advancements in online partial discharge monitoring and...
TRANSCRIPT
![Page 1: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/1.jpg)
Advancements in online partial
discharge monitoring and assessment
of MV through EHV Substation assets
![Page 2: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/2.jpg)
Abstract:For decades it has been recognized that partial discharge assessment is an excellent method for determining asset health.
• On line non-invasive techniques for monitoring and surveying have been proven to provide the necessary level of detail for condition assessment without impacting system operation.
• Techniques exist now to test assets from 3KV to 500KV and beyond. Metal clad switchgear and busswork, GIS switchgear and busses, air insulated assets (insulators, arrestors, bushings, etc.), as well as paper insulated and extruded cables can all be tested on-line without an outage.
This presentation will give a brief overview of the causes and effects of partial discharge and then examine the various technologies available for finding it on-line.
Examples of field success stories will also be given.
![Page 3: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/3.jpg)
Topics for Today
Who is EA Technology
Causes and effects of Partial Discharge
Sensing Technologies
Transient Earth Voltage
Ultrasonic Reception
Radio Frequency Current Transformers
Ultra High Frequency Radio Detection
Recent Advancements in Detection
![Page 4: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/4.jpg)
• Provide products and services for measuring, monitoring and managing physical assets for electric utilities
• Consulting on a wide range of power system issues
• Produce inspection and maintenance standards and procedures
• Forensic failure investigation services
• Major patron of the Institute of Asset Management
• Instrumental in PAS 55 and ISO 55000 development
• EATLLC – US Subsidiary in NJ
![Page 5: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/5.jpg)
Partial Discharge - A flashover of part of the insulation system due to a localized electric field greater than the dielectric withstand capability of that part where the overall insulation system remains capable of withstanding the applied electrical field.
Void
GroundConductor
V withstand of C2 < applied field V withstand of C1&C3 > applied field
What is Partial Discharge (PD)?
5
One effect of this flashover is a high frequency current pulse that travels through the capacitance of the insulation (C1 & C3)
HF CurrentPulse
C1 C2 C3
![Page 6: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/6.jpg)
Products of Partial Discharge
6
Partial discharge breakdown of insulation produces:
Light, Heat, Smell, Sound, Electromagnetic Waves, and an
HF Electric Current
+
Water
Nitric
AcidElectric
TEV
![Page 7: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/7.jpg)
Partial Discharge (PD)
Where can it occur
- Any insulation (Air, Oil, Solid, GIS)
- Wide range of voltages (>4KV)
- Any age equipment
- Types of equipment
- Metal clad circuit breakers / switchboards
- Bus ducts (Segregated phase, ISO Phase, GIS)
- Cables
- Overheard insulators
![Page 8: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/8.jpg)
Types of PD
![Page 9: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/9.jpg)
Practical Non-Intrusive PD
Detection Methods
Internal discharge activity
• Transient Earth Voltage (TEV) Detection
• RFCT Detection of Current Pulse
• UHF Detection of EMI
Surface discharge activity
• Ultrasonic Detection
• TEV Detection - high amplitude surface discharge
• RFCT Detection of Current Pulse
• UHF Detection of EMI
![Page 10: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/10.jpg)
Internal Partial Discharge Effect 1
(current pulse - TEV)
10
HV BUSBAR
PARTIAL DISCHARGEJOINT/GASKET
HV BUSBAR
HIGH FREQUENCY PULSE TO METALWORK VIA
CAPACITANCE OF INSULATOR
TEV RESULTS DUE TO IMPEDANCE OF GROUNDING
At HF, PD currents are constrained to
Flow in a thin layer on the surface of
Conductor.
Skin depth in mild steel at 100MHz
0.5um
UltraTEV
PULSE TRAVELS VIA SKIN EFFECT
![Page 11: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/11.jpg)
HV BUSBAR
EM WAVEEM WAVE
PARTIAL DISCHARGEJOINT/GASKET
HV BUSBAR
Internal Partial Discharge Effect 2
(EM Wave)
11
PULSE TRAVELS VIA SKIN EFFECT
TEV RESULTS DUE TO IMPEDANCE OF GROUNDING
This effect is usually less than the current pulse unless the PD is
phase to phase!
