Page 1: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

LVGP By Micron Power Delivery

Advanced transformers built for the

industrial environment

Catalog:

LVGP-14A

Supercedes: LVGP-14

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 2: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

Table of Contents Low Voltage General Purpose Transformers Page

General information 2

Selection Guide Single Phase 4

Three Phase 5

Single Phase Part Numbers and Wiring Diagrams 6-11

Three Phase Part Numbers and Wiring Diagrams 12-19

Buck-Boost Applications Selection Guide 19-20

Buck-Boost and Low Output Voltage Transformer Part Numbers 20-21

Single Phase Adjustments 21-23 Three Phase Adjustments 24-28 Unusual Adjustments 29-30

What is a LVGP Transformer 32-34

OTHER MICRON PRODUCTS ImperviTRAN™/GlobalTRAN™ 600 Volt Class Control Transformers From 25Va through 5Kva

DINergy™ Industrial DIN-Mount Switching Power Supplies Single-Phase and Three Phase from 18 watts thought 960 watts

Reactors, Medium Voltage and Custom Coils

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 3: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

2 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

Low Voltage General Purpose Transformers

UL Listed, CSA Certified Single Phase Type 1-E Encapsulated

UL Listed Three Phase Type 3-E Encapsulated

UL listed Single Phase Type 1-V Ventilated

UL Listed Three Phase Type 3-V Ventilated

Type 1-E general purpose transformers are single phase, resin encapsulated designs suitable for indoor or outdoor applications. It's totally enclosed, non-ventilated enclosure make it ideally suited for use in areas that contain dust, moisture, or corrosive fumes. Available in ratings through 25 KVA type 1-E transformers can be mounted in any position for indoor installations and in upright positions only for outdoor installations.

Type 3-E resin encapsulated, 3-phase transformers are available in ratings of 3-75 KVA. Its totally enclosed non-ventilated enclosure makes the 3-E ideally suited for outdoor as well as indoor locations. Type 3-E transformers utilize the 185°C insulation system with 115°C rise. 3-E transformers 3-15 KVA are T-T connected.

1-V general purpose transformers are single phase ventilated units designed primarily for indoor locations (also for outdoor , 600 volt class with the addition of weathershields). The 1-V utilizes a 220°C insulation system with 150°C rise and is available in ratings of 15-167 KVA.

The 3-phase 3-V ventilated dry-type is available in ratings of 15-750 KVA. Its 220°C insulation system (150°C rise) is self-extinguishing. 3-V enclosures are designed for indoor locations (or outdoor, 600 volt class with addition of weathershields).

Mounting Units installed outdoors must be mounted in upright position. Efficiency The Micron series of ventilated 600 volt class general purpose distribution transformers meet NEMA TP-1 efficiency

requirements and federal energy efficiency laws as mandated by the Energy Policy Act of 2005. Distribution

transformers installed in the United States are required to meet these energy efficiency requirements.

Winding Terminations

Primary and secondary windings are terminated in the wiring compartment. Encapsulated units have copper leads or

stabs brought out for connections. Micron recommends external cables be rated 90°C (sized at 75°C ampacity) for

encapsulated designs.

Series-Multiple Windings

Series-multiple windings consist of 2 similar coils in each winding which can be connected in series or parallel

(multiple). Transformers with series-multiple windings are designated with an "X" or"/" between the voltage ratings.

such as primary voltage of "120/240" or "240 X 480". If the series-multiple winding is designated by an "X" the winding

can be connected only for a series or parallel. With the"/" designation, a mid-point also becomes available in addition

to the series or parallel connection. As an example, a 120 X 240 winding can be connected for either 120 (parallel) or

240 (series), but a 120/240 winding can be connected for 120 (parallel), or 240 (series), or 240 with a 120 mid-point.

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 4: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

3 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

General Information Industry Standards All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI and IEEE standards. All 600 volt class transformers are UL listed unless otherwise noted.

Seismic Qualified The Micron family of dry-type distribution transformers is seismically tested, seismically qualified, and exceeds requirements of the Uniform Building Code (UBC) and California Code Title 24.

Frequency Micron standard dry-type distribution transformers are designed for 60 Hz operation. Transformers required for other frequencies must be specifically designed.

Overload Capability Short term overload is designed into transformers as required by ANSI. Basically, dry-type distribution transformers will deliver 200% nameplate load for one-half hour; 150% load for one-hour; and 125% load for four-hours without being damaged provided that a constant 50% load precedes and follows the overload. See ANSI C57 .96-01.250 for additional limitations. Continuous overload capacity is not deliberately designed into a transformer because the design objective is to be within the allowed winding temperature rise with nameplate loading.

Insulation System & Temperature Rise Industry standards classify insulation systems and rise as shown below:

Insulation System Classification

Ambient

+ Winding

Rise

+ Hot Spot

= Temp. Class

The design life of transformers having different insulation systems is the same – the lower temperature systems are designed for the same life as the higher temperature systems.

40°C 55°C 10°C 105°C

40°C 80°C 30°C 150°C

40°C 115°C 30°C 185°C

Sound Levels

KVA NEMA Average₁ Sound Level in dB

All Micron 600 volt class dry-type distribution transformers are designed to meet NEMA ST-20 levels as listed.

0-9 40

10-50 45 51-150 50

151-300 55 301-500 60

₁. Applies to general purpose transformers only.

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 5: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

4 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

Selection Guide for Single Phase Transformers

Single Phase AC Motors₁ 1. Determine the primary (source) voltage

-the voltage presently available.

2. Determine the secondary (load) voltage

-the voltage needed at the load. 3. Determine the Kva load: If the load is defined in Kva, a transformer

can be selected from the tabulated data.

If the load rating is given in amperes,

determine the load Kva from the Full Load

Current chart. To determine Kva when volts

and amperes are known, use the formula:

Kva = Volts x Amperes

1000 If the load is an AC motor, determine the

minimum transformer Kva from the chart at the right.

Select a transformer rating equal to or greater than the load Kva.

4. Define tap arrangements needed. 5. Define temperature rise. Using the above procedure, select the transformer from the listings in this catalog.

Full Load Current in Amperes₁ – Single Phase Circuits Kva₂ 120 Volts 208 Volts 220 Volts 240 Volts 277 Volts 480 Volts 600 Volts 2400 Volts 4160 Volts

0.250 2 1.2 1.1 1 0.9 0.5 0.4 0.10 0.06

0.500 4.2 2.4 2.3 2.1 1.8 1 0.8 0.21 0.12

0.750 6.3 3.6 3.4 3.1 2.7 1.6 1.3 0.31 0.18

1 8.3 4.8 4.5 4.2 3.6 2.1 1.7 0.42 0.24

1.5 12.5 7.2 6.8 6.2 5.4 3.1 2.5 0.63 0.36

2 16.7 9.6 9.1 8.3 7.2 4.2 3.3 0.83 0.48

3 25 14.4 13.6 12.5 10.8 6.2 5 1.2 0.72

5 41 24 22.7 20.8 18 10.4 8.3 2.1 1.2

7.5 62 36 34 31 27 15.6 12.5 3.1 1.8

10 83 48 45 41 36 20.8 16.7 4.2 2.4

15 125 72 68 62 54 31 25 6.2 3.6

25 208 120 114 104 90 52 41 10.4 6

37.5 312 180 170 156 135 78 62 15.6 9

50 416 240 227 208 180 104 83 20.8 12

75 625 360 341 312 270 156 125 31.3 18

100 833 480 455 416 361 208 166 41.7 24

167 1391 802 759 695 602 347 278 69.6 40.1

₁. When motor service factor is greater than 1, increase Full Load amps proportionally. Example: If service factor is 1.15,

increase above amp values by 15%.

₂. If motors are started more than once per hour, increase the minimum transformer Kva by 20%.

Full Load Amperes

HORSEPOWER 115V 208V 220V 230V MINIMUM KVA₂

1/6 4.4 2.4 2.3 2.2 0.53

1/4 5.8 3.2 3 2.9 0.70

1/3 7.2 4 3.8 3.6 0.87

1/2 9.8 5.4 5.1 4.9 1.18

3/4 13.8 7.6 7.2 6.9 1.66

1 16 8.8 8.4 8 1.92

1-1/2 20 11 10.4 10 2.40

2 24 13.2 12.5 12 2.88

3 34 18.7 17.8 17 4.10

5 56 30.8 29.3 28 6.72

7-1/2 80 44 42 40 9.60

10 100 55 52 50 12.0

EXAMPLE OF TRANSFORMER SELECTION FOR

1.5HP SINGLE-PHASE MOTOR. ALTERNATELY,

MULTIPLY VOLTS (115) x AMPS (20) AND

DIVIDE BY 1,000 = 2.3KVA

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 6: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

5 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

Selection Guide for Three Phase Transformers Three Phase AC Motors₁

1. Determine the primary (source)

voltage – the voltage available.

2. Determine the secondary (load)

voltage – the voltage needed at

the load.

3. Determine the KVA load.

If the load is defined in KVA, a

transformer can be selected

directly from the table.

If the load rating is given in amperes,

determine the load Kva from the Full

load Current chart. To determine Kva

when volts and amperes are known,

use the formula:

Kva= Volts x Amperes x 1.732

1000

If the load is an AC motor, determine

the minimum transformer Kva from

the chart at the right.

Select a transformer rating equal or

greater than the load Kva.

4. Define tap arrangements needed.

5. Define temperature rise.

Using the above procedure, select the transformer from the listings in this catalog.

Full Load Current in Amperes₁ – Three Phase Circuits

₁. When motor service factor is greater than 1, increase Full Load amps proportionally. Example: If service factor is 1.15, increase above amp values by 15%. ₂. If motors are started more than once per hour, increase the minimum transformer Kva by 20%.

Kva₂ 208 Volts

240 Volts

380 Volts

480 Volts

600 Volts

2400 Volts

4160 Volts

3 8.3 7.2 4.6 3.6 2.90 0.72 0.42

6 16.6 14.4 9.1 7.2 5.8 1.4 0.83

9 25 21.6 13.7 10.8 8.6 2.2 1.2

15 41.7 36.1 22.8 18 14.4 3.6 2.1

22.5 62.4 54.1 34.2 27.1 21.6 5.4 3.1

30 83.4 72.3 45.6 36.1 28.9 7.2 4.2

37.5 104 90.3 57 45.2 36.1 9 5.2

45 124 \\\

108 68.4 54.2 43.4 10.8 6.3

50 139 120 76 60.1 48.1 12 6.9

75 208 180 114 90 72 18 10.4

112.5 312 270 171 135 108 27.1 15.6

150 416 360 228 180 144 36.1 20.8

225 624 541 342 270 216 54.2 31.3

300 832 721 456 360 288 72.2 41.6

500 1387 1202 760 601 481 120 69.4

750 2084 1806 1140 903 723 180 104

1000 2779 2408 1519 1204 963 241 139

FULL LOAD AMPS

HORSEPOWER 208V 230V 380V 460V 575V MINIMUM KVA₂

1/2 2.2 2.0 1.2 1.0 0.8 0.9

3/4 3.1 2.8 1.7 1.4 1.1 1.2

1 4.0 3.6 2.2 1.8 1.4 1.5

1-1/2 5.7 5.2 3.1 2.6 2.1 2.1

2 7.5 6.8 4.1 3.4 2.7 2.7

3 10.7 9.6 5.8 4.8 3.9 3.8

5 16.7 15.2 9.2 7.6 6.1 6.3

7-1/2 24 22 14 11 9 9.2

10 31 28 17 14 11 11.2

15 46 42 26 21 17 16.6

20 59 54 33 27 22 21.6

25 75 68 41 34 27 26.6

30 88 80 48 40 32 32.4

40 114 104 63 52 41 43.2

50 143 130 79 65 52 52

60 170 154 93 77 62 64

75 211 192 116 96 77 80

100 273 248 150 124 99 103

125 342 312 189 156 125 130

150 396 360 218 180 144 150

200 528 480 291 240 192 200

EXAMPLE OF TRANSFORMER SELECTION

FOR A 1.5HP THREE-PHASE MOTOR.

