitchen 1. CabinetsGood Fair Poor N/A None

XObservations:• No deficiencies observed.

2. CountersGood Fair Poor N/A None

XObservations:• Solid Surface tops noted.• Wood counter tops noted.

3. DishwasherGood Fair Poor N/A None

XObservations:• Operated.

4. DoorsGood Fair Poor N/A None

X

Page 76: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 75 of 125

5. Garbage DisposalGood Fair Poor N/A None

XObservations:• Operated - appeared functional at time of inspection.

6. MicrowaveGood Fair Poor N/A None

X

7. Cook top conditionGood Fair Poor N/A None

XObservations:• Gas cook top noted.

8. Oven & RangeGood Fair Poor N/A None

XObservations:• Oven: gas burners

9. SinksGood Fair Poor N/A None

X

Page 77: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 76 of 125

10. Drinking FountainGood Fair Poor N/A None

XObservations:• There was no drinking fountain present in this kitchen.

11. Spray WandGood Fair Poor N/A None

XObservations:• There was no spray wand present in this kitchen.

12. Hot Water DispenserGood Fair Poor N/A None

X

13. Soap DispenserGood Fair Poor N/A None

X

14. Trash CompactorGood Fair Poor N/A None

X

15. Vent ConditionGood Fair Poor N/A None

XMaterials: Exterior Vented

Page 78: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 77 of 125

16. Window ConditionGood Fair Poor N/A None

XMaterials: Wood framed casement window noted. • Wood framed fixedwindow noted.

17. Floor ConditionGood Fair Poor N/A None

XMaterials: Hardwood flooring is noted.

Page 79: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 78 of 125

18. PlumbingGood Fair Poor N/A None

X

19. Ceiling ConditionGood Fair Poor N/A None

XMaterials: There are drywall ceilings noted.

20. Security BarsGood Fair Poor N/A None

X

21. Patio DoorsGood Fair Poor N/A None

X

22. Screen DoorsGood Fair Poor N/A None

X

Page 80: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 79 of 125

23. ElectricalGood Fair Poor N/A None

XObservations:• No major system safety or function concerns noted at time of inspection.

24. GFCIGood Fair Poor N/A None

XObservations:• GFCI in place and operational.

25. Wall ConditionGood Fair Poor N/A None

XMaterials: Drywall walls noted.

Page 81: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 80 of 125

Main house laundry 1. Locations

Locations: Midfloor

2. CabinetsGood Fair Poor N/A None

XObservations:• No deficiencies observed.

3. CountersGood Fair Poor N/A None

XObservations:• Plastic laminate tops noted.

4. Dryer VentGood Fair Poor N/A None

X

Page 82: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 81 of 125

5. ElectricalGood Fair Poor N/A None

XObservations:• Outlets did not work

6. GFCIGood Fair Poor N/A None

XObservations:• GFCI did not respond to test, suggest replacing for safety.

7. Exhaust FanGood Fair Poor N/A None

X

8. Gas ValvesGood Fair Poor N/A None

X

9. Wash BasinGood Fair Poor N/A None

X

Page 83: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 82 of 125

10. Floor ConditionGood Fair Poor N/A None

XMaterials: Ceramic tile is noted.

11. PlumbingGood Fair Poor N/A None

XObservations:• Older style metal traps noted. Buyer is cautioned that these traps can leakat any time due to corrosion.

Page 84: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 83 of 125

12. Wall ConditionGood Fair Poor N/A None

XMaterials: Drywall walls noted.

13. Ceiling ConditionGood Fair Poor N/A None

XMaterials: There are drywall ceilings noted.

14. Security BarsGood Fair Poor N/A None

X

15. DoorsGood Fair Poor N/A None

XObservations:• Pocket door does not operate smoothly. .

16. Window ConditionGood Fair Poor N/A None

XMaterials: Wood framed casement window noted.

Page 85: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 84 of 125

Page 86: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 85 of 125

Garage laundry 1. Locations

Locations: Garage

2. CabinetsGood Fair Poor N/A None

X

3. CountersGood Fair Poor N/A None

X

4. Dryer VentGood Fair Poor N/A None

XObservations:• The dryer vent is missing the exterior cover.

