addressable fire alarm systems - horing lih

2
3 Addressable System QA Series Addressable Fire Alarm Systems QA17-K QA17-H QA17-B QA17-A QA19 QA0817 RS-485 QA16 Addressable Fire Alarm Control Panel QA17-K Conventional Manual Call Point Conventional Detector Fire Alarm Bell Remote Indicating Lamp Conventional Detector QA16 Addressable Fire Alarm Control Panel QA Series Addressable Fire Alarm System Configuration QA17-A QA01 Addressable Photoelectric Smoke Detector QA05 Addressable Combination Smoke and Heat Detector QA06 Addressable Heat Detector QA19 Addressable Manual Call Point QA0817 Addressable Manual Call Point QA17-H QA17-B QA17-B QA17-H QA17-B HORING LIH INDUSTRIAL CO., LTD.

Upload: others

Post on 02-Feb-2022

50 views

Category:

Documents


1 download

TRANSCRIPT

3

Addressable System

QA SeriesAddressable Fire Alarm Systems

QA17-K

QA17-HQA17-B

QA17-A

QA19QA0817

RS-485

QA16 Addressable Fire Alarm Control Panel

QA17-K

Conventional Manual Call Point

Conventional Detector

Fire Alarm Bell

Remote Indicating Lamp

Conventional Detector

QA16 Addressable Fire Alarm Control Panel

QA Series Addressable Fire Alarm System Configuration

QA17-A

QA01 Addressable Photoelectric Smoke

Detector

QA05 Addressable Combination Smoke

and Heat Detector

QA06 Addressable Heat Detector

QA19 Addressable Manual Call Point

QA0817 Addressable Manual Call PointQA17-H

QA17-BQA17-BQA17-H QA17-B

HORING LIH INDUSTRIAL CO., LTD.

4

Addressable System

Characteristics• Low power consumption in monitoring mode, high stability.

• Easy installation, either single module installation or several modules installed on a special mounting bar. Implanted type gang box is available to suit the decoration design.

• The Module is designed with separate input and output

wiring.

SpecificationsModel QA19 QA0817Purpose Signal will directly sent to panelSystem Connected Control panel loop Input Source Loop signalOutput Contacts/Load N/AAddress Coding BinaryOperating Voltage 26 V DCAlarm Current 6mAQuiescent Current 850µAAmbient Temperature 0°C ~ +50°CMaterial Fire-proof plasticColor RedDimensions(mm) 140(Dia.) x 45(H) 87.5(H) x 87.5(W) x 54(D)Remarks - Protection Cover is optional

SpecificationsModel QA17-K QA17-B QA17-A QA17-HType Monitor Module Control Module Output Module Isolator Module

Purpose Confirmation of external signal

Input & Output for all systems

Supply higher current such as evacuation

Isolate from control unit when external fault

System Connected Receive activation signal from external device

Series with conventional detector Series with QA17-B Series with all system zone

Input Source Activation signal Loop signal 24VDC / 110VAC / 220VAC Zone short circuit

Output Contacts/Load N/A 1 in 2 out COM. N.O. N.C. 1.5A @30V DC

COM. N.O. N.C. 4A @30VDC,

2.5A @ 250VACN/A

EOL Resistor 10kΩ 10kΩ N/A N/AAddress Coding Binary Binary N/A N/AAmbient Temp. 0°C ~ +50°CMaterial Fire-proof plasticColor GreenDimensions (mm) H x W x D 55 x 27 x 16 60 x 76 x 31

Module Series

Addressable Manual Call Points

• Control Module QA17-B is designed to control input & output for all kinds of systems. (fire alarm, smoke evacua-tion, sprinkler, foam , winding door...etc.)

• Output module QA17-A can directly connect with power source. The output voltage from N.O. & N.C. will be the same as input voltage.

• Monitor module QA17-K is designed to monitor security condition, such as water supply, pump action ...etc.

HORING LIH INDUSTRIAL CO., LTD.