UltraTEV
![Page 12: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/12.jpg)
TEV from PD
EMI from PD
Corona
PD Hawk
PD Spectrum (Simplified)
• Partial Discharge
causes a
broadband EMI
emission
(approx. 3-3000
MHz)
• Corona causes a
smaller band EMI
emission (30-400
MHz)
• TEV caused by
capacitive currents
are typically in the
3-80 MHz band
Partial Discharge Frequency Spectrum
![Page 13: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/13.jpg)
13
Probable Internal
No Internal Significant
Discharging
PossibleSurface Discharging
ProbableBackgroundInterference
Probable Floating Metal
Bad Conn
Partial Discharge TEV Interpretation
![Page 14: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/14.jpg)
Partial Discharge damage found
through TEV sensing
Channel cutthrough resin by discharge
![Page 15: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/15.jpg)
Surface Discharge Detection
Through Ultrasonic Sensing
• In severe cases, audible sound may be present
• Less severe deterioration may be detected
using ultrasonic detecting instruments
• Sound spectrum in the 40kHz range
• Characteristic sound more important than
absolute level
![Page 16: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/16.jpg)
Cracks / contaminated
surface
Carbonized tracking
Discharge noise can be picked up
with Ultrasonic detector via gap
Measurement relies on an
air path from source to
sensor
Types of access
Cable box vents
CB Bushings / HV spouts
Gaps around panel joints
Bolt holes
Contact probe
Designed to work though cabinet
metalwork, no direct air path needed
Surface Discharge
![Page 17: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/17.jpg)
Environmental Factors
• Moisture in air will play a significant role in whether discharge is active
• When monitoring ultrasonically the environmental conditions (%RH and Temperature) should also be monitored
0
10
20
30
40
50
60
70
80
90
100
29/03/2005
00:00
03/04/2005
00:00
08/04/2005
00:00
13/04/2005
00:00
18/04/2005
00:00
23/04/2005
00:00
28/04/2005
00:00
03/05/2005
00:00
08/05/2005
00:00
13/05/2005
00:00
Date
%R
H, T
emp
erat
ure
0
1
2
3
4
5
6
7
8
9
10
Lev
el o
f U
ltra
son
ic A
ctiv
ity
°C %RH Ultrasonic
![Page 18: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/18.jpg)
Surface Discharge Activity Detected
by Ultrasonic Sensing
![Page 19: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/19.jpg)
Tracking due to PD on a panelboard
![Page 20: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/20.jpg)
PD Current Pulse Detection using an
RFCTHow Does It Work?
Earth Ground
Phase Reference
Void (PD Site)
Reflected PD Current Pulse
Initial Pulse Reflected Pulse
Distance from RFCT to PD site can be derived from knowing the time between the pulses and the length of the cable
Far end of cable
MeasuringDevice
![Page 21: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/21.jpg)
Cable Termination Screen Failure
Found through RFCT sensing
![Page 22: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/22.jpg)
Utility Field Results of RFCT Sensing
They classified their results into Green, Amber, & Red
• Green is a test where no partial discharge was found.
• Amber is a test result where some levels of PD were detected.
• Red means that PD levels indicating significant degradation were detected.
UK utility Electricity North West Limited (ENWL) shared the results of a two year evaluation of RFCT based Cable PD detection that involved the online condition assessment of 191 33KV MV cables on their network over a two year period.
Over the course of two years, they experienced the following failure rates:• Red - 41.2%• Amber - 21.7%• Green – 1.9%
![Page 23: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/23.jpg)
Internal Partial Discharge Overhead
insulator (EM Wave)
23
EM Wave
PD Hawk
![Page 24: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/24.jpg)
Example of Internal PD Found in Outdoor Switchyard
• Internal Partial Discharge in a 12KV Medium Voltage Cable
Phase Resolved Plot Showing Internal Partial Discharge
12KV Medium Voltage Cable
1800
![Page 25: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/25.jpg)
Example of Surface PD Found in Outdoor Switchyard
• Surface Partial Discharge in a 66KV Circuit Breaker
66KV Circuit Breaker
1800
Phase Resolved Plot Showing Surface Partial Discharge
![Page 26: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/26.jpg)
Re-cap of Non-Intrusive PD Detection Methods
• Metal Clad Switchgear / Busses / Air Cooled Transformers
• Internal discharge – Transient Earth Voltage
• Surface Discharge – Ultrasonic
• Medium, High, and Extra High Voltage Cables
• Internal discharge – RFCT Detection
• Surface Discharge (Terminations) - Ultrasonic
• Air Insulated Switchgear
• Internal discharge – UHF Detection of EMI
• Surface Discharge – Ultrasonic & UHF Detection
• GIS switchgear
• Internal discharge – UHF Detection
![Page 27: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/27.jpg)
Recent Advancements in Online - PD Detection
• Phase resolved plots for TEV, Ultrasonic, RFCT, UHF
• Helps discern desired signal from noise
• Waveform plots for TEV, Ultrasonic, RFCT, UHF
• Helps discern desired signal from noise
![Page 28: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/28.jpg)
• Automatic PD Detection Algorithms
• Assist user, reduce mis-readings
• NFC (Near Field Communications) Tags
• Eliminate data entry and reduce possible mistakes
Recent Advancements in Online - PD Detection
![Page 29: Advancements in online partial discharge monitoring and ...eatechnology.com/americas/wp-content/uploads/sites/... · • On line non-invasive techniques for monitoring and surveying](https://reader033.vdocuments.site/reader033/viewer/2022060723/608369b3d28a3a1dfc2b8ee1/html5/thumbnails/29.jpg)
• Full time non-invasive monitoring
• Monitor cables, metal clad switchgear, GIS Switchgear
• On-board storage and report generation with WiFi / USB / HTML
• Promotes standardized test reports and sharing of data
Recent Advancements in Online - PD Detection