5. ElectricalGood Fair Poor N/A None

X

6. GFCIGood Fair Poor N/A None

X

7. Exhaust FanGood Fair Poor N/A None

X

8. Gas ValvesGood Fair Poor N/A None

X

Page 87: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 86 of 125

9. Wash BasinGood Fair Poor N/A None

X

10. Floor ConditionGood Fair Poor N/A None

XMaterials: Marble floors noted.

11. PlumbingGood Fair Poor N/A None

X

12. Wall ConditionGood Fair Poor N/A None

XMaterials: Drywall walls noted.

13. Ceiling ConditionGood Fair Poor N/A None

XMaterials: There are drywall ceilings noted.

14. Security BarsGood Fair Poor N/A None

X

15. DoorsGood Fair Poor N/A None

X

16. Window ConditionGood Fair Poor N/A None

X

Page 88: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 87 of 125

Main house interior areas 1. BarGood Fair Poor N/A None

X

2. CabinetsGood Fair Poor N/A None

XObservations:• No deficiencies observed.

3. Ceiling FansGood Fair Poor N/A None

XObservations:• Operated normally when tested, at time of inspection.

4. ClosetsGood Fair Poor N/A None

XObservations:• The closet is in serviceable condition.

Page 89: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 88 of 125

5. Door BellGood Fair Poor N/A None

XObservations:• The inspector was not able to operate the doorbell.

6. DoorsGood Fair Poor N/A None

X

Page 90: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 89 of 125

7. ElectricalGood Fair Poor N/A None

XObservations:• Some outlets not accessible due to furniture and or stored personal items.• Several bulbs not working

8. Security BarsGood Fair Poor N/A None

X

9. Smoke DetectorsGood Fair Poor N/A None

X

10. Stairs & HandrailGood Fair Poor N/A None

X

11. Window-Wall AC or HeatGood Fair Poor N/A None

X

Page 91: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 90 of 125

12. Ceiling ConditionGood Fair Poor N/A None

XMaterials: There are drywall ceilings noted.

13. Patio DoorsGood Fair Poor N/A None

X

14. Screen DoorsGood Fair Poor N/A None

X

Page 92: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 91 of 125

15. Wall ConditionGood Fair Poor N/A None

XMaterials: Drywall walls noted.

16. FireplaceGood Fair Poor N/A None

XMaterials: Living RoomMaterials: Masonry fireplace noted.Observations:• The fireplace damper is damaged and not functional; The lever will notopen or close the damper correctly. Do not attempt to start a fire untilcorrected.

Page 93: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 92 of 125

17. Window ConditionGood Fair Poor N/A None

XMaterials: Wood framed casement window noted.

Page 94: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 93 of 125

18. FloorGood Fair Poor N/A None

Page 95: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 94 of 125

Main house bedrooms 1. Locations

Locations: Upstairs

2. CabinetsGood Fair Poor N/A None

XObservations:• No deficiencies observed.

3. Ceiling FansGood Fair Poor N/A None

XObservations:• Operated normally when tested, at time of inspection.

4. ClosetsGood Fair Poor N/A None

XObservations:• The closet is in serviceable condition.

Page 96: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 95 of 125

5. DoorsGood Fair Poor N/A None

XObservations:• Double door entryway.

6. ElectricalGood Fair Poor N/A None

X

7. FireplaceGood Fair Poor N/A None

X

8. Floor ConditionGood Fair Poor N/A None

XFlooring Types: Carpet is noted.

Page 97: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 96 of 125

9. Security BarsGood Fair Poor N/A None

X

10. Smoke DetectorsGood Fair Poor N/A None

XObservations:• There were no smoke detectors present in the bedroom(s).

11. Wall ConditionGood Fair Poor N/A None

XMaterials: Drywall walls noted.

12. Window-Wall AC or HeatGood Fair Poor N/A None

X

13. Window ConditionGood Fair Poor N/A None

X

Page 98: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 97 of 125

14. Ceiling ConditionGood Fair Poor N/A None

XMaterials: There are drywall ceilings noted.

