DESCRIPTION
Micron Transformers. Presented by Richard Lussier and John Levine Levine Lectronics and Lectric. Types Of Transformers. Impervitran Globaltran LVGP Buck Boost Power Supplies. Impervitran. Made in USA First Encapsulated Transformer 20 Year Warranty - PowerPoint PPT PresentationTRANSCRIPT
Micron Transformers
Presented by
Richard Lussier and John Levine
Levine Lectronics and Lectric
Types Of Transformers
• Impervitran
• Globaltran
• LVGP
• Buck Boost
• Power Supplies
Impervitran
• Made in USA• First Encapsulated Transformer• 20 Year Warranty• Secondary Fuse Clips where applicable• Optional Primary Clips ( Factory / Field)• Touch Safe Terminal Covers • 14 Standard Primary / Secondary selections• 105 / 130 / 180 degree c rise
IMPERVITRAN
• Ratings UL CSA 50 – 60 HZ Rated
• 25VA – 5 KVA open type• Multiple Primary / Secondary
values• Center tap secondary available• Primary Voltages up to 600V AC• Secondary Voltages 24V AC• Custom Transformers
Globaltran
• International Transformer
• CE Labeled
• 50 – 60 HZ Ratings
• Meets or exceeds IEC-742
• Standard with Touch Safe Terminals IP20
• 20 Year Warranty
• 7 Standard Pri / Sec Offerings
• 50 VA – 750 VA ratings
• Customs Available
LVGPLow Voltage General Purpose
• Dry Type Enclosed Transformers
• Single Phase / Three Phase Ratings
• Indoor / Outdoor Ratings with optional drip hoods
• 60 HZ Rating only• Type 1 or 3R Enclosure
Rating Available
LVGPSingle Phase
• Seven Standard Voltage Patterns
• Voltage Range Pri 120 to 600V
• Secondary 120 – 240V AC
• KVA Range 0.5 KVA – 167 KVA
• Transformers 2 KVA and Below Copper
• Transformers 3 KVA and Above Aluminum
LVGPThree Phase
• 8 Standard Voltage Ranges
• Voltage Range Primary 208V – 600V
• Secondary 120V – 480V
• KVA Range 3 KVA – 750 KVA
• Transformers 2 KVA and Below Copper
• Transformers 3 KVA and Above Aluminum
Buck Boost Transformers
• Buck Boost Transformers are used to convert a lower or higher voltage to a more suitable voltage.
• Ex. 230 to 208V Buck
• 240 to 277 Boost
• Range is about 20 % voltage change
• Both Single and Three Phase Conversations
• Wired in Autotransformer configuration
Power Supplies• UL/ CUL/ UL508 / CE • 5 Year Warranty• Voltage Input 85V – 264VAC• Secondary Voltage 12/24/48VDC• Wattage 60 – 480 • Current 2.5 – 13.3 amps• Operating Temp - 10 Deg – 60 deg C• DIN Rail Mounting• Power Boost 25% for 5 sec
Power Supply
• First IP67 Power Supply on Market
• UL Recogonized, CUR, CE
• Voltage 90 -264 V Primary
• 24 VDC Secondary
• 2 or 4 amp version
• 50 – 100 watt
Micron Transformers
Capabilities Module
Product Capabilities
• ENCAPSULATED CONTROL TRANSFORMERSIMPERVITRAN DESIGN -- Part numbers beginning with B
• VOLTAGE CAPABILITY– Primary 100V through 600V– Secondary 5V through 240V
• VA RANGE – 25VA through 5000 VA
• TEMPERATURE CLASS 105, 130 & 180
• Terminations available– 4-terminal block-standard– 6-terminal block-optional– Fastons-optional
• Installed fusing capabilities– Type "K" (13/32 x 1-1/2) secondary clips
(standard for most part numbers)– Class "CC" primary fuse block – Type "M" (9/16 x 2) secondary clips– Type "Q" (1/4 x 1-1/4) secondary clips– Thermal fusing– Custom options available
Product Capabilities
III LOW VOLTAGE GENERAL PURPOSE (LVGP) and BUCK-BOOST 600 Volt Class Part numbers starting with G, J
• Single phase encapsulated and ventilated from 50VA through 167KVA
• Three phase encapsulated and ventilated from 3 through 750KVA
Features & Benefits
Features ImperviTRAN designs
feature Class 105C, 130C & 180C encapsulated construction.
Benefits Customers can choose the
design system that best serves their needs.
Features ImperviTRAN designs feature molded terminal
block construction.
All have provision for SafeTouch IEC-529/IP-20
rated termination covers.
Benefits Molded terminal blocks
provide superior strength, electrical
insulation and ease of wire termination. IEC-529/IP-20 terminal covers provide unsurpassed product safety.
Features Provision for secondary
fusing is standard on most designs utilizing molded terminal blocks.
Provision for primary fusing available on
most designs.
Benefits Saves valuable panel space
and simplifies panel assembly.
Features GlobalTRAN designs are
approved to IEC-989, 742 or 61558 and carry the CE mark. GlobalTRAN is designed in ImperviTRAN construction.
Benefits Meets the requirements of
the international Low Voltage Directive 72/73/EEC.
GlobalTRAN can be designed to virtually any customer application.
Features Unprecedented 20 year
warranty on control Transformers (600 volt class).
Benefits Worry free performance for
the life of the application.
Features
General purpose enclosed units available in a wide selection of encapsulated or ventilated, tapped and untapped configuration.
Benefits Allows for one of the widest
product choices in the industry.
Micron Transformers
Part number module
ImperviTRAN, ValuTRAN, EconoTRAN
• All ImperviTRAN P/Ns begin with “B”– B050BTZ13JK
• All obsolete ValuTRAN P/Ns begin with “V”– VF1K0BTZ13JK
• All obsolete EconoTRAN P/Ns begin with “E”– EF1K0BTZ13
GlobalTRAN
• GlobalTRAN is built in ImperviTRAN construction.
• All GlobalTRAN P/Ns end in “GA,GAF or GAH”– B050-2001-GA– B150-2004-GAF– B1K0-2008-GAH
Frequency
• ImperviTRAN designs are rated at 50/60 Hertz (Hz).
• A 50Hz rated device can operate at 60Hz but a 60Hz device can’t operate at 50Hz.– A device can always operate at a frequency higher
than nameplate.
• Some P/Ns include an “F” or “N” after the initial letter.– VF1K0BTZ13JK– BN1K0BTZ13– HN1K5G1519P
• The “F” = 50/60Hz.• The “N” = 60Hz.
Exceptions
• P/Ns that date back before 1983– May include a letter as the 2nd or 3rd character. This
identified the customer.
– BRQX040JCBXT7-50
– May include an “X” as the 2nd – 4th character. This identified special construction.
– BX100MBT13
– BRQX040JCBXT7-50
Temperature Class
• An ending “F” denotes Class 130°C.• B150BTZ13JKF
– Internally, Micron may replace with a leading “M”.• M150BTZ13JK
• An ending “H” denotes Class 180°C.• B1K5BTZ13JKH
– Internally, Micron may replace with a leading “N”.• N1K5BTZ13JK
VA/KVA
• VA = Volts X Amps• KVA = VA X 1000
• The numbers following the initial letter in the P/N = VA size.– B050BTZ13JK (50VA)– B100BTZ13JK (100VA)– B100-2003-GA– VF1K0BTZ13JK (1000VA or 1KVA)
Primary Voltages
• The letters following the VA size = primary voltage.– B050LP7JK
• letters and representative voltages are:– B = 230 P = 240 W = 575– L = 120 R = 380– M = 208 T = 460– Q = 277 U = 480
• A “Z” as the last letter = transformer can handle a voltage range 5% of nominal voltage (triple rated).– B050BTZ13JK
• 220/230/240
– B050WZ13XK• 550/575/600
– B1K0BTWZ37XKH• 220/230/240, 440/460/480, 550/575/600
Exceptions
• The “Z” is deleted on triple rated P/Ns that would be longer than 12 characters.– B100MBT713XK
• All voltage reference is deleted from serialized P/Ns.– B150-0484-1
– B150-2004-GAF
Secondary Voltages
• The numbers following the primary voltage = secondary voltage– B050LP7JK B050PU1519JJ
– B050MQ15XK EF1K0BTZ1318
– B050MBT713XK
• letters and representative voltages are:– 7 = 24 18 = 230
– 13 = 115 19 = 240
– 15 = 120 34 = 110/220
Exceptions
• All voltage reference is deleted from serialized P/Ns.– B150-0484-1– B150-2004-GAF
Accessories
jumpersfuse clips
covers
Jumpers
• Jumpers are used to connect terminals together. Common uses are to derive either 230 or 460 from a series/parallel wound device or sometimes to connect fuse clips on the terminal block.
• Jumpers are denoted by a “J” as one or both of the final 2 characters on the P/N.– B050 BTZ13JK– B050PU1519JJ
Exceptions• Jumpers are included but not denoted in the
following P/N constructions:
EconoTRANEF1K0BTZ13
GlobalTRANB100-2003-GA
• The letter “T” as one of the last 2 characters denotes an optional Stack ‘n Store (J3) jumper.– B100BTZ13TK
Secondary Fuse Clips
• Virtually all ImperviTRAN products include mounted fuse clips for a 13/32 X 1-1/2 midget fuse on the secondary side.
• This is denoted with a “K” at the end of the P/N, –1 on a serialized P/N & “F” on GlobalTRAN.– B050BTZ13JK– B050MQ15XK– B050-0482-1 – B050-2001-GF
• Mounted fuse clips for ¼ X 1¼ or 9/16 X 2 type secondary fuses can be ordered by substituting the “K” with the following letter:– Q = ¼ X 1¼ B100BTZ13JQ
– M = 9/16 X 2 B100BTZ13JM
• A “-3” at the end of a serialized P/N= no fusing capability.
Primary Fuse Blocks
• Class ‘CC’ style & midget style fuse blocks can be ordered as a factory installed option on ImperviTRAN & ValuTRAN.
• The letter “R” as the next to last character = a class ‘CC’ fuse block.– B100BTZ13RB
• The letter “N” as the next to last character = a midget style fuse block.– B100BTZ13NB
• A “–8” on a serialized P/N = class ‘CC’ fuse block.– B100-0483-8
• The letter “K” at the end of a GlobalTRAN P/N = class ‘CC’ fuse block.– B100-2003-GK
• The letter “G” at the end of a GlobalTRAN P/N when secondary fusing is also ordered = class ‘CC’ fuse block.– B100-2003-GG
Exceptions
• P/Ns dating before 1983– Will not include characters for jumpers or fuse clips
(although installed).– B100BTZ13– May include a customer identifier after the secondary
voltage identifier.– BX050ER7-FE– May include an identifier calling out a design feature, ie:
CT = Center Tap– B050L7-CT
Safetouch Covers
• Safetouch covers are included with all GlobalTRAN products.
• Safetouch covers are available for all products that utilize the ImperviTRAN design.