AIR CONDITIONING FOR LARGE MULTISTORY BUILDINGS

PREPARED BYNOOR AZILA BINTI JAMARI

LECTURERCIVIL ENGINEERING DEPARTMENT

Page 2: Air conditioning for large multistory buildings

Most large multistory buildings use highly centralized air conditioning equipment. The roof and basement are the usual choice for these central station systems.

The basement has the advantage of easy utility connections, noise isolation, not being valuable rental area and the fact that structural loads are not a problem.

INTRODUCTION

Page 3: Air conditioning for large multistory buildings

The roof is the ideal location for fresh air intakes and heat rejection to the atmosphere.

Cooling tower are noisy, produce very hot and humid exhaust air, so the best location for cooling rower is placed on the roof.

SECTION OF A TYPICAL MULTISTORY BUILDING WITH A ROOFTOP CENTRAL STATION MECHANICAL SYSTEM

Page 4: Air conditioning for large multistory buildings

In most buildings, the mechanical equipment is shown to be on the roof. This section shows an all-air system served by a single central air handling unit on the roof.

To avoid the large vertical ducts, separate air handling units can be placed on each floor and only water circulates vertically. This saves much energy because moving air great distances requires much power.

MECHANICAL EQUIPMENT IS STILL ON THE ROOF, EACH FLOOR HAS A SEPARATE AHU

Page 5: Air conditioning for large multistory buildings

The advantage of all-air system is complete control over air quality is possible. The disadvantage is that all-air systems are very bulky and a significant part of the building volume must be devoted to them.

There are 5 system in all-air system categories. i. Central Plants ii. Variable Air Volume (V.A.V) iii. Terminal Reheat System iv. Multizone System v. Double Duct System

ALL-AIR SYSTEM

Page 6: Air conditioning for large multistory buildings

The central air conditioning system has the limitation of the same air quality being delivered throughout the building.

If the structure is zoned or divided and compartmented into several different functions such as offices, workshops, canteen.

The temperature of each element can be controlled with zoned thermostats.

The fan precedes the chiller and reheater coils and blow air through the air-handling unit.

Several ducts radiate from the unit to designated zones within the building.

CENTRAL PLANTS SYSTEM

Page 7: Air conditioning for large multistory buildings

CENTRAL PLANTS SYSTEM

Page 8: Air conditioning for large multistory buildings

This is a single duct system that can easily have many zones. A variable air volume control box is located wherever a duct enters a separate zone.

A thermostat in each zone controls the air flow by operating a damper in the V.A.V control box. More cooling is required, more cool air is allowed to enter the zone.

ii. VARIABLE AIR VOLUME SYSTEMS

Page 9: Air conditioning for large multistory buildings

Floor plan of a VAV system.

VAV system.

VAV control box.

Page 10: Air conditioning for large multistory buildings

At the first the terminal reheat system looks just like the V.A.V system but in fact it is very different.

This system has terminal reheat boxes in which electric strip heaters or hot water coils reheat air previously cooled.

All others zones will reheat the cold air to the desired temperature.

iii. TERMINAL REHEAT SYSTEM

Terminal reheat system.

Page 11: Air conditioning for large multistory buildings

In this system, every zone receives air at the required temperature through a separate duct.

These ducts are supplied by a special multizone air handling unit that custom mixes hot and cold air for each zone.

This is accomplished by motorized dampers located in the air handling unit but controlled by thermostats in each zone. Depending on the temperature, the ratio of hot and cold air varies but the total amount of air is constant.

iv. MULTIZONE SYSTEM

Page 12: Air conditioning for large multistory buildings

The multizone unit is supplied with hot water, chilled water and a small amount of fresh air.

Each multizone unit can handle about 8 zones.

Because moderate air temperatures are created by mixing hot and cold air, this system also wasteful of energy.

Disadvantage this system are costs relatively high while the thermal control is relatively poor.

Page 13: Air conditioning for large multistory buildings

Like the multizone system, the double duct system mixes hot and cold air to achieve the required air temperature.

Instead of mixing the air at a central air handling unit, mixing boxes are dispersed throughout the building.

The double duct system creates a high level of thermal comfort and allows for great zoning flexibility, it is very expensive, requires much building space and its wasteful of energy.

v. DOUBLE DUCT SYSTEM

Double duct system.

Page 14: Air conditioning for large multistory buildings

To reduce the size of the ducts, a high-velocity version of this system

High-velocity air systems (6000 feet/minute) consume more fan power than normal velocity systems(2000 feet/minute).

Because of these problem and because V.A.V system are a good alternative, dual duct systems are not used much anymore.

Page 15: Air conditioning for large multistory buildings

These system supply both airand water to each zone of a building.

It greatly decreases the size of the equipment because of the immense heart-carrying capacity of water as opposed to air.

Air is supplied mainly because of the need for ventilation.

There are 2 system in air-water system categories. i. Induction System ii. Fan- coil with supplementary airBut in this topic is cover induction system only

AIR-WATER SYSTEM

Page 16: Air conditioning for large multistory buildings

A small quantity of high-velocity air is supplied to each zone to supply the required fresh air and to induce room air to circulate.

Most induction terminal units are found under windows where they can effectively neutralize the heat gain.

As the high-velocity air shoots into the room it induces a large amount of room air to circulates.

This combination of room air and fresh air, then passes over heating or cooling coils.

INDUCTION SYSTEM

Page 17: Air conditioning for large multistory buildings

Local thermostats regulate the temperature by controlling the flow of either hot or cold water through the coils.

It takes a lot of fan power to circulate air at high velocity throughout a building.

Because of the high cost of energy and the expense of high-velocity ductwork, the use of induction systems is limited.

Induction system.

Page 18: Air conditioning for large multistory buildings

Induction system.

Induction unit with cooling or heating coils

Page 19: Air conditioning for large multistory buildings

These systems supply no air. There are 2 system in all-water system

categories. i. Fan-coil System ii. Water Loop Heat Pump SystemBut in this topic is cover Fan-coil system only.

ALL-WATER SYSTEM

Page 20: Air conditioning for large multistory buildings

The fan-coil unit basically consists of a fan and a coil within water circulates.

The units are in the form of cabinets for placement under windows.

The fan blows room air across coils containing either hot or cold water.

Thermostatically controlled valves regulate the flow of water through the coils.

A 4 pipe system, which is has 2 pipes for hot water supply and return and another 2 pipes for cold water supply and return.

FAN-COIL SYSTEM

Page 21: Air conditioning for large multistory buildings

Condensation on the cooling coils must be collected in a pan and drained away.

When the fan-coil unit is on an outside wall, it is possible to have an outdoor air intake connected to the unit.

A three-speed fan switch allows occupants of the zone to have some control over the temperature.

Fan-coil units are most appropriate for air conditioning buildings with small zones (eg. Apartments, condominiums, motels, hotels, hospitals and schools).

Fan coil units also located above windows, in small closets or in the dropped ceiling above a bathroom.

Page 22: Air conditioning for large multistory buildings

Fan Coil System.

Schematic diagram of an under window FCU ( 4 pipe system).

Page 23: Air conditioning for large multistory buildings

FCU placed in a small closet.

FCU placed above a dropped ceiling.