15. Patio DoorsGood Fair Poor N/A None

X

16. Screen DoorsGood Fair Poor N/A None

X

Page 99: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 98 of 125

Main house master bedroom 1. Locations

Locations: Upstairs

2. CabinetsGood Fair Poor N/A None

XObservations:• No deficiencies observed.

3. Ceiling FansGood Fair Poor N/A None

XObservations:• Operated normally when tested, at time of inspection.

4. ClosetsGood Fair Poor N/A None

XObservations:• The closet is in serviceable condition.

Page 100: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 99 of 125

5. DoorsGood Fair Poor N/A None

X

6. ElectricalGood Fair Poor N/A None

XObservations:• Some outlets not accessible due to furniture and or stored personal items.

7. FireplaceGood Fair Poor N/A None

XMaterials: BedroomMaterials: Masonry fireplace noted.Observations:• Damper was opened and closed several times.• Have a fireplace professional evaluate and repair any issues found beforeattempting to use fireplace.

Page 101: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 100 of 125

8. Floor ConditionGood Fair Poor N/A None

XFlooring Types: Floating laminate type flooring noted.

9. Security BarsGood Fair Poor N/A None

X

10. Smoke DetectorsGood Fair Poor N/A None

XObservations:• **Smoke Detectors**

Page 102: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 101 of 125

11. Wall ConditionGood Fair Poor N/A None

XMaterials: Drywall walls noted.

12. Window-Wall AC or HeatGood Fair Poor N/A None

X

13. Window ConditionGood Fair Poor N/A None

XMaterials: Wood framed casement window noted.

Page 103: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 102 of 125

14. Ceiling ConditionGood Fair Poor N/A None

XMaterials: There are drywall ceilings noted.

15. Patio DoorsGood Fair Poor N/A None

X

16. Screen DoorsGood Fair Poor N/A None

X

Page 104: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 103 of 125

Studio bathroom 1. Locations

2. CabinetsGood Fair Poor N/A None

X

3. Ceiling ConditionGood Fair Poor N/A None

XMaterials: There are drywall ceilings noted.

4. CountersGood Fair Poor N/A None

X

5. DoorsGood Fair Poor N/A None

X

Page 105: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 104 of 125

6. ElectricalGood Fair Poor N/A None

XObservations:• Light fixture or bulb apparently inoperable at . Change bulb(s) and check.• Light bulbs are missing at various fixtures throughout the house, andcannot be evaluated.

7. GFCIGood Fair Poor N/A None

XObservations:• GFCI in place and operational

8. Exhaust FanGood Fair Poor N/A None

XObservations:• The bath fan is a worn unit which may be at the end of its useful life.

Page 106: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 105 of 125

9. Floor ConditionGood Fair Poor N/A None

XMaterials: Ceramic tile is noted.

10. HeatingGood Fair Poor N/A None

X

11. MirrorsGood Fair Poor N/A None

X

Page 107: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 106 of 125

12. PlumbingGood Fair Poor N/A None

XObservations:• Older style metal traps noted. Buyer is cautioned that these traps can leakat any time due to corrosion.

13. Security BarsGood Fair Poor N/A None

X

14. ShowersGood Fair Poor N/A None

XObservations:• functional

Page 108: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 107 of 125

15. Shower WallsGood Fair Poor N/A None

XObservations:• Fiberglass surround noted.

Page 109: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 108 of 125

16. Bath TubsGood Fair Poor N/A None

X

17. EnclosureGood Fair Poor N/A None

XObservations:• The shower enclosure was functional at the time of the inspection.

18. SinksGood Fair Poor N/A None

XObservations:• Supply line showing signs of corrosion

Page 110: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 109 of 125

19. ToiletsGood Fair Poor N/A None

XObservations:• 0bserved as functional and in good visual condition.• Operated when tested. No deficiencies noted.

20. Window ConditionGood Fair Poor N/A None

XMaterials: Vinyl framed casement window noted.

Page 111: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 110 of 125

Page 112: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 111 of 125

Main house master bathroom 1. Locations

2. CabinetsGood Fair Poor N/A None

3. Ceiling ConditionGood Fair Poor N/A None

4. CountersGood Fair Poor N/A None

5. DoorsGood Fair Poor N/A None

6. ElectricalGood Fair Poor N/A None

Page 113: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 112 of 125

7. GFCIGood Fair Poor N/A None

8. Exhaust FanGood Fair Poor N/A None

9. Floor ConditionGood Fair Poor N/A None

10. HeatingGood Fair Poor N/A None

11. MirrorsGood Fair Poor N/A None

Page 114: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 113 of 125

12. PlumbingGood Fair Poor N/A None

13. Security BarsGood Fair Poor N/A None

14. ShowersGood Fair Poor N/A None

15. Shower WallsGood Fair Poor N/A None

16. Bath TubsGood Fair Poor N/A None

Page 115: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 114 of 125

17. EnclosureGood Fair Poor N/A None

18. SinksGood Fair Poor N/A None

Page 116: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 115 of 125

19. ToiletsGood Fair Poor N/A None

20. Window ConditionGood Fair Poor N/A None

Page 117: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 116 of 125

Page 118: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 117 of 125

Main house bathroom 1. Locations

2. CabinetsGood Fair Poor N/A None

3. Ceiling ConditionGood Fair Poor N/A None

4. CountersGood Fair Poor N/A None

5. DoorsGood Fair Poor N/A None

6. ElectricalGood Fair Poor N/A None

Page 119: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 118 of 125

7. GFCIGood Fair Poor N/A None

8. Floor ConditionGood Fair Poor N/A None

9. MirrorsGood Fair Poor N/A None

10. PlumbingGood Fair Poor N/A None

11. ShowersGood Fair Poor N/A None

Page 120: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 119 of 125

12. Shower WallsGood Fair Poor N/A None

13. EnclosureGood Fair Poor N/A None

Page 121: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 120 of 125

14. SinksGood Fair Poor N/A None

15. ToiletsGood Fair Poor N/A None

Page 122: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 121 of 125

16. Window ConditionGood Fair Poor N/A None

Page 123: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 122 of 125

Main house 1/2 bath 1. Locations

2. Ceiling ConditionGood Fair Poor N/A None

X

3. DoorsGood Fair Poor N/A None

X

4. ElectricalGood Fair Poor N/A None

XObservations:• No major system safety or function concerns noted at time of inspection.

5. GFCIGood Fair Poor N/A None

XObservations:• No GFCI protection present, suggest installing GFCI protected receptaclesfor safety.

6. Exhaust FanGood Fair Poor N/A None

XObservations:• The bath fan was operated and no issues were found.

Page 124: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 123 of 125

7. Floor ConditionGood Fair Poor N/A None

XMaterials: Ceramic tile is noted.

8. MirrorsGood Fair Poor N/A None

X

9. PlumbingGood Fair Poor N/A None

XObservations:• No concerns at this time

10. SinksGood Fair Poor N/A None

XObservations:• No deficiencies observed.• Sink appears to be in good condition.

Page 125: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 124 of 125

11. ToiletsGood Fair Poor N/A None

XObservations:• Operated when tested. No deficiencies noted.

Page 126: All Island Home Inspectionsallislandhomeinspectionsllc.com/pdf/1234_Sample_drive.pdf · and circuit checked for proper wiring by a licensed electrician, A double tap occurs when two

All Island Home Inspections

Page 125 of 125

GlossaryGlossary

Term Definition

ABS Acronym for acrylonitrile butadiene styrene; rigid black plasticpipe used only for drain lines.

Double Tap A double tap occurs when two conductors are connected underone screw inside a panelboard. Most circuit breakers do notsupport double tapping, although some manufacturers, such aslike Cutler Hammer, make hardware specially designed for thispurpose.

Double tapping is a defect when it is used on incompatibledevices. If the conductors come loose, they cause overheatingand electrical arcing, and the risk of fire is also present. A doubletap can be accommodated by installing a new circuit boardcompatible with double tapping. It is also possible to add anothercircuit breaker or install a tandem breaker to the existing breakerbox.

GFCI A special device that is intended for the protection of personnelby de-energizing a circuit, capable of opening the circuit wheneven a small amount of current is flowing through the groundingsystem.