ALTERNATELY, MULTIPLY VOLTS (208) x

AMPS (5.7) AND THAT PRODUCT BY 1.732

THEN DIVIDE BY 1,000 = 2.05KVA

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 7: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

6 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

SINGLE PHASE

(1) 1@+10%FCBN at 240V Primary; 2@ +5%FCBN at 480V Primary (2) 2@+5%FCBN at 240V Primary; 4@ +2.5% FCBN at 480V primary (3) 1@ +5%, 2@ -5% at 240V Primary; 2@+2.5%, 4@ -2.5% at 480V Primary

KVA CATALOG NUMBER

TAPS FCAN

TAPS FCBN

DESIGN TYPE

TEMP RISE °C

H W D WEIGHT

LBS FRAME

NUMBER WIRING

DIAGRAM WEATHER

SHIELD

GROUP “A”: PRI: 240 X 480 SEC: 120/240 60HZ

.050 G050A1KF1A01 - - 1E 115 6.50 3.88 3.50 7 52 A

.075 G075A1KF1A01 - - 1E 115 6.50 3.88 3.50 7 54 A

.100 G100A1KF1A01 - - 1E 115 6.50 3.88 3.50 7 54 A

.150 G150A1KF1A01 - - 1E 115 6.50 3.88 3.50 8 55 A

.250 G250A1KF1A02 - - 1E 115 6.50 4.88 3.88 12 57 A

.500 G500A1KF1A02 - - 1E 115 6.50 4.88 4.63 16 57 A

.750 G750A1KF1A02 - - 1E 115 8.38 6.00 5.50 26 58A A

1 G001K1KF1A02 - - 1E 115 10.75 6.10 6.00 31 67 A

1.5 G1X5K1KF1A02 - - 1E 115 10.75 6.10 6.00 42 67 A

2 G002K1KF1A02 - - 1E 115 10.75 6.10 6.00 42 68 A

3 G003K1KF7A03 1 1 1E 115 14.25 7.69 8.00 65 176 B

5 G005K1KF7A03 1 1 1E 115 16.00 10.38 9.88 105 177 B

7.5 G7X5K1KF7A03 1 1 1E 115 16.00 10.38 9.88 123 178 B

10 G010K1KF7A03 1 1 1E 115 19.00 13.38 10.50 193 179 B

15 G015K1KF6A03 2 2 1E 115 19.00 13.38 10.50 216 180 C

25 G025K1KF6A03 2 2 1E 115 23.38 16.38 14.50 375 182 C

15 G015K2KF6A04 3 3 1V 150 27.00 20.00 16.50 246 816 3XA WS11MI

25 G025K2KF6A04 3 3 1V 150 37.53 22.60 19.50 359 818 3XA WS11MI

37.5 G037K2KF6A04 3 3 1V 150 37.53 22.60 19.50 374 818 3XA WS11MI

50 G050K2KF9A04 3 3 1V 150 42.00 24.00 23.38 555 819 3XA WS16MI

75 G075K2KF6A04 3 3 1V 150 42.00 24.00 23.38 740 820 3XA WS16MI

100 G100K2KF6A04 3 3 1V 150 63.00 30.00 34.00 841 821 3XA WS13MI

KVA CATALOG NUMBER

TAPS FCAN

TAPS FCBN

DESIGN TYPE

TEMP RISE °C

H W D WEIGHT

LBS FRAME

NUMBER WIRING

DIAGRAM WEATHER

SHIELD

GROUP “B”: PRI: 190/200/208/220 X 380/400/416/440 SEC: 110/220 50/60HZ

1 G001K1PG1A06 - - 1E 115 10.75 6.10 6.00 42 67 D

1.5 G1X5K1PG1A06 - - 1E 115 14.25 7.69 8.00 65 176 D

2 G002K1PG1A07 - - 1E 115 14.25 7.69 8.00 65 176 D

3 G003K1PG1A07 - - 1E 115 16.00 10.38 9.88 113 177 D

5 G005K1PG1A07 - - 1E 115 16.00 10.38 9.88 140 178 D

7.5 G7X5K1PG1A07 - - 1E 115 19.00 13.38 10.50 193 179 D

10 G010K1PG1A07 - - 1E 115 19.00 13.38 10.50 216 180 D

15 G015K1PG1A07 - - 1E 115 23.38 16.38 14.50 375 182 D

THESE ARE THE AVAILABLE ADJUSTMENT TAPS

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 8: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

7 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

DIAGRAM “A” DIAGRAM “B” DIAGRAM “C”

DIAGRAM “3XA” DIAGRAM “D” WDG VOLTS CONNECT LINE WDG VOLTS CONNECT LINE

PRI

Use both cables provided

H1-H2

504 H5-10

PRI

440 H5-H6 H1-H10

492 H5-9 416 H4-H6 H1-H9

480 H4-9 400 H3-H6 H1-H8

468 H4-8 380 H2-H6 H1-H7

456 H3-8 220 H1H6-H5H10 H1-H10

444 H3-7 208 H1H6-H4H9 H1-H9

432 H2-7 200 H1H6-H3H8 H1-H8

Use 1 cable per connex 190 H1H6-H2H7 H1-H7

252 5 to H2-10 to H1

240 4 to H2-9 to H1

228 3 to H2-8 to H1

216 2 to H2-7 to H1

SEC

240 X2-X3 X1-X4

SEC

220 X2-X3 X1-X4

120 X1X3-X2X4 110 X1X3-X2X4

120/240 X2-X3* X1-X3-X4 110/220 X2-X3* X1-X3-X4 *Three wire operation

WDG VOLTS CONNECT LINE WDG VOLTS CONNECT LINE

WDG VOLTS CONNECT LINE

PRI 480 H2-H3 H1-H4

PRI

480 H3-H4

H1-H6

PRI

480 H4-H5

H1-H8

240 H1H3-H2H4 456 H3-H5 468 H3-H5

SEC

240 X2-X3 X1-X4 432 H2-H5 456 H3-H6

120 X1X3-X2X4 240 H1H4-H3H6 444 H2-H6

120/240 X2-X3* X1-X3-X4 216 H1H5-H2H6

432 H2-H7

SEC

240 X2-X3 X1-X4

240 H1H5-H4H8

120 X1X3-X2X4 228 H1H6-H3H8

120/240 X2-X3* X1-X3-X4 216 H1H7-H2H8

SEC

240 X2-X3 X1-X4

120 X1X3-X2X4

120/240 X2-X3* X1-X3-X4

*Three wire operation

EXAMPLES OF TWO 5% TAPS @ 480V

AND ONE 10% TAP AT 240V

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 9: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

8 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

(4) 2@ -5%

(5) 4@ -2.5%

(6) 2@ +2.5%; 4@ -2.5%

(6) 2@ +2.5%; 4@ -2.5%

(7) 1@ +5%; 2@ -5%

KVA CATALOG NUMBER

TAPS FCAN

TAPS FCBN

DESIGN TYPE

TEMP RISE °C

H W D WEIGHT

LBS FRAME

NUMBER WIRING

DIAGRAM WEATHER

SHIELD

GROUP “D”: PRI: 600 SEC: 120/240 60HZ

1 G001K1RF8A02 - 4 1E 115 8.38 6.00 5.50 31 59 H

1.5 G1X5K1RF8A02 - 4 1E 115 10.75 6.10 6.00 42 67 H

2 G002K1RF8A02 - 4 1E 115 10.75 6.10 6.00 42 68 H

3 G003K1RF8A03 - 4 1E 115 14.25 7.69 8.00 65 176 H

5 G005K1RF8A03 - 4 1E 115 16.00 10.38 9.88 105 177 H

7.5 G7X5K1RF8A03 - 4 1E 115 16.00 10.38 9.88 123 178 H

10 G010K1RF8A03 - 4 1E 115 19.00 13.38 10.50 193 179 H

15 G015K1RF5A03 - 5 1E 115 19.00 13.38 10.50 216 180 I

25 G025K1RF2A03 6 6 1E 115 20.67 13.60 19.00 395 132 J

25 G025K2RF2A04 6 6 1V 150 37.53 22.60 19.50 355 818 V WS11MI

37.5 G037K2RF2A04 6 6 1V 150 37.53 22.60 19.50 375 818 V WS11MI

50 G050K2RF2A04 6 6 1V 150 42.00 24.00 23.38 594 819 V WS16MI

75 G075K2RF2A04 6 6 1V 150 42.00 24.00 23.38 755 820 V WS16MI

100 G100K2RF2A04 6 6 1V 150 63.00 30.00 34.00 865 821 V WS13MI

KVA CATALOG NUMBER

TAPS FCAN

TAPS FCBN

DESIGN TYPE

TEMP RISE °C

H W D WEIGHT

LBS FRAME

NUMBER WIRING

DIAGRAM WEATHER

SHIELD

GROUP “E”: PRI: 208 SEC: 120/240 60HZ

.500 G500A1HF1A02 - - 1E 115 6.50 4.88 4.63 16 57 L

1 G001K1HF1A02 - - 1E 115 10.75 6.10 6.00 31 67 L

1.5 G1X5K1HF1A02 - - 1E 115 10.75 6.10 6.00 42 67 L

2 G002K1HF1A02 - - 1E 115 10.75 6.10 6.00 42 68 L

3 G003K1HF1A03 - - 1E 115 14.25 7.69 8.00 65 176 L

5 G005K1HF1A03 - - 1E 115 16.00 10.38 9.88 113 177 L

7.5 G7X5K1HF1A03 - - 1E 115 16.00 10.38 9.88 123 178 L

10 G010K1HF1A03 - - 1E 115 19.00 13.38 10.50 193 179 L

15 G015K1HF1A03 - - 1E 115 19.00 13.38 10.50 216 180 L

25 G025K1HF1A03 - - 1E 115 22.38 16.38 14.50 395 182 L

25 G025K2HF1A04 6 6 1V 150 37.53 22.60 19.50 346 818 260A WS11MI

37.5 G037K2HF1A04 6 6 1V 150 37.53 22.60 19.50 374 818 260A WS11MI

50 G050K2HF1A04 6 6 1V 150 42.00 24.00 23.38 545 819 260A WS16MI

75 G075K2HF1A04 6 6 1V 150 42.00 24.00 23.38 568 820 260A WS16MI

100 G100K2HF1A04 7 7 1V 150 63.00 30.00 34.00 1178 821 551A WS13MI

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 10: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

9 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

DIAGRAM “H” DIAGRAM “I” DIAGRAM “J” WDG VOLTS CONNECT LINE

WDG VOLTS CONNECT LINE

WDG VOLTS CONNECT LINE

PRI

600

H1-H4

PRI

600

H1-H5

PRI

630

H1-H6

570 H1-H3 585 H1-H4 615 H1-H5

540 H2-H3 570 H1-H3 600 H1-H4

555 H2-H4 585 H2-H5

540 H2-H3 570 H2-H4

555 H3-H5

540 H3-H4

SEC

240 X2-X3 X1-X4

SEC

240 X2-X3 X1-X4

SEC

240 X2-X3 X1-X4

120 X1X3-X2X4 120 X1X3-X2X4 120 X1X3-X2X4

120/240 X2-X3* X1-X3-X4 120/240 X2-X3* X1-X3-X4 120/240 X2-X3* X1-X3-X4 *Three wire operation

DIAGRAM “V” DIAGRAM “L” DIAGRAM “260A”

VOLTS TAP

WDG VOLTS CONNECT LINE

WDG VOLTS CONNECT LINE

630 1 PRI 208 X1-X2

USE BOTH

CABLES PROVIDED

X1-X2

615 2

SEC

240 H2-H3 H1-H4

218 5 TO 10

600 3 120 H1H3-H2H4 213 5 TO 9

585 4 120/240 H1-H3-H4* H1-H3-H4 PRI 208 4 T0 9

570 5 *Three wire operation

203 4 TO 8

555 6 198 3 TO 8

540 7 192 3 TO 7

187 2 TO 7

SEC

240 H2-H3 H1-H4 120 H1H3-H2H4

120/240* H2-H3 H1-H3-H4

* Three wire operation

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 11: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

10 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

DIAGRAM “551A” DIAGRAM “262C”

WDG VOLTS CONNECT LINE

WDG VOLTS CONNECT LINE

PRI

Use 1 cable per

connex

X1-X2

PRI Use both cables provided

H1-H2

218 5 to X2-10 to X1 291 5-10

208 4 to X2-9 to X1 284 5-9

198 3 to X2-8 to X1 277 4-9

187 2 to X2-7 to X1 270 4-8

SEC

240 H2-H3 H1-H4

263 3-8

120 H1H3-H2H4 256 3-7

120/240 H2-H3* H1-H3-

H4 249 2-7

*Three wire operation

SEC

240 X2-X3 X1-X4

120 X1X3-X2X4

120/240 X2-X3* X1-X3-X4 *Three wire operation

(6) 2@ +2.5%; 4@ -2.5%

KVA CATALOG NUMBER

TAPS FCAN

TAPS FCBN

DESIGN TYPE

TEMP RISE °C

H W D WEIGHT

LBS FRAME

NUMBER WIRING

DIAGRAM WEATHER

SHIELD

GROUP “F”: PRI: 277 SEC: 120/240 60HZ

3 G003K1MF1A03 - - 1E 115 14.25 7.69 8.00 55 176 M

5 G005K1MF1A03 - - 1E 115 16.00 10.38 9.88 113 177 M

7.5 G7X5K1MF1A03 - - 1E 115 16.00 10.38 9.88 123 178 M

10 G010K1MF1A03 - - 1E 115 19.00 13.38 10.50 193 179 M

15 G015K1MF1A03 - - 1E 115 19.00 13.38 10.50 180 180 M

25 G025K1MF1A03 - - 1E 115 22.38 16.38 14.50 375 182 M

25 G025K2MF1A04 6 6 1V 150 37.53 22.60 19.50 346 818 262C WS11MI

37.5 G037K2MF1A04 6 6 1V 150 37.53 22.60 19.50 391 818 262C WS11MI

50 G050K2MF1A04 6 6 1V 150 42.00 24.00 23.38 555 819 262C WS16MI

75 G075K2MF1A04 6 6 1V 150 42.00 24.00 23.38 568 820 262C WS16MI

100 G100K2MF1A04 6 6 1V 150 63.00 30.00 34.00 1178 821 262C WS13MI

KVA CATALOG NUMBER

TAPS FCAN

TAPS FCBN

DESIGN TYPE

TEMP RISE °C

H W D WEIGHT

LBS FRAME

NUMBER WIRING

DIAGRAM WEATHER

SHIELD

GROUP “G”: PRI: 120 X 240 SEC: 120/240 60HZ

1 G001K1EF1A02 - - 1E 115 10.75 6.10 6.00 31 67 K

1.5 G1X5K1EF1A02 - - 1E 115 10.75 6.10 6.00 42 67 K

2 G002K1EF1A02 - - 1E 115 10.75 6.10 6.00 42 68 K

3 G003K1EF1A03 - - 1E 115 14.25 7.69 8.00 55 176 K

5 G005K1EF1A03 - - 1E 115 16.00 10.38 9.88 113 177 K

7.5 G7X5K1EF1A03 - - 1E 115 16.00 10.38 9.88 123 178 K

10 G010K1EF1A03 - - 1E 115 19.00 13.38 10.50 193 179 K

15 G015K1EF1A03 - - 1E 115 19.00 13.38 10.50 216 180 K

25 G025K1EF1A03 - - 1E 115 22.38 16.38 14.50 375 182 K

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 12: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

11 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

DIAGRAM “M” DIAGRAM “K”

WDG VOLTS CONNECT LINE

WDG VOLTS CONNECT LINE

PRI 277 H1-H2

PRI 240 H2-H3

H1-H4 120 H1H3-H2H4

SEC

240 X2-X3 X1-X4

SEC

240 X2-X3 X1-X4

120 X1X3-X2X4 120 X1X3-X2X4

120/240 X2-X3* X1-X3-X4

120/240 X2-X3* X1-X3-X4 *Three wire operation *Three wire operation

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 13: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

12 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

THREE PHASE

(6) 2@ +2.5%; 4@ -2.5%

(7) 1@ +5%; 2@ -5%

DIAGRAM “342B” DIAGRAM “351A”

VOLTS TAP VOLTS TAP

218 1 218 1

213 2 208 2

208 3 198 3

203 4 187 4

198 5

192 6

187 7

DIAGRAM “333B”

VOLTS CONNECT

218 3 TO 4

208 3 TO 5

198 2 TO 4

187 2 TO 5

KVA CATALOG NUMBER

TAPS FCAN

TAPS FCBN

DESIGN TYPE

TEMP RISE °C

H W D WEIGHT

LBS FRAME

NUMBER WIRING

DIAGRAM WEATHER

SHIELD

GROUP “H”: PRI: 208∆ SEC: 480Y/277 60HZ

15 G015K5HQ2A04 6 6 3V 150 30.00 23.00 16.50 196 912B 342B WS38MI

30 G030K5HQ2A04 6 6 3V 150 30.00 23.00 16.50 296 912B 342B WS38MI

45 G045K5HQ2A04 6 6 3V 150 30.00 23.00 16.50 385 912B 342B WS38MI

75 G075K5HQ2A04 6 6 3V 150 39.00 29.00 22.00 590 914D 342B WS39MI

112.5 G112K5HQ2A04 7 7 3V 150 46.58 28.00 23.00 784 916A 351A WS19MI

150 G150K5HQ2A04 7 7 3V 150 46.58 28.00 23.00 931 916A 351A WS19MI

225 G225K5HQ4A04 7 7 3V 150 62.20 31.25 30.25 1550 918A 333B WS34MI

300 G300K5HQ4A04 7 7 3V 150 75.00 44.50 35.75 2274 919E 333B WS35MI

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 14: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

13 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

(4) 2@ -5%, (6) 2@ +2.5%; 4@ -2.5%, (7) 1@ +5%; 2@ -5%

DIAGRAM “AA” DIAGRAM “BB”

WDG VOLTS LINE VOLTS CONNECT LINE

PRI

240 H1-H2-H3 252 1-6

H1-H2-H3

228 H4-H5-H6 246 1-5

216 H7-H8-H9 240 1-4

234 2-5

228 2-4

222 3-5

216 3-4

DIAGRAM “280C” DIAGRAM “DD”

VOLTS TAP VOLTS CONNECT

252 1

252 3 TO 4

246 2 240 3 TO 5

240 3 228 2 TO 4

234 4 216 2 TO 5

228 5

222 6

216 7

KVA CATALOG NUMBER

TAPS FCAN

TAPS FCBN

DESIGN TYPE

TEMP RISE °C

H W D WEIGHT

LBS FRAME

NUMBER WIRING

DIAGRAM WEATHER

SHIELD

GROUP “I”: PRI: 240∆ SEC: 208Y/120 60HZ

9 G009K3JH8A03 - 4 3E 115 15.90 16.93 10.00 190 103 AA

15 G015K3JH8A03 - 4 3E 115 17.38 20.00 10.50 275 95 AA

30 G030K3JH2A03 6 6 3E 115 26.58 21.81 11.65 422 243 BB

45 G045K3JH2A03 6 6 3E 115 26.58 24.81 13.53 660 244 BB

15 G015K5JH2A04 6 6 3V 150 30.00 23.00 16.50 206 912B 280C WS38MI

30 G030K5JH2A04 6 6 3V 150 30.00 23.00 16.50 297 912B 280C WS38MI

45 G045K5JH2A04 6 6 3V 150 30.00 23.00 16.50 332 912B 280C WS38MI

75 G075K5JH2A04 6 6 3V 150 39.00 29.00 22.00 562 914D 280C WS39MI

112.5 G112K5JH2A04 6 6 3V 150 46.58 28.00 23.00 760 916A 280C WS19MI

150 G150K5JH2A04 6 6 3V 150 46.58 28.00 23.00 974 916A 280C WS19MI

225 G225K5JH5A04 7 7 3V 150 56.18 31.11 24.25 1460 917 DD WS34MI

300 G300K5JH5A04 7 7 3V 150 62.20 31.25 30.25 1650 918A DD WS34MI

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 15: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

14 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

(4) 2 @-5%; (5) [email protected]%; (6) 2 @+2.5%, [email protected]%; (8) 2@+2.5%, [email protected]%

DIAGRAM “FF” DIAGRAM “GG” DIAGRAM “HH”

WDG VOLTS LINE WDG VOLTS LINE WDG VOLTS LINE

PRI

480 H1-H2-H3

PRI

504 H1-H2-H3

PRI

480 H1-H2-H3

456 H4-H5-H6 492 H4-H5-H6 468 H4-H5-H6

432 H7-H8-H9 480 H7-H8-H9 456 H7-H8-H9

468 H10-H11-H12 444 H10-H11-H12

456 H13-H14-H15 432 H13-H14-H15 Three Phase 3 wire to three phase 4 wire. For step-up do not connect neutral “X0”

SHARE

KVA CATALOG NUMBER

TAPS FCAN

TAPS FCBN

DESIGN TYPE

TEMP RISE °C

H W D WEIGHT

LBS FRAME

NUMBER WIRING

DIAGRAM WEATHER

SHIELD

GROUP “J”: PRI: 480∆ SEC: 208Y/120 60HZ

3 G003K3QH8A03 - 4 3E 115 13.40 15.93 8.25 116 201 FF

6 G006K3QH8A03 - 4 3E 115 15.90 16.93 10.00 165 200 FF

6 G006K3QH3A03 8 8 3E 115 15.90 16.93 10.00 165 200 GG

9 G009K3QH8A03 - 4 3E 115 15.90 16.93 10.00 185 103 FF

9 G009K3QH5A03 - 5 3E 115 15.90 16.93 10.00 185 103 HH

9 G009K3QH3A03 8 8 3E 115 15.90 16.93 10.00 185 103 GG

15 G015K3QH8A03 - 4 3E 115 17.38 20.00 10.50 275 95 FF

15 G015K3QH5A03 - 5 3E 115 17.38 20.00 10.50 275 95 HH

15 G015K3QH3A03 8 8 3E 115 17.38 20.00 10.50 275 95 GG

30 G030K3QH2A03 6 6 3E 115 26.58 21.81 11.65 422 243 II

45 G045K3QH2A03 6 6 3E 115 26.58 24.81 13.53 720 244 II

75 G075K3QH2A03 6 6 3E 115 32.00 30.30 15.70 1275 245 II

15 G015K5QH2A04 6 6 3V 150 30.00 23.00 16.50 152 912B 280B WS38MI

30 G030K5QH2A04 6 6 3V 150 30.00 23.00 16.50 310 912B 280B WS38MI

45 G045K5QH2A04 6 6 3V 150 30.00 23.00 16.50 310 912B 280B WS38MI

75 G075K5QH2A04 6 6 3V 150 39.00 29.00 22.00 480 914D 280B WS39MI

112.5 G112K5QH2A04 6 6 3V 150 46.58 28.00 23.00 630 916A 280B WS19MI

150 G150K5QH2A04 6 6 3V 150 46.58 28.00 23.00 820 916A 280B WS19MI

225 G225K5QH2A04 6 6 3V 150 56.16 33.00 28.00 1200 928 657A WS41MI

300 G300K5QH2A04 6 6 3V 150 59.60 36.75 32.50 1444 929 657A WS42MI

500 G500K5QH2A04 8 8 3V 150 68.38 44.45 36.45 2600 924 428B WS40MI

750 G750K5QH2A04 6 6 3V 150 C/F C/F C/F 2900 920E KK WS35MI

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 16: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

15 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

DIAGRAM “II” DIAGRAM “280B” DIAGRAM “657B”

VOLTS CONNECT LINE VOLTS TAP VOLTS CONNECT

504 1-6

H1-H2-H3

504 1 504 5 TO 6

492 1-5 492 2 492 6 TO 4

480 1-4 480 3 480 4 TO 7

468 2-5 468 4 468 7 TO 3

456 2-4 456 5 456 3 TO 8

444 3-5 444 6 444 8 TO 2

432 3-4 432 7 432 2 TO 9

DIAGRAM “428B” DIAGRAM “KK”

VOLTS CONNECT VOLTS CONNECT

504 3 TO 4 504 4 TO 5

492 3 TO 5 492 4 TO 6

480 3 TO 6 480 4 TO 7

468 2 TO 5 468 3 TO 6

456 2 TO 6 456 3 TO 7

444 2 TO 6

432 2 TO 7

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 17: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

16 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

(4) 2 @-5%; (5) 4 @-2.5%; (6) 2 @+2.5%, [email protected]%;

DIAGRAM “B1B” DIAGRAM “C1C “ DIAGRAM “D1D”

KVA CATALOG NUMBER

TAPS FCAN

TAPS FCBN

DESIGN TYPE

TEMP RISE °C

H W D WEIGHT

LBS FRAME

NUMBER WIRING

DIAGRAM WEATHER

SHIELD

GROUP “L”: PRI: 480∆ SEC: 240∆/120LT 60HZ LIGHTING TAP ON 3V UNITS ONLY

3 G003K4QJ8A03 - 4 3E 115 13.40 15.93 8.25 116 201 B1B

6 G006K4QJ8A03 - 4 3E 115 15.90 16.93 10.00 165 200 B1B

9 G009K4QJ5A03 - 5 3E 115 15.90 16.93 10.00 185 103 C1C

15 G015K4QJ5A03 - 5 3E 115 17.38 20.00 10.50 275 95 C1C

30 G030K4QJ2A03 6 6 3E 115 26.58 21.81 11.65 422 243 D1D

45 G045K4QJ2A03 6 6 3E 115 26.58 24.81 13.53 660 244 D1D

15 G015K6QJ9B02 6 6 3V 150 30.00 23.00 16.50 152 912B LL WS38MI

30 G030K6QJ9B02 6 6 3V 150 30.00 23.00 16.50 310 912B LL WS38MI

45 G045K6QJ9B02 6 6 3V 150 30.00 23.00 16.50 480 912B LL WS38MI

75 G075K6QJ9B02 6 6 3V 150 39.00 29.00 22.00 600 914D LL WS39MI

112.5 G112K6QJ9B02 6 6 3V 150 46.58 28.00 23.00 600 916A LL WS19MI

150 G150K6QJ9B02 6 6 3V 150 46.58 28.00 23.00 820 916A LL WS19MI

225 G225K6QJ9B02 6 6 3V 150 56.18 31.11 24.25 1300 917 LL WS34MI

300 G300K6QJ9B02 6 6 3V 150 57.50 36.25 32.18 2400 923 LL WS37MI

500 G500K6QJ9B02 6 6 3V 150 75.00 44.50 35.75 2600 919E MM WS35MI

WDG VOLTS LINE WDG VOLTS LINE VOLTS CONNECT LINE

PRI

480 H1-H2-H3

PRI

480 H1-H2-H3 504 1-6

H1-H2-H3

456 H4-H5-H6 468 H4-H5-H6 492 1-5

432 H7-H8-H9 456 H7-H8-H9 480 1-4 Three phase 3 wire to three phase 3 wire 444 H10-H11-H12 468 2-5

432 H13-H14-H15 456 2-4 Three phase 3 wire to three phase 3 wire 444 3-5

432 3-4

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 18: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

17 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

DIAGRAM “LL” DIAGRAM”MM”

VOLTS TAP VOLTS CONNECT

504 1

504 4 TO 5

492 2 492 4 TO 6

480 3 480 4 TO 7

468 4 468 3 TO 6

456 5 456 3 TO 7

444 6 444 2 TO 6

432 7 432 2 TO 7

(8) 2 @+2.5%, 2 @-2.5%; (6) 2 @+2.5%, [email protected]%;

DIAGRAM “NN” DIAGRAM “PP” DIAGRAM “QQ”

WDG VOLTS LINE VOLTS CONNECT LINE VOLTS TAP

PRI

504 H1-H2-H3

504 1-6

H1-H2-H3

504 1

492 H4-H5-H6 492 1-5 492 2

480 H7-H8-H9 480 1-4 480 3

468 H10-H11-H12 468 2-5 468 4

456 H13-H14-H15 456 2-4 456 5

444 3-5 444 6

432 3-4 432 7

SHARE

KVA CATALOG NUMBER

TAPS FCAN

TAPS FCBN

DESIGN TYPE

TEMP RISE °C

H W D WEIGHT

LBS FRAME

NUMBER WIRING

DIAGRAM WEATHER

SHIELD

GROUP “M”: PRI: 480∆ SEC: 480Y/277 60HZ

9 G009K3QQ3A03 8 8 3E 115 15.90 16.93 10.00 190 103 NN

15 G015K3QQ3A03 8 8 3E 115 17.38 20.00 10.50 275 95 NN

30 G030K3QQ2A03 6 6 3E 115 26.58 21.81 11.65 422 243 PP

45 G045K3QQ2A03 6 6 3E 115 26.58 24.81 13.53 660 244 PP

15 G015K5QQ2A04 6 6 3V 150 30.00 23.00 16.50 196 912B QQ WS38MI

30 G030K5QQ2A04 6 6 3V 150 30.00 23.00 16.50 308 912B QQ WS38MI

45 G045K5QQ2A04 6 6 3V 150 30.00 23.00 16.50 331 912B QQ WS38MI

75 G075K5QQ2A04 6 6 3V 150 39.00 29.00 22.00 513 914D QQ WS39MI

112.5 G112K5QQ2A04 6 6 3V 150 46.58 28.00 23.00 650 916A QQ WS19MI

150 G150K5QQ2A04 6 6 3V 150 46.58 28.00 23.00 770 916A QQ WS19MI

225 G225K5QQ2A04 6 6 3V 150 56.18 31.11 24.25 1300 917 QQ WS34MI

300 G300K5QQ2A04 6 6 3V 150 62.20 31.25 30.25 2400 918A QQ WS34MI

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 19: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

18 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

(10) 2 @-2.5%; (6) 2 @+2.5%, [email protected]%

(6) 2 @+2.5%, [email protected]%

DIAGRAM “SS” DIAGRAM “TT”

WDG VOLTS LINE VOLTS CONNECT LINE

PRI

600 H1-H2-H3

630 1-6

H1-H2-H3

570 H4-H5-H6 615 1-5

540 H7-H8-H9 600 1-4

Three phase 3 wire to three phase 4 wire For step up, do not connect neutral “X0”

585 2-5

570 2-4

555 3-5

540 3-4

KVA CATALOG NUMBER

TAPS FCAN

TAPS FCBN

DESIGN TYPE

TEMP RISE °C

H W D WEIGHT

LBS FRAME

NUMBER WIRING

DIAGRAM WEATHER

SHIELD

GROUP “N”: PRI: 600∆ SEC: 208Y/120 60HZ

9 G009K3RH8A03 - 10 3E 115 15.90 16.93 10.00 185 103 SS

15 G015K3RH8A03 - 10 3E 115 17.38 20.00 10.50 275 95 SS

30 G030K3RH2A03 6 6 3E 115 26.58 21.81 11.65 422 243 TT

45 G045K3RH2A03 6 6 3E 115 26.58 24.81 13.53 660 244 TT

15 G015K5RH2A04 6 6 3V 150 30.00 23.00 16.50 196 912B UU WS38MI

30 G030K5RH2A04 6 6 3V 150 30.00 23.00 16.50 308 912B UU WS38MI

45 G045K5RH2A04 6 6 3V 150 30.00 23.00 16.50 331 912B UU WS38MI

75 G075K5RH2A04 6 6 3V 150 39.00 29.00 22.00 513 914D UU WS39MI

112.5 G112K5RH2A04 6 6 3V 150 46.58 28.00 23.00 650 916A UU WS19MI

150 G150K5RH2A04 6 6 3V 150 46.58 28.00 23.00 770 916A UU WS19MI

225 G225K5RH2A04 6 6 3V 150 56.18 31.11 24.25 1300 917 UU WS34MI

300 G300K5RH2A04 6 6 3V 150 62.20 31.25 30.25 2400 918A UU WS34MI

KVA CATALOG NUMBER

TAPS FCAN

TAPS FCBN

DESIGN TYPE

TEMP RISE °C

H W D WEIGHT

LBS FRAME

NUMBER WIRING

DIAGRAM WEATHER

SHIELD

GROUP “O”: PRI: 600∆ SEC: 240∆ 60HZ

30 G030K4RJ2A03 6 6 3E 115 26.58 21.81 11.65 422 243 WW

45 G045K4RJ2A03 6 6 3E 115 26.58 24.81 13.53 660 244 WW

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 20: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

19 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

DIAGRAM “UU” DIAGRAM “WW”

BUCK-BOOST TRANSFORMERS

Single and Three Phase Applications – 60Hz

A Buck-Boost Transformer is used to provide an economical method of correcting a lower or higher voltage to a

voltage rating more suitable for efficient operation of electrical equipment.

Buck-Boost Transformers are small Kva, single phase, 600 volt class insulating transformers with dual primary and dual

secondary windings. If wired as an isolation transformer, they can be utilized to provide for applications requiring 12,

16, 24, 32 or 48 Vac up through 7.5Kva. However, they are usually connected as autotransformers by utilizing one unit

for single phase applications and either two or three units banked for three phase operation. They are primarily used

for motor operation and should not be used for motor control circuits, to correct fluctuating line voltage or to obtain a

neutral on a delta system. These applications require transformers especially designed for these specific applications.

NOTE: When installation is to be made on a grounded system, consideration must be given to the resulting voltage.

Thus, on a 208 grounded wye/120 system the voltage can be boosted to 240 volts but the voltage to ground will be

139 volts. If 240/120 volts with a midpoint ground is needed, a standard two-winding transformer must be used.

The following formula can be used to calculate specific requirements.

For Single Phase For Three Phase

LOAD KVA= LOAD KVA=

Load Voltage x Full Load Amps Load Voltage x Full Load Amps x 1.732

1000 1000

For quick selection data, refer to the tables on the following pages.

VOLTS CONNECT VOLTS CONNECT LINE

630 4 TO 5

630 1-6

H1-H2-H3

615 4 TO 6 615 1-5

600 4 TO 7 600 1-4

585 3 TO 6

585 2-5

570 3 TO 7

570 2-4

555 2 TO 6 555 3-5

540 2 TO 7 540 3-4

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 21: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

20 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

Selection Requirements Selection Information

First, you should have this information before selecting

a buck-boost transformer.

Line Voltage- The voltage that you want to buck

(decrease) or boost (increase). This can be found by

measuring the supply line voltage with a voltmeter.

Load Voltage- The voltage at which your equipment is

designed to operate. This is listed on the nameplate of

the equipment.

Load Amps or Load Kva- You do not need to know both

– one or the other is sufficient for selection purposes.

This information usually can be found on the

nameplate of the equipment that you want to operate.

Frequency- The supply line frequency must be the

same as the frequency of the equipment being

operated. Micron Buck-Boost transformers operate at

60 Hertz only.

Phase- The supply line should be the same as the

equipment to be operated – either single or three

phase.

Transformer Interconnection

For three phase applications, interconnections of

transformers should be made in a junction box. Two or

three transformers may be used depending on an open

delta (2) or wye (3) connection.

5-Step Selector

The tables which follow will simplify the selection of

the buck-boost transformers. There are no calculations

needed; simply follow these 5 steps.

1. Refer to the table having the same output voltage as

the equipment that you want to operate. For example,

if you are installing a 240 volt, 6Kva single phase load,

use Selection Table Number 4.

2. Select the available line voltage across the top of the

chart which is closest to the actual supply voltage. In

the example, if the available line voltage is 213 volts,

use the 212 volt Column.

3. Read down the column until you reach an output

Kva or amps rating equal to or greater than the load

requirements. Since 6Kva, in the example, is not listed,

use the next higher rating or 7.5Kva.

4. Read across to the far left columns for the catalog

number and quantity of transformers for your

application. In the example, you will need (1) catalog

number J001K1EB1A02.

5. Connect the selected buck-boost transformer(s) in

accordance with the connection diagram specified at

the bottom of the “Available Voltage” column. In the

example, Diagram “F” would be used.

NOTE: For 1 phase connections and 3 phase open delta

connections, inputs and outputs may be reversed. Kva

capacity remains constant.

Buck-Boost Product Groups

KVA CATALOG NUMBER

DESIGN TYPE

TEMP RISE °C

H W D WEIGHT

LBS FRAME

NUMBER

GROUP “A”: PRI: 120 X 240 SEC: 16/32 60 HZ

.050 J050A1EB1A01 1E 115 6.50 3.88 3.50 7 52

.100 J100A1EB1A01 1E 115 6.50 3.88 3.50 7 54

.150 J150A1EB1A01 1E 115 6.50 3.88 3.50 8 55

.250 J250A1EB1A02 1E 115 6.50 5.00 3.88 12 57

.500 J500A1EB1A02 1E 115 6.50 4.88 4.63 13 57

.750 J750A1EB1A02 1E 115 8.38 6.00 5.50 21 58A

1 J001K1EB1A02 1E 115 8.38 6.00 5.50 31 67

1.5 J1X5K1EB1A02 1E 115 10.50 6.38 6.13 40 67

2 J002K1EB1A02 1E 115 10.50 6.38 6.13 40 68

3 J003K1EB1A03 1E 115 14.13 7.75 8.00 65 176

5 J005K1EB1A03 1E 115 16.00 10.38 9.88 113 177

7.5 J7X5K1EB1A03 1E 115 16.00 10.38 9.88 123 178

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 22: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

21 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

Need Single Phase 115 Volts, 60Hz (Table Number 1)

KVA CATALOG NUMBER

DESIGN TYPE

TEMP RISE °C

H W D WEIGHT

LBS FRAME

NUMBER

GROUP “B”: PRI: 240 X 480 SEC: 24/48 60 HZ

.050 J050A1KC1A01 1E 115 6.50 3.88 3.50 7 52

.100 J100A1KC1A01 1E 115 6.50 3.88 3.50 7 54

.150 J150A1KC1A01 1E 115 6.50 3.88 3.50 8 55

.250 J250A1KC1A02 1E 115 6.50 5.00 3.88 12 57

.500 J500A1KC1A02 1E 115 6.50 4.88 4.63 13 57

.750 J750A1KC1A02 1E 115 8.38 6.00 5.50 21 58A

1 J001K1KC1A02 1E 115 8.38 6.00 5.50 31 67

1.5 J1X5K1KC1A02 1E 115 10.50 6.38 6.13 40 67

2 J002K1KC1A02 1E 115 10.50 6.38 6.13 40 68

3 J003K1KC1A03 1E 115 14.13 7.75 8.00 65 176

5 J005K1KC1A03 1E 115 16.00 10.38 9.88 113 177

7.5 J7X5K1KC1A03 1E 115 16.00 10.38 9.88 123 178

KVA CATALOG NUMBER

DESIGN TYPE

TEMP RISE °C

H W D WEIGHT

LBS FRAME

NUMBER

GROUP “C”: PRI: 120 X 240 SEC: 12/24 60 HZ

.050 J050A1EA1A01 1E 115 6.50 3.88 3.50 7 52

.100 J100A1EA1A01 1E 115 6.50 3.88 3.50 7 54

.150 J150A1EA1A01 1E 115 6.50 3.88 3.50 8 55

.250 J250A1EA1A02 1E 115 6.50 5.00 3.88 12 57

.500 J500A1EA1A02 1E 115 6.50 4.88 4.63 13 57

.750 J750A1EA1A02 1E 115 8.38 6.00 5.50 21 58A

1 J001K1EA1A02 1E 115 8.38 6.00 5.50 31 67

1.5 J1X5K1EA1A02 1E 115 10.50 6.38 6.13 40 67

2 J002K1EA1A02 1E 115 10.50 6.38 6.13 40 68

3 J003K1EA1A03 1E 115 14.13 7.75 8.00 65 176

5 J005K1EA1A03 1E 115 16.00 10.38 9.88 113 177

7.5 J7X5K1EA1A03 1E 115 16.00 10.38 9.88 123 178

Units Req’d

Unit Kva

Catalog Number

Have Available Voltage Of

84 91 96 100 102 105 127 130 138 146

Max Load Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps

1 .05 J050A1EA1A01 - - - - 0.24 2.09 - - - - 0.48 4.17 0.54 4.58 - - 0.29 2.50 - -

1 .05 J050A1EB1A01 0.13 1.14 0.18 1.56 - - 0.31 2.70 0.36 3.13 - - - - 0.41 3.54 - - 0.23 1.98

1 .10 J100A1EA1A01 - - - - 0.48 4.17 - - - - 0.96 8.33 1.10 9.17 - - 0.58 5.00 - -

1 .10 J100A1EB1A01 0.26 2.29 0.36 3.12 - - 0.62 5.41 0.72 6.25 - - - - 0.82 7.08 - - 0.46 3.95

1 .15 J150A1EA1A01 - - - - 0.72 6.25 - - - - 1.44 12.5 1.60 13.7 - - 0.87 7.50 - -

1 .15 J150A1EB1A01 0.39 3.44 0.54 4.69 - - 0.93 8.12 1.08 9.37 - - - - 1.30 10.6 - - 0.69 5.93

1 .25 J250A1EA1A02 - - - - 1.20 10.4 - - - - 2.39 20.8 2.63 22.9 - - 1.44 12.5 - -

1 .25 J250A1EB1A02 0.66 5.73 0.90 7.81 - - 1.56 13.5 1.80 15.6 - - - - 2.03 17.7 - - 1.14 9.88

1 .50 J500A1EA1A02 - - - - 2.40 20.8 - - - - 4.79 41.6 5.27 45.8 - - 2.87 25 - -

1 .50 J500A1EB1A02 1.32 11.5 1.80 15.6 - - 3.11 27.1 3.59 31.2 - - - - 4.07 35.4 - - 2.27 19.8

1 .75 J750A1EA1A02 - - - - 3.60 31.2 - - - - 7.19 62.4 7.90 68.7 - - 4.31 37.5 - -

1 .75 J750A1EB1A02 1.98 17.2 2.70 23.4 - - 4.67 40.6 5.39 46.8 - - - - 6.10 53.1 - - 3.41 29.6

1 1.0 J001K1EA1A02 - - - - 4.79 41.7 - - - - 9.58 83.3 10.5 91.7 - - 5.75 50 - -

1 1.0 J001K1EB1A02 2.64 22.9 3.59 31.2 - - 6.23 54.1 7.19 62.5 - - - - 8.14 70.8 - - 4.55 39.5

1 1.5 J1X5K1EA1A02 - - - - 7.20 62.5 - - - - 14.4 125 15.8 137 - - 8.62 75 - -

1 1.5 J1X5K1EB1A02 3.95 34.4 5.39 46.9 - - 9.34 81.2 10.8 93.7 - - - - 12.2 106 - - 6.82 59.3

1 2.0 J002K1EA1A02 - - - - 9.58 83.3 - - - - 19.2 16.7 21.1 183 - - 11.5 100 - -

1 2.0 J002K1EB1A02 5.27 45.8 7.19 62.5 - - 12.5 108 14.4 125 - - - - 16.3 142 - - 9.10 79.2

1 3.0 J003K1EA1A03 - - - - 14.37 125.1 - - - - 28.7 249.9 31.5 275.1 - - 17.3 150 - -

1 3.0 J003K1EB1A03 7.92 68.7 10.77 93.6 - - 18.69 162.3 21.57 187.5 - - - - 24.4 212.4 - - 13.6 118.5

1 5.0 J005K1EA1A03 - - - - 23.95 208.5 - - - - 47.9 416.5 52.5 458.5 - - 28.7 250 - -

1 5.0 J005K1EB1A03 13.2 115 18 156 - - 31.15 270.5 35.95 312.5 - - - - 40.7 354 - - 22.7 197.5

1 7.5 J7X5K1EA1A03 - - - - 36 312 - - - - 71.9 624 79 687 - - 43.1 357 - -

1 7.5 J7X5K1EB1A03 19.8 172 27 234 - - 46.7 406 53.9 468 - - - - 61 531 - - 34.1 296

Connection Diagram D B B C A A A A B B

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 23: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

22 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

Need Single Phase 120 Volts, 60Hz (Selection Table Number 2)

DIAGRAM “A” DIAGRAM “B”

DIAGRAM “C” DIAGRAM “D”

Units Req’d

Unit Kva

Use Catalog

Number

Have Available Voltage Of

88 95 100 104 106 109 132 136 144 152

Max Load Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps

1 .05 J050A1EA1A01 - - - - 0.25 2.09 - - - - 0.50 4.17 0.55 4.58 - - 0.30 2.50 - -

1 .05 J050A1EB1A01 0.14 1.15 0.19 1.56 - - 0.33 2.70 0.38 3.13 - - - - 0.43 3.54 - - 0.24 1.98

1 .10 J100A1EA1A01 - - - - 0.50 4.17 - - - - 1.00 8.33 1.10 9.17 - - 0.60 5.00 - -

1 .10 J100A1EB1A01 0.29 2.29 0.38 3.12 - - 0.65 5.41 0.75 6.25 - - - - 0.85 7.08 - - 0.48 3.95

1 .15 J150A1EA1A01 - - - - 0.75 6.25 - - - - 1.50 12.5 1.60 13.7 - - 0.90 7.50 - -

1 .15 J150A1EB1A01 0.41 3.44 0.56 4.69 - - 0.98 8.12 1.12 9.37 - - - - 1.27 10.6 - - 0.71 5.93

1 .25 J250A1EA1A02 - - - - 1.25 10.4 - - - - 2.50 20.8 2.75 22.9 - - 1.50 12.5 - -

1 .25 J250A1EB1A02 0.69 5.73 0.94 7.81 - - 1.62 13.5 1.87 15.6 - - - - 2.12 17.7 - - 1.19 9.88

1 .50 J500A1EA1A02 - - - - 2.50 20.8 - - - - 5.00 41.6 5.50 45.8 - - 3.00 25 - -

1 .50 J500A1EB1A02 1.37 11.5 1.87 15.6 - - 3.25 27.1 3.75 31.2 - - - - 4.25 35.4 - - 2.37 19.8

1 .75 J750A1EA1A02 - - - - 3.75 31.2 - - - - 7.50 62.4 8.25 68.7 - - 4.50 37.5 - -

1 .75 J750A1EB1A02 2.06 17.2 2.82 23.4 - - 4.87 40.6 5.62 46.8 - - - - 6.37 53.1 - - 3.56 29.6

1 1.0 J001K1EA1A02 - - - - 5.00 41.7 - - - - 10 83.3 11 91.7 - - 6.00 50 - -

1 1.0 J001K1EB1A02 2.75 22.9 3.75 31.2 - - 6.50 54.1 7.50 62.5 - - - - 8.50 70.8 - - 4.75 39.5

1 1.5 J1X5K1EA1A02 - - - - 7.50 62.5 - - - - 15 125 16.5 137 - - 9.00 75 - -

1 1.5 J1X5K1EB1A02 4.12 34.4 5.62 46.9 - - 9.75 81.2 11.2 93.7 - - - - 12.7 106 - - 7.12 59.3

1 2.0 J002K1EA1A02 - - - - 10 83.3 - - - - 20 167 22 183 - - 12 100 - -

1 2.0 J002K1EB1A02 5.50 45.8 7.50 62.5 - - 13 108 15 125 - - - - 17 142 - - 9.50 79.2

1 3.0 J003K1EA1A03 - - - - 15 125.1 - - - - 30 249.9 33 275.1 - - 18 150 - -

1 3.0 J003K1EB1A03 8.25 68.7 11.25 93.6 - - 19.5 162.3 22.5 187.5 - - - - 25.5 212.4 - - 14.25 118.5

1 5.0 J005K1EA1A03 - - - - 25 208.5 - - - - 50 416.5 55 458.5 - - 30 250 - -

1 5.0 J005K1EB1A03 13.75 114.5 18.75 156 - - 32.5 270.5 37.5 312.5 - - - - 42.5 354 - - 23.7 197.5

1 7.5 J7X5K1EA1A03 - - - - 37.5 312 - - - - 75 624 82.5 687 - - 45 375 - -

1 7.5 J7X5K1EB1A03 20.6 172 28.2 234 - - 48.7 406 56.2 468 - - - - 63.7 531 - - 35.6 296

Connection Diagram D B B C A A A A B B

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 24: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

23 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

Need Single Phase 230Volts, 60Hz (Selection Table Number 3)

Need Single Phase 240 Volts, 60Hz (Selection Table Number 4)

Units Req’d

Unit Kva

Use Catalog

Number

Have Available Voltage Of

199 203 207 209 216 219 242 246 253 260

Max Load Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps

1 .05 J050A1EA1A01 - - - - 0.43 1.88 0.48 2.08 - - 0.96 4.16 1.00 4.38 - - 0.53 2.29 - -

1 .05 J050A1EB1A01 0.31 1.36 0.36 1.56 - - - - 0.72 3.12 - - - - 0.77 3.34 - - 0.41 1.77

1 .10 J100A1EA1A01 - - - - 0.86 3.75 0.96 4.17 - - 1.92 8.33 2.01 8.75 - - 1.05 4.58 - -

1 .10 J100A1EB1A01 0.62 2.71 0.72 3.12 - - - - 1.44 6.25 - - - - 1.53 6.67 - - 0.82 3.54

1 .15 J150A1EA1A01 - - - - 1.29 5.62 1.44 6.25 - - 2.87 12.5 3.02 13.1 - - 1.58 6.87 - -

1 .15 J150A1EB1A01 0.93 4.06 1.08 4.69 - - - - 2.16 9.37 - - - - 2.30 10 - - 1.22 5.31

1 .25 J250A1EA1A02 - - - - 2.15 9.37 2.39 10.4 - - 4.79 20.8 5.03 21.9 - - 2.63 11.5 - -

1 .25 J250A1EB1A02 1.55 6.77 1.80 7.81 - - - - 3.59 15.6 - - - - 3.83 16.7 - - 2.04 8.85

1 .50 J500A1EA1A02 - - - - 4.31 18.7 4.79 20.8 - - 9.58 41.6 10.1 43.7 - - 5.27 22.9 - -

1 .50 J500A1EB1A02 3.11 13.5 3.60 15.6 - - - - 7.19 31.2 - - - - 7.67 33.3 - - 4.07 17.7

1 .75 J750A1EA1A02 - - - - 6.46 28.2 7.19 31.2 - - 14.4 62.4 15.1 65.6 - - 7.90 34.4 - -

1 .75 J750A1EB1A02 4.66 20.3 5.40 23.4 - - - - 10.8 46.8 - - - - 11.5 50 - - 6.11 26.6

1 1.0 J001K1EA1A02 - - - - 8.62 37.5 9.58 41.7 - - 19.2 83.3 20.1 87.5 - - 10.5 45.8 - -

1 1.0 J001K1EB1A02 6.23 27.1 7.2 31.2 - - - - 14.4 62.5 - - - - 15.3 66.7 - - 8.15 35.4

1 1.5 J1X5K1EA1A02 - - - - 12.9 56.2 14.4 62.5 - - 28.7 125 30.2 131 - - 15.8 68.7 - -

1 1.5 J1X5K1EB1A02 9.34 40.6 10.8 46.9 - - - - 21.6 93.7 - - - - 23 100 - - 12.2 53.1

1 2.0 J002K1EA1A02 - - - - 17.2 75 19.2 83.3 - - 38.3 167 40.2 175 - - 21.1 91.7 - -

1 2.0 J002K1EB1A02 12.5 54.2 14.4 62.5 - - - - 28.7 125 - - - - 30.7 133 - - 16.3 70.8

1 3.0 J003K1EA1A03 - - - - 25.8 112.5 28.7 125.1 - - 57.6 249.9 60.3 262.5 - - 31.5 137.4 - -

1 3.0 J003K1EB1A03 18.6 81.3 21.6 93.6 - - - - 43.2 187.5 - - - - 45.9 200.1 - - 24.4 106.2

1 5.0 J005K1EA1A03 - - - - 43.1 187.5 47.9 208.5 - - 96 416.5 100.5 437.5 - - 52.5 229 - -

1 5.0 J005K1EB1A03 31.1 135.5 36 156 - - - - 72 312.5 - - - - 76.5 333.5 - - 40.7 177

1 7.5 J7X5K1EA1A03 - - - - 64.6 282 71.9 312 - - 144 624 151 656 - - 79 344 - -

1 7.5 J7X5K1EB1A03 46.6 203 54 234 - - - - 108 468 - - - - 115 500 - - 61.1 266

Connection Diagram G F G F E E E E F F

Units Req’d

Unit Kva

Use Catalog Number

Have Available Voltage Of

208 212 216 218 225 229 252 256 264 272

Max Load Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps

1 .05 J050A1EA1A01 - - - - 0.45 1.88 0.50 2.08 - - 1.00 4.16 1.05 4.38 - - 0.55 2.29 - -

1 .05 J050A1EB1A01 0.32 1.35 0.38 1.56 - - - - 0.75 3.12 - - - - 0.80 3.33 - - 0.42 1.77

1 .10 J100A1EA1A01 - - - - 0.90 3.75 1.00 4.17 - - 2.00 8.33 2.10 8.75 - - 1.10 4.58 - -

1 .10 J100A1EB1A01 0.65 2.71 0.75 3.12 - - - - 1.50 6.25 - - - - 1.60 6.67 - - 0.85 3.54

1 .15 J150A1EA1A01 - - - - 1.35 5.62 1.50 6.25 - - 3.00 12.5 3.15 13.1 - - 1.65 6.87 - -

1 .15 J150A1EB1A01 0.98 4.06 1.12 4.69 - - - - 2.25 9.37 - - - - 2.40 10 - - 1.27 5.31

1 .25 J250A1EA1A02 - - - - 2.25 9.37 2.50 10.4 - - 5.00 20.8 5.25 21.9 - - 2.75 11.5 - -

1 .25 J250A1EB1A02 1.62 6.77 1.87 7.81 - - - - 3.75 15.6 - - - - 4.00 16.7 - - 2.12 8.85

1 .50 J500A1EA1A02 - - - - 4.50 18.7 5.00 20.8 - - 10 41.6 10.5 43.7 - - 5.50 22.9 - -

1 .50 J500A1EB1A02 3.25 13.5 3.75 15.6 - - - - 7.50 31.2 - - - - 8.00 33.3 - - 4.25 17.7

1 .75 J750A1EA1A02 - - - - 6.75 28.2 7.5 31.2 - - 15 62.4 15.7 65.6 - - 8.25 34.4 - -

1 .75 J750A1EB1A02 4.87 20.3 5.62 23.4 - - - - 11.2 46.8 - - - - 12 50 - - 6.37 26.6

1 1.0 J001K1EA1A02 - - - - 9.00 37.5 10 41.7 - - 20 83.3 21 87.5 - - 11 45.8 - -

1 1.0 J001K1EB1A02 6.50 27.1 7.50 31.2 - - - - 15 62.5 - - - - 16 66.7 - - 8.5 35.4

1 1.5 J1X5K1EA1A02 - - - - 13.5 56.2 15 62.5 - - 30 125 31.5 131 - - 16.5 68.7 - -

1 1.5 J1X5K1EB1A02 9.75 40.6 11.2 46.9 - - - - 22.5 93.7 - - - - 24 100 - - 12.7 53.1

1 2.0 J002K1EA1A02 - - - - 18 75 20 83.3 - - 40 167 42 175 - - 22 91.7 - -

1 2.0 J002K1EB1A02 13 54.2 15 62.5 - - - - 30 125 - - - - 32 133 - - 17 70.8

1 3.0 J003K1EA1A03 - - - - 27 112.5 30 125.1 - - 60 249.9 63 262.5 - - 33 137.4 - -

1 3.0 J003K1EB1A03 19.5 81.3 22.5 93.6 - - - - 45 187.5 - - - - 48 200.1 - - 25.5 106.2

1 5.0 J005K1EA1A03 - - - - 45 187 50 208 - - 100 416.5 105 437.5 - - 55 229 - -

1 5.0 J005K1EB1A03 32.5 135 37.5 156 - - - - 75 312 - - - - 80 333 - - 42.5 177

1 7.5 J7X5K1EA1A03 - - - - 67.5 282 75 312 - - 150 624 157 656 - - 82.5 344 - -

1 7.5 J7X5K1EB1A03 48.7 203 56.2 234 - - - - 112 468 - - - - 120 500 - - 63.7 266

Connection Diagram G F G F E E E E F F

FROM EXAMPLE OF BUCK-BOOST SELECTION PROCESS

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 25: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

24 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

DIAGRAM “E” DIAGRAM “F” DIAGRAM “G”

THREE PHASE APPLICATIONS WARNING! THREE PHASE AUTOTRANSFORMERS SHOULD NEVER BE USED TO OBTAIN 4-WIRE OUTPUT WITH

3-WIRE INPUT. 4-WIRE OUTPUT REQUIRES 4-WIRE WYE INPUT.

Need Three Phase Open Delta 230 Volts, 60Hz (Selection Table Number 5)

Units Req’d

Unit Kva

Use Catalog Number

Have Available Voltage Of

199 203 207 209 216 219 242 246 253 260

Max Load Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps

2 .05 J050A1EA1A01 - - - - 0.75 1.87 0.83 2.08 - - 1.66 4.17 1.74 4.37 - - 0.91 2.29 - -

2 .05 J050A1EB1A01 0.54 1.35 0.62 1.56 - - - - 1.24 3.12 - - - - 1.33 3.33 - - 0.70 1.77

2 .10 J100A1EA1A01 - - - - 1.49 3.75 1.66 4.17 - - 3.32 8.33 3.48 8.75 - - 1.83 4.58 - -

2 .10 J100A1EB1A01 1.08 2.71 1.24 3.12 - - - - 2.49 6.25 - - - - 2.65 6.67 - - 1.41 3.54

2 .15 J150A1EA1A01 - - - - 2.24 5.62 2.49 6.25 - - 4.98 12.5 5.23 13.1 - - 2.74 6.87 - -

2 .15 J150A1EB1A01 1.62 4.06 1.87 4.69 - - - - 3.73 9.37 - - - - 3.98 10 - - 2.12 5.13

2 .25 J250A1EA1A02 - - - - 3.30 9.37 4.15 10.4 - - 8.30 20.8 8.71 21.9 - - 4.56 11.5 - -

2 .25 J250A1EB1A02 2.70 6.77 3.11 7.81 - - - - 6.22 15.6 - - - - 6.64 16.7 - - 3.52 8.85

2 .50 J500A1EA1A02 - - - - 7.47 18.7 8.30 20.8 - - 16.6 41.7 17.4 43.7 - - 9.73 22.9 - -

2 .50 J500A1EB1A02 5.39 13.5 6.22 15.6 - - - - 12.4 31.2 - - - - 13.3 33.3 - - 7.05 17.7

2 .75 J750A1EA1A02 - - - - 11.2 28.2 12.4 31.2 - - 24.9 62.4 26.1 65.6 - - 13.7 34.4 - -

2 .75 J750A1EB1A02 8.09 20.3 9.33 23.4 - - - - 18.7 46.8 - - - - 19.9 50 - - 10.6 26.6

2 1.0 J001K1EA1A02 - - - - 14.9 37.5 16.6 41.7 - - 33.2 83.3 34.8 87.5 - - 18.3 45.8 - -

2 1.0 J001K1EB1A02 10.8 27.1 12.4 31.2 - - - - 24.9 62.5 - - - - 26.5 66.7 - - 14.1 35.4

2 1.5 J1X5K1EA1A02 - - - - 22.4 56.2 24.9 62.5 - - 49.8 125 52.3 131 - - 27.4 68.7 - -

2 1.5 J1X5K1EB1A02 16.2 40.6 18.7 46.9 - - - - 37.3 93.7 - - - - 39.8 100 - - 21.2 53.1

2 2.0 J002K1EA1A02 - - - - 29.9 75 33.2 83.3 - - 66.4 167 69.7 175 - - 36.5 91.7 - -

2 2.0 J002K1EB1A02 21.6 54.2 24.9 62.5 - - - - 49.8 125 - - - - 53.1 133 - - 28.2 70.8

2 3.0 J003K1EA1A03 - - - - 44.7 112.5 49.8 125.1 - - 99.6 249.9 104.4 262.5 - - 54.9 137.4 - -

2 3.0 J003K1EB1A03 32.4 81.3 32.7 93.6 - - - - 74.7 187.5 - - - - 79.5 200 - - 42.3 106.2

2 5.0 J005K1EA1A03 - - - - 74.7 187 83 208 - - 166 417 174 437 - - 91.3 229 - -

2 5.0 J005K1EB1A03 53.9 135 62.2 156 - - - - 124 312.5 - - - - 133 333 - - 70.5 177

2 7.5 J7X5K1EA1A03 - - - - 112 282 124 312 - - 249 624 261 656 - - 137 344 - -

2 7.5 J7X5K1EB1A03 80.9 203 93.3 234 - - - - 187 468 - - - - 199 500 - - 106 266

Connection Diagram L K L K I I I I K K

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 26: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

25 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

Need Three Phase Open Delta 240 Volts, 60 Hz (Selection Table Number 6)

DIAGRAM “I” DIAGRAM “K” DIAGRAM “L”

Units Req’d

Unit Kva

Use Catalog

Number

Have Available Voltage Of

208 212 216 218 225 229 252 256 264 272

Max Load Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps

2 .05 J050A1EA1A01 - - - - 0.73 1.87 0.87 2.08 - - 1.73 4.16 1.82 4.37 - - 0.95 2.29 - -

2 .05 J050A1EB1A01 0.56 1.35 0.65 1.56 - - - - 1.30 3.12 - - - - 1.38 3.33 - - 0.74 1.77

2 .10 J100A1EA1A01 - - - - 1.56 3.75 1.73 4.17 - - 3.46 8.33 3.64 8.75 - - 1.91 4.58 - -

2 .10 J100A1EB1A01 1.13 2.71 1.30 3.12 - - - - 2.60 6.25 - - - - 2.77 6.67 - - 1.47 3.54

2 .15 J150A1EA1A01 - - - - 2.34 5.62 2.60 6.25 - - 5.19 12.5 5.45 13.1 - - 2.86 6.87 - -

2 .15 J150A1EB1A01 1.69 4.06 1.95 4.69 - - - - 3.90 9.37 - - - - 4.15 10 - - 2.21 5.31

2 .25 J250A1EA1A02 - - - - 3.90 9.37 4.33 10.4 - - 8.66 20.8 9.09 21.9 - - 4.76 11.5 - -

2 .25 J250A1EB1A02 2.81 6.77 3.25 7.81 - - - - 6.49 15.6 - - - - 6.92 16.7 - - 3.68 8.85

2 .50 J500A1EA1A02 - - - - 7.79 18.7 8.66 20.8 - - 17.3 41.6 18.2 43.7 - - 9.53 22.9 - -

2 .50 J500A1EB1A02 5.63 13.5 6.50 15.6 - - - - 13 31.2 - - - - 13.8 33.3 - - 7.36 17.7

2 .75 J750A1EA1A02 - - - - 11.7 28.2 13 31.2 - - 26 62.4 27.3 65.6 - - 14.3 34.4 - -

2 .75 J750A1EB1A02 8.44 20.3 9.75 23.4 - - - - 19.5 46.8 - - - - 20.8 50 - - 11 26.6

2 1.0 J001K1EA1A02 - - - - 15.6 37.5 17.3 41.7 - - 34.6 83.3 36.4 87.5 - - 19.1 45.8 - -

2 1.0 J001K1EB1A02 11.3 27.1 13 31.2 - - - - 26 62.5 - - - - 27.7 66.7 - - 14.7 35.4

2 1.5 J1X5K1EA1A02 - - - - 23.4 56.2 26 62.5 - - 51.9 125 54.5 131 - - 28.6 68.7 - -

2 1.5 J1X5K1EB1A02 16.9 40.6 19.5 46.9 - - - - 39 93.7 - - - - 41.5 100 - - 22.1 53.1

2 2.0 J002K1EA1A02 - - - - 31.2 75 34.6 83.3 - - 69.3 167 72.7 175 - - 38.1 91.7 - -

2 2.0 J002K1EB1A02 22.5 54.2 26 62.5 - - - - 25 125 - - - - 55.4 133 - - 29.4 70.8

2 3.0 J003K1EA1A03 - - - - 46.8 112.5 51.9 125.1 - - 103.8 249.9 109.2 262.5 - - 57.3 137.4 - -

2 3.0 J003K1EB1A03 33.9 81.3 39 93.6 - - - - 78 187.5 - - - - 83.1 200 - - 44.1 106.2

2 5.0 J005K1EA1A03 - - - - 77.9 187 86.6 208 - - 173 416 182 437 - - 95.3 229 - -

2 5.0 J005K1EB1A03 56.3 135 65 156 - - - - 130 312 - - - - 138 333 - - 73.6 177

2 7.5 J7X5K1EA1A03 - - - - 117 282 130 312 - - 260 624 273 656 - - 143 344 - -

2 7.5 J7X5K1EB1A03 84.4 203 97.5 234 - - - - 195 468 - - - - 208 500 - - 110 266

Connection Diagram L K L K I I I I K K

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 27: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

26 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

Need Three Phase Wye 208 Volts, 60Hz (Selection Table Number 7)

DIAGRAM “M” DIAGRAM “N”

DIAGRAM “O” DIAGRAM “P”

Units Req’d

Unit Kva

Use Catalog

Number

Have Available Voltage Of

152 265 173 180 184 189 229 236 250 264

Max Load Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps

3 .05 J050A1EA1A01 - - - - 0.75 2.08 - - - - 1.50 4.16 1.65 4.58 - - 0.90 2.50 - -

3 .05 J050A1EB1A01 0.41 1.15 0.56 1.56 - - 0.98 2.71 1.12 3.12 - - - - 1.27 3.54 - - 0.71 1.98

3 .10 J100A1EA1A01 - - - - 1.50 4.17 - - - - 3.00 8.33 3.30 9.17 - - 1.80 5.00 - -

3 .10 J100A1EB1A01 0.82 2.29 1.12 3.12 - - 1.95 5.41 2.25 6.25 - - - - 2.55 7.08 - - 1.42 3.95

3 .15 J150A1EA1A01 - - - - 2.25 6.25 - - - - 4.50 12.5 4.95 13.7 - - 2.70 7.50 - -

3 .15 J150A1EB1A01 1.24 3.44 1.69 4.69 - - 2.92 8.12 3.73 9.37 - - - - 3.82 10.6 - - 2.14 5.93

3 .25 J250A1EA1A02 - - - - 3.75 104 - - - - 7.50 20.8 8.25 22.9 - - 4.50 12.5 - -

3 .25 J250A1EB1A02 2.06 5.73 2.81 7.81 - - 4.87 13.5 5.62 15.6 - - - - 6.35 17.7 - - 3.56 9.88

3 .50 J500A1EA1A02 - - - - 7.50 20.8 - - - - 15 41.6 16.5 45.8 - - 9.0 25 - -

3 .50 J500A1EB1A02 4.12 11.5 5.62 15.6 - - 9.75 27.1 11.2 31.2 - - - - 12.7 35.4 - - 7.12 19.3

3 .75 J750A1EA1A02 - - - - 11.2 31.2 - - - - 22.5 62.4 24.7 68.7 - - 13.5 37.5 - -

3 .75 J750A1EB1A02 6.19 17.2 8.44 23.4 - - 14.6 40.6 16.8 46.8 - - - - 19 53.1 - - 10.7 29.3

3 1.0 J001K1EA1A02 - - - - 15 41.7 - - - - 30 83.3 33 91.7 - - 18 50 - -

3 1.0 J001K1EB1A02 8.25 22.9 11.2 31.2 - - 19.5 54.1 22.5 62.5 - - - - 25.5 70.8 - - 14.2 39.5

3 1.5 J1X5K1EA1A02 - - - - 22.5 62.5 - - - - 45 125 49.5 137 - - 27 75 - -

3 1.5 J1X5K1EB1A02 12.4 34.4 16.9 46.9 - - 29.2 81.2 33.7 93.7 - - - - 38.2 106 - - 21.4 59.3

3 2.0 J002K1EA1A02 - - - - 30 83.3 - - - - 60 167 66 183 - - 361 100 - -

3 2.0 J002K1EB1A02 16.5 45.8 22.5 62.5 - - 39 108 45 125 - - - - 51 142 - - 28.5 79.2

3 3.0 J003K1EA1A03 - - - - 45 125 - - - - 90 249.9 99 275.1 - - 54 150 - -

3 3.0 J003K1EB1A03 24.7 68.7 33.6 93.6 - - 58.5 162.3 67.5 187.5 - - - - 76.5 212.4 - - 46.2 118.5

3 5.0 J005K1EA1A03 - - - - 75 208 - - - - 150 416 165 458 - - 90 250 - -

3 5.0 J005K1EB1A03 41.2 115 56.2 156 - - 97.5 271 112 312 - - - - 127 354 - - 71.2 198

3 7.5 J7X5K1EA1A03 - - - - 112 312 - - - - 225 624 274 687 - - 135 375 - -

3 7.5 J7X5K1EB1A03 61.9 172 84.4 234 - - 146 406 168 468 - - - - 190 531 - - 107 293

Connection Diagram P N N O M M M M N N

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 28: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

27 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

Need Three Phase Wye 230 Volts, 60Hz (Selection Table Number 8)

Need Three Phase Wye 240 Volts, 60Hz (Selection Table Number 9)

Units Req’d

Unit Kva

Use Catalog Number

Have Available Voltage Of

183 192 199 208 218 241 245 253 260 265

Max load Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps

3 .05 J050A1EA1A01 - - .083 2.08 - - 1.65 4.58 1.66 4.17 1.74 4.37 - - 0.91 2.29 - - - -

3 .05 J050A1EB1A01 0.62 1.56 - - 0.54 1.35 - - - - - - 1.33 3.33 - - 0.70 1.77 0.62 1.56

3 .10 J100A1EA1A01 - - 1.66 4.17 - - 3.30 9.17 3.32 8.35 3.48 8.75 - - 1.83 4.58 - - - -

3 .10 J100A1EB1A01 1.25 3.12 - - 1.08 2.71 - - - - - - 2.65 6.67 - - 1.41 3.54 1.25 3.12

3 .15 J150A1EA1A01 - - 2.49 6.25 - - 4.95 13.7 4.98 12.5 5.23 13.1 - - 2.74 6.87 - - - -

3 .15 J150A1EB1A01 1.87 4.69 - - 1.62 4.06 - - - - - - 3.98 10 - - 2.12 5.31 1.87 4.69

3 .25 J250A1EA1A02 - - 4.15 10.4 - - 8.20 22.9 8.30 20.9 8.71 21.9 - - 4.56 11.5 - - - -

3 .25 J250A1EB1A02 3.11 7.81 - - 2.70 6.77 - - - - - - 6.63 16.7 - - 3.52 8.85 3.11 7.81

3 .50 J500A1EA1A02 - - 8.30 20.8 - - 16.5 45.8 16.6 41.7 17.4 43.7 - - 9.31 22.9 - - - -

3 .50 J500A1EB1A02 6.22 15.6 - - 5.39 13.5 - - - - - - 13.3 33.3 - - 7.05 17.7 6.22 15.6

3 .75 J750A1EA1A02 - - 12.4 31.2 - - 24.7 68.8 24.9 62.6 26.1 65.5 - - 13.7 34.4 - - - -

3 .75 J750A1EB1A02 9.33 23.4 - - 8.09 20.3 - - - - - - 19.9 50 - - 10.6 26.6 9.33 23.4

3 1.0 J001K1EA1A02 - - 16.6 41.7 - - 33 91.7 33.2 83.5 34.8 87.5 - - 18.3 45.8 - - - -

3 1.0 J001K1EB1A02 12.5 31.2 - - 10.8 27.1 - - - - - - 26.5 66.7 - - 14.1 35.4 12.5 31.2

3 1.5 J1X5K1EA1A02 - - 24.9 62.5 - - 49.5 137 49.8 125 52.3 131 - - 27.4 68.7 - - - -

3 1.5 J1X5K1EB1A02 18.7 46.9 - - 16.2 40.6 - - - - - - 39.8 100 - - 21.2 53.1 18.7 46.9

3 2.0 J002K1EA1A02 - - 33.2 83.3 - - 66 183 66.4 167 69.7 175 - - 36.6 91.6 - - - -

3 2.0 J002K1EB1A02 24.9 62.5 - - 21.6 54.2 - - - - - - 53.1 133 - - 28.2 70.8 24.9 62.5

3 3.0 J003K1EA1A03 - - 49.8 125.1 - - 99 275 99.6 250.5 104.4 262.5 - - 54.9 137.4 - - - -

3 3.0 J003K1EB1A03 37.5 93.6 - - 32.4 81.3 - - - - - - 79.5 200 - - 42.3 106.2 37.5 93.6

3 5.0 J005K1EA1A03 - - 83 208 - - 165 458 166 417 174 437 - - 91.3 229 - - - -

3 5.0 J005K1EB1A03 62.2 156 - - 53.9 135 - - - - - - 133 333 - - 70.5 177 62.2 156

3 7.5 J7X5K1EA1A03 - - 124 312 - - 247 688 249 626 261 656 - - 137 344 - - - -

3 7.5 J7X5K1EB1A03 93.3 234 - - 80.9 203 - - - - - - 199 500 - - 106 266 93.3 234

Connection Diagram N N S M Q Q Q R R S

Units Req’d

Unit Kva

Use Catalog

Number

Have Available Voltage Of

190 200 208 218 228 252 256 264 272 277

Max Load Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps

3 .05 J050A1EA1A01 - - 0.86 2.08 - - 0.86 2.08 1.73 4.17 1.85 4.37 - - 0.95 2.29 - - - -

3 .05 J050A1EB1A01 0.65 1.65 - - 1.27 3.05 - - - - - - 1.39 3.33 - - 0.74 1.77 0.65 1.56

3 .10 J100A1EA1A01 - - 1.73 4.17 - - 1.73 4.17 3.46 8.34 3.64 8.75 - - 1.91 4.58 - - - -

3 .10 J100A1EB1A01 1.30 3.12 - - 2.55 6.12 - - - - - - 2.77 6.67 - - 1.47 3.54 1.30 3.12

3 .15 J150A1EA1A01 - - 2.59 6.25 - - 2.59 6.25 5.20 12.50 5.46 13.10 - - 2.86 6.87 - - - -

3 .15 J150A1EB1A01 1.95 4.69 - - 3.82 9.16 - - - - - - 4.16 10 - - 2.21 5.31 1.95 4.69

3 .25 J250A1EA1A02 - - 4.32 10.40 - - 4.32 10.40 8.66 20.90 9.09 21.90 - - 4.76 11.50 - - - -

3 .25 J250A1EB1A02 3.25 7.81 - - 6.30 15.10 - - - - - - 6.93 16.70 - - 3.68 8.85 3.25 7.81

3 .50 J500A1EA1A02 - - 8.65 20.80 - - 8.65 20.80 17.30 41.70 18.20 43.70 - - 9.53 22.90 - - - -

3 .50 J500A1EB1A02 6.50 15.60 - - 12.70 30.40 - - - - - - 13.90 33.30 - - 7.36 17.70 6.50 15.60

3 .75 J750A1EA1A02 - - 13.0 31.20 - - 13.0 31.20 26.0 62.60 27.30 65.60 - - 14.30 34.40 - - - -

3 .75 J750A1EB1A02 9.75 23.40 - - 19.2 46 - - - - - - 20.8 50 - - 11 26.6 9.75 23.40

3 1.0 J001K1EA1A02 - - 17.3 41.7 - - 17.3 41.7 34.6 83.4 36.4 87.5 - - 19.1 45.8 - - - -

3 1.0 J001K1EB1A02 13 31.2 - - 25.5 61.2 - - - - - - 27.7 66.7 - - 14.7 35.4 13 31.2

3 1.5 J1X5K1EA1A02 - - 25.9 62.5 - - 25.9 62.5 52 125 54.6 131 - - 28.6 68.7 - - - -

3 1.5 J1X5K1EB1A02 19.5 46.9 - - 38.2 91.6 - - - - - - 41.6 100 - - 22.1 53.1 19.5 46.9

3 2.0 J002K1EA1A02 - - 34.6 83.3 - - 34.6 83.3 69.3 167 72.8 175 - - 38.1 91.7 - - - -

3 2.0 J002K1EB1A02 26 62.5 - - 51 122.4 - - - - - - 55.4 133 - - 29.5 70.8 26 62.5

3 3.0 J003K1EA1A03 - - 51.9 125.1 - - 51.9 125.1 103.8 250.2 109.2 262.5 - - 57.3 137.4 - - - -

3 3.0 J003K1EB1A03 39 93.6 - - 76.5 183.6 - - - - - - 83.1 200 - - 44.1 106.2 39 93.6

3 5.0 J005K1EA1A03 - - 86.5 208 - - 86.5 208 173 417 182 437 - - 95.3 229 - - - -

3 5.0 J005K1EB1A03 65 156 - - 127.2 305.2 - - - - - - 139 333 - - 73.6 177 65 156

3 7.5 J7X5K1EA1A03 - - 130 312 - - 130 312 260 626 273 656 - - 143 344 - - - -

3 7.5 J7X5K1EB1A03 97.5 234 - - 192 460 - - - - - - 208 500 - - 110 266 97.5 234

Connection Diagram N N M R Q Q Q R R S

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 29: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

28 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

Need Three Phase Wye Need Three Phase Wye

460 Volts, 60Hz (Selection Table Number 10) 480 Volts, 60Hz (Selection Table Number 11)

DIAGRAM “M” DIAGRAM “N” DIAGRAM “Q”

DIAGRAM “R” DIAGRAM “S”

# Units

Unit Kva

Use Catalog

Number

Have Available Voltage Of Have Available Voltage Of

406 418 432 438 # Units

Unit Kva

Use Catalog Number

424 436 450

Max Load Max Load Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps

3 .05 J050A1EA1A01 - - 1.66 2.08 - - 3.22 4.04 3 .05 J050A1EA1A01 - - 1.7 2.1 - -

3 .05 J050A1EB1A01 1.25 1.57 - - 2.49 3.12 - - 3 .05 J050A1EB1A01 1.3 1.56 - - 2.6 3.13

3 .10 J100A1EA1A01 - - 3.31 4.15 - - 6.62 8.31 3 .10 J100A1EA1A01 - - 3.5 4.2 - -

3 .10 J100A1EB1A01 2.49 3.12 - - 4.97 6.24 - - 3 .10 J100A1EB1A01 2.6 3.12 - - 5.2 6.25

3 .15 J150A1EA1A01 - - 4.97 6.24 - - 9.94 12.48 3 .15 J150A1EA1A01 - - 5.2 6.25 - -

3 .15 J150A1EB1A01 3.73 4.68 - - 7.46 9.36 - - 3 .15 J150A1EB1A01 3.9 4.68 - - 7.8 9.38

3 .25 J250A1EA1A02 - - 8.28 10.39 - - 16.6 20.84 3 .25 J250A1EA1A02 - - 8.7 10.4 - -

3 .25 J250A1EB1A02 6.22 7.81 - - 12.4 15.56 - - 3 .25 J250A1EB1A02 6.5 7.82 - - 13 15.6

3 .50 J500A1EA1A02 - - 16.6 20.84 - - 33.2 41.67 3 .50 J500A1EA1A02 - - 17.4 20.9 - -

3 .50 J500A1EB1A02 12.5 15.69 - - 24.69 31.25 - - 3 .50 J500A1EB1A02 13 15.6 - - 26 31.2

3 .75 J750A1EA1A02 - - 24.8 31.12 - - 49.6 62.25 3 .75 J750A1EA1A02 - - 26 31.2 - -

3 .75 J750A1EB1A02 18.7 23.47 - - 37.3 46.82 - - 3 .75 J750A1EB1A02 19.5 23.4 - - 39 46.9

3 1.0 J001K1EA1A02 - - 33.1 41.54 - - 66.2 83.09 3 1.0 J001K1EA1A02 - - 35 42 - -

3 1.0 J001K1EB1A02 24.9 31.25 - - 49.7 62.38 - - 3 1.0 J001K1EB1A02 26 31.2 - - 52 62.5

3 1.5 J1X5K1EA1A02 - - 49.7 62.38 - - 99.4 124.75 3 1.5 J1X5K1EA1A02 - - 52 62.5 - -

3 1.5 J1X5K1EB1A02 37.3 46.94 - - 74.6 93.63 - - 3 1.5 J1X5K1EB1A02 39 46.8 - - 78 93.8

3 2.0 J002K1EA1A02 - - 66.3 83.22 - - 133 166.93 3 2.0 J002K1EA1A02 - - 69 82.9 - -

3 2.0 J002K1EB1A02 49.7 62.38 - - 99.5 124.88 - - 3 2.0 J002K1EB1A02 52 62.5 - - 104 125

3 3.0 J003K1EA1A03 - - 99.3 124.64 - - 198.6 249.27 3 3.0 J003K1EA1A03 - - 104 125 - -

3 3.0 J003K1EB1A03 74.6 93.93 - - 149 187.01 - - 3 3.0 J003K1EB1A03 78 93.8 - - 156 187.6

3 5.0 J005K1EA1A03 - - 166 208.35 - - 322 404.16 3 5.0 J005K1EA1A03 - - 174 209.2 - -

3 5.0 J005K1EB1A03 125 156.89 - - 249 312.53 - - 3 5.0 J005K1EB1A03 130 156.3 - - 260 312.7

3 7.5 J7X5K1EA1A03 - - 248 311 - - 496 622 3 7.5 J7X5K1EA1A03 - - 260 312 - -

3 7.5 J7X5K1EB1A03 187 235 - - 373 468 - - 3 7.5 J7X5K1EB1A03 195 234 - - 390 469

Connection Diagram R R Q Q R R Q

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 30: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

29 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

Single Phase Group “B” Applications, 60Hz (Selection Table Number 12)

DIAGRAM “B” DIAGRAM “E” DIAGRAM “F”

Three Phase Group “B” Applications, 60Hz (Selection Table Number 13)

DIAGRAM “I” DIAGRAM “K” DIAGRAM “N”

#

Units ₁

Unit Kva

Use Catalog

Number

Available Voltage/Output Voltage 200/240 230/277 346/380 362/380 378/416 416/457 436/480 458/480 277/230 480/456 504/480 528/480

Max load Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps

1 .25 J250A1KC1A02 1.25 5.2 1.44 5.2 1.98 5.2 3.95 10.4 2.16 5.2 2.38 5.2 2.5 5.2 4.99 10.4 1.44 6.26 5.23 11.4 5.47 11.4 2.75 5.72

1 .50 J500A1KC1A02 2.5 10.4 2.88 10.4 3.95 10.4 7.9 20.8 4.33 10.4 4.76 10.4 4.99 10.4 9.98 20.8 2.88 12.5 10.4 22.8 10.9 22.8 5.49 11.4

1 .75 J750A1KC1A02 3.75 15.6 4.32 15.6 5.93 15.6 11.9 31.2 6.49 15.6 7.14 15.6 7.49 15.6 15 31.2 4.33 18.8 15.7 34.2 16.4 34.2 8.24 17.2

1 1.0 J001K1KC1A02 5.0 20.8 5.76 20.8 7.9 20.8 15.8 41.6 8.65 20.8 9.52 20.8 9.98 20.8 20 41.6 5.76 25 20.9 45.6 21.8 45.6 11 22.9

1 1.5 J1X5K1KC1A02 7.5 31.2 8.64 31.2 11.9 31.2 23.8 62.5 13 31.2 14.3 31.2 15 31.2 30 62.5 8.64 37.6 31.3 68.4 32.8 68.4 16.5 34.3

1 2.0 J002K1KC1A02 10 41.6 11.5 41.6 15.8 41.6 31.6 83.3 17.3 41.6 19 41.6 20 41.6 40 83.3 11.5 50.1 41.8 91.2 43.7 91.2 22 45.8

1 3.0 J003K1KC1A03 15 62.5 17.3 62.5 23.8 62.5 47.5 125 26 62.5 28.6 62.5 30 62.5 60 125 17.3 75.3 62.7 136 65.2 136 33 68.8

1 5.0 J005K1KC1A03 25 104 28.8 104 39.5 104 79 208 43.3 104 47.6 104 49.9 104 99.8 208 28.8 125.3 104.5 227 108 227 54.9 114.4

1 7.5 J7X5K1KC1A03 37.5 156 43.2 156 59.3 156 118.6 312 64.9 156 71.4 156 74.9 156 149.8 312 43.2 187.9 156.8 341 163 341 82.4 171.6

Connection Diagram B B F E F F F E B E E F

Unit Kva

Use Catalog

Number

Available Voltage/Output Voltage 362/380 346/416 430/473 400/480 436/380 460/483 457/380 504/480 528/480

Max Load Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps

.25 J250A1KC1A02 6.52 10.4 3.75 5.2 4.26 5.2 4.33 5.2 4.33 5.2 8.7 10.4 4.12 6.25 9.08 10.9 4.76 5.72

.50 J500A1KC1A02 13.0 20.8 7.5 10.4 8.52 10.4 8.65 10.4 8.65 10.4 17.4 20.8 8.23 12.5 18.2 21.8 9.51 11.4

.75 J750A1KC1A02 19.6 31.2 11.2 15.6 12.8 15.6 13 15.6 13 15.6 26.1 31.2 12.3 18.8 27.2 32.8 14.3 17.2

1.0 J001K1KC1A02 26.1 41.6 15 20.8 17 20.8 .17.3 20.8 17.3 20.8 34.8 41.6 16.5 25 36.3 43.7 19 22.9

1.5 J1X5K1KC1A02 39.1 62.4 22.5 31.2 25.5 31.2 26 31.2 26 31.2 52.2 62.4 24.7 37.5 54.5 65.5 28.5 34.3

2.0 J002K1KC1A02 52.2 83.2 30 41.6 34.1 41.6 34.6 41.6 34.6 41.6 69.6 83.2 32.9 50 72.6 87.4 38 45.8

3.0 J003K1KC1A03 78.4 125 45 62.5 51.2 62.5 52 62.5 52 62.5 104.6 125 49.5 75.2 109.7 131.3 57.2 68.8

5.0 J005K1KC1A03 130.4 208 75.1 104 85.2 104 86.6 104 86.6 104 174 208 82.3 125.1 181.6 218.4 95.1 114.4

7.5 J7X5K1KC1A03 195.6 312 112.6 156 127.8 156 129.9 156 129.9 156 261 312 123.5 187.6 272.4 327.6 142.7 171.6

Connection Diagram I N K N K I N I K

Units Required 2 3 2 3 2 2 3 2 2

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 31: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

30 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

Need Three Phase Open Delta 480 Volts, 60Hz Need Single Phase 480 Volts, 60Hz

(Selection Table Number 14) (Selection Table Number 15)

DIAGRAM “I” DIAGRAM “J” DIAGRAM “T”

DIAGRAM “E” DIAGRAM “H” DIAGRAM “U”

Units Req’d

Use Catalog

Number

Have Available Volts Of Have Available Volts Of

600 575 575 Units Req’d

Use Catalog Number

600 575 575

Max Load Max Load Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps Kva-Amps

2 G500A1KF1A02 4.3 5.1 - - - - 1 G500A1KF1A02 2.5 5.2 - - - -

2 G001K1RF8A02 - - - - 4.1 4.9

1 G001K1RF8A02 - - - - 2.4 5.0

2 G750A1KF1A02 6.5 7.8 - - - - 1 G750A1KF1A02 3.7 7.7 - - - -

2 G001K1RF8A02 - - - - 6.2 7.4 1 G001K1RF8A02 - - - - 3.6 7.5

2 G001K1KF1A02 8.6 10.3 - - - - 1 G001K1KF1A02 5.0 10.4 - - - -

2 G001K1RF8A02 - - - - 8.3 9.9 1 G001K1RF8A02 - - - - 4.8 10

2 G1X5K1KF1A02 13 15.6 - - - - 1 G1X5K1KF1A02 7.5 15.6 - - - -

2 G1X5K1RF8A02 - - - - 12.4 14.9 1 G1X5K1RF8A02 - - - - 7.2 15

2 G002K1KF1A02 17.2 20.6 - - - - 1 G002K1KF1A02 10 20.8 - - - -

2 G002K1RF8A02 - - - - 16.5 19.8 1 G002K1RF8A02 - - - - 9.6 20

2 G003K1KF7A03 25.8 31 - - - - 1 G003K1KF7A03 15 31.2 - - - -

2 G003K1RF8A03 - - - - 24.8 29.8 1 G003K1RF8A03 - - - - 14.3 29.7

2 G005K1KF7A03 43.2 51.9 - - - - 1 G005K1KF7A03 25 52 - - - -

2 G005K1RF8A03 - - - - 41 49.3 1 G005K1RF8A03 - - - - 24 50

2 G7X5K1KF7A03 65 78.1 - - - - 1 G7X5K1KF7A03 37.5 78.1 - - - -

2 G7X5K1RF8A03 - - - - 62 74.5 1 G7X5K1RF8A03 - - - - 36 75

2 G010K1KF7A03 86 103.4 - - - - 1 G010K1KF7A03 50 104.1 - - - -

2 G010K1RF8A03 - - 83 99.8 - - 1 G010K1RF8A03 - - 48 100 - -

2 G015K1KF6A03 130 156.3 - - - - 1 G015K1KF6A03 75 156.2 - - - -

2 G015K1RF8A03 - - 124 149.1 - - 1 G015K1RF8A03 - - 72 150 - -

Connection Diagram I J T Connection Diagram E H U

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 32: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

31 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

Transformer Accessories Wall Mounting Brackets are used to wall mount most

15 through 75Kva and some 100 and 112.5Kva Type

1-V and 3-V transformers. this bracket allows for 6”

Clearance from the wall as recommended by Micron.

A Weathershield Kit consisting of a front and rear cover shield must be installed on all ventilated dry-type

transformers when the unit is located outdoors. The shields

protect the transformer top ventilation openings against rain

but allow for proper ventilation. Field installation hardware

is not required. Proper installation provides a NEMA 3R

rating.

Refer to the specific transformer listing for selection of the

proper kit.

What is an LVGP Transformer: Transformers are AC to AC devices. You cannot transform DC Enclosed Power Transformers can be either single or three phase. They are also called "LVGPs" or "Dry Types". These are always in a potted or ventilated enclosure. TERMS: Sinusoidal: Or sine wave. A mathematical function that describes a smooth repetitive oscillation. The phase is defined where in the cycle the oscillation begins. See following depiction.

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 33: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

32 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

Three Phase: The common method of electrical power generation and transmission. The generator at the power station converts mechanical power into a set of alternating electrical currents, one from each electromagnetic coil or winding of the generator. The currents are sinusoidal functions of time, all at the same frequency but with different phases. The phases are equally spaced and separated from each other by 120 degrees. 3 cycles 120° apart = 360° or one revolution of the generator. It is the revolving magnetic field caused by the three phases that causes an electric motor to start turning.

2-Pole/Phase Three Phase Motor

Single Phase: Single phase power is produced from a three phase source by connecting either between a phase and neutral or connecting phase-to-phase. Interestingly, single phase cannot produce necessary revolving magnetic field to start an electric motor turning. All single phase motors need additional circuits for starting. A single-phase sine wave is depicted as is a 2-Pole Single-Phase motor. as opposed to the rotating field produced by three phase, the single phase fields merely oscillates. Once rotation begins the momentum of the rotor allows rotation through the "dead areas". A phase-leading current is necessary to begin rotation and is developed by the added resistance of a start winding or by a capacitor.

Neutral: The neutral is the point on a three phase system where each of the phase points are equal in magnitude and equally spaced in phase. It is the mathematical center of an equilateral triangle formed by the three phase points. Because of this, the phase-to-phase voltage is √3 (1.732) times the phase-to-neutral voltage. Example: 120V phase-to-neutral X 1.732 = 208V phase-to-phase. G015K5QH2A04 has a secondary of 208Y/120 The neutral allows the balancing of single phase loads between any/all of the individual three phase legs and the neutral point while still allowing for normal three phase loading. The neutral is also a grounded conductor which typically ties to the system's earth ground at the breaker panel. FCAN/FCBN: An acronym for Full Capacity Above Normal and Full Capacity Below Normal. These are taps on the primary side to adjust for slightly low or high line voltage. Expressed in % of adjustment. Example: FCAN: 2 @ +2.5% / FCBN: 4 @ -2.5%

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 34: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

33 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

Phase-to-Phase: Voltage measured between any two "corners" of a Delta connection or between any two "legs" of a Wye connection. Wye: Also called “Star”. All phase windings are connected at a common point (resembles a star) which is typically where a fourth wire (neutral) and a ground is connected. Three phase loads are connected to the “A”, “B” and “C” (line-to-line) terminations while single phase loads are typically connected line-to-neutral. Unless they are light, connecting single phase loads line-to-line unevenly loads two windings, may unbalance the phases and derates the transformer more than connecting line-to-neutral.

Delta: A common three-wire, three phase system in which the voltage potential between each pair of wires is the actual transformer voltage. Although typically ungrounded, a “grounded reference” can be developed by center-tapping the “A”-“C” winding (see High Leg) allowing for more load flexibility. High Leg: Also called a “Wild Leg” or “Stinger”. On a three phase Delta system, a mid-point or center tap of the “A” to “C” phase winding is labeled “N” and becomes a grounded reference (sometimes referenced to as neutral). Voltage measurements between possible connection points on the above diagram are as follows: Phase-to-Phase Phase-to-Neutral “A”-“B” = 240V “A”-“N” = 120V (240/2) “B”-“C” = 240V “B”-“N” = 208V (240/2 X √₃) “C”-“A” = 240V “C”-“N” = 120V (240/2)

High Leg Delta systems provide increased voltage flexibility over similar Wye systems because, in addition to a ground and 120 volt single phase, they offer a higher (240V) three phase connection. The disadvantage is that no single phase 120 volt load can be connected to the “B” leg and this may unbalance the total load. Open Delta: A three phase transformer bank using two transformers. Although one side of the Delta is physically not there, an electrical measurement is possible across the missing side (diagram below)

An Open Delta is not as efficient as a three transformer system and is normally reserved for smaller loads. An Open Delta is capable of 57.7% of a true Delta load. Many three phase buck-boost applications are wired in Open Delta configuration.

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 35: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

34 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A

NOTES

Courtesy of Steven Engineering, Inc. - (800) 258-9200 - [email protected] - www.stevenengineering.com

Page 36: Advanced transformers built for the industrial environment · All Micron dry-type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI

35 Contact Micron Industries Corporation: +1.630.516.1222 www.micronpower.com Form: LVGP-14A