alarms and trips
DESCRIPTION
Alarms and TripsTRANSCRIPT
AUXILIARY BOILER ALARMS AND TRIPS
AUXILIARY BOILER ALARMS AND TRIPSS NO DESCRIPTION OF ALARMMeasuring RangeSET POINTAlarms/TripsInterval
1Boiler drum high water level -+230mmH2o, 18.8 maAlarmWeekly
2Boiler drum low water level--160mmH2o, 6.8maAlarmWeekly
3Boiler drum water level too low-210mmH2o, 5.2maTrip and alarm Weekly
4Boiler drum steam pr. high0.2-2.45MPa1.72MPatrip and alarm Monthly
5Drum high steam pressure (High mode)0.2-2.45MPa1.68MPaAlarmMonthly
6Drum Low steam pressure (High mode)0.2-2.45MPa1.1MPaAlarmMonthly
7Boiler Drum low steam pressure 0.2-2.45MPa0.45 MPaAlarmMonthly
8Fuel oil pressure low0.2-2.45MPa1.38MPaTrip and alarm Monthly
9Auto stand-by oil pressure low0.2-2.45MPa1.57MPaAlarmMonthly
10Oil temp. high/low20-230 degree140/85 degreeTrip and alarmMonthly
11Low atomizing steam pressure0.1-0.98MPa0.34MPaTrip and alarmMonthly
12Low combustion air pressure-10KPaTrip and alarmMonthly
13Burner wind box temp. high20-250 degree200 degreeTrip and alarmMonthly
14Control air pressure low.1-.98Mpa.39MPaTrip and alarmMonthly
15Flame failTripMonthly
16FD fan over loadTrip and alarmMonthly
17Emergency stopTrip and alarmMonthly
18Smoke density high0-100 %AlarmMonthly
19Power failTripMonthly
WASTE OIL INCINERATORS NoDescription of AlarmSet PointF.O SHUT OFF /INCINERATOR STOPAlarm &IndicationInterval
1Burner fan abnormal-YESYESMONTHLY
2Cooling fan abnormal-YESYESMONTHLY
3Furnace temp. high1100 degreeYESYESMONTHLY
4Waste oil pressure lowYESYESMONTHLY
5Furnace pressure high-0.1KPaYESYESMONTHLY
6Waste oil pressure low0.1 MPaYESYESMONTHLY
7Exh. Gas temp. high320 degreeYESYESMONTHLY
8Aux. burner oil pressure low0.5MPaYESYESMONTHLY
9Atomizing air pressure low40KPaYESYESMONTHLY
10BCU abnormal-YESYESMONTHLY
11Control source failure-YES-MONTHLY
12Door lock abnormalYES-MONTHLY
NO1/NO2/NO3 D/G ALARMS AND TRIPS.S NODESCRIPTION OF ALARMSMEASURING RANGE SET POINTALARMS AND TRIPSInterval
1Jacket water temp. high80-90 degree95 degreealarmMonthly
2Jacket water temp. too high 100 degreeTrips and alarmMonthly
3L.O pressure low0.5-0.6 Mpa0.45MPaAlarmMonthly
4L.O pressure too low0.40 MPaTrips and alarmMonthly
5CFW(HT )pressure low0.15-0.40MPa0.13MPaAlarmMonthly
6L.O oil temp. high55-70 degree75 degreeAlarmMonthly
7F.O high pr. pipe leakAlarm at high Monthly
8Sump level lowAlarm at lowMonthly
9Turbo charger L.O pr. Low0.30-0.60MPa0.30MPaAlarmMonthly
10F.O pressure low0.7-0.75MPa0.60MPaAlarmMonthly
11Starting air pressure low0.7-1MPa0.66MPaAlarmMonthly
12Priming L.O pr. Low0.02-0.25MPa.02alarmMonthly
13Control air pressure low0.7-1 MPa0.66MPaAlarmMonthly
14Exh Gas T/C inlet for both group100-620 degree610 degreeAlarmMonthly
15Over speed TripMonthly
NO1/NO2 MAIN AIR COMPRESSORS NODESCRIPTION OF ALARMSSET POINTMEASURING RANGEALARMS AND TRIPSINTERVAL
1L.O PRESSURE LOW0.1 MPaTRIPS AND ALARMSMONTHLY
2DISCHARGE AIR TEMP. HIGH90TRIPS AND ALARMSMONTHLY
M/E ALARMS AND TRIPSS NODESCRIPTION OF ALARMSMEASURING RANGE SET POINTAlarms,Trips/SlowdownINTERVAL
1Over speed103 RPMTrips3 MONTHLY
2Main L.O low pr0.14-0.26MPa0.06Trips3 MONTHLY
3Thrust Pad High Temp55-65 degree85Trips3 MONTHLY
4Main L.O inlet low Pr0.14-0.26MPa0.08Auto slow down3 MONTHLY
5Cool F.w inlet pr. Low0.28-0.41MPa0.22MPaAuto slow down3 MONTHLY
6Cylinder oil non-flowAuto slow down3 MONTHLY
7Piston cooling oil non flowAuto slow down3 MONTHLY
8Piston cooling oil high temp.50-65 degree75 degreeAuto slow down3 MONTHLY
9Scavange space fire90 degreeAuto slow down3 MONTHLY
10Thrust pad high temp.55-65 degree75 degreeAuto slow down3 MONTHLY
11Oil mist high densityAuto slow down3 MONTHLY
