ADDENDUM NO. CC-2 CC-2 - 1
ADDENDUM NO. CC-2 PLATTVIEW JR & SR HIGH SCHOOL RENOVATIONS SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS SPRINGFIELD, NEBRASKA DLR GROUP PROJECT NO. 10-13125-30 COMBINED CONTRACT September 20, 2017 NOTICE TO BIDDERS: Amend the Project Manual and Drawings to the above referenced project as follows:
PROJECT MANUAL ITEM NO. 1 SECTION 004113 BID FORM
A. Delete Bid Form and substitute new Bid Form as shown on Attachment No. 1. ITEM NO. 2 SECTION 074113.16 STANDING-SEAM METAL ROOF PANELS
A. 1.2.A. Add the following: “and metal wall panels.”
B. 2.2. Add the following: “AND METAL WALL PANELS”
ITEM NO. 3 SECTION 123553.15 PLASTIC-LAMINATED-CLAD CASEWORK AND LABORATORY
CASEWORK
A. 2.7.C Add paragraph.
C. Cork for direct, frameless application at millwork (Tack Surface – TS-1):
1. Manufacturers: Subject to compliance with requirements, provide products by the following:
a. Forbo Flooring Systems.
2. Linoleum Resilient Cork Sheet, Bulletin Board: Seamless, homogeneous, self-sealing sheet consisting of granulated cork, linseed oil, resin binders, and dry pigments that are mixed and calendared onto a natural burlap backing; with integral color throughout with surface-burning characteristics indicated.
a. Color: As selected from manufacturer’s full range. b. Thickness: 1/4 inch (6 mm). c. ASTM E-84 (Fuel Contribution): Class B. d. NFPA 253 (Critical Radiant Flux): Class II. e. Adhesive for Installation to Wall and Millwork Surfaces: Manufacturer’s standard adhesive applied with notch trowel at manufacturer’s recommended
spreading rate.
B. Delete Paragraph 2.11.A in its entirety.
C. Delete Paragraph 2.11.B in its entirety.
Architecture Engineering Planning Interiors
6457 Frances Street, Suite 200 Omaha, NE 68106
tel 402/393-4100 fax 402/393-8747
www.dlrgroup.com
PLATTVIEW JR & SR HIGH SCHOOL RENOVATIONS 10-13125-30 SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS SPRINGFIELD, NEBRASKA
ADDENDUM NO. CC-2 CC-2 - 2
D. Paragraph 2.11.C, add the following:
1. “Troughs to be 2 inches deep.”
E. Subparagraph 2.13.B.1, add the following:
1. “In Room F223.”
F. Delete Subparagraph 2.13.B.2 in its entirety.
ITEM NO. 4 SECTION 223400 FUEL FIRED, DOMESTIC WATER HEATERS
A. Subparagraph 2.1.A.1 add the following: “c. Lochinvar”
B. Subparagraph 2.1.A.2 add the following: “c Lochinvar”
C. Subparagraph 2.1.A.3 add the following: g. Bell & Gosset
ITEM NO. 5 SECTION 224000 PLUMBING FIXTURES
A. Subparagraph 2.1.A.5 add the following manufacturer: “5. Sloan.”
B. Paragraph 2.12, add the following:
“E. CS-4: Single compartment, counter-mounting, stainless-steel commercial sink.
1. Overall Dimensions: 22 inches x 19-1/2 inches x 7-5/8-inch. 2. Metal Thickness: 18 gage. 3. Each Compartment:
a. Dimensions: 18 inches x 14 inches x 7-5/8-inch. b. Drains: Provide with Elkay LK-2219 Type 304 stainless steel body an removable conical basket strainer with metal ball bearing locking stem and rubber stopper with NPS 1-1/2 (DN 40) tailpiece.
1) Location: Off-Centered Rear.
c. Sink undercoating to dampen sound and prevent condensation.”
ITEM NO. 6 SECTION 232123 HYDRONIC PUMPS
A. Paragraph 2.1.A. add the following: “6. Armstrong”
PLATTVIEW JR & SR HIGH SCHOOL RENOVATIONS 10-13125-30 SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS SPRINGFIELD, NEBRASKA
ADDENDUM NO. CC-2 CC-2 - 3
ITEM NO. 7 SECTION 233423 POWER VENTILATORS A. Paragraph 2.1.A. add the following: “4. Twin city Fan Company”
PLATTVIEW JR & SR HIGH SCHOOL RENOVATIONS 10-13125-30 SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS SPRINGFIELD, NEBRASKA
ADDENDUM NO. CC-2 CC-2 - 4
DRAWINGS ITEM NO. 6 DRAWING A1.2F FLOOR PLAN, MAIN LEVEL – AREA F
A. Modify Drawing as shown per Attachment A1.2F-1.
ITEM NO. 7 DRAWING A9.1 DOOR AND FRAME SCHEDULE
A. Door F103A add Frame Type “1” and Door Type “A”.
B. Door F216 Janitor, delete hardware set “26” and replace with hardware set “20”. ITEM NO. 8 DRAWING A11.1 CASEWORK ELEVATIONS
A. Modify Drawing as shown per Attachment A11.1-1.
ITEM NO. 9 DRAWING A11.2 CASEWORK ELEVATIONS
A. Modify Drawing as shown on Attachment A11.2-1.
ITEM NO. 10 DRAWING MD1.1F HVAC DEMOLITION PLAN, LOWER LEVEL – AREA F
A. Modify Drawing as shown on Attachment MD1.1F-1.
ITEM NO. 11 DRAWING MD1.2F HVAC DEMOLITION PLAN, MAIN LEVEL – AREA F
A. Modify Drawing as shown on Attachment MD1.2F.
ITEM NO. 12 DRAWING M1.2F HVAC PLAN, MAIN LEVEL – AREA F
A. Modify Drawing as shown on Attachment M1.2F-1.
ITEM NO. 13 DRAWING M2.1F HVAC PIPING PLAN, LOWER LEVEL – AREA F
A. Modify Drawing as shown on Attachment M2.1F-1.
ITEM NO. 14 DRAWING M2.2F HVAC PIPING PLAN, MAIN LEVEL – AREA F
A. Modify Drawing as shown on Attachment M2.2F-1.
ITEM NO. 15 DRAWING M4.1 MECHANICAL DETAILS
A. Modify detail 4 per as shown on Attachment M4.1-1.
ITEM NO. 16 DRAWING M4.2 MECHANICAL DETAILS
A. Modify details 5 & 9 as shown on Attachment M4.2-1.
ITEM NO. 17 DRAWING M5.1 MECHANICAL SCHEDULES
A. Modify Drawing as shown on Attachment M5.1-1.
PLATTVIEW JR & SR HIGH SCHOOL RENOVATIONS 10-13125-30 SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS SPRINGFIELD, NEBRASKA
ADDENDUM NO. CC-2 CC-2 - 5
ITEM NO. 18 DRAWING M5.2 MECHANICAL SCHEDULES
A. Modify Drawing as shown on Attachment M5.2-1.
ITEM NO. 19 DRAWING P0.1C UNDERGROUND PLUMBING PLAN, MAIN LEVEL – AREA C
A. Modify Drawing as shown on Attachment P0.1C-1.
ITEM NO. 20 DRAWING P1.2F PLUMBING PLAN, MAIN LEVEL – AREA F
A. Modify Drawing as shown on Attachment P1.2F-1.
ITEM NO. 21 DRAWING P2.1 PLUMBING LARGE SCALE PLANS & RISER DIAGRAMS
A. Modify drawing as shown on Attachment P2.1-1.
ITEM NO. 22 DRAWING P2.2 PLUMBING LARGE SCALE PLANS
A. Modify Drawing as shown on Attachment P2.2-1.
ITEM NO. 23 DRAWING P3.1 WASTE AND VENT RISER DIAGRAMS
A. Modify Drawing as shown on Attachment P3.1-1.
ITEM NO. 24 DRAWINGS FP1.1F, FP1.2C, AND FP1.2F
A. Remove note 4 from Fire Suppression Legend Notes on Attachments FP1.1F-1, FP1.2C-1, and FP1.2F-1.
ITEM NO. 25 DRAWING E7.1 ELECTRICAL LIGHTING SCHEDULES
A. Modify light fixture schedule type P3 on Drawing as shown on Attachment E7.1-1.
END OF ADDENDUM
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30 SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET SPRINGFIELD, NEBRASKA
BID FORM 004113 - 1
DOCUMENT 004113 - BID FORM COMBINED CONSTRUCTION Platteview Jr High & High School Renovations Springfield Platteview Community Schools 14801 South 108th Street Springfield, Nebraska 58059 DLR Group Project No. 10-13125-30 Issue Date: August 29, 2017 Bid of_______________________________________________________________________________, /_/ a corporation organized and existing under the laws of the State of _______________________; _ /_/ a partnership consisting of _____________________________________________ , partners; or _ /_/ a sole proprietor; hereinafter called the Bidder. To: Brett Richards, Superintendent Springfield Platteview Community Schools 14801 South 108th Street Springfield, Nebraska 68059 The undersigned acknowledges that he has received and familiarized himself with the following: Project Manual: Divisions and Sections as listed in the Table of Contents Drawings: As listed on the Index of Drawings Sheet Addenda: No. _________________ Dated ________________
No. _________________ Dated ________________
No. _________________ Dated ________________
The undersigned further acknowledges that he has visited the site and familiarized himself with local conditions affecting the cost of the Work at the place where the Work is to be done.
Attachment No. 1 for Addendum CC-2, Dated September 20, 2017
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30 SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET SPRINGFIELD, NEBRASKA
BID FORM 004113 - 2
In submitting this Bid, the undersigned agrees:
1. To furnish all material, labor, tools, expendable equipment, and all utility and transportation services necessary to provide and complete, in a workmanlike manner, all of the Work required for the Combined Construction, including General Construction, Mechanical Work, Electrical Work, and Elevator Work, in accord with the Bidding Documents prepared by DLR Group inc., for the consideration hereinafter set forth.
2. To hold his Bid open for thirty (30) days after the receipt of Bids and to accept the provisions of the
Instructions to Bidders regarding disposition of Bid Security. 3. To enter into and execute a Contract if awarded on the basis of this Bid, to furnish a Performance Bond and a Labor and Material Payment Bond in accord with the General Conditions and General Requirements of this Contract, and to deliver executed Owner-Contractor Agreements and Bonds to the Architect-Engineer within ten (10) days after notification of award, for submittal to the Owner for his approval and acceptance. 4. To substantially complete the Work as specified in Division 01 Section “Summary.” LUMP SUM BASE BID: The undersigned hereby proposes and agrees to provide the foregoing for the Lump Sum of ____________________________________________________________dollars ($__________________). (Amount shall be shown in both words and figures. In case of discrepancy, the amount shown in words will govern.)
PRIME SUBCONTRACTORS: The undersigned proposes the following Prime Subcontractors: Mechanical Work: _________________________________________________________________ Electrical Work: ___________________________________________________________________ ALTERNATES: The above Lump Sum Base Bid may be modified in accord with the following Alternates as may be accepted by the Owner. Provide a bid for all Alternates. If there is no cost to the work described, indicate so by writing zero, $0. If you do not provide a bid price, indicate so by writing, “No Bid.” ALTERNATE NO. CC-1. All work in the renovation of the High School Locker Room “Area C”. If this Alternate is accepted, add to the Lump Sum Base Bid the sum of ________________________________________________________________ dollars ($______________).
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30 SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET SPRINGFIELD, NEBRASKA
BID FORM 004113 - 3
ALTERNATE NO. CC-2. Pre-manufacture metal canopy system. If this Alternate is accepted, add to the Lump Sum Base Bid the sum of _______________________________________________________________ dollars ($______________). ALTERNATE NO. CC-3. Add acoustical baffles. If this Alternate is accepted, add to the Lump Sum Base Bid the sum of ________________________________________________________________ dollars ($______________). UNIT PRICE BIDS: The undersigned hereby proposes and agrees to provide the foregoing in relation to the following Work. The quantities specified may be modified by a Change Order in accord with the following Unit Prices: 1. Furnish and install the Repair of Gypsum Roof Deck as specified:
Add ($ ___ __) for each square foot added
2. Furnish and install the Replacement of Additional Steel Roof Deck as specified:
Add ($ _____) for each square foot added
ALTERNATES AND UNIT PRICES: The Lump Sum Base Bid may be modified in accord with the Alternates and Unit Prices as proposed by the undersigned on his completed Bid Forms for the respective projects. The undersigned has attached the required Bid Security and other items required in the Instructions to Bidders. The undersigned has attached the required Bid Security. In submitting this Bid, it is understood that the right to reject any and all Bids and to waive irregularities in the bidding has been reserved by the Owner. Dated this _____________________________________ day of ______________________ _____, 20_____ ___________________________________________________ Name of Bidder
PLATTEVIEW JR HIGH & HIGH SCHOOL RENOVATIONS 10-13125-30 SPRINGFIELD PLATTEVIEW COMMUNITY SCHOOLS BID SET SPRINGFIELD, NEBRASKA
BID FORM 004113 - 4
___________________________________________________ Address of Bidder ___________________________________________________ Authorized Officer ___________________________________________________ Area Code/Telephone Number
END OF DOCUMENT
UP
DN
UP
UPUP
A5.132
A5.1
A5.1
A5.1
12
52
42
A B C
D
E F G H J K
1
2
3
4 5
6
7
8
9
10
11
GYMNASIUM
F244
KITCHEN
F239
STORAGE
F240
VEST
F247
OFFICE
F234
STORAGE
F245
CLASSROOM
F233
GIRLS
F243
BOYS
F242
ELECTRICAL
F238
COORIDOR
F241
VEST
F201
EARLYEDUCATION
F202
EARLYEDUCATION
F203BOYS
F204
GIRLS
F205
BOYS
F213
GIRLS
F214
PRINCIPAL
F207
NURSE
F209
WORK ROOM
F211
GUIDANCE
F208
CLASSROOM
F222
CLASSROOM
F221
SPECIAL ED
F230
JANITOR
F216
CLASSROOM
F228
TEACHERSLOUNGE
F220
WOMENS
F217
MENS
F218
CLASSROOM
F229
SCIENCE
F223
CONFERENCEROOM
F225
ELEC
F224
TOILET
F210
SMOKECURTAIN
LEARNINGCOMMONS
F232
ALCOVE
F236
RECEPTION
F206
CORRIDOR
F215
COORIDOR
F227
CORRIDOR
F212
CORRIDOR
F219
F241
F209
F208
F222
F216
F225
F228 F229
F221
F217
F223
F233
F230
F210
F207
F218
F220
F213
F214
F245
F227
F234
F242 F243
F239B
F244
F239C
F240
F247
F239A
F237
F239
F202
F212
A2.1
23
A2.1
25
OFFICE
F231
F203
8' MBD 8' MMBD
8' MMBD
8' M
MB
D
8' MBD
8' MMBD
4' MBD
8' MBD
8' M
BD
8' M
MB
D
8' M
BD
LIFT
4' MBD
4' MBD
JANITOR
F237
A11.111
8' M
BD
12
13
TV(NIC)
16/ A
11.1
A11.1 21
4' MBD4' TBD
A11.134
25
14
A11.1
24
SMARTBOARD(OFCI)
8' M
BD
8' MBD
8' MBD
MOBILE MARKERBOARD(NIC)
HO
OD
STORAGE
F226
8' M
BD
4' MBD
4' M
BD
4' M
BD
4' M
BD
4' M
BD
4' M
BD
A11.2
12
A11.133
A11.122
A11.1 23
A11.1
42
43
A11.1 45
44
46
A11.1
52
51F223A
F224
F226 F231
F238
F233A
41/ A
11.1
19' - 6"
TV(NIC)
6' - 6" 22' - 10 5/8" 22' - 10 3/8" 6' - 5" 27' - 9 1/4"
OFFICE
F235
F235
F244A
EWC-2 EWC-1
F
E
E
F
F
G
G
H
J
K
F202A
F201
14/ A11.2
16/ A11.2
LABOVE
1' - 0 3/8" 9' - 0"
6' -
8"
5' -
4"
5' -
0"
10' -
6"
8' - 9" 12' - 0"
3' - 4"
27' -
9 1
/4"
7' -
8 7
/8"
7' -
4"
7' -
5"
28' -
0"
40' -
4"
32' -
8"
8' -
6"
12' -
8"
9' - 0 1/4" 18' - 9"
25' -
11
1/8"
F219
F232
26/ A11.1
26/ A11.126/ A11.1
26/ A11.1
26/ A11.1
13/ A11.2
56
A7.1
9' -
0"
MECHANICAL
F246
F246
A8.1
36
A8.1
46
A8.1
31
TYP. FIN. FL.112' - 0"
TYP. FIN. FL.108' - 4"
TYP. FIN. FL.108' - 4"
TYP. FIN. FL.108' - 4"
TYP. FIN. FL.112' - 0"
25
A7.1
2' - 10" 8' - 0"
2' -
10"
2' -
10"
1' - 6"4' T
BD
6' M
BD
4' T
BD
FEC/B
FEC
FEC
FE
FEC
26' -
6 5
/16"
51
A7.1
53
A7.1
CO
PIE
R(N
IC)
C
C
CC
C
C
C
C
C
C
C
FD
FD
FD
FD
22' - 5" 1' - 1" 22' - 3"
1' -
10"
EWC-2
ICE
(NIC
)R
EF
(NIC
)
VE
ND
(NIC
)
3' -
8"
3' - 4"
A2.1
41
POWER DOOROPERATOR
POWER DOOROPERATOR
DOOR OPERATORSWITCH
POWER DOOROPERATOR
DOOR OPERATORSWITCH
A-1 A A-1 A-1 A-1
A-1A-1
A A A A A A A A A A A A A A A A A A A A A A
A A A A A A A A A A A A A A A A A A A A A A A A A
A8.1
32
FD
NEW STRUCTURALSTOOP - SEE STRUCTURE
DOOR OPERATORSWITCH
40' - 7 1/8"
21
A11.2
WOOD BENCH PROVIDEDBY ATHLETIC LOCKERMANUFACTURER, TYP
6' - 10"6' - 10"
A12.136
A2.1
43
A2.1
45
STORAGE
F248
F1F1
F1 M1
F
C
F
F
F1
F1
F1
NNF1
F1
J
J
F1
F1
J
J
F1
F1
F1
F1
F1
F1
A1
F1 F1
A
A1
E1
E1
E1
E1
E1
E1
D
A1
E1
E
B
BB
B
B
E
B1
F1
B1
B
E
B
B
B
A
A
M1
F1
F1
CG-1
CG
CG-1
CG
CG
CG
CG
ABOVE
F236
N
N
CG
CG
CG CG CG
M1
K
4' -
0"
56
A10.2
TYP
ALIGN WITH WALLWITH WINDOW JAMB
GOGGLESCABINET
2' - 6"
2' -
6"
A
A
A10.1
15TYP
9' -
4"
25/ A11.2
26/ A
11.2
1 REMOVE WALL IN ITS ENTIRETY.
REMOVE DOOR, FRAME AND HARWARE IN ITS ENTIRETY.
REMOVE CONCRETE RISERS IN HATCHED AREA FOR NEW SLAB ONGRADE CONCRETE FLOOR.
SAWCUT AND REMOVE FLOOR IN HATCHED AREA FOR ELECTRICALCONDUIT - COORDINATE WITH ELECTRICAL. PATCH AND REPAIRCONCRETE SLAB TO MATCH ADJACENT ELEVATIONS.
SAWCUT AND REMOVE FLOOR IN HATCHED AREA FOR PLUMBINGWORK - COORDINATE WITH MECHANICAL. PATCH AND REPAIRCONCRETE SLAB TO MATCH ADJACENT ELEVATIONS.
SAWCUT AND REMOVE PORTION OF WALL TO THE DIMENSIONSINDICATED FOR NEW OPENING. PATCH AND REPAIR REMAININGPORTION OF WALL TO MATCH ADJACENT SURFACES. PATCH ANDREPAIR FLOOR WITH SELF-LEVELING COMPOUND TO MATCHADJACENT FLOOR ELEVATION.
REMOVE PLUMBING FIXTURE IN ITS ENTIRETY- COORDINATEWITH MECHANICAL.
REMOVE EXISTING TOILET PARTION AND ASSOCIATED ACCESSORIESIN ITS ENTIRETY.
REMOVE MIRRORS, TOILET TISSUE DISPENSERS, SANITARYNAPKIN DISPOSALS AND SOAP DISPENSERS IN THEIR ENITRETY.PATCH AND REPAIR WALLS AS NEEDED.
REMOVE FLOOR TILE AND WALL TILE IN ITS ENTIRETY, PATCHAND REPAIR WALL AS NEEDED. PATCH, REPAIR AND PREPAREFLOOR FOR NEW FLOORING.
REMOVE WINDOW IN ITS ENTIRETY.
REMOVE CASEWORK IN ITS ENTIRETY.
REMOVE LOCKERS IN THEIR ENTIRETY.
REMOVE EXISTING CARPET.
REMOVE VCT FLOORING.
GRIND/MECHANICALLY ABRADE CONCRETE FLOOR TO REMOVEADHESIVIES/COATINGS FOR INSTALLATION OF NEW FLOORING.
REMOVE EXISTING RAMP, HANDRAILS RAILS IN THEIR ENTIRETY.
REMOVE EXISTING HANDRAILS.
REMOVE EXISTING PIT IN ITS ENTIRETY. PREPARE FOR NEWCONCRETE SLAB ON GRADE FLOOR. MATCH ADJACENT FLOORELEVATIONS.
REMOVE PARTITION WALL AND ASSOCIATED ACCESSORIESIN ITS ENTIRETY.
REMOVE EXISTING TACKWALL ON EXTERIOR WALLS.
REMOVE AND SALVAGE CARPET TILE AND RETURN TO OWNER.
SAWCUT AND REMOVE PORTION OF WALL TO THE DIMENSIONSINDICATED STARTING AT 3'-4" AFF UP TO STRUCTURE FOR NEW OPENING.
REMOVE EXISTING ASPHALT FOR NEW STRUCTURAL STOOP.
REMOVE EXISTING CONCRETE FOR NEW STURUCTURAL STOOP TOPPING.
REMOVE EXISTING STAIRS IN ITS ENTIRETY.
BLEACHERS TO BE REMOVED BY OWNER.
REMOVE EXISTING LADDER.
REMOVE BASE CASEWORK. UPPER CASEWORK TO REMAIN.
REMOVE AND SALVAGE FACE BRICK, TO BE USED FOR INFILL WHERESHOWN ON EXTERIOR ELEVATIONS.
REMOVE EXISTING CONCRETE CURB IN ITS ENTIRETY.
SAWCUT AND REMOVE HATCHED PORTION OF CONCRETE.
REMOVE SECTION OF STEEL TUBE CURB TO MAKE LEVEL WITH EXISTINGFINISH FLOOR FOR INSTALLATION OF NEW LIFT. COORDINATE SIZE OF OPENINGWITH THE SIZE OF LIFT BEING INSTALLED BY LIFT MANUFACTURER.
REMOVE EXISTING CARPET AND ADHESIVE ON STEEL TUBE CURB. PREPARESURFACE FOR NEW PRIMER AND PAINT.
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/2
0/2
017 1
:46:4
8 P
M
C:\R
evit\1
0-1
3125-3
0_A
R_2016_C
entr
al_
jlim
bach.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
FLO
OR
PLA
N, M
AIN
LE
VE
L -
AR
EA
FA1.2F
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NORTHSCALE: 1/8" = 1'-0"
FLOOR PLAN, MAIN LEVEL - AREA F
CC
-29/
21/1
7A
DD
EN
DU
M C
C-2
CC-2CC-2
MICROWAVE(NIC)
MICROWAVE(NIC)
FRIDGE(NIC)
VENDING(NIC) ICE
(NIC)
COUNTER TOP: PL-2CABINETS: PL-1
3' - 0" 3' - 0" 3' - 3"
3' - 0" 3' - 0" 1' - 9" 3' - 0"
W2052 W9330 W2052
B2542 B1050
9' - 3"
2' -
10"
1' -
8"
2' -
6"
7' -
0"
KNEESPACE
D1211 B2360
10' - 9"
ELEC DEVICE- SEE ELECTRICAL
SINK/FAUCETSEE MECHANICAL
PTDSDHC
COUNTER TOP: PL-2CABINETS: PL-1
3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0"
15' - 0"
2' -
6"
1' -
8"
2' -
10"
W2052 W2052 W2052 W2052 W2052
B2360 D1223 D1223 D1223 D1223 B2360
3' - 0"
FILLER PANEL
3' - 0" 3' - 3" 3' - 3" 3' - 3"
FILLER PANEL
3' - 0"
18' - 10 1/2"
ELEC DEVICE- SEE ELECTRICAL
COUNTER TOP: PL-2CABINETS: PL-1
3' - 0" 2' - 0"
5' - 0"
2' -
6"
1' -
0"
8"2'
- 1
0"
7' -
0"
W2052 H2051
B2360 D1211
2' - 9" 1' - 0"
3' - 9"
ELEC DEVICE- SEE ELECTRICAL
KNEESPACE
COUNTER TOP: PL-2COUNTER TOP: SS-1CABINETS: PL-1
3' - 0" 2' - 6" 2' - 0" 1' - 4" 1' - 3" 1' - 3" 4' - 3 1/2" 1' - 4" 1' - 4" 1' - 4" 3' - 0" 1' - 6" 2' - 3"
2' -
10"
1' -
8"
2' -
6"
D1223 D1223 D1211 D2800 D3320 D2800 D2800 D2800 D1223 D1211 B1050
2' -
6"
7 1/
2"4
1/2"
7' -
0" SS-1 ELEC DEVICE
- SEE ELECTRICALLOCKS, TYP
SS-1PL-2
PL-2
PL-1
CC-2
COUNTER TOP: PL-2VERTICAL: PL-1
2' -
6"
24
A11.2
ELEC DEVICE- SEE ELECTRICAL
PL-1
KNEESPACE
COUNTER TOP: PL-2CABINETS: PL-1
UNDERCOUNTERREFR (NIC)
2' - 6" 3' - 0"
10' - 1 1/8"
B2542 D1223
4' -
2"
2' -
10"
2' -
6"
2' -
0"
2' -
6"
7' -
0"
1' - 3" 3' - 0" 3' - 0" 2' - 6"
9' - 9"
H2050 W2052 W2052 W2052
ELEC DEVICE- SEE ELECTRICAL
LOCKS, TYP
SINK/FAUCETSEE MECHANICAL
PTDSD HC
PL-1 COUNTER TOP: PL-2CABINETS: PL-1
2' -
6"
1' -
0"
3' -
6"
7' -
0"
2' -
6"
2' -
0"
2' -
6"
3' - 3" 3' - 3" 1' - 0"
7' - 6"
W2052 W2052 H2051
ELEC DEVICE- SEE ELECTRICAL
COUNTER TOP: PL-2CABINETS: PL-1
3' - 0" 1' - 4" 1' - 4"
2' -
10"
4' -
2"
7' -
0"
5' - 8"
T2586 D2800 D2800
LOCKS, TYP
ELEC DEVICE- SEE ELECTRICAL
KNEESPACE
COUNTER TOP: PL-2CABINETS: PL-1VERTICAL: PL-1
2' -
6"
1' -
0"
3' -
6"
2' - 6" 2' - 9"
5' - 3"
D3320 D1223
23
A11.2LOCKS, TYP
ELEC DEVICE- SEE ELECTRICAL
PL-1
SS-1
PL-2TS-1
SUPPORTBRACKET
COUNTER TOP: PL-2CABINETS: PL-1
3' - 0"
FILLER PANEL
3' - 0"
FILLER PANEL
3' - 0"
9' - 2 1/16"
D1223 B2360B2360
2' - 6" 2' - 6" 2' - 6"
7' - 6"
2' -
6"
1' -
8"
2' -
10"
7' -
0"
W2052 W2052 W2052
COUNTER TOP: PL-2CABINETS: PL-1
3' - 0" 3' - 0" 3' - 0" 3' - 0"
12' - 0"
4' -
2"
2' -
10"
7' -
0"
T2586 D1223 D1223 D1223
LOCKS, TYPELEC DEVICE- SEE ELECTRICAL
COUNTER TOP: PL-2CABINETS: PL-1
2' - 9" 1' - 9" 1' - 0" 3' - 0"
8' - 6"
2' -
10"
1' -
8"
2' -
6"
7' -
0"
2' - 9" 2' - 9" 3' - 0"
8' - 6"
D1223 D1223 T2586
H2050W2051W2052
ELEC DEVICE- SEE ELECTRICAL
COUNTER TOP: PL-2CABINETS: PL-1
2' - 6"
FILLER PANEL
3' - 3" 3' - 3" 3' - 0"
4' - 6" 3' - 0"
T2102 D1223 D1223 B2360
H9210 W2052
12' - 1 1/8"
2' -
10"
1' -
8"
2' -
6"
7' -
0"
LOCKS, TYP
ELEC DEVICE- SEE ELECTRICAL
CABINETS: PL-1
1' - 9" 1' - 9" 1' - 9" 1' - 9" 1' - 9"
8' - 9"
T2050 T2050 T2050 T2050 T2050
7' -
0"
LOCKS, TYP
CABINETS: PL-1
1' - 9" 1' - 9" 1' - 9" 1' - 9" 1' - 9" 1' - 9" 1' - 9"
T2050 T2050 T2050 T2050 T2050 T2050 T2050
7' -
8"
4' - 0"
FUMEHOOD
KNEE SPACE
ELEC DEVICE- SEE ELECTRICAL
CEILING CLOSURE BYHOOD MANUFACTURER
COUNTER TOP: BLACK EPOXYCABINETS: PL-1
1' - 6" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 2' - 6"
W2050 W2052 W2052 W2052 W2052 W2341
16' - 0"
1' - 6" 3' - 0" 3' - 0" 3' - 0" 1' - 9" 3' - 9"
16' - 0"
D1120 B2542 D1223 D1223 D1120 D1139
1' -
6"
1' -
0"
1' -
8"
2' -
10"
7' -
0"
PEG BOARD DRYING RACK
LOCKS, TYP
ELEC DEVICE- SEE ELECTRICAL
SINK/FAUCETBY CASEWORK MFR
HC
COUNTER TOP: BLACK EPOXYCABINETS: PL-1
2' - 9" 1' - 0"
3' - 9"
3' - 0"
D1223
2' -
10"
8"1'
- 0
"2'
- 6
"
7' -
0"
W2052 H2051
VENTED CHEMICALSTORAGE CABINETS
LOCKS, TYP
ELEC DEVICE- SEE ELECTRICAL
GWB CEILING ATTOP OF CASEWORK
COUNTER TOP: BLACK EPOXYCABINETS: PL-1
2' - 0" 3' - 0" 2' - 0" 2' - 0"
9' - 0"
2' - 0" 3' - 0" 2' - 0" 3' - 9"
10' - 9"
D1120 B2522 D1120 D1139
W2050 W2052 W2051 W2051
1' -
6"
1' -
0"
1' -
8"
2' -
10"
7' -
0" ELEC DEVICE
- SEE ELECTRICAL
LOCKS, TYP
SINK/FAUCETBY CASEWORK MFR
COUNTER TOP: BLACK EPOXYCABINETS: PL-1
3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0"
18' - 0"
3' - 3" 3' - 3" 3' - 3" 3' - 3" 3' - 3"
16' - 3"
2' -
10"
1' -
8"
2' -
6"
7' -
0"
W2052 W2052 W2052 W2052 W2052 W2052
D1223 D1223 D1223 D1223 D1223
LOCKS, TYP ELEC DEVICE- SEE ELECTRICAL
COUNTER TOP: BLACK EPOXYCABINETS: PL-1
2' - 0" 2' - 0" 3' - 0" 2' - 0"
9' - 0"
2' -
10"
1' -
8"
1' -
0"
1' -
6"
7' -
0"
3' - 9" 2' - 0" 3' - 0" 2' - 0"
10' - 9"
D1211 B2522 D1211D1138
W2050 W2050 W2052 W2051
ELEC DEVICE- SEE ELECTRICAL
LOCKS, TYP
SINK/FAUCETBY CASEWORK MFR
PTD SD
COUNTER TOP: BLACK EPOXYCABINETS: PL-1
EYEWASH/SHOWER
2' - 6" 2' - 6"
5' - 0"
W2052 W2052
2' - 9" 1' - 6"
4' - 3"
D1223 D1120
2' -
10"
1' -
8"
2' -
6"
7' -
0"ELEC DEVICE
- SEE ELECTRICAL
LOCKS ,TYP
COUNTER TOP: BLACK EPOXYCABINETS: PL-1
GOGGLE CABINET
2' - 6" 2' - 0" 2' - 0" 3' - 0" 3' - 0" 1' - 6"
14' - 0"
3' - 9" 2' - 9" 3' - 0" 3' - 0" 1' - 6"
14' - 0"
D1138 D1223 D1223 B2522 D1211
W2340 W2050 W2051 W2052 W2052 W2051
2' -
10"
1' -
8"
2' -
6"
7' -
0" ELEC DEVICE
- SEE ELECTRICAL
LOCKS, TYP
SINK/FAUCETBY CASEWORK MFR
PTD SD
1' - 6" 3' - 0" 3' - 0" 3' - 0" 1' - 9" 3' - 9"
COUNTER TOP: CRPL-1CABINETS: PL-1
16' - 0"
1' - 6" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 2' - 6"
16' - 0"
D1120 B2542 D1223 D1223 D1120 D1139
W2050 W2052 W2052 W2052 W2052 W2341
ELEC DEVICE- SEE ELECTRICAL
LOCKS, TYP
PEG BOARD DRYING RACK
PTD
SINK/FAUCETSEE MECHANICAL
SD
HC
COUNTER TOP: CRPL-1CAB1NETS: PL-1
2' - 9" 1' - 0"
3' - 9"
3' - 0"
2' -
10"
8"1'
- 0
"2'
- 6
"
7' -
0"
W2052 H2051
D1223
ELEC DEVICE- SEE ELECTRICAL
LOCKS, TYP
COUNTER TOP: CRPL-1CABINETS: PL-1
3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0"
18' - 0"
3' - 0" 2' - 6" 2' - 6" 2' - 6" 2' - 6" 3' - 0"
16' - 0"
B2522 D1223 D1223 D1223 D1223 B2522
W2052W2052W2052W2052W2052W2052
2' -
10"
1' -
8"
2' -
6"
7' -
0"ELEC DEVICE
- SEE ELECTRICAL
LOCKS, TYP
SINK/FAUCETSEE MECHANICAL
SINK/FAUCETSEE MECHANICAL
SD PTD SD PTD
UNDERCOUNTERREFR (NIC)
COUNTER TOP: CRPL-1CABINETS: PL-1
2' - 6" 2' - 6" 2' - 3" 2' - 8 1/2"
9' - 11 1/2"
3' - 6" 1' - 9" 2' - 2 1/8" 2' - 8 1/2"
10' - 1 5/8"
2' -
10"
1' -
8"
2' -
6"
7' -
0"
W2340 W2052 W2052
T2632D12111092
LOCKS ,TYP
ELEC DEVICE- SEE ELECTRICAL
SINK/FAUCETSEE MECHANICAL
COUNTER TOP: CRPL-1CABINETS: PL-1
AQUA TANK(NIC)
3' - 0" 1' - 6"
4' - 6"
W2052 W2051
2' - 0" 3' - 9"
5' - 9"
D1120 D1139
2' -
6"
1' -
8"
2' -
10"
7' -
0"
ELEC DEVICE- SEE ELECTRICAL
LOCKS, TYP
COUNTER TOP: CRPL-1CABINETS: PL-1
3' - 0" 3' - 3" 3' - 3" 3' - 0" 1' - 6"
14' - 0"
3' - 0" 3' - 3" 3' - 3" 3' - 0" 1' - 6"
14' - 0"
2' -
10"
1' -
8"
1' -
0"
1' -
6"
7' -
0"
W2052 W2052 W2052 W2052 W2051
D1223 D1223 D1223 B2522 D1211
ELEC DEVICE- SEE ELECTRICAL
LOCKS,TYP
SINK/FAUCETSEE MECHANICAL
PTD SD
GOGGLE CABINET
CASEWORK AND MILLWORK GENERAL NOTES
A. CASEWORK AND MILLWORK GENERAL NOTES APPLYTO ALL CASEWORK AND MILLWORK SHEETS.
B. CASEWORK SPECIFIED UNDER DIVISION 12,UNLESS NOTED OTHERWISE.
C. BASE AND TALL STORAGE CABINETS: 24 INCHESDEEP, UNLESS NOTED OTHERWISE.
D. WALL CABINETS: 14 INCHES DEEP, UNLESS NOTEDOTHERWISE.
E. TALL STORAGE UNITS TO BE 24 INCHES DEEP,UNLESS NOTED OTHERWISE.
F. PROVIDE ADJUSTABLE SHELVING IN CASEWORK,UNLESS NOTED OTHERWISE.
G. CATALOG NUMBERS SHOWN ON THE ELEVATIONSFOR CASEWORK ARE TMI REFERENCE NUMBERS,UNLESS NOTED OTHERWISE. (M) AFTER THECATALOG NUMBER INDICATES THE CABINET ISSHOWN MODIFIED FROM STANDARD.
H. WHERE ELECTRICAL DEVICES ARE LOCATED INCASEWORK, CASEWORK CONTRACTOR SHALLPROVIDE FINISHED OPENINGS. COORDINATELOCATION AND QUANTITY WITH ELECTRICALCONTRACTOR.
I. PROVIDE JOINT SEALANT AT PERIMETER JOINTSWHERE COUNTERTOPS, BACK AND SIDESPLASHES, CASEWORK, AND MILLWORK ABUTWALLS.
J. FIELD VERIFY DIMENSIONS OF CABINETLOCATIONS IN BUILDING PRIOR TO FABRICATION.
K. PROVIDE LOCKS AT DOORS AND DRAWERS WHEREINDICATED.
L. PROVIDE FINISHED ENDS AT ALL EXPOSED ENDSOF CASEWORK AND MILLWORK.
M. ALL EXPOSED SURFACES IN OPEN SHELVING SHALLBE PLASTIC LAMINATE COVERED.
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
Rev
isio
ns
9/2
0/2
017 1
:46:5
8 P
M
C:\R
evit\1
0-1
3125-3
0_A
R_2016_C
entr
al_
jlim
bach.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
CA
SE
WO
RK
ELE
VA
TIO
NS
A11.1
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
SCALE: 1/4" = 1'-0"A11.1
11 F220 TEACHERS LOUNGESCALE: 1/4" = 1'-0"A11.1
12 F220 TEACHERS LOUNGESCALE: 1/4" = 1'-0"A11.1
13 F220 TEACHERS LOUNGESCALE: 1/4" = 1'-0"A11.1
14 F211 WORK ROOMSCALE: 1/4" = 1'-0"A11.1
16 F206 RECEPTION
SCALE: 1/4" = 1'-0"A11.1
21 F209 NURSESCALE: 1/4" = 1'-0"A11.1
22 F231 OFFICESCALE: 1/4" = 1'-0"A11.1
23 F208 GUIDANCESCALE: 1/4" = 1'-0"A11.1
24 F206 RECEPTIONSCALE: 1/4" = 1'-0"A11.1
25 F211 WORK ROOMSCALE: 1/4" = 1'-0"A11.1
26 TYPICAL CLASSROOM
SCALE: 1/4" = 1'-0"A11.1
33 F230 SPECIAL EDSCALE: 1/4" = 1'-0"A11.1
34 F211 WORK ROOMSCALE: 1/4" = 1'-0"A11.1
35 F122 STORAGESCALE: 1/4" = 1'-0"A11.1
36 F122 STORAGE
SCALE: 1/4" = 1'-0"A11.1
41 F223 SCIENCESCALE: 1/4" = 1'-0"A11.1
42 F223 SCIENCESCALE: 1/4" = 1'-0"A11.1
43 F223 SCIENCESCALE: 1/4" = 1'-0"A11.1
44 F223 SCIENCESCALE: 1/4" = 1'-0"A11.1
45 F223 SCIENCESCALE: 1/4" = 1'-0"A11.1
46 F223 SCIENCE
SCALE: 1/4" = 1'-0"A11.1
51 F223 SCIENCESCALE: 1/4" = 1'-0"A11.1
52 F223 SCIENCESCALE: 1/4" = 1'-0"A11.1
53 F111 SCIENCESCALE: 1/4" = 1'-0"A11.1
54 F111 SCIENCESCALE: 1/4" = 1'-0"A11.1
55 F111 SCIENCESCALE: 1/4" = 1'-0"A11.1
56 F111 SCIENCE
SCALE: 1/4" = 1'-0"A11.1
32 F111 SCIENCESCALE: 1/4" = 1'-0"A11.1
31 F111 SCIENCE
LOCKS, TYP
CC
-29/
21/1
7A
DD
EN
DU
M C
C-2
CC-2
CC-2
CC-2CC-2
CC-2
CC-2
CC-2
CC-2
CC-2
CC-2
CC-2 CC-2
CC-2
CC-2
CC-2
COUNTER TOP: PL-2CABINETS: PL-1
2' - 9" 2' - 9" 2' - 9" 2' - 9" 1' - 0"
12' - 0"
2' -
10"
8"1'
- 0
"2'
- 6
"
7' -
0"
3' - 0" 3' - 0" 3' - 0" 3' - 0"
12' - 0"
W2052 W2052 W2052 W2052 H2051
D1223 D1223 D1223 D1223
ELEC DEVICE- SEE ELECTRICAL
COUNTER TOP: PL-2CABINETS: PL-1
3' - 0" 3' - 0" 2' - 9" 1' - 0"
9' - 9"
3' - 3" 3' - 3" 3' - 3"
9' - 9"
W2052 W2052 W2052 H2051
D1223 D1223 D1223
2' -
10"
8"1'
- 0
"2'
- 6
"
7' -
0"ELEC DEVICE
- SEE ELECTRICAL
EQ EQ EQ EQ EQ EQ
COUNTERTOP: SS-1VERTICAL: PL-1
21
A11.2
2' -
6"
1' -
8"
28' - 0"
EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ
ALIGN WITH METAL STUD, TYP
ALIGN WITH STEEL TUBE, TYP
ELEC DEVICE- SEE ELECTRICAL
PL-1
SS-1
4' -
2"
EQ EQ EQ EQ EQ EQ
COUNTERTOP: SS-1VERTICAL: PL-1
21
A11.2
3' -
6"
EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ EQ
ALIGHN WITH STEEL TUBE, TYP
ALIGN WITH METAL STUD, TYP
28' - 0"
ELEC DEVICE- SEE ELECTRICAL
PL-1
SS-1
CABINETS: PL-1
EWC-2
3' - 0" 3' - 0"
T2052 T2052
EWC-1
WOOD BENCH PROVIDEDBY ATHLETIC LOCKERMANUFACTURER, TYP
6' - 10" 6' - 10"
ELEC DEVICE- SEE ELECTRICAL
RECESSEDPULLS, TYP
3/4" PLY WOOD
4" BASE, PLAM-4,APPLIED DIRECTLYTO GWB
HSS 3X3X1/4 TUBE STEEL SUPPORT @4'-0" O.C. MAX, AND 6" FROM EACHEND
5X8X3/8 BASEPLATE W/ (2) 1/2" DIAM. X2 1/2" EMBEDDED EXPANSIONANCHORS
6" MTL STUDS @ 16" O.C.3/4" PLYWOOD
1/2" SOLID SURFACING(SS) TYP
EASED EDGES
1/8
1/4
COUNTER TOP SUPPORT
3/4" PLYWOOD
1/2" SOLID SURFACING (SS) TYP
1/2" SOLID SURFACING (SS) TYP
8"3'
- 6
"
2' -
6"
3/4" MDF BOTH SIDES
PL-1, BOTH SIDES
3/4" SUPPORT BRACKET,PLAM- 5 ON PLY WD
OUTLETS PER ELECTRICAL
PL-2
LIGHT FIXTURE, PER ELECTRICALDRAWINGS
3/4" PLY WOOD
4" BASE, PLAM-4,APPLIED DIRECTLYTO 1/4" PLYWOOD
1' - 6"
3' -
6"
2"
3"
3/4" MDF
1' - 8"
1/4
HSS 3X3X1/4 TUBE STEEL SUPPORT @4'-0" O.C. MAX, AND 6" FROM EACHEND
1/2" PLATE W/ (2) 1/2" DIAM. X 2 3/4"THROUGH BOLT ANCHORS
HSS 1X1X3/16, PROVIDEAT EACH VERTICAL POST
2" GROMMET PLACED 4'-0" OC, STARTING2'-0" FROM PLAN WEST EDGE
1/8
6" MTL STUDS @ 16" O.C.
PL-1
SS-1
TS-1
WALL TYPE PER PLAN
2"x2" EDGE NAILER
3/4" PLYWOOD
1 1/2" x 1 1/2" STEEL ANGLE 24"VERTICAL LEG 18" HORIZONTAL LEGFASTEN TO METAL STUDS @ 16" O.C.
FASTEN WITH #10SCREW @ 6" O.C.
PL-2
UN
O2'
- 1
0"
WALL FINISH, PER SCHEDULE
8" @ SIM1' - 8"
5/8" MDF
PL-1
EXISTING WALL
SOLID SURFACE
1' -
0"
2' -
6"
3' -
6" PLASTIC LAMINATE
COUNTERTOP: SS-1VERTICAL: PL-1
LIGHT FIXTURE -SEE ELECTRICAL
SOLID SURFACE
PLASTIC LAMINATE
COUNTERTOP: SS-1VERTICAL: PL-1
LIGHT FIXTURE -SEE ELECTRICAL
1' -
0"
2' -
6"
3' -
6"
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
Rev
isio
ns
9/2
0/2
017 1
:47:0
2 P
M
C:\R
evit\1
0-1
3125-3
0_A
R_2016_C
entr
al_
jlim
bach.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
CA
SE
WO
RK
ELE
VA
TIO
NS
A11.2
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
SCALE: 1/4" = 1'-0"A11.2
11 F115 CONFERENCE ROOMSCALE: 1/4" = 1'-0"A11.2
12 F225 CONFERENCE ROOMSCALE: 1/4" = 1'-0"A11.2
14 F232 LEARNING COMMONSSCALE: 1/4" = 1'-0"A11.2
16 F232 LEARNING COMMONSSCALE: 1/4" = 1'-0"A11.2
13 F244 GYMNASIUM
SCALE: 1" = 1'-0"A11.2
21 DESK SECTIONSCALE: 1" = 1'-0"A11.2
23 RECEPTION DESK - SECTIONSCALE: 1" = 1'-0"A11.2
24 TYP. WALL MOUNTED COUNTERSCALE: 1/4" = 1'-0"A11.2
25 F206 RECEPTIONSCALE: 1/4" = 1'-0"A11.2
26 F206 RECEPTION
CC
-29/
21/1
7A
DD
EN
DU
M C
C-2
CC-2
CC-2
CC-2
CC-2
CC-2
CC-2
CC-2 CC-2
A B C
D
E F G H J K
1
2
3
4 5
6
7
8
9
10
11
EXISTING HEAT PUMP ANDACCOCIATED DUCTWORK ANDPIPING TO BE REMOVED. (TYP)
EXISTING HOTWATER BOILERSTO BE REMOVED
EXISTING CONDENSERWATER PUMPS TO BEREMOVED
EXISTING HOT WATERHEATER AND STORAGETANK TO BE REMOVED
EXISTING HEAT EXCHANGERAND CIRCULATION PUMP TOBE REMOVED
EXISTING TOWERSTORAGE TANK TOBE REMOVED
REMOVE ALL CONDENSER WATERPIPING AND ACCESSORIES ASSOCIATEDWITH BOILER/TOWER HEAT PUMP LOOP.
REMOVE ALL CONDENSER WATERPIPING IN VERTICAL CHASE
REMOVE EXISTING EXHAUSTDUCTWORK. COORDINATE WITH ARCHTO SEAL PENETRATION IN FLOOR.
GENERAL DEMOLITION NOTES:
1. THE EXTENT OF REMOVAL FOR THIS PROJECT SHALLGENERALLY CONSIST OF REMOVAL OF THE AIR SIDECOMPONENTS OF THE EXISTING HEAT PUMP SYSTEM.THIS SHALL INCLUDE ALL EXISTING GEOTHERMAL HEATPUMPS, AS WELL AS ALL ASSOCIATED DUCTWORK,DIFFUSERS, GRILLES, AND CONTROLS. ITEMS TO BEREMOVED SHALL BE SHOWN IN FULL-TONE. ITEMS TOREMAIN SHALL REMAIN HALF-TONE.
2. PIPING AND DUCTWORK REMOVAL SHALL INCLUDE THEREMOVAL OF ALL EXISTING PIPE HANGERS AND DUCTHANGERS.
3. THE ACTUAL LOCATIONS OF THE EQUIPMENT AND/ORPIPING AND DUCTWORK MAY VARY SLIGHTLY DUE TOAS-BUILT CONDITIONS. ANY PIPING OR DUCTWORKTHAT IS TO BE REMOVED SHALL BE REMOVED IN ITSENTIRETY. NO DUCTWORK OR PIPING SHALL BEABANDONED IN PLACE UNLESS IT HAS BEENSPECIFICALLY CALLED OUT TO BE ABANDONED INPLACE. IF UNEXPECTED CONDITIONS AREENCOUNTERED, NOTIFY THE OWNER'SREPRESENTATIVE. THE CONTRACTOR SHALL BEARTHE COSTS OF DAMAGE RESULTING FROM FAILURE TOEXERCISE REASONABLE CARE FOR CONTINUINGOPERATIONS WITHOUT NOTIFYING THE OWNER.
4. PRIOR TO ANY NEW WORK BEING COMPLETED, THEENTIRE HEAT PUMP WATER LOOP, SHALL BEEMPTIED, FLUSHED, AND CLEANED. DISCONNECT ALLEQUIPMENT FROM WATER LOOP PER THESPECIFICATIONS AND DRAWING DETAILS PRIOR TOFLUSHING. OWNER'S REPRESENTATIVE SHALL SIGNOFF ON WATER QUALITY PER SPECIFICATIONS.
5. WHERE DEMOLITION OCCURS, PATCH ALL ROOF ANDWALL PENETRATIONS TO MATCH EXISTING CONDITIONS.
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
LEGEND NOTESLEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/2
2/2
017 2
:54:1
4 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
HV
AC
DE
MO
LIT
ION
PLA
N, LO
WE
R L
EV
EL -
AR
EA
FM
D1.1
F
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NORTHSCALE: 1/8" = 1'-0"
HVAC DEMOLITION PLAN, LOWER LEVEL - AREA F
CC
-39/
25/1
7A
DD
EN
DU
M C
C-3
CC-3
A B C
D
E F G H J K
1
2
3
4 5
6
7
8
9
10
11
EXISTING HEAT PUMP ANDACCOCIATED DUCTWORK ANDPIPING TO BE REMOVED. (TYP)
REMOVE ALL CONDENSER WATERPIPING IN VERTICAL CHASE
REMOVE COOLING TOWER AND ALLPIPING AND ACCESSORIES ASSOCIATEDWITH BOILER/TOWER HEAT PUMP LOOP.
REMOVE ALL CONDENSER WATERPIPING AND ACCESSORIES ASSOCIATEDWITH BOILER/TOWER HEAT PUMP LOOP.
EXISTING EXHAUST FAN ON ROOFAND ACCOCIATED DUCTWORK TOBE REMOVED. COORDINATE WITHARCHITECTURE TO SEALPENETRATIONS IN ROOF.
EXISTING EXHAUST FAN ON ROOFAND ACCOCIATED DUCTWORK TO BEREMOVED. COORDINATE WITHARCHITECTURE TO SEALPENETRATIONS IN ROOF.
EXISTING HEAT PUMPS ANDACCOCIATED DUCTWORK TO BEREMOVED. COORDINATE WITHARCHITECTURE TO SEALPENETRATIONS IN ROOF.
GENERAL DEMOLITION NOTES:
1. THE EXTENT OF REMOVAL FOR THIS PROJECT SHALLGENERALLY CONSIST OF REMOVAL OF THE AIR SIDECOMPONENTS OF THE EXISTING HEAT PUMP SYSTEM.THIS SHALL INCLUDE ALL EXISTING GEOTHERMAL HEATPUMPS, AS WELL AS ALL ASSOCIATED DUCTWORK,DIFFUSERS, GRILLES, AND CONTROLS. ITEMS TO BEREMOVED SHALL BE SHOWN IN FULL-TONE. ITEMS TOREMAIN SHALL REMAIN HALF-TONE.
2. PIPING AND DUCTWORK REMOVAL SHALL INCLUDE THEREMOVAL OF ALL EXISTING PIPE HANGERS AND DUCTHANGERS.
3. THE ACTUAL LOCATIONS OF THE EQUIPMENT AND/ORPIPING AND DUCTWORK MAY VARY SLIGHTLY DUE TOAS-BUILT CONDITIONS. ANY PIPING OR DUCTWORKTHAT IS TO BE REMOVED SHALL BE REMOVED IN ITSENTIRETY. NO DUCTWORK OR PIPING SHALL BEABANDONED IN PLACE UNLESS IT HAS BEENSPECIFICALLY CALLED OUT TO BE ABANDONED INPLACE. IF UNEXPECTED CONDITIONS AREENCOUNTERED, NOTIFY THE OWNER'SREPRESENTATIVE. THE CONTRACTOR SHALL BEARTHE COSTS OF DAMAGE RESULTING FROM FAILURE TOEXERCISE REASONABLE CARE FOR CONTINUINGOPERATIONS WITHOUT NOTIFYING THE OWNER.
4. PRIOR TO ANY NEW WORK BEING COMPLETED, THEENTIRE HEAT PUMP WATER LOOP, SHALL BEEMPTIED, FLUSHED, AND CLEANED. DISCONNECT ALLEQUIPMENT FROM WATER LOOP PER THESPECIFICATIONS AND DRAWING DETAILS PRIOR TOFLUSHING. OWNER'S REPRESENTATIVE SHALL SIGNOFF ON WATER QUALITY PER SPECIFICATIONS.
5. WHERE DEMOLITION OCCURS, PATCH ALL ROOF ANDWALL PENETRATIONS TO MATCH EXISTING CONDITIONS.
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
LEGEND NOTESLEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/2
2/2
017 2
:54:1
5 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
HV
AC
DE
MO
LIT
ION
PLA
N, M
AIN
LE
VE
L -
AR
EA
FM
D1.2
F
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NORTHSCALE: 1/8" = 1'-0"
HVAC DEMOLITION PLAN, MAIN LEVEL - AREA F
CC
-29/
20/1
7A
DD
EN
DU
M C
C-2
CC-2
UP
S
S
S
S
S
FS
S S
S
S
S
SS
S
S
S
S
S
S
SS
S
S
S
S
S
A
A
B
B
C
C
D
D
E
E
F
F
G
G
H
H
J
J
K
K
1
2
3
4 5
6
7
8
9
10
11
ELECTRICAL
F104
MECHANICAL
F103
VEST
F124
STORAGE
F122MEDIA CENTER
F121
COMPUTER LAB
F108
CLASSROOM
F109
CLASSROOM
F110
CLASSROOM
F120
CLASSROOM
F117
CLASSROOM
F119
CLASSROOM
F118
SCIENCE
F111
CONFERENCEROOM
F115
DATA
F113
CUSTODIAL
F102
STORAGE
F114
CORRIDOR
107
CORRIDOR
F101
CORRIDOR
F116
RAMP/STAIR
F1S1
GREEN ROOM
F123
8"x10" SA
8" ø130 CFM
D-1
10"x
8" S
A
8" ø130 CFM
D-1
8" ø130 CFM
D-1
8" ø130 CFM
D-1
HP-F05
8" ø130 CFM
D-1
8" ø130 CFM
D-1
6" ø120 CFM
D-1
6" ø120 CFM
D-16" ø
120 CFM
D-1
HP-F03
8" ø225 CFM
D-1
8" ø225 CFM
D-1
8" ø225 CFM
D-1
HP
-F02
8" ø130 CFM
D-1
8" ø130 CFM
D-1
8" ø130 CFM
D-1
HP-F01
10" ø285 CFM
D-1
10" ø265 CFM
D-1
10" ø265 CFM
D-1
6" ø75 CFM
D-1
10" ø365 CFM
D-1
10" ø365 CFM
D-1
10" ø365 CFM
D-1
HP-F06
HP-F08
HP
-F10
HP
-F09
10" ø250 CFM
D-110" ø
250 CFM
D-1
6" ø100 CFM
D-1
6" ø100 CFM
D-1
HP-F11
6" ø120 CFM
D-1
6" ø120 CFM
D-1
6" ø120 CFM
D-1
HP-F07
HP
-F04
8" ø220 CFM
D-1
18"x12" SA10"x12" SA
10"x8" SA
8"x10" SA
12"x
10"
SA
10"x8" SA
10"x
10"
SA
18"x
10"
SA
8" ø335 CFM
D-2
8" ø335 CFM
D-2
8" ø335 CFM
D-2
6"x8
" S
A
200 CFM
250 CFM
300 CFM
100 CFM
250 CFM
250 CFM
250 CFM
250 CFM
250 CFM
UH-F1
GDWH-F103
T-F103
ET-1
TMV-1
FIRE PUMPROOM
F103A
8"x6" EA 10"x10" EA
8"x6
" E
A
10"x
10"
EA
10"ø
OA
14"x
12"
OA
20"x14" OA
12"ø
OA
10"ø
OA
26"x14" OA10
"ø O
A
26"x
14"
OA
30"x
14"
OA
10"ø
OA
8"ø
OA
14"x10" OA
20"ø
SA
AC-F1
34"x
14"
OA
34/14 OA UP
10"ø OA
G-224" x 24"
G-224" x 24"
30"x
14"
OA
10"ø OA
10"ø OA
R-136" x 18"
G-224" x 24"
14"x12" RA
10"ø SA
12"x12" TA
12"x12" RA
D-224" x 24"12"x12" TA
12"x12" TA
24"x
12"
RA
G-224" x 24"
10"ø OA
14"x12" RA
G-224" x 24"
12"x12" TA
14"x12" RA
G-224" x 24"
12"x12" TA
20"x16" RA
G-224" x 24"
20"x16" RA
12"x12" TA
12"x12" TA
14"x12" RA
G-224" x 24"12"x12" TA
16"x14" SA
10/10 EA UP
10"x10" EA
24"x14" RA
CC- 1
G-112" x 12"120 CFM
12"x12" TA
REFRGERANT PIPING UPTO CU-F01 ON ROOF
G-112" x 12"150 CFM
G-112" x 12"150 CFM
G-112" x 12"75 CFM
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-112" x 12"
G-112" x 12"
12"x12" TA
12"x12" TA
12"x12" TA
G-224" x 24"
R-224"x6"
175 CFM(TYP 4)
300 CFM
250 CFM
SP-2
SP-3
ROUTE DUCTWORK AS HIGH ASPOSSIBLE. RE-USE CURRENTPENETRATIONS IN WALL
24"x14" RA
18"x10" RA
CC-2
3" FLUE AND COMBUSTION AIRUP TO ROOF THRU CHASE.
GENERAL HVAC PLAN NOTES:
1. LIMIT ALL FLEXIBLE DUCT RUNS TO 3 FEET MAXIMUM LENGTH.FLEXIBLE DUCT(S) SHALL BE OF THE SAME SIZE AS THE DIFFUSERNECKS THAT THEY CONNECT TO UNLESS NOTED OTHERWISE.
2. COORDINATE EXACT LOCATIONS OF ALL DIFFUSERS WITHELECTRICAL, FIRE SPRINKLERS, AND GRID CEILINGS.
3. BALANCING DAMPERS SHALL BE LOCATED ABOVE ACCESSIBLE CEILINGS. IF THIS IS NOT POSSIBLE, ACCESS PANELS SHALL BE PROVIDED. ACCESS PANELS SHALL BE TAMPERPROOF
LOCKABLE ACCESS PANLES FOR ACCESS TO CONTROL VALVES,MOTORIZED DAMPERS, SHUT-OFF VALVES, AND SIMILARCOMPONENTS THAT ARE NOT LOCATED OVER AN ACCESSIBLECEILING. VOLUME DAMPERS SHALL BE PROVIDED WITH REMOTEDAMPER OPERATORS WITH ADJUSTABLE COVER IN NON-ACCESSABLE CEILING AREAS. SEE DETAIL 8, SHEET M4.2,"REMOTE VOLUME DAMPER" AND SPECIFICATIONS FORFURTHER INFORMATION.
4. PROVIDE CEILING AND/OR WALL ACCESS DOORS FOR ACCESS TODUCT ACCESS DOORS RELATED TO THE INSPECTION ANDRESETTING OF FIRE DAMPERS AND COMBINATION SMOKE ANDFIRE DAMPERS. PROVIDE MINIMUM 18" X 18" SIZE. CEILINGAND/OR WALL ACCESS DOOR RATING SHALL BE EQUIVALENT TOCEILING AND/OR WALL WHERE DOOR IS TO BE INSTALLED.
5. BRANCH DUCT SIZES SHALL BE THE SAME AS THE NECK SIZE OFTHE DIFFUSERS OR THE CONNECTION SIZE OF THE GRILLES,UNLESS NOTED OTHERWISE.
6. HORIZONTAL HEAT PUMPS:A. MANUFACTURER-RECOMMENDED SERVICE ACCESS AREAS
FOR HORIZONTAL HEAT PUMPS HAVE BEEN SHOWN ON THEPLANS.
B. LOCATE THE HORIZONTAL HEAT PUMP UNITS IN AREAS THATALLOW FOR EASY REMOVAL OF THE FILTER AND EASYACCESS TO HEAT PUMP UNIT ACCESS PANELS. LEAVEENOUGH SPACE FOR SERVICE PERSONNEL TO PERFORMMAINTENANCE OR REPAIR. PROVIDE SUFFICIENT ROOM TOMAKE WATER, ELECTRICAL, DUCT AND CONDENSATE DRAINCONNECTIONS.
C. IF ANY DUCTWORK OR PIPING (DOMESTIC WATER, FIRE,WATER LOOP, CONDENSATE DRAIN, NATURAL GAS,ELECTRICAL CONDUIT, CONTROLS CONDUIT IS RUN WITHINTHE SERVICE AREAS, THE PIPE, CONDUIT OR DUCT SHALL BEREMOVED AND RE-ROUTED IF POSSIBLE SO IT IS NOT WITHINTHE SERVICE AREA.
D. ALLOW ADEQUATE ROOM BELOW THE HEAT PUMP UNIT FORA CONDENSATE TRAP. DO NO LOCATE THE HEAT PUMP UNITABOVE ANY PIPING SYSTEMS WHERE POSSIBLE. EACHHORIZONTAL HEAT PUMP UNIT SHALL BE PROVIDED WITH AFILTER BRACKET FOR SIDE FILTER REMOVAL. THECONTRACTOR MAY CONVERT OR MODIFY THIS FILTERBRACKET TO ALLOW FOR BOTTOM REMOVAL OF THE FILTERIF IT PROVIDES A BETTER, MORE ACCESSIBLE INSTALLATION.
E. GENERALLY SPEAKING, HORIZONTAL HEAT PUMPS ARELOCATED AS HIGH AS POSSIBLE, BUT STILL ACCESSIBLEFROM A LADDER.
7. VERTICAL HEAT PUMPS:A. SEE 'VERTICAL HEAT PUMP INSTALLATION' DETAIL ON SHEET
M4.1 FOR REQUIREMENTS.
8. FOR OUTSIDE AIR SUPPLY DUCTWORK SIZES TO HEAT PUMPS,REFER TO HEAT PUMP SCHEDULE ON SHEET M5.1.
9. GENERALLY SPEAKING, DUCTWORK THROUGHOUT THE BUILDINGWAS LOCATED AS HIGH AS POSSIBLE TO ALLOW ROOM FORFITTINGS DOWN TO DIFFUSERS AND OTHER TRADES.
10. RTU EXHAUST OUT OF CLASSROOMS SHALL EQUAL THE OUTSIDEAIR CFM TO CLASSROOM UNLESS STATED OTHERWISE.
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
LEGEND NOTESLEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/2
2/2
017 2
:53:4
1 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
HV
AC
PLA
N, LO
WE
R L
EV
EL -
AR
EA
FM
1.1
F
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NORTHSCALE: 1/8" = 1'-0"
HVAC PLAN, LOWER LEVEL - AREA F
CC
- 19/
13/1
7A
DD
EN
DU
M C
C-1
CC
-29/
20/1
7A
DD
EN
DU
M C
C-2
DN
FS
FS
S
SS
S
S
S
SS
FS
FS
FS
FS
SS
FS
S
SS
S
S
S
S
S
SS
S
S
S
S H
S
S
S
S
A B C
D
E F G H J K
1
2
3
4 5
6
7
8
9
10
11
OFFICE
F234CLASSROOM
F233
VEST
F201
EARLYEDUCATION
F202
EARLYEDUCATION
F203BOYS
F204
GIRLS
F205
BOYS
F213
GIRLS
F214
PRINCIPAL
F207
NURSE
F209WORK ROOM
F211
GUIDANCE
F208
CLASSROOM
F222
CLASSROOM
F221
SPECIAL ED
F230JANITOR
F216
CLASSROOM
F228
TEACHERSLOUNGE
F220
WOMENS
F217
MENS
F218CLASSROOM
F229
SCIENCE
F223
CONFERENCEROOM
F225
ELEC
F224
RECEPTION
F206
CORRIDOR
F212
LEARNINGCOMMONS
F232
TOILET
F210
OFFICE
F235
STORAGE
F226
OFFICE
F231
CORRIDOR
F219
CORRIDOR
F215
COORIDOR
F227
34"x14" RA
HP-F25
HP
-F24
HP
-F22
HP
-F19
HP
-F20
HP
-F14
HP
-F18
100 CFM
300 CFM
HP
-F21
HP
-F17
HP
-F16
HP
-F15
12"x8" OA
14"x
8" O
A
14"x8" OA
16"x10" OA
22"x
10"
OA
14"x10" OA
24"x12" OA 16"x12" OA 14"x10" OA
10"x
8" O
A
10"x
8" O
A
10"x
8" O
A
8"x6" EA
8"x6" EA
12"x8" EA
18"x
10"
EA
18"x10" EA
18"x14" EA
22"x
14"
EA
20"x
10"
EA
12"x8" EA
14"x10" EA
20"x6" SA 18"x8" SA 18"x8" SA 18"x8" SA
20"x10" SA
18"x12" SA
12"ø
SA
12" ø565 CFM
D-1
12" ø565 CFM
D-1
24"x10" RA
8"ø OA
16"x10" SA
6" ø150 CFM
D-1
6" ø150 CFM
D-1
6" ø150 CFM
D-1
6" ø150 CFM
D-1
26"x16" OA
20"x8" RA
G-224" x 24"
14"x10" SA
12"x
8" O
A
8"ø
OA
8"ø OA
34/14 OA DN
8" ø230 CFM
D-1
TYP 2
16"x
10"
SA
8" ø200 CFM
D-18" ø
200 CFM
D-1
8" ø200 CFM
D-1
8" ø200 CFM
D-1
8"x1
0" S
A
G-224" x 24"
22"x22" RA
8"x8" TA
12"x12" TA
R-120" x 6"
400 CFM
R-120" x 6"
350 CFM
R-120" x 6"
350 CFM
R-120" x 6"
350 CFM
R-120" x 6"
350 CFM
30"x8" RA
8"x8" TA
8" ø270 CFM
D-1
12"x12" TA
10"x
8" O
A
14"x
10"
SA
8" ø315 CFM
D-1
8" ø315 CFM
D-16" ø
70 CFM
D-1
12"x12" TA
14"x
10"
SA
10"x10" SA
8" ø230 CFM
D-1
8" ø235 CFM
D-18" ø
235 CFM
D-1
10"x10" SA
8" ø230 CFM
D-1
8" ø235 CFM
D-18" ø
235 CFM
D-1
14"x10" SA
16"x10" OA
10"x10" SA
8" ø235 CFM
D-18" ø
235 CFM
D-1
8" ø230 CFM
D-1
14"x
10"
SA
10"x8" EA
10"x8" EA10"x8" EA
14"x10" SA
8" ø230 CFM
D-1
8" ø235 CFM
D-18" ø
235 CFM
D-1
10"x10" SA
12"x12" TA
10"x8" OA
20"ø SA
16"ø
SA
16"ø
SA
12" ø565 CFM
D-4
TYP 4
16"x12" EA
10/10 EA DN
R-130" x 24"
1250 CFM
30"X12" RA UPTO RTU-F01
20"X20" SA UPTO RTU-F01
G-124" x 24"
12"x12" TA
HP-F23
12"ø SA
8"ø
EA
12"ø SA16
"x14
" S
A
34"x
14"
EA
12"x6" OA
8" ø250 CFM
D-1
8" ø250 CFM
D-1
8" ø250 CFM
D-1
8" ø250 CFM
D-1
8" ø230 CFM
D-1
8" ø240 CFM
D-1
8" ø230 CFM
D-1
G-224" x 24"
G-224" x 24"
12"x10" SA
12"x12" SA
24"x8" RA
G-224" x 24"
G-112" x 12"100 CFM
12"x12" TA
10" ø325 CFM
D-1
10" ø325 CFM
?
8" ø200 CFM
D-110" ø
275 CFM
D-1
8"x6
" O
A
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-124" x 24"
G-112" x 12"100 CFM
G-112" x 12"100 CFM
G-112" x 12"100 CFM
8"x8" TA
G-112" x 12"
G-112" x 12"
10"x
6" O
A
12"x
8" O
A
G-224"x24"G-2
24"x24"
G-224"x24"
G-224"x24"
G-224"x24"
G-224"x24"
G-224"x24"
G-224"x24"
G-112" x 12"
G-112" x 12"
G-112" x 12"150 CFM
G-112" x 12"150 CFM
CC- 1
HP
-F12
G-124" x 24"
6" ø75 CFM
D-1
6" ø75 CFM
D-1
G-224" x 24"
HP
-F13
270 CFM
90 CFM
210 CFM
210 CFM
260 CFM
200 CFM
200 CFM
200 CFM
200 CFM
260 CFM
150 CFM
120 CFM
12"x
10"
OA
10"ø
OA
10"ø OA
G-124" x 24"
12"x10" SA 8"x8" SA
R-18" x 6"
100 CFM
R-18" x 6"
100 CFM
12"x12" TA
R-18" x 6"
50 CFM
R-18" x 6"
50 CFM
G-112" x 12"225 CFM
G-112" x 12"225 CFM
10"x10" EA10"x10" EA
8"x6
" E
A
10/10 EA OPENTO PLENUM
10"x10" TA
10"x10" TA
R-218"x6"
175 CFM(TYP 4)
24"x
8" R
A
22"x8" RA
12"x
12"
SA
10"x
12"
SA
14"x14" SA
24"x8" RA24"x8" RA
22"x8" RA22"x8" RA
24"x12" RA
20"x8" RA
32"x8" RA
30"x12" RA
10"x
10"
SA
30"x
10"
SA
CC-2
GENERAL HVAC PLAN NOTES:
1. LIMIT ALL FLEXIBLE DUCT RUNS TO 3 FEET MAXIMUM LENGTH.FLEXIBLE DUCT(S) SHALL BE OF THE SAME SIZE AS THE DIFFUSERNECKS THAT THEY CONNECT TO UNLESS NOTED OTHERWISE.
2. COORDINATE EXACT LOCATIONS OF ALL DIFFUSERS WITHELECTRICAL, FIRE SPRINKLERS, AND GRID CEILINGS.
3. BALANCING DAMPERS SHALL BE LOCATED ABOVE ACCESSIBLE CEILINGS. IF THIS IS NOT POSSIBLE, ACCESS PANELS SHALL BE PROVIDED. ACCESS PANELS SHALL BE TAMPERPROOF
LOCKABLE ACCESS PANLES FOR ACCESS TO CONTROL VALVES,MOTORIZED DAMPERS, SHUT-OFF VALVES, AND SIMILARCOMPONENTS THAT ARE NOT LOCATED OVER AN ACCESSIBLECEILING. VOLUME DAMPERS SHALL BE PROVIDED WITH REMOTEDAMPER OPERATORS WITH ADJUSTABLE COVER IN NON-ACCESSABLE CEILING AREAS. SEE DETAIL 8, SHEET M4.2,"REMOTE VOLUME DAMPER" AND SPECIFICATIONS FORFURTHER INFORMATION.
4. PROVIDE CEILING AND/OR WALL ACCESS DOORS FOR ACCESS TODUCT ACCESS DOORS RELATED TO THE INSPECTION ANDRESETTING OF FIRE DAMPERS AND COMBINATION SMOKE ANDFIRE DAMPERS. PROVIDE MINIMUM 18" X 18" SIZE. CEILINGAND/OR WALL ACCESS DOOR RATING SHALL BE EQUIVALENT TOCEILING AND/OR WALL WHERE DOOR IS TO BE INSTALLED.
5. BRANCH DUCT SIZES SHALL BE THE SAME AS THE NECK SIZE OFTHE DIFFUSERS OR THE CONNECTION SIZE OF THE GRILLES,UNLESS NOTED OTHERWISE.
6. HORIZONTAL HEAT PUMPS:A. MANUFACTURER-RECOMMENDED SERVICE ACCESS AREAS
FOR HORIZONTAL HEAT PUMPS HAVE BEEN SHOWN ON THEPLANS.
B. LOCATE THE HORIZONTAL HEAT PUMP UNITS IN AREAS THATALLOW FOR EASY REMOVAL OF THE FILTER AND EASYACCESS TO HEAT PUMP UNIT ACCESS PANELS. LEAVEENOUGH SPACE FOR SERVICE PERSONNEL TO PERFORMMAINTENANCE OR REPAIR. PROVIDE SUFFICIENT ROOM TOMAKE WATER, ELECTRICAL, DUCT AND CONDENSATE DRAINCONNECTIONS.
C. IF ANY DUCTWORK OR PIPING (DOMESTIC WATER, FIRE,WATER LOOP, CONDENSATE DRAIN, NATURAL GAS,ELECTRICAL CONDUIT, CONTROLS CONDUIT IS RUN WITHINTHE SERVICE AREAS, THE PIPE, CONDUIT OR DUCT SHALL BEREMOVED AND RE-ROUTED IF POSSIBLE SO IT IS NOT WITHINTHE SERVICE AREA.
D. ALLOW ADEQUATE ROOM BELOW THE HEAT PUMP UNIT FORA CONDENSATE TRAP. DO NO LOCATE THE HEAT PUMP UNITABOVE ANY PIPING SYSTEMS WHERE POSSIBLE. EACHHORIZONTAL HEAT PUMP UNIT SHALL BE PROVIDED WITH AFILTER BRACKET FOR SIDE FILTER REMOVAL. THECONTRACTOR MAY CONVERT OR MODIFY THIS FILTERBRACKET TO ALLOW FOR BOTTOM REMOVAL OF THE FILTERIF IT PROVIDES A BETTER, MORE ACCESSIBLE INSTALLATION.
E. GENERALLY SPEAKING, HORIZONTAL HEAT PUMPS ARELOCATED AS HIGH AS POSSIBLE, BUT STILL ACCESSIBLEFROM A LADDER.
7. VERTICAL HEAT PUMPS:A. SEE 'VERTICAL HEAT PUMP INSTALLATION' DETAIL ON SHEET
M4.1 FOR REQUIREMENTS.
8. FOR OUTSIDE AIR SUPPLY DUCTWORK SIZES TO HEAT PUMPS,REFER TO HEAT PUMP SCHEDULE ON SHEET M5.1.
9. GENERALLY SPEAKING, DUCTWORK THROUGHOUT THE BUILDINGWAS LOCATED AS HIGH AS POSSIBLE TO ALLOW ROOM FORFITTINGS DOWN TO DIFFUSERS AND OTHER TRADES.
10. RTU EXHAUST OUT OF CLASSROOMS SHALL EQUAL THE OUTSIDEAIR CFM TO CLASSROOM UNLESS STATED OTHERWISE.
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
LEGEND NOTESLEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/2
2/2
017 2
:53:5
0 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
HV
AC
PLA
N, M
AIN
LE
VE
L -
AR
EA
FM
1.2
F
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NORTHSCALE: 1/8" = 1'-0"
HVAC PLAN, MAIN LEVEL - AREA F
CC
- 19/
13/1
7A
DD
EN
DU
M C
C-1
CC
-29/
20/1
7A
DD
EN
DU
M C
C-2
UP
SS
S
S
S
S
S
S
SS
S
A
A
B
B
C
C
D
D
E
E
F
F
G
G
H
H
J
J
K
K
1
2
3
4 5
6
7
8
9
10
11
MEDIA CENTER
F121
1601 SF
STORAGE
F122175 SF
GREEN ROOM
F123
180 SF
CLASSROOM
F120
791 SF
CORRIDOR
F101947 SF
CLASSROOM
F119718 SF
CLASSROOM
F118714 SF
CLASSROOM
F117725 SF
CLASSROOM
F110703 SF
CORRIDOR
F116382 SF
CONFERENCEROOM
F115
213 SF
DATA
F113
134 SF
STORAGE
F11459 SF
SCIENCE
F111999 SF
CORRIDOR
107453 SF
COMPUTER LAB
F108747 SF
CLASSROOM
F109742 SF
GIRLS
F106163 SF
BOYS
F105
131 SF
CUSTODIAL
F102207 SF
RAMP/STAIR
F1S1
715 SF
MECHANICAL
F103583 SF
ELECTRICAL
F104126 SF
VEST
F124
39 SF
HP-F06
HP-F05
HP-F07
HP-F03
HP
-F04
HP
-F02
HP-F01
HP-F11
HP-F08
HP
-F09
HP
-F10
1"1" CR1"1" CS
1"1" CR
1"1" CS
1 1/2"1 1/2" CS1 1/2"1 1/2" CR
3/4"3/4" CR3/4"3/4" CS
1 1/2"1 1/2" CS
1 1/2"1 1/2" CR
1"1" CR1"1" CS
1 1/2"1 1/2" CS
1 1/2"1 1/2" CR
1"1" CS1"1" CR 1 1/2"1 1/2" CR
1 1/2"1 1/2" CS
1"1" CS
1"1" CR
1"1" CR1"1" CS
1"1" CS1"1" CR
2"2" CS2"2" CR
1"1" CR1"1" CS
1"1" CS1"1" CR
2"2" CS2"2" CR
3/4"3/4" CS3/4"3/4" CR
1 1/4"1 1/4" CS
1 1/4"1 1/4" CR
2 1/2"2 1/2" CR2 1/2"2 1/2" CS
4"4" CR
4"4" CR
CONDESER WATER LINES ROUTEDUNDERGROUND TO GEOTHERMAL VAULT.SEE SITE UTILITY PLAN FOR CONTINUATION
CS/R PIPING UP. SEE SHEETM2.2F FOR CONTINUATION P-F02
P-F01CS/R PIPING ROUTED UNDERFLOOR OF ROOM F233
GENERAL HVAC PIPING PLAN NOTES:
1. VALVES SHALL BE LOCATED ABOVE ACCESSIBLE CEILINGS. IFTHIS IS NOT POSSIBLE, ACCESS PANELS SHALL BE PROVIDED.ACCESS PANELS SHALL BE TAMPERPROOF LOCKABLE PANELSFOR ACCESS TO CONTROL VALVES, MOTORIZED DAMPERS,SHUT-OFF VALVES, VOLUME DAMPERS AND SIMILAR COMPONENTSTHAT ARE NOT LOCATED OVER AN ACCESSIBLE CEILING.
2. GENERALLY SPEAKING, WATER LOOP PIPING SHALL BE RUN ASHIGH AS POSSIBLE, BETWEEN JOISTS AND THROUGH JOISTWEBBING TO PROVIDE MAXIMUM CLEARANCE TO DUCTWORK ANDOTHER TRADES. PIPING SHALL BE AT LOW ENOUGH ELEVATIONTO ALLOW PROPER BRANCH TAPS TO BE MADE (OFF TOP OF MAINS)AND ROUTED TO THEIR ASSOCIATED HEAT PUMPS. STACK PIPINGWHERE REQUIRED.
3. WLS AND WLR PIPING CONNECTIONS TO HEAT PUMPS ARE SIZEDAS SHOWN ON THE HEAT PUMP SCHEDULE. SEE SHEET M5.1.
4. CONDENSATE DRAIN (CD) PIPING IS SIZED AS SHOWN ON THEHEAT PUMP SCHEDULE. SEE SHEET M5.1. WHERE CD IS NOTSHOWN ON THE DRAWINGS, ROUTE TO THE NEAREST FLOORDRAIN.
5. HORIZONTAL HEAT PUMPS:A. MANUFACTURER-RECOMMENDED SERVICE ACCESS AREAS
FOR HORIZONTAL HEAT PUMPS HAVE BEEN SHOWN ON THEPLANS.
B. LOCATE THE HORIZONTAL HEAT PUMP UNITS IN AREAS THATALLOW FOR EASY REMOVAL OF THE FILTER AND EASYACCESS TO HEAT PUMP UNIT ACCESS PANELS. LEAVEENOUGH SPACE FOR SERVICE PERSONNEL TO PERFORMMAINTENANCE OR REPAIR. PROVIDE SUFFICIENT ROOM TOMAKE WATER, ELECTRICAL, DUCT AND CONDENSATE DRAINCONNECTIONS.
C. IF ANY DUCTWORK OR PIPING (DOMESTIC WATER, FIRE,WATER LOOP, CONDENSATE DRAIN, NATURAL GAS,ELECTRICAL CONDUIT, CONTROLS CONDUIT IS RUN WITHINTHE SERVICE AREAS, THE PIPE, CONDUIT OR DUCT SHALL BEREMOVED AND RE-ROUTED IF POSSIBLE SO IT IS NOT WITHINTHE SERVICE AREA.
D. ALLOW ADEQUATE ROOM BELOW THE HEAT PUMP UNIT FORA CONDENSATE TRAP. DO NO LOCATE THE HEAT PUMP UNITABOVE ANY PIPING SYSTEMS WHERE POSSIBLE. EACHHORIZONTAL HEAT PUMP UNIT SHALL BE PROVIDED WITH AFILTER BRACKET FOR SIDE FILTER REMOVAL. THECONTRACTOR MAY CONVERT OR MODIFY THIS FILTERBRACKET TO ALLOW FOR BOTTOM REMOVAL OF THE FILTERIF IT PROVIDES A BETTER, MORE ACCESSIBLE INSTALLATION.
E. GENERALLY SPEAKING, HORIZONTAL HEAT PUMPS ARELOCATED AS HIGH AS POSSIBLE, BUT STILL ACCESSIBLEFROM A LADDER.
6. VERTICAL HEAT PUMPS:A. SEE 'VERTICAL HEAT PUMP INSTALLATION' DETAIL ON SHEET
M4.1 FOR REQUIREMENTS.
7. BRANCH PIPING CONNECTIONS FROM THE PIPING MAINS SHALL BE TAKEN OFF THE TOP OR SIDES OF THE PIPE. BRANCH PIPING OFF THE BOTTOM OF THE WATER LOOP PIPING MAINS IS SPECIFICALLY PROHIBITED UNLESS IT HAS BEEN SPECIFICALLY SHOWN TO BE PIPEDOFF THE BOTTOM OF THE PIPING MAIN.
8. REFRIGERANT PIPE SIZES SHALL BE AS DETERMINED BY THESUCCESSFUL MANUFACTURER.
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
LEGEND NOTESLEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/2
2/2
017 2
:53:5
1 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
HV
AC
PIP
ING
PLA
N, LO
WE
R L
EV
EL -
AR
EA
FM
2.1
F
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NORTHSCALE: 1/8" = 1'-0"
HVAC PIPING PLAN, LOWER LEVEL - AREA F
CC
- 19/
13/1
7A
DD
EN
DU
M C
C-1
CC
-29/
20/1
7A
DD
EN
DU
M C
C-2
CC- 1
CC-2
DN
UP
S
S
S
S
S
SS
S
S
S
S H
A B C
D
E F G H J K
1
2
3
4 5
6
7
8
9
10
11
GYMNASIUM
F2442718 SF
STORAGE
F245159 SF
MECHANICAL
F24673 SF
OFFICE
F23564 SF
OFFICE
F23464 SF
CLASSROOM
F233922 SF
GIRLS
F243208 SF
BOYS
F242184 SF
STORAGE
F24096 SF
KITCHEN
F239
585 SF
COORIDOR
F241128 SF
ALCOVE
F236
68 SF
JANITOR
F23795 SF
ELECTRICAL
F238
98 SF
LEARNINGCOMMONS
F2321085 SF
RAMP/STAIR
F1S1715 SF
CORRIDOR
F2121373 SF
RECEPTION
F206
272 SF
WORK ROOM
F211149 SFNURSE
F209
118 SF
TOILET
F21062 SF
GUIDANCE
F208281 SF
PRINCIPAL
F207244 SF
VEST
F201
126 SF
EARLYEDUCATION
F202666 SF
EARLYEDUCATION
F203473 SF
BOYS
F20420 SF
GIRLS
F20520 SF
TEACHERSLOUNGE
F220344 SF
CORRIDOR
F219203 SF
CLASSROOM
F221746 SF
CLASSROOM
F222757 SF
CLASSROOM
F228725 SF
CLASSROOM
F229713 SF
SPECIAL ED
F230642 SF
OFFICE
F231
67 SF
STORAGE
F226
94 SF
CONFERENCEROOM
F225236 SFSCIENCE
F2231089 SF
ELEC
F22465 SF
MENS
F21863 SF
WOMENS
F21764 SF
JANITOR
F21644 SF
GIRLS
F214163 SF
BOYS
F213131 SF
CORRIDOR
F215327 SF
COORIDOR
F227384 SF
VEST
F24745 SF
HP
-F22
HP
-F21
HP
-F20
HP
-F19
HP
-F18
HP
-F17
HP
-F16
HP
-F15 H
P-F
14H
P-F
13
HP
-F24
HP-F23
HP-F25
1"1" CR1"1" CS
1 1/4"1 1/4" CR
1 1/4"1 1/4" CS
1 1/2"1 1/2" CS
1 1/2"1 1/2" CR
1"1" CR
1"1" CS
1 1/2"1 1/2" CS
1 1/2"1 1/2" CR
1 1/2"1 1/2" CR1 1/2"1 1/2" CS
1"1" CR1"1" CS 2 1/2"2 1/2" CS
2 1/2"2 1/2" CR1"1" CR1"1" CS
2 1/2"2 1/2" CS
2 1/2"2 1/2" CR
1"1" CR
1"1" CS
2 1/2"2 1/2" CS
2 1/2"2 1/2" CR
1"1" CR
1"1" CS
2 1/2"2 1/2" CS
2 1/2"2 1/2" CR
1 1/4"1 1/4" CS
1 1/4"1 1/4" CR
1"1" CR1"1" CS
1 1/2"1 1/2" CS
1 1/2"1 1/2" CR
3"3" CR3"3" CS
3"3" CS3"3" CR
1 1/2"1 1/2" CR1 1/2"1 1/2" CS
1"1" CS
1"1" CR
1 1/2"1 1/2" CR
1 1/2"1 1/2" CS
1"1" CS
1"1" CR
1"1" CS
1"1" CR
1 1/4"1 1/4" CS1 1/4"1 1/4" CR
4"4" CS
4"4" CR
P-F01
P-F02
2-1/2" CS/R DOWN TOSERVE LOWER LEVEL
4" CONDENSER WATER THRUWALL TO CEILING PLENUM.ROUTE PIPING TO EXTERIORPLUMBING CHASE.
ROUTE PIPING AS HIGH ASPOSSIBLE IN JOIST SPACEABOVE CORRIDOR.
CC- 1
ET-F2
AS-F1
GENERAL HVAC PIPING PLAN NOTES:
1. VALVES SHALL BE LOCATED ABOVE ACCESSIBLE CEILINGS. IFTHIS IS NOT POSSIBLE, ACCESS PANELS SHALL BE PROVIDED.ACCESS PANELS SHALL BE TAMPERPROOF LOCKABLE PANELSFOR ACCESS TO CONTROL VALVES, MOTORIZED DAMPERS,SHUT-OFF VALVES, VOLUME DAMPERS AND SIMILAR COMPONENTSTHAT ARE NOT LOCATED OVER AN ACCESSIBLE CEILING.
2. GENERALLY SPEAKING, WATER LOOP PIPING SHALL BE RUN ASHIGH AS POSSIBLE, BETWEEN JOISTS AND THROUGH JOISTWEBBING TO PROVIDE MAXIMUM CLEARANCE TO DUCTWORK ANDOTHER TRADES. PIPING SHALL BE AT LOW ENOUGH ELEVATIONTO ALLOW PROPER BRANCH TAPS TO BE MADE (OFF TOP OF MAINS)AND ROUTED TO THEIR ASSOCIATED HEAT PUMPS. STACK PIPINGWHERE REQUIRED.
3. WLS AND WLR PIPING CONNECTIONS TO HEAT PUMPS ARE SIZEDAS SHOWN ON THE HEAT PUMP SCHEDULE. SEE SHEET M5.1.
4. CONDENSATE DRAIN (CD) PIPING IS SIZED AS SHOWN ON THEHEAT PUMP SCHEDULE. SEE SHEET M5.1. WHERE CD IS NOTSHOWN ON THE DRAWINGS, ROUTE TO THE NEAREST FLOORDRAIN.
5. HORIZONTAL HEAT PUMPS:A. MANUFACTURER-RECOMMENDED SERVICE ACCESS AREAS
FOR HORIZONTAL HEAT PUMPS HAVE BEEN SHOWN ON THEPLANS.
B. LOCATE THE HORIZONTAL HEAT PUMP UNITS IN AREAS THATALLOW FOR EASY REMOVAL OF THE FILTER AND EASYACCESS TO HEAT PUMP UNIT ACCESS PANELS. LEAVEENOUGH SPACE FOR SERVICE PERSONNEL TO PERFORMMAINTENANCE OR REPAIR. PROVIDE SUFFICIENT ROOM TOMAKE WATER, ELECTRICAL, DUCT AND CONDENSATE DRAINCONNECTIONS.
C. IF ANY DUCTWORK OR PIPING (DOMESTIC WATER, FIRE,WATER LOOP, CONDENSATE DRAIN, NATURAL GAS,ELECTRICAL CONDUIT, CONTROLS CONDUIT IS RUN WITHINTHE SERVICE AREAS, THE PIPE, CONDUIT OR DUCT SHALL BEREMOVED AND RE-ROUTED IF POSSIBLE SO IT IS NOT WITHINTHE SERVICE AREA.
D. ALLOW ADEQUATE ROOM BELOW THE HEAT PUMP UNIT FORA CONDENSATE TRAP. DO NO LOCATE THE HEAT PUMP UNITABOVE ANY PIPING SYSTEMS WHERE POSSIBLE. EACHHORIZONTAL HEAT PUMP UNIT SHALL BE PROVIDED WITH AFILTER BRACKET FOR SIDE FILTER REMOVAL. THECONTRACTOR MAY CONVERT OR MODIFY THIS FILTERBRACKET TO ALLOW FOR BOTTOM REMOVAL OF THE FILTERIF IT PROVIDES A BETTER, MORE ACCESSIBLE INSTALLATION.
E. GENERALLY SPEAKING, HORIZONTAL HEAT PUMPS ARELOCATED AS HIGH AS POSSIBLE, BUT STILL ACCESSIBLEFROM A LADDER.
6. VERTICAL HEAT PUMPS:A. SEE 'VERTICAL HEAT PUMP INSTALLATION' DETAIL ON SHEET
M4.1 FOR REQUIREMENTS.
7. BRANCH PIPING CONNECTIONS FROM THE PIPING MAINS SHALL BE TAKEN OFF THE TOP OR SIDES OF THE PIPE. BRANCH PIPING OFF THE BOTTOM OF THE WATER LOOP PIPING MAINS IS SPECIFICALLY PROHIBITED UNLESS IT HAS BEEN SPECIFICALLY SHOWN TO BE PIPEDOFF THE BOTTOM OF THE PIPING MAIN.
8. REFRIGERANT PIPE SIZES SHALL BE AS DETERMINED BY THESUCCESSFUL MANUFACTURER.
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
LEGEND NOTESLEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/2
2/2
017 2
:53:5
3 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
HV
AC
PIP
ING
PLA
N, M
AIN
LE
VE
L -
AR
EA
FM
2.2
F
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NORTHSCALE: 1/8" = 1'-0"
HVAC PIPING PLAN, MAIN LEVEL - AREA F
CC
- 19/
13/1
7A
DD
EN
DU
M C
C-1
CC
-29/
20/1
7A
DD
EN
DU
M C
C-2
CC-2
20'-0" (TYP)
1", 33 GPM PER BORE (TYP)
NO 90° ELBOWS (TYP), SEE WELLDETAIL 1/M4.3
20'-0
" (T
YP
)
FROM VALVE VAULT, TYP.
2"2"1-1/2"1-1/2"1-1/4"1"1"
2" 2" 1-1/2" 1-1/2" 1-1/4" 1"
TO VALVE VAULT
WLR
WLR
WLS
WLS
2"
1"
5'-0
" M
IN(V
ER
IFY
)
6"x2" WELD-O-LET (TYP)
PRESSURE / TEMPERATURE TESTPORT (TYP)
2" WLR (2" WLS BEYOND)
2" BALANCING VALVE W/ SHUT-OFF VALVE ON WLR (TYP)
PIPE SUPPORT (TYP) SPACE EVERY10'-0" FOR STEEL PIPE. SPACE PER MFRSRECOMMENDATIONS FOR POLYETHYLENE PIPE (TYP)
POLYETHYLENE x STEEL PIPEADAPTOR (TYP) SEE PIPING NOTE 1
4" WLR4" WLSSHUT-OFF VALVE NOT SHOWN. SEE PLAN VIEW.
SAND BACKFILL (SEE 235800.)
COATED 14 GA. COPPER TRACEWIRE ATTACHED TO PIPE ALONGENTIRE LENGTH
COMPACTED EARTH BACKFILL (ROCKFREE)
ORIGINAL GRADE
COMPACTED TRENCH BACKFILL
FILL BOREHOLE WITH THERMALLYENHANCED BENTONITE GROUT
MAIN RADIUS = 25 TIME DIAMETERBACKFILL THIS AREA BY HAND TOPREVENT KINKING OF PIPE.
REVERSE RETURN PIPING (PERHEADER PIPING DETAIL)
WLS HEADER PIPING
2'-0"
18"
(MIN
)
4" 5'-0" (MIN)
1" SDR II POLYETHYLENE PIPE RATEDAT160 PSIG @ 78° F (SEESPECIFICATIONS) NO JOINTSALLOWED BETWEEN HEADER ANDU-BEND
PREFABRICATED U-BEND CONNECTION
NOTE: WLS-WLR TO BE PIPED IN A REVERSE RETURN CONFIGURATION
300'
-0"
BO
RE
DE
PT
H6"
DIA
. BO
RE
WLR HEADER PIPING
1
REFERENCED NOTES:
1. MINIMUM TRENCH DEPTH IS 60". IF AT 60" DEPTH THE BOTTOM OF THETRENCH IS OF SOIL WITH ROCKS AND SHARP STONES, CONTRACTORSHALL OVER-EXCAVATE AN ADDITIONAL 12" AND REPLACE SPOILED SOILWITH COMPACTED SAND BACKFILL. SEE SPECIFICATION 235800.
90° ELBOW DN(TYP)
ISOLATION VALVE ON WLR
4" WLS
4" WLR
2'-6
"M
IN
POLYETHYLENE x STEELPIPE ADAPTOR. (TYP)SEE PIPING NOTE 1.
STEEL PIPE HEADERMANIFOLD (TYP)SEE PIPING NOTE 1.
2" SHUT-OFF VALVE ON WLS (TYP)
SEAL ANNULAR SPACEBETWEEN PIPE ANDSLEEVE WITH FLEXIBLEPOLYURETHANE FOAM(TYP)
HOSE ADAPTOR (TYP)
2" PURGE / DRAINVALVE (TYP)
BLIND FLANGE (TYP)
THERMOMETER (TYP)PRESSURE GAUGE (TYP)
1'-0"(TYP)
1'-0"(TYP)
2" WLS (TYP)
2" WLR (TYP)
2" SHUT-OFF VALVE ON WLS (TYP)
2" BALANCING VALVE W/ SHUT-OFF VALVE ON WLR (TYP)SET BALANCING VALVE AT 45GPM
36"
MIN
X"
Ø C
OM
BU
ST
ION
AIR
INT
AK
E
COMBUSTION AIR OPTION 1 COMBUSTION AIR OPTION 2 GAS VENT
X"
Ø C
OM
BU
ST
ION
AIR
INT
AK
E
APPROVED RAIN CAP
ROOF FLASHING
1" CLEARANCE
ROOF FLASHING
1" CLEARANCE
X"
Ø G
AS
VE
NT
ING
36"
MIN
APPROVED VENT TERMINAL
GUY WIRES. ATTACH TO ROOFSTRUCTURE.
36"
MIN
36"
MIN
10'
6' M
IN
A SCREEN WITH MESH SIZE NOT SMALLER THAN1" X 1" SHALL BE INSTALLED AT THE INLET OF THEDUCTED COMBUSTION AIR DUCT
THE BOILER VENT TERMINATION SHALL BEAT LEAST 3 FEET ABOVE ANY FORCED-AIRBUILDING INLET THAT IS LOCATED WITHIN10 FEET OF THE BOILER VENT.
-
-10'
NOTE:INTAKETHE BOILER AIR INTAKE SHALL BE LOCATED AT LEAST 3 FEET BELOW ANY VENT TERMINATION WITHIN 10 FEET.INSTALL LARGE-MESH SCREENS TO PROTECT AGAINST THE ENTRY OF FOREIGN OBJECTS BUT THE 'FREEAREA' SHALL BE AT LEAST TWICE THE FLUE CROSS-SECTIONAL AREA.
VENTVENT VERTICAL DISCHARGE SHALL EXTEND AT LEAST 3 FEET ABOVE THE ROOF THROUGH PROPERLY FLASHEDPENETRATIONS, AND AT LEAST 2 FEET ABOVE ANY OBJECT WITHIN A 10-FOOT HORIZONTAL DISTANCE.
HYDRONIC INDICATOR SYSTEM, MOUNTON PIPE
FLEXIBLE CONNECTION
SUCTION DIFFUSER
SUPPORT LEG
HOUSEKEEPING PAD
PUMP BASE PLATE
REDUCER
SILENT LIFT CHECK VALVE
SHUT-OFF VALVE (TYP)
FLOOR
BLOW DOWN VALVE WITH CAP
AIRFLOW
AIRFLOW
AIRFLOW
OA DUCT WITH BALANCING DAMPER
PIPING CONNECTIONS SEE, *
FLEXIBLE DUCT CONN. TYP.
WATER SOURCE HEAT PUMP
SPRING VIBRATION ISOLATORS(TYP OF 4)
3/8" SUPPORT RODS DOWN FROMSTRUCT. (TYP. OF 4)
RA DUCT W/ BALANCING DAMPER
SA DUCT W/ BALANCING DAMPER
RETURN AIR
HEAT PUMP
MECHANICAL CONTRACTOR SHALLPROVIDE SHEET METAL OR PLYWOODEQUAL IN SIZE TO FILTER & LABEL"FILTER PULL SPACE DO NOTREMOVE" ON BOTH SIDES. SECTIONSSHALL REMAIN IN-PLACE UNTIL LAY-IN-CEILING PANELS ARE INSTALLED ATWHICH TIME THE MECHANICALCONTRATOR SHALL REMOVE THESIGN. SUPPORT FROM STRUCTUREOR FROM DUCTWORK.
FILTER PULL SPACE
DO NOT R
EMOVE
SUPPLYAIRFLOW
RETURNAIRFLOW
OUTSIDEAIRFLOW
SUPPLY DUCTBALANCINGDAMPER
WLS/WLR PIPING.FOR CONNECTIONTO HEAT PUMP SEEDETAIL 6/M4.1
VERTICAL HEAT PUMP
MASON INDUSTRIES SUPER KNEOPRENE PAD OR EQUALSIZE AS REQUIRED BYEQUIPMENT WEIGHT (TYP 4)
PIPE CONDENSATE DRAINTO FLOOR DRAIN.SEE 18/M4.1
OUTSIDE AIR DUCTBALANCING DAMPER
RETURN DUCTBALANCING DAMPER
INSTALLATION NOTES:
1. GENERALLY, 1 OR 2 VERTICAL HEAT PUMPS WILL BE LOCATEDIN EVERY HEAT PUMP CLOSET.
2. CARE HAS BEEN TAKEN IN THE ARRANGEMENT OF THEMECHANICAL COMPONENTS WITHIN THE CLOSET TO ALLOWSUFFICIENT SERVICE ACCESS TO CONTROLS, COMPRESSORS,REFRIGERATION COMPONENTS, FILTERS, BLOWER AND BLOWERMOTOR. ALL SYSTEM COMPONENTS SHALL GENERALLY BEINSTALLED AS SHOWN ON THE PLANS AND PER THIS DETAIL.
3. HEAT PUMP SHOULD BE LOCATED WITH ACCESS TO FILTER ANDSERVICE PANEL(S) AT SIDE(S) OF MACHINE. CONSULTMANUFACTURER FOR LOCATION OF ACCESS PANEL. A MINIMUM36-INCH CLEARANCE SHOULD BE ALLOWED IN FRONT OF EACHSERVICE ACCESS PANEL SIDE.
4. THE ARRANGEMENT OF THE MECHANICAL COMPONENTS HASBEEN DESIGNED TO ALLOW ADEQUATE CODE-REQUIREEDCLEARANCES AROUND ELECTRICAL DISCONNECTS IN THESECLOSETS. SEE ELECTRICAL PLANS FOR LOCATIONS OF THESEDISCONNECTS.A. ELECTRICAL CONDUIT & PIPE ROUTING MUST NOT BLOCK
FILTER REMOVAL. FILTERS OFTEN PULL STRAIGHT UP,SOMETIMES THEY ARE REMOVABLE FROM SIDE. ALSO,CONDUIT & PIPE ROUTING SHOULD NOT INTERFERE WITHACCESS PANELS.
INSTALLATION NOTES (CONT'D):
5. THE PIPING SHALL BE ARRANGED IN A MANNER THAT ALLOWSMAINTENANCE ACCESS TO THE TWO-WAY CONTROL VALVESAND HEAT PUMP HOSE KIT ASSEMBLY.A. ALL VALVES ON VERTICAL PIPES SHALL HAVE THEIR STEMS
ORIENTED TO GIVE MAXIMUM OPERATIONAL CLEARANCE,OR SHALL BE ORIENTED AS DIRECTED BY THE ENGINEER.
B. VALVES SHALL BE LOCATED SO AS TO BE EASILYACCESSIBLE TO THE OPERATOR OF THE EQUIPMENT.
C. AUTOMATIC FLOW CONTROL (BALANCE) VALVES SHALL BEORIENTED SO THE P/T PLUGS ARE ACCESSIBLE TO THEBALANCING CONTRACTOR.
D. AUTOMATIC 2-WAY (TEMPERATURE CONTROL VALVES)SHALL BE ORIENTED SO THAT THEIR VISUAL INDICATOR ISREADILY AND CLEARLY VISIBLE, AND THE OPEN/CLOSEPOSITION SHALL BE CLEARLY MARKED ON THE ACTUATOR.
E. VALVES SHALL BE LOCATED WITHIN 6'-0" AFF.F. PIPING SHALL BE RIGIDLY ANCHORED TO THE BUILDING
STRUCTURE SO AS TO PREVENT THE TRANSFER OFLOADING (WEIGHT) OR OTHER FORCES TO CONNECTIONSAT THE HEAT PUMP UNITS
6. BRANCH PIPING CONNECTIONS FROM THE WATER LOOP PIPINGMAINS IN THE CORRIDOR SHALL BE TAKEN OFF THE TOP OR SIDESOF THE PIPE. BRANCH PIPING OFF THE BOTTOM OF THE WATERLOOP PIPING MAINS IS SPECIFICALLY PROHIBITED.
7. THE DISCHARGE DUCT FROM EACH HEAT PUMP SHALL CONSISTOF A FLEXIBLE CONNECTOR AT THE HEAT PUMP UNIT, AND ATRANSITION PIECE FROM THE DISCHARGE COLLAR OF THE HEATPUMP TO THE PLAN DUCT SIZE. SEE PLANS FOR CONFIGURATIONOF TRANSITION PIECES (VARIES BY HEAT PUMP).
FLEXIBLE DUCTCONNECTIONW/BONDING JUMPER(BY ELECRICAL)ACROSS ALL FLEXCONNECTORS (TYP)
INSTALLATION NOTES (CONT'D):
8. ALL VERTICAL DUCTWORK THAT IS LOCATED ABOVE AFLEXIBLE DUCT CONNECTOR SHALL BE RIGIDLYSUPPORTED SO THE WEIGHT OF THE DUCTWORK DOESNOT BEAR ON THE FLEXIBLE DUCT CONNECTOR FABRICAT THE HEAT PUMP UNITS.
9. THE RETURN AIR DUCTS SHALL GENERALLY BEBROUGHT INTO THE MECHANICAL ROOM AS SHOWN,TYPICALLY AS HIGH TO STRUCTURE AS POSSIBLE.EACH RETURN DUCT SHALL HAVE A VOLUME DAMPER.THE RETURN DUCT AT EACH HEAT PUMP SHALL HAVE AVOLUME DAMPER AND A FLEXIBLE CONNECTOR.
10. EACH RETURN AIR DUCT CONNECTIONS AT THE HEATPUMP UNITS SHALL HAVE A SIDE ACCESS FILTER RACK.FILTER PULL ACCESS SHALL TYPICALLY BE BETWEENTHE TWO VERTICAL HEAT PUMPS, AND IS REPRESENTEDBY A DASHED AREA ON THE PLANS. THESECLEARANCES MUST BE MAINTAINED UPON FINALINSTALLATION OF MECHANICAL EQUIPMENT.
11. THE OUTDOOR AIR DUCT SHALL BE CONNECTED TO THERETURN AIR DUCT WITH A LOW LOSS FITTING. SEEPLANS FOR FITTING ARRANGEMENT. GENERALLY SPEAKING,OUTDOOR AIR DUCTS SHALL BE RUN AS HIGH ASPOSSIBLE, TIGHT TO STRUCTURE. WHEN DUCT ENTERSCLOSET AT A HIGHER ELEVATION THAN HEAT PUMPRETURN DUCTWORK, PROVIDE ELBOW DOWN TO LOW LOSSWYE FITTING (IN VERTICAL).
12. SERVICE CLEARANCE FOR HEAT PUMP UNITS HAS BEENREPRESENTED ON THE PLANS BY A DASHED AREA.THESE CLEARANCES MUST BE MAINTAINED UPON FINALINSTALLATION OF MECHANICAL EQUIPMENT.
P T
P T
WLS
CD PIPE TO DRAIN
HEATPUMP
UNION W/ P/T TEST PORT & MANUAL AIR VENT
2-WAY CONTROL VALVE FURNISEDBY TCC, INSULATED BY MC
INSULATED RETURN HOSE
INSULATED SUPPLY HOSE
CONDENSATE DRAIN P-TRAP SEEDETAIL 20/M4.1
BLOWDOWN VALVE W/ THREADEDHOSE CONNECTION
WYE TYPE STRAINER W/ INTEGRALBALL VALVE & P/T TEST PORTS
EXTENDED YOKES FOR INSULATION (TYP)AT VALVES & P/T PORTS
SHUT-OFF VALVE
BALL VALVE W/ INTEGRAL UNION,AUTOMATIC FLOW VALVE & DUAL P/TTEST PORTS
INSULATED CONDENSATE DRAINLINES
BRAIDED FLEXIBLE CONNECTOR W/ SWIVEL ENDAT EQUIP & FIXED END AT PIPING CONNECTION
P T P T
P T
UNION
5'-0" MAX
NOTE:FOR SAME HANGER DETAIL FOR PIPE TRAPEZE HANGERS
UNDERSIDE SUPPORTS OR SIDE-MOUNTED ANGLE BRACKETS BY HEATPUMP MFR
STEEL JOIST OR STEEL BEAM
MECHANICAL UNIT
3/8" THREADED RODS (BY MECH)
1-3/8" x 1-5/8" UNISTRUT CHANNELBETWEEN DECK RIBS (BY MECH)
WELD OR BOLT TO STEEL JOISTS (BYMECH)
LOOPED SUPPLY HOSE ORTEMPORARY PIPING
STRAINER
FLOW CONTROL VALVE
RETURN
SUPPLY
TERMINAL UNIT
THIS DETAIL IS NOT TO BE USED AS THE PIPING CONNECTION DETAIL FOR THE HEAT PUMPUNITS. THE PURPOSE OF THIS DETAIL IS TO ILLUSTRATE THE PROCEDURE TO BE USED FORBYPASSING THE HEAT PUMP UNITS DURING THE FLUSHING AND CLEANING OF THE HYDRONICSYSTEM. THIS IS METHODOLOGY AS OUTLINED BY GRISWOLD CONTROLS. REFER TO DETAILXX/M4.1 FOR HEAT PUMP UNIT CONNECTION DETAIL.
CLEANING AND DRAINING THE SYSTEM:
PRIOR TO FULL SYSTEM START-UP, ALL PIPING SHALL BE THOROUGHLY CLEANED TO REMOVE DIRT AND DEBRIS.TO FLUSH OUT THE PIPING SYSTEM PROPERLY, THE HOSE KITS SHALL BE MODIFIED AS SHOWN ON THE DETAIL BY"LOOPING THE SUPPLY HOSE AND RETURN PIPING TOGETHER, THUS BY-PASSING THE TERMINAL UNIT (HEATPUMP), AND FLOW CONTROL VALVE. THIS PROCEDURE SHALL BE USED TO PROTECT THE TERMINAL UNITS FROMCONTAMINATION.
PROCEDURE FOR "LOOPING" HOSES:
1. DISASSEMBLE THE RETURN SIDE HOSE KIT ASSEMBLY, BUT LEAVE THE BALL VALVE CONNECTED TO THERETURN PIPE.
2. REMOVE THE INTERNAL SCREEN FROM THE Y-STRAINER WHILE FLUSHING THE SYSTEM.3. LOOSEN THE SUPPLY SIDE HOSE FROM THE TERMINAL UNIT, AND "LOOP" IT DIRECTLY TO THE BALL VALVE ON
THE RETURN SIDE PIPING (A COUPLING MAY BE REQUIRED DEPENDING ON THE BALL VALVE CONNECTIONTYPE).
4. AFTER ALL HOSES HAVE BEEN "LOOPED", START THE SYSTEM PUMP TO CLEAN THE PIPING SYSTEM OFPARTICLES LARGER THAN APPROXIMATELY 1/16" IN DIAMETER (I.E. WELD SPLATTER, MILL SCALE, AND OTHERCONTAMINANTS). REFER TO "HYDRONIC PIPING" SPECIFICATION FOR CLEANING AND FLUSHINGINSTRUCTIONS.
FINAL CONNECTIONS:
1. SHUT OFF BOTH BALL VALVES ON THE SUPPLY AND RETURN CONNECTIONS TO THE UNITS. IF A STRAINER ANDDRAIN VALVE ARE INSTALLED, OPEN THE DRAIN VALVE TO REMOVE THE FLUSHING WATER FROM THECONNECTING HOSE.
2. BREAK THE TEMPORARY "LOOP", AND REINSTALL THE FLOW CONTROL VALVE AND THE RETURN SIDE HOSE.3. CONNECT BOTH HOSES TO THE TERMINAL UNIT AS SHOWN ON DETAIL XX/M4.1.4. REINSTALL THE INTERNAL SCREEN IN THE Y-STRAINER.5. OPEN BOTH SUPPLY AND RETURN BALL VALVES, AND FILL THE SYSTEM WITH FLUID.6. BLEED ANY ENTRAINED AIR SO THAT THE FLOW CONTROL VALVE WILL REMAIN FULL OF FLUID DURING
OPERATION.
BUILDING WALL INTERIOR
RIVET (TYP)
RECTANGULAR DUCTWORK
SEAL ALL WALL PENETRATIONS (TYP)
PIPING & INSULATION
GALV. STEEL DRAWBANDTYPE ESCUTCHEON, 3" WIDE
ROUND DUCTWORK
SATIN FINISH OR ALUMINUMSPLIT-TYPE ESCUTCHEON
SLEEVE IN MASONRY WALL (TYP)
CONCEALED DUCTWORK& PIPING
EXPOSED DUCTWORK& PIPING IN FINSHED SPACES
HANGER CLAMP OR BAND
BOLT
STRAP OR ANGLE
NUT
ANGLE
ROD
DUCT
LONG FLAT SPANS ON OVAL DUCTHAVE A TENDENCY TO SAG. OVALDUCT WITH A MAJOR AXIS OF 42INCHES OR MORE SHALL BEREINFORCED PER SMACNA HVACDUCT CONSTRUCTION STANDARDSTYPE 2.
CHANNEL OR ANGLE
NOTES:1. DO NOT EXCEED ALLOWABLE LOAD LIMITS OF ANY OR ALL OF THE INDIVIDUAL TRAPEZE PARTS.2. DO NOT PENETRATE DUCT OR DUCT INSULATION VAPOR BARRIER WHEN SECURING HANGERS TO
DUCTWORK. EVENTUALLY THE PENETRATIONS WILL LEAK.3. USE HANGER CLAMPS OR BANDS FOR ROUND DUCTS AS ROUND DUCT TENDS TO DEFORM ON
TRAPEZE HANGERS.4. TEARS, PUNCTURES, ETC. SHALL BE REPAIRED WITH TAPE OR MASTIC TO MAINAIN THE INTEGRITY
OF THE VAPOR BARRIER.5. DO NOT USE ANY STRAP HANGERS WITH SCREWS ON ANY DUCTWORK THAT IS EXTERNALY
WRAPPED.
PROVIDE A SECTION OF HIGHCOMPRESSION STRENGTHINSULATION AT EACH HANGER POINT.INSULATION MAY BE HALF ROUND ORFULL ROUND AND EXTENDED 2"BEYOND GALVANIZED SHIELD EACHWAY.
HANGER ROD WITH CLEVIS HANGER
PIPE
UNI-STRUT CHANNEL
GALV. IRON SHEET SHIELD (12" LONG)
INSULATION
PIPE
NOTES:
1. ATTACH SUPPORTS FOR ALL PIPING SUSPENDED FROM THE STEELSTRUCTURE TO THE TOP CHORD OF JOISTS OR BEAM.
2. PROVIDE COPPER OR PLASTIC COATED HANDERS FOR NON-INSULATED COPPER PIPE.
VD
LINEAR DIFFUSER
ROUND DUCT WRAP INSULATION
CEILING
SUPPLY MAIN WRAP INSULATION
45° ENTRY TAP RECTANGULAR TOROUND
FLEX CONNECTION NO BENDS MAX.5'-0" LONG
VD
DIFFUSER
ROUND DUCT WRAP INSULATION
CEILING
SUPPLY MAIN WRAP INSULATION
45° ENTRY TAP RECTANGULAR TOROUND
FLEX CONNECTION NO BENDS MAX.5'-0" LONG
WALL
1" ACCOUSTICAL DUCT LINER
W W * 1.5
NOTE:1) DAMPER MUST BE U.L. APPROVED & INSTALLED AS PER
MANUFACTURER U.L. RECOMMENDATIONS. UL555, UL555A & UL55C.2) PROVIDE ACCESS PANELS IN WALLS OR CHASES.
DUCT
MOUNTING ANGLE14 GA
DAMPER ACTUATOR(SMOKE & FIRE/SMOKE DAMPERS)
MOUNTING ANGLE14 GA
14 GA SLEEVE
FIRE, SMOKE, OR COMBINATIONFIRE/SMOKE DAMPER
BREAKDOWN JOINT
ALLOW FOR 1/8" EXP OF SLEEVE INSETTING ANGLES. ANGLES TO LAPSTRUCTURE A MIN. OF 1" AROUNDENTIRE OPENING.
DAMPERACCESS
WALL ORPARTITION
WLR
WLRWLS
WLS
4" FROM SYSTEM
4" ISOLATION VALVES, TYPICAL
THERMOMETER (TYP)
PLASTIC TO METAL PIPE FLANGETRANSITION.
METAL PIPE SYSTEM INSTALLED BYMECHANICAL CONTRACTOR.PLASTIC PIPE SYSTEM INSTALLED BYWELL FIELD CONTRACTOR.
4" TO GROUND LOOP FIELD VAULT
1" HOSE CONNECTION W/LOCKINGBALL VALVE (FILL & FLUSHING)
EMCS BULB WELL (TYP)
MANUAL AIR VENT (TYP)
4" TO PUMP SYSTEM
X"
Y"
INSTALL ADDITIONAL VENT ATINTERVALS OF 10' WHEN PIPINGDOWNSTREAM OF TRAP EXCEEDS15'
FLOOR DRAIN
CLEAN OUT
1" AIR GAP
PITCH DOWN TOWARD DRAIN
OPEN END
CLEAN OUT
DRAIN LINE SHALL BE AT LEAST THESAME SIZE AS THE NIPPLE ON THEDRAIN PAN
EQUIP MUST BE MOUNTED HIGHENOUGH VIA HOUSEKEEPING PADAND/OR EQUIPMENT RAILS TO ENSUREX AND Y DIMENSIONS
NOTES:1. ON DRAW-THRU UNITS, THE (X) DIMENSION (IN INCHES) SHALL BE 1.5 TIMES THE AIR HANDLING-UNITS
SUCTION PRESSURE AT OPERATING CONDITIONS, BUT IN NO CASE LESS THAN 2-INCHES.2. ON BLOW-THRU UNITS, THE (X) DIMENSION (IN INCHES) CAN BE AS SMALL AS 2 INCHES, BUT THE (Y)
DIMENSION (IN INCHES) SHALL BE 1.5 TIMES THE AIR HANDLING UNITS TOTAL STATIC PRESSURE BUTIN NO CASE LESS THAN 2 INCHES.
X=DISTANCE BETWEEN THE DRAIN PAN OUTLET AND THE TRAPY=TRAP DEPTH
3/4" BALL VALVE W/HOSE END THREADCONNECTION
THREAD PIPE CAP DO NOT SEAL WELD
LOW POINT
WELDOLET
SOCKET WELD
PITCH DOWNTO DRAIN
HVAC PIPING LOW POINT DRAINA
3/4" LEAD FREE BALL VALVE W/HOSEEND THREAD CONNECTION CAP ANDCHAIN
LOW POINT
PITCH DOWNTO DRAIN
PLUMBING PIPING LOW POINT DRAINB
REFRIGERANT LINES, CONDENSATELINE, AND CONDUIT (REFER TOPLANS)
PORTALS PLUS INC. MODEL C12 CAP
PORTALS PLUS INC. RC SERIES 18GAUGE GALVANIZED ROOF CURBSYSTEM 16" MIN
NOTES:1. CONTRACTOR SHALL ONLY CUT OPENINGS THRU ROOF DECK AND INSULATION THE SIZE REQUIRED
FOR THE PIPING TO BE INSTALLED. THE ROOF OPENING SHALL NOT BE CUT TO THE SIZE OF THEROOF CURB.
2. ROOF INSULATION SHALL BE CONTINUOUS INSIDE OF THE ROOF PENETRATION VAULT.3. THE VAULT/HOUSING, INCLUDING HOUSING CURB, PIPE COLLARS & SEALS, GASKETS AND STAINLESS
STEEL MOUNTING HARDWARE SHALL BE FURNISHED BY PORTALS PLUS INC.
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
Rev
isio
ns
9/2
2/2
017 2
:53:5
8 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
ME
CH
AN
ICA
L D
ET
AIL
SM
4.1
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
SCALE: 3/8" = 1'-0"M4.1
1 GEOTHERMAL LOOP PIPING CIRCUITSCALE: 3/8" = 1'-0"M4.1
2 GEOTHERMAL VAULT SECTIONSCALE: 3/8" = 1'-0"M4.1
3 GEOTHERMAL BORE SECTIONSCALE: 3/8" = 1'-0"M4.1
4 GEOTHERMAL VAULT PLAN
SCALE: 12" = 1'-0"M4.1
5 COND BOILER / WATER HTR COMBUSTION AIR INTAKE & GAS VENTSCALE: 3/8" = 1'-0"M4.1
6 END SUCTION PUMPSCALE: 12" = 1'-0"M4.1
7 HEAT PUMP MOUNTINGSCALE: 3/8" = 1'-0"M4.1
8 HEAT PUMP FILTER ACCESS
SCALE: 3/8" = 1'-0"M4.1
9 VERTICAL AND HORIZONTAL HEAT PUMPSCALE: 3/8" = 1'-0"M4.1
10 HEAT PUMP PIPING
SCALE: 3/8" = 1'-0"M4.1
12 MECH UNIT HANGING DETAIL (UNIT WT <300LBS)
SCALE: 3/8" = 1'-0"M4.1
11 FLUSHING PIPING CONNECTION
SCALE: 3/8" = 1'-0"M4.1
13 DUCT/PIPE WALL PENETRATIONSSCALE: 3/8" = 1'-0"M4.1
14 DUCTWORK HANGING DETAILSCALE: 3/8" = 1'-0"M4.1
15 PIPE INSULATION AT HANGERSSCALE: 3/8" = 1'-0"M4.1
16 DIFF DUCT CONN HORIZ FLEX
SCALE: 3/8" = 1'-0"M4.1
17 TRANSFER DUCTSCALE: 3/8" = 1'-0"M4.1
18 COMBO FIRE/SMOKE DAMPERSCALE: 3/8" = 1'-0"M4.1
19 WATER LOOP ENTRANCE ISOSCALE: 3/8" = 1'-0"M4.1
20 CONDENSATE DRAIN P-TRAPSCALE: 12" = 1'-0"M4.1
21 LOW POINT DRAINSCALE: 12" = 1'-0"M4.1
22 ROOF PIPE PORTAL
CC
-29/
20/1
7A
DD
EN
DU
M C
C-2
CC-2
VV
BALANCING VALVE
CHECK VALVE
UNION (TYP)
PRESSURE GAUGE
STRAINER
ISOLATION VALVE (TYP)
INLINE PUMP
VV
DRAIN VALVE WITHHOSE END CONNECTIONS
V
V
V
TO PUMP SUCTION
FLOOR MOUNTED PRESSURIZEDEXPANSION TANK, ET-E02
STEEL ANGLE OR UNI-STRUT FOR AIRSEPARATOR LARGER THAN 8"
SET RELIEF VALVE AT 100 PSI
HIGH CAPACITY AIR VENT (TYP)
FOR AIR SEPARATOR 8" AND SMALLER ATTACH PIPEHANGERS TO THE TANGENTIAL NOZZLES. FOR AIRSEPARTATORS LARGER THAN 8" PROVIDE SUPPORTSUNDER SKIRT OF SEPARATORNOTE: DO NOT USE LIFTING LUGS TO SUPPORT UNIT
AIR SEPARATOR
CONNECT TO SIDE OF PIPING, TOP ORBOTTOM CONNECTION WILL NOT BEALLOWED
1"
ANTI-THERMO SIPHON LOOP, INSTALLPER MFR INSTRUCTIONS
3/4" DRAIN VALVE W/ THREADED HOSECAP (TYP)
4" HIGH EQUIP PAD BY GEN
FLOOR
V V V V 1” CW MAKE-UP
FULL SIZE BY-PASS
GLOBE VALVE
REDUCED PRESSURE BACKFLOWPREVENTER, RUN DRAIN LINE FULL SIZETO FD/FS
1/2" TAP OFF TOP OF CW LINE
CW SUPPLY 1-1/2" OR SMALLER SUPPLYINGA FLUSH VALVE
BALL VALVE
PROVIDE ADDITIONAL ACCESS PANEL ORLOCATE TRAP PRIMER BEHIND PLUMBINGCHASE ACCESS PANEL TRAP PRIMER SHALLBE WITHIN 16" OF ACCESS PANEL DOOR
TRAP PRIMER, PRECISION PLUMBINGPRODUCTS, PRIME-RITE MODELPR500SS OR EQUAL
PRECISION PLUMBING PRODUCTS,DISTRIBUTION UNIT
1/2" SEAMLESS COPPER TUBING TOFLOOR DRAIN TRAP PRIMERCONNECTION (TYP). ENTIRE LENGTH OFTUBING SHALL HAVE ARMAFLEXINSULATION. TUBING SHALL SLOPE TOFLOOR DRAIN WITH NO LOW POCKETS.
24"
MIN
NON-FREEZE POST HYDRANT
ROOF INSULATION
ROOF STRUCTURE
PIPE CLAMP
VALVE BOOT WITH 1/8" TAP FORBLEED FITTING CONNECTION
BALL VALVE
1/2" BALL DRIP,PIPE TO FLOOR DRAIN
RUBBER BOOT & FASTENER BYROOF SYSTEM MFR
OUTSIDEBUILDING
INSIDEBUILDING
GAS SERVICE TO BUILDING
3/8" GAUGE PORT WITH PLUG
GAS METER
GAS PRESSURE REGULATOR
UNION (TYP)
SERVICE SHUT-OFF VALVE MARK, OR TAG TOINDICATE THE EXISTENCE OF THE SEPARATEEMERGENCY POWER SUPPLY SHUTOFF VALVE
GAS SERVICE LINE
GRADE
2 PSI GAS SERVICE TO BUILDING. ALL EXTERIORGAS PIPING TO BE PAINTED WITH HIGHPERFORMANCE COATING
MECHANICAL LINK SEAL & GALVANIZED STEELPIPE SLEEVE. CAULK TO MAKE WEATHERTIGHT
TO EMERGENCY GENERATOR
MARK OR TAG TO INDICATE THE EXISTENCE OFTHE MAIN BUILDING SUPPLY SHUTOFF VALVE
ROOF
MAIN LEVEL
DRIP LEG
TOWATERHEATER
TO ROOF TOPUNITS ANDSCIENCE ROOM
LEADER, SAME SIZE AS DRAINAGELINE UP TO 4".USE 4" FOR LARGER DRAINAGE PIPING.
TWO-WAY PIPE FITTING
JAY R. SMITH FIGURE NO 4258C OR 4263LCLEANOUT HOUSING WITH BRONZE TAPERTHREAD CLEANOUT PLUG OR EQUAL
CONCRETE SIDEWALK OR PAVING (BYOTHERS)
GRADE CLEANOUT WITH FLUSHCOVERS. COORDINATE LOCATIONWITH JOINT PATTERN IN SIDEWALK, ORWHEN LOCATED ON GRADE, PROVIDE12" x 36" 2400 PSI CONCRETE PAD
3"
8"
PUMP ON
PUMP OFF
DIFFERENTIAL MERCURY FLOATSWITCH
BASIN
CHECK VALVE
SHUT-OFF VALVE
2" FORCE MAIN
STEEL COVER PLATE
FLOOR
INLET
34" 34
"
*
ADJUST LAVATORY SETBACKTO CLEAR INSIDE CASEWORK& ADA KNEE & TOE CLEARANCES
SEE SPECIFICATIONSFOR LAVATORY & TRIM
OFFSET WASTE
ADJUST WASTE CONNECTIONROUGH-IN AS REQUIRED FOR TRAPPARALLEL TO WALL TOWARDS COLDWATER SUPPLY SIDE
TRAP PARALLEL TO WALL
FLOOR
ESCUTCHEON
CASEWORK ENCLOSURE BY OTHERS
SEE SPECIFICATIONS FOR LAVATORY& TRIM
ESCUTCHEON
OFFSET WASTE
ADJUST WASTE CONNECTIONROUGH-IN AS REQUIRED FOR TRAPPARALLEL TO WALL TOWARDS COLDWATER SUPPLY SIDE
TRAP PARALLEL TO WALL
FLOOR
A WALL - MOUNTED A COUNTER - MOUNTED
THERMOMETER (TYP)
ROOF LINE
PROVIDE MFR'S VENTTERMINATION CAP FORCOMBUSTION AIR INLET DUCT,6-INCH DIAMETER (TYP)
PROVIDE MFR'S VENTTERMINATION CAP FOREXHAUST VENT (TYP)
2"
CO
MB
US
TIO
N A
IR
GA
S V
EN
T
RELIEF VALVE (TYP)
PER PVI, "TO MAXIMIZE WATER HEATER EFFICIENCY, DONOT CONNECT THE BUILDING RETURN OR DISHWASHERRECIRCULATION PIPING (≈ 5 GPM) DIRECTLY TO THE COLDINLET. CONNECTION DIRECTLY TO THE DEDICATED BUILDINGRETURN FITTING LOCATED AT THE REAR OF THE TANK ATMIDTANK LEVEL."
COLD INLET(BACK OF UNIT)
CONDENSATE DRAIN LINE(BACK OF UNIT)(TYP)
DRAIN VALVE (TYP)
6" HOUSE KEEPING PAD (TYP)
FLOOR
CONDENSATE TRAP
NEUTRALIZATION TANK
EXISTING FLOOR DRAIN
RE
L
GDWH-1
2"3/4"
CW
2"
P-F04
3/4"
G
140
HW
C
SHUT-OFF VALVE (TYP)
POUNDS TO INCHESREGULATOR (TYP)
UNION (TYP)
DIRT LEG (TYP)
SHUT-OFF (TYP)
UNION (TYP)
NC BYPASS VALVE
2"
2"
140
HW
RE
L
AQUASTAT
2"
T-1
HOUSE KEEPING PAD
3/4"
1"
CW
110
HW
C
110
HW
C
110
HW
C
140
HW
HEAT TRAP
TMV-1
1-1/2"
2"3/4"
140 HW
140 HWC
140 HW
110 HW
110 HWC
1-1/2"
1/2"
P-F03
(TYP)
2"
SHUT-OFF (TYP)
EXPANSION TANK
P-EX
1
M4.2
ET-1
1"
FLOOR
CLASSROOM STATION
CEILING
CONNECT TO DUAL GAS TURRET
ZONE MASTER GAS SHUT-OFF VALVE
STEEL PIPING TO RUN IN WALLRECESS NOT RIGIDLY SECUREDSEE ARCH
FROM GAS MAIN
TO ADDITIONAL GAS COCKS INCLASSROOM
G G
GAS SHUT-OFF PUSH BUTTON"EMERGENCY PANIC PUSH BUTTON",SEE SPEC. 231120
ROOM MASTER GAS SHUT-OFF PANEL"WALL MOUNTED UTILITY CONTROLPANEL", SEE SPEC. 231120
S
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
Rev
isio
ns
9/2
2/2
017 2
:54:0
1 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
ME
CH
AN
ICA
L D
ET
AIL
SM
4.2
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
SCALE: 3/8" = 1'-0"M4.2
1 INLINE PUMPSCALE: 12" = 1'-0"M4.2
2 WATER SYSTEM MAKE-UP & AIR CONTROL PIPINGSCALE: 12" = 1'-0"M4.2
3 FLOOR DRAIN TRAP PRIMERSCALE: 3/8" = 1'-0"M4.2
4 POST HYDRANT ROOFSCALE: 12" = 1'-0"M4.2
5 GAS SERVICE ENTRANCE DETAILSCALE: 12" = 1'-0"M4.2
6 TWO WAY GRADE CLEANOUT DETAIL
SCALE: 12" = 1'-0"M4.2
7 SUMP PUMP DETAIL
SCALE: 12" = 1'-0"M4.2
10 ADA ACCESSIBLE LAVATORY OR COUNTER SINK DETAILSCALE: 12" = 1'-0"M4.2
9 DOMESTIC HOT WATER HEATER WITH STORAGE TANK DETAIL
SCALE: 3/8" = 1'-0"M4.2
8 MASTER GAS SHUTOFF
CC
-29/
20/1
7A
DD
EN
DU
M C
C-2
CC-2
CC-2
CC-2
PUMPS
PUMP MIN MOTOR DATA MECH
MARK SERVES LOCATION PUMP TYPE GPM HEADEFF
HP V PH HZ RPM BASIS OF DESIGNNOTES
(FT WG) (%) [WATTS]
P-F01 HEAT PUMP LOOP F246 END SUCTION 225 85 73 7.5 460 3 60 1760 TACO SFI2510C 1
P-F02 HEAT PUMP LOOP F246 END SUCTION 225 85 73 7.5 460 3 60 1760 TACO SFI2510C 1
P-F03 140 Deg. RETURN F103 LEAD FREE IN-LINE 2 9 - 1/40 115 1 60 3250 TACO 006B
P-F04 140 Deg. RECIR. F103 LEAD FREE IN-LINE 4 8 - 1/40 115 1 60 3250 TACO 006B
1. PUMP SHALL HAVE INTEGRATED PUMP AND VFD WITH WITH SELF-SENSING PRO-BALANCE TECHNOLOGY.
FAN SCHEDULE
FAN DATA ELECTRICAL DATAUNIT
FAN BLADEESP
FAN DRIVEHP MAX MOTORIZED WEIGHT
MECH
MARK SERVES TYPE TYPE CFM (IN WG) RPM TYPE [WATTS] V PH HZ dBA DAMPER (LBS) BASIS OF DESIGN NOTES
EF-C1 RM 247 ROOF CENTRIFUGAL 675 0.5 1100 DIRECT 1/4 120 1 60 51 YES 56 COOK ACE-D 120C13D 1,2,3,4,6
EF-C2 RM 251 ROOF CENTRIFUGAL 675 0.5 1100 DIRECT 1/4 120 1 60 51 YES 56 COOK ACE-D 120C13D 1,2,3,4,6
EF-C3 RM 260 ROOF CENTRIFUGAL 725 0.5 1120 DIRECT 1/4 120 1 60 52 YES 56 COOK ACE-D 120C15D 1,2,3,4,6
EF-C4 RM 261 ROOF CENTRIFUGAL 885 0.5 1185 DIRECT 1/4 120 1 60 54 YES 56 COOK ACE-D 120C15D 1,2,3,4,6
EF-C5 RM 259 ROOF CENTRIFUGAL 150 0.5 1375 DIRECT 1/8 120 1 60 46 YES 46 COOK ACE-D 90C15DL 1,2,3,4,5,6
EF-C6 RM 256 ROOF CENTRIFUGAL 300 0.5 1435 DIRECT 1/8 120 1 60 53 YES 46 COOK ACE-D 90C15DH 1,2,3,4,5,6
EF-C7 RM 255 ROOF CENTRIFUGAL 300 0.5 1435 DIRECT 1/8 120 1 60 53 YES 46 COOK ACE-D 90C15DH 1,2,3,4,5,6
EF-C8 RM 252 ROOF CENTRIFUGAL 150 0.5 1375 DIRECT 1/8 120 1 60 46 YES 46 COOK ACE-D 90C15DL 1,2,3,4,5,6
EF-F1 RM F233 ROOF CENTRIFUGAL 550 0.5 1463 DIRECT 1/8 120 1 60 46 YES 47 COOK ACE-DEC 100C17DEC 1,2,3,4,6,7
EF-F2 RM F233 ROOF CENTRIFUGAL 180 0.5 1550 DIRECT 1/8 120 1 60 46 YES 48 COOK ACE-D 70C15DH 1,2,3,4,6
MECHANICAL NOTES:
1. FAN SELECTION WITH THE FOLLOWING PARAMETER: NOT ALLOWED TO OPERATE IN MOTOR SAFETY FACTOR.
2. PROVIDE WITH 115 VOLT ALUMINUM MOTORIZED BACKDRAFT DAMPER AND ACTUATOR.
3. PROVIDE WITH SOLID STATE SPEED CONTROLLER, SHIPPED LOOSE FOR FIELD WIRING BY ELECTRICAL CONTRACTOR.
4. PROVIDE DISCONNECT SWITCH IN NEMA-1 ENCLOSURE FACTORY MOUNTED AND WIRED.
5. FAN SHALL BE INTERLOCKED WITH LIGHT/WALL SWITCH. LIGHT/WALL SWITCH AND FAN POWER WIRING BY ELECTRICAL CONTRACTOR.
6. PROVIDE 13-INCH HEIGHT INSULATED ROOF CURB WITH DOUBLE METAL SHELL LINER TO PROTECT CURB INSULATION FROM MOISTURE LADEN AIR.
7. FAN CONNECTED TO LABORATORY FUME HOOD. INTERLOCK FAN OPERATION WITH FUME HOOD SWITCH.
DIFFUSER, REGISTER & GRILLE SCHEDULE
MAX MAX OPPOSED PANEL FACE MECH
MARK STATIC PD NC BLADE FRAME SIZE SIZE FINISH MATERIAL BASIS OF DESIGN NOTES
(IN WG) (DECIBELS) DAMPER TYPE (IN) (IN)
D-1 0.10 25 --- SEE PLANS 24x24 24x24 WHITE STEEL PRICE SPD 1,2,3
D-2 0.10 25 --- SEE PLANS 24x24 24x24 WHITE STEEL PRICE PPD2 1,2,3,6,8
D-3 0.10 35 --- LAY-IN SEE PLANS SEE PLANS WHITE STEEL PRICE TDAC 1,2,5
D-4 0.10 35 --- LAY-IN SEE PLANS SEE PLANS WHITE STEEL PRICE RCD 1,2,9
R-1 0.10 25 PRICE DAL SURFACE SEE PLANS SEE PLANS WHITE STEEL PRICE 920D 1,2
R-2 0.10 25 PRICE DAL SURFACE SEE PLANS SEE PLANS WHITE ALUMINUM PRICE SDGE 1,2,7
G-1 0.08 25 --- LAY-IN SEE PLANS SEE PLANS WHITE ALUMINUM PRICE 80 1,2,3
G-2 0.08 25 --- SEE PLANS SEE PLANS SEE PLANS WHITE ALUMINUM PRICE 80FF 1,2,3,4
MECHANICAL NOTES:
1. NC VALUES ARE BASED ON A ROOM ABSORPTION OF 10 db, RE 10-12 WATTS.
2. SEE PLANS FOR NECK SIZE AND CFM.
3. COORDINATE WITH CEILINGS ON FRAME TYPE. PROVIDE A ALUMINUM SURFACE MOUNT ADAPTER FRAME FOR GYP CEILING INSTALLATION.
4. PROVIDE WITH A MERV-8 RATED FILTER WITH GRILLE.
5. UNIT SHALL INCLUDE A SELF-ACTING THERMAL EXPANSION ACTUATOR. AT SA TEMPERAURES BELOW 68 DEG F THE SUPPLY AIR IS DISCHARGED HORIZONTALLY. AT 75 DEG F THE SA
IS DISCHARGED AT A SLIGHT DOWNWARD ANGLE. ABOVE 75 DEG F THE SA IS ANGLED DOWNWARD WITH FULL VERTICAL PROJECTION AT A SA ABOVE 82 DEG F.
6. DIFFUSER TO PROVIDE VAV HEATING AND COOLING. PROVIDE WITH A WALL-MOUNTED ASSEMBLY FOR ROOM TEMPERATURE SENSING IN HEATING MODE AS WELL AS SETPOINT
ADJUSTMENT FOR HEATING AND COOLING. PROVIDE WITH OPTIONAL BACNET INTERFACE.
7. REGISTER SHALL HAVE AIR SCOOP.
8. PROVIDE A SINGLE BALANCING REMOTE TO ALLOW ADJUSTMENT TO THE VAV DIFFUSER MINIMUM AND MAXIMUM SET POINTS. REMOTE SHALL GIVEN TO OWNER UPON COMPLETION OF PROJECT.
9. ADJUST BLADES TO THROW AIR DOWNWARD AT 20 DEGREES DIFFERENTIAL.
ROOF-TOP AIR CONDITIONING, HEATING & VENTILATING UNIT - GAS FIRED SCHEDULE
MINIMUM MINIMUM COOLING CAPACITY AT ENTERING CONDITIONS SHOWN HEATING DATA ELECTRICAL DATA
MARK CFM OUTSIDE ESP TOTAL CAP SENS. CAP EAT DB/WB LAT DB AMB. AIR INPUT OUTPUT EAT DB LAT DB V PH MCA MAX FUSE BASIS OF DESIGN MECH
AIR (IN WG) (MBH) (MBH) (°F) (°F) ENT. COND. (F) (MBH) (MBH) (°F) (°F) AMPS NOTES
RTU-C1 2000 675 0.8 77.1 57.7 85/70 55 95 160 128.0 30.0 90.0 480 3 14.8 20 DAIKIN DPS006A 1 THRU 7
RTU-C2 2000 675 0.8 77.1 57.7 85/70 55 95 160 128.0 30.0 90.0 480 3 14.8 20 DAIKIN DPS006A 1 THRU 7
RTU-C3 2000 725 0.8 77.1 57.7 85/70 55 95 160 128.0 30.0 90.0 480 3 14.8 20 DAIKIN DPS006A 1 THRU 7
RTU-C4 2500 885 0.8 97.4 72.9 85/70 55 95 200 160.0 30.0 90.0 480 3 18.8 20 DAIKIN DPS007A 1 THRU 7
RTU-F1 2500 1250 0.5 60.9 44.9 85/71 55 95 120 96 56.0 93.0 480 3 32.1 40 DAIKIN DPS005A 1 THRU 8
MECHANICAL NOTES:
1. EXTERNAL STATIC PRESSURE AS SHOWN IS EXTERNAL TO THE UNIT AND IS THE STATIC PRESSURE AVAILABLE FOR DUCTWORK AND ACCESSORIES.
TOTAL STATIC PRESSURE = EXTERNAL + INTERNAL STATIC PRESSURE. DESIGN FOR MID-LIFE PRESSURE DROP FOR FILTER LOADING. THIS IS IN ADDITION TO THE
CLEAN FILTER PRESSURE DROP.
2. ALL SECTIONS (FIELD OR FACTORY FABRICATED) OF THE AIR HANDLING UNIT SHALL BE DOUBLE WALL INSULATED AS PER THE SPECIFICATIONS.
3. PROVIDE ACCESS DOORS IN ALL FILTER, ACCESS AND FAN MODULES.
4. PROVIDE DOUBLE WALL DRAIN PANS UNDER ALL COIL MODULES OR SECTIONS.
5. DAMPERS LOCATED IN THE MIXING BOX / ECONOMIZER MODULE SHALL BE PROVIDED BY THE AHU MANUFACTURER. SEE SPECIFICATIONS.
6. PROVIDE WITH MODULATING HOT-GAS REHEAT WITH A SPACE HUMIDITY SENSOR.
7. RTU CONTROLS SHALL BE A SINGLE-ZONE VARIABLE-AIR-VOLUME CONFIGURATION.
8. RTU PROVIDED WITH INTEGRAL ENERGY RECOVERY WHEEL
SUMMER OPERATION WHEEL DATA: EAT 95° Fdb, 76°Fwb; LAT 78° Fdb, 67.3°Fwb / CAPACITY - 40 MBH / EFFECTIVENESS - 0.64 