aermec awhp white paper final 8-30-13

Upload: dhayanandh-murugan

Post on 03-Jun-2018

229 views

Category:

Documents


2 download

TRANSCRIPT

  • 8/11/2019 Aermec AWHP White Paper Final 8-30-13

    1/10

    1

    Design considerations for commercialair-to-water heat pumps

    Advantages of using air to water heat pumps

    Using air to water heat pumps (AWHPs) as the primary source of heating and cooling commercialbuildings gives architects and engineers a long-term solution to designing sustainable buildings.

    The heat pumps provide all the benefits of a hydronic system with the performance and energyefficiency of variable refrigerant flow (VRF) designs. Their many features include:

    capability AWHPs can provide energy for a buildings cooling, heating, and domestic hot water

    demands at outdoor temperatures from 5F to 105F. AWHPs can produce watertemperatures similar to condensing boilers running at their peak efficiencies,

    depending on outside air temperatures.

    efficiency Energy recovery options, including true simultaneous heating and cooling, result in

    energy use comparable to VRF systems:

    Average annual energy savings of over 40% compared to a typical boiler-plus-chillerapplication.

    Installation costs are generally lower (savings are site specific).

    flexibility Hydronic systems powered by heat pumps allow long-term heating and cooling

    flexibility as tenant requirements and building use change. AWHPs can be the energysource for:

    water-source heat pumps

    fan coils radiant heating and cooling

    perimeter baseboard heating central system air handlers

    make-up air handlers

    VAV units a combination of systems

    In addition, AWHP equipment can be sized to maximize seasonal efficiency by using atrim boiler for the few hours a year of the coldest-design-or-below temperatures. VRF

    systems must be sized to provide all of the heat at design conditions, meaning that theequipment is oversized for the vast majority of the heating season.

    2013 Western Environmental Services Corporation. All rights reserved.

    Permission granted to reproduce for personal and educational use only.

  • 8/11/2019 Aermec AWHP White Paper Final 8-30-13

    2/10

    2

    adaptability AWHP technology adapts to existing water pipe systems. Configurations areavailable that provide both domestic hot water and heating or cooling for two-pipe fan

    coil systems; provide simultaneous heating and cooling for four-pipe fan coil systems;or maintain loop temperature for water-source heat pumps systems. And as technology

    changes or refrigerant requirements change, the buildings energy system can be easily

    retrofitted to adapt to new technologies.

    safety Hydronic systems minimize refrigerant volume and components both inside and

    outside the building envelope, reducing costs and risk of leaks and eliminating the needfor leak detection systems in occupied spaces.

    AWHP un it with factory-installed circulation pumps and buffer tank

    AWHP basics

    Two white papers on the Wescor website provide introductions to how AWHPs work, theirefficiencies, and financial comparisons:

    Heat Pump Water Heater Basics

    Heat Pump Water Heaters: Design Details

    This white paper goes beyond the basics of heating domestic hot water and explains how to useAWHP technology to heat and cool buildings in a whole-building design.

  • 8/11/2019 Aermec AWHP White Paper Final 8-30-13

    3/10

    3

    Basic operating designs

    The following two sections provide schematics for designing basic two- and four-pipe AWHPsystems. For more involved system designs, call your local Wescor representative.

    Were here to helpcall your Wescor representative for assistance when designing AWHPprojects.

    Two-pipe systems

    In a typical two-pipe fan coilsystem, the entire building is either in heating or cooling mode, and

    seasonal change-over is usually required. (Aermec systems do not require seasonal changeovers,because the system easily changes between heating and cooling.) In two-pipe systems, the heat

    pump has two separate operations, one for each mode.

    In cooling mode, the heat pump can provide all the chilled water while also capturing energy from

    the chilled water loop to provide energy to the domestic hot water circuit if there is a demand.

    In heating mode, the heat pump can provide energy to the buildings hot water loop while also

    providing energy to the domestic hot water loop.

    If a building is using water source heat pumps for heating and cooling individual zones, the AWHPcan be used to maintain the loop temperature throughout the year.

    Basic internal AWHP operating production for two-pipe system + DHW

    Cold water production on ly to system

    Bldg cooling return

    Description Functioning

    1Heat exchangersystem side

    Evaporatorcold water produc

    2Heat exchangerDHW side

    not running

    3Heat exchangersource side

    Condenserheat exchange wi

    Bldg cooling supply

    33

    2

    1

    Compressor

    Compressor

  • 8/11/2019 Aermec AWHP White Paper Final 8-30-13

    4/10

    4

    Hot water production only to system

    Product ion hot water only to DHW

    Description Functioning

    1Heat exchangersystem side

    Condenserhot water produc

    2Heat exchangerDHW side

    not running

    3Heat exchangersource side

    Evaporatorheat exchange w

    Bldg heating return

    Bldg heating supply

    2

    1

    3 3

    2

    1

    Description Functioning

    1Heat exchangersystem side

    not running

    2Heat exchangerDHW side

    CondenserDHW production

    3Heat exchangersource side

    Evaporatorheat exchange w

    DHW supply

    DHW return

    3 3

  • 8/11/2019 Aermec AWHP White Paper Final 8-30-13

    5/10

    5

    Product ion co ld water to system and hot water to DHW

    Product ion hot water to system and hot water to DHW

    3

    3

    2

    1

    DHW supply

    DHW return

    Bldg cooling return

    Bldg cooling supply

    Description Functioning

    1Heat exchangersystem side

    Evaporatorcold water produc

    2Heat exchangerDHW side

    CondenserDHW production

    3Heat exchangersource side

    not running

    3

    3

    2

    1

    DHW supply

    DHW return

    Bldg heat return

    Bldg heat supply

    Description Functioning

    1Heat exchangersystem side

    Condenserhot water produc

    2Heat exchangerDHW side

    CondenserDHW production

    3Heat exchangersource side

    Evaporatorheat exchange w

  • 8/11/2019 Aermec AWHP White Paper Final 8-30-13

    6/10

    6

    Four-pipe systems

    Four-pipe systems can handle simultaneous and independent demands for hot and cold water, andchangeover is not required. In this configuration, the advanced microprocessor control logic

    operates the unit in one of the following modes.

    Cooling only

    The controller activates the cold water circuit, and the heat pump acts as a traditional chillerwith energy taken from the cold water loop and sent to the outside air through the finned coils.

    With dual compressors on this circuit, the unit can operate efficiently at part-load conditions.If there is a demand for domestic hot water, the energy taken from the cold water loop can be

    transferred to the domestic water loop.

    Heating only

    The controller activates the hot water circuit, and the heat pumps evaporator coil takes energy

    from the outside air and uses the condensers heat exchanger to heat the water in the hot waterloop. This is different from the usual approach of a reverse cycle heat pump, because the hot

    water is produced in a different heat exchanger than the one used to produce cold water. Thisseparates the two hot-cold sections required for four-pipe systems.

    Simultaneous heating and cooling

    The unit operates as a water-to-water heat pump, moving energy from the cold-water circuit to

    the hot-water circuit. The on-board microprocessor controller controls the evaporator andcondenser operation of each circuit and automatically changes from one configuration to the

    other depending on the buildings demand. Because it uses separate circuits for the hot-waterand cold-water loops, the unit can provide partial to full cooling while at the same timeproviding partial to full heating. Having multiple circuits and compressors ensures maximum

    efficiency while in part-load or full-load conditions.

    Domestic hot water while heating the building system loop

    A water to water heat exchanger can be added so excess energy can be transferred to thebuildings domestic water system from the building hot water system loop.

  • 8/11/2019 Aermec AWHP White Paper Final 8-30-13

    7/10

    7

    Basic operating layout for four-pipe system

    Cold water production on ly to system

    Hot water production only to system

    33

    2

    1

    Description Function

    1Heat exchangercooling side

    Evaporacold watproducti

    2Heat exchangerheating side

    not runn

    3Heat exchangersource side

    Condensheat excwith air

    Bldg cooling return

    Bldg cooling supply

    Description Function

    1Heat exchangercooling side

    not runn

    2Heat exchangerheating side

    Condenshot wateproducti

    3 Heat exchangersource side

    Evapora

    heat excwith air

    Bldg heat supply

    Bldg heat return

    3 3

    2

    1

  • 8/11/2019 Aermec AWHP White Paper Final 8-30-13

    8/10

    8

    Simultaneous hot and cold water production to system

    Description Functioning

    1Heat exchangercooling side

    Evaporatorcold water productio

    2Heat exchangerheating side

    Condenserhot water production

    3Heat exchangersource side

    not running

    Bldg heat supply

    Bldg heat return

    Bldg cooling return

    Bldg cooling supply

    3

    3

    2

    1

  • 8/11/2019 Aermec AWHP White Paper Final 8-30-13

    9/10

    9

    Why we chose Aermecs AWHPs

    We are impressed with Aermec AWHPs and think you will be, too.

    experience Aermec, a European company with over 1500 employees, is one of the largest HVAC

    manufacturers in the world. They have over 50 years experience building HVACsystems and over 20 years building AWHPs.

    quality Aermec uses axial fans, scroll compressors, and plate heat exchangers. Each unit has atleast two compressors and refrigerant circuits for redundancy and good performance

    under part-load conditions.

    Aermecs 46-person Research and Develop Department has six test chambers sized totest units up to 250 tons at temperatures ranging from 5F to 130F and RH from 20%

    to 95%.

    Aermec test chamber

    certification All Aermec systems are tested and rated in-house to Eurovent standards (includingoperation during defrost conditions,included in their COP calculations) and are

    certified by AHRI in the US. When an energy analysis shows a units output at designconditions, be assured that these are the equipments actual operating parameters.

  • 8/11/2019 Aermec AWHP White Paper Final 8-30-13

    10/10

    10

    innovation Aermec units can provide simultaneous heating and cooling under full or part load

    conditions and can provide free cooling when in simultaneous operation. On-boardmicroprocessor controllers provide autonomous operation with full control and

    minimum management required by the building management system. Hydronic

    accessories (such as pumps, buffer tanks, or a second hydronic circuit fed by adesuperheater) can be factory installed within the same footprint.

    selection Aermec manufacturers a full range of AWHPs, water-to-water heat pumps, andchillers. Heat pumps for commercial applications (buildings that have independent

    requirements for heating and cooling) range from 12 to 262 tons. Larger tonnage unitswith screw compressors are also available.

    Aermec robotic assembly