12Cool F.W high temp.80-85 degree90 degreeAuto slow down3 MONTHLY
13Exh. Gas temp. high250-375 degree450Auto slow down3 MONTHLY
14Aft S/T bearing temp. high30-45 degree55 degreeAuto slow down3 MONTHLY
15Main brg. Inlet pr. Low0.14-0.26MPa0.12alarm3 MONTHLY
16Piston cool inlet pr low0.14-0.26MPa0.12Alarm3 MONTHLY
17T/C L.O inlet pr low0.18-0.27MPa0.15Alarm3 MONTHLY
18Cool F.w inlet pr. Low0.28-0.41MPa0.26Alarm3 MONTHLY
19Cool S.w inlet pr. Low0.1-0.2Mpa0.17MPaAlarm3 MONTHLY
20F.o Inlet pr. Low0.7-0.8MPa0.65MPaAlarm3 MONTHLY
21Starting air pr. Low1.5-2.94MPa1.5MPaAlarm3 MONTHLY
22Remote control air pr. Low0.69MPa0.55MPaAlarm3 MONTHLY
23Safety control air pr. Low0.69MPA0.55MPaAlarm3 MONTHLY
24L.O inlet temp high55-70 degree55 degreeAlarm3 MONTHLY
25Piston cooling oil Cyl. Outlet temp. high0-150 degree70 degreeAlarm3 MONTHLY
26Thrust pad temp. high0-150 degree70 degreeAlarm3 MONTHLY
27F.O inlet temp. high0-200 degree150 degreeAlarm3 MONTHLY
28Exh gas cylinder outlet deviation high/low-300 - +300
-50 - +50+50 degree
-50 degreeAlarm3 MONTHLY
29Exh gas T/c inlet temp. high0-600 degree510 degreeAlarm3 MONTHLY
30Exh. Gas T/C outlet0-600 degree400 degreealarm3 MONTHLY
31Mist catcher drain level highHigh level alarm3 MONTHLY
PURIFIERS ALARMS/TRIPSS NODESCRIPTION OF ALARMSSET POINTAlarms/TripsINTERVAL
1No1&2 F.O purifier High inlet pressure.0.30 MPaAlarmMonthly
2No1 & 2 F.O purifier back pressure low0.14Alarm and stopMonthly
3No1 & 2 F.O purifier inlet temp. high110 degreeAlarmMonthly
4No1 & 2 L.O purifier High inlet pressure0.30MPaAlarmMonthly
5No1 &2 L.O purifier back pressure low0.09Alarm & stopMonthly
6No1 &2 L.O purifier inlet temp. high95 degreeAlarmMonthly
IG ALARMS AND TRIPSSl noDESCRIPTION OF ALARMSNormal conditionAlarm conditionAlarms/TripsINTERVAL
1O2 % high< 5%> 8%AlarmMonthly
2Scrubber drain level highHigh levelAlarm and stopMonthly
3IG fan abnormal stopAlarm and stopMonthly
4Deck seal low-flow1.4 meter cube/hr0.84mtr cube/hrAlarm Monthly
5Deck seal level lowLow levelAlarm and stopMonthly
6IG main line temp. high< 60 degree> 65 degreeAlarm and stopMonthly
7IG main line pr. High7-8 Kpa14 KpaAlarmMonthly
8IG main line pr. Low 2 Kpa Alarm and COPT tripMonthly
9IG main line pr. Extra Low1kpaAlarm and COPT trip
10Control air pressure low0.6-0.9MPa< 0.4 MPaAlarm and stopMonthly
11Scrubber SW pressure low0.1Mpa0.08MPaAlarm and stopMonthly
12Emergency stopAlarm and stopMonthly
COPT NO1,2&3 ALARMS AND TRIPSSl noDESCRIPTION OF ALARMSRangeSET POINTAlarms/TripsInterval
1Cargo pump turbine over speed trip(electrical)1687-1718 Rpm1710 RpmAlarm and trip1 M
2Cargo pump turbine over speed trip(mechanical)1702-1748 Rpm1740 RpmAlarm and trip1 M
3LO low pressure trip0.05 MpaAlarm and trip1 M
4High back Pressure trip0.1 Mpa0.1 MpaAlarm and trip1 M
5Hand trip deviceAlarm and trip1 M
6Remote trip Device(electric)Alarm and trip1 M
7Emg trip device (Mani fold)1 M
8Emg trip device (p/p room entrance)1 M
9Emg trip device (p/p room)1 M
10Pump casing O.H 75/80 degree75/80 degreeAlarm & trip1 M
11Pump Bearing O.H (Upper)85/90 degree85/90 degreeAlarm & trip1 M
12Pump Bearing O.H (Lower)85/90 degree85/90 degreeAlarm & trip1 M
13B.H S.B.O.H 85/90 degree85/90 degreeAlarm & trip1 M
14Pump over pressure trip1.57 Mpa1.57 MpaAlarm & trip1 M
15LO low pressure 0.06Alarm1 M
16LO high temperature55 degreeAlarm1 M
BALLAST PUMPS ALARM AND TRIPSSl noDESCRIPTION OF ALARMSRangeSET POINTAlarms/TripsInterval
1Pump casing O.H 75/80 degree75/80 degreeAlarm & trip1 M
2Pump Bearing O.H (Upper)85/90 degree85/90 degreeAlarm & trip1 M
3Pump Bearing O.H (Lower)85/90 degree85/90 degreeAlarm & trip1 M
4B.H S.B.O.H 85/90 degree85/90 degreeAlarm & trip1 M
INSPECTION DATE
DESCRIPTION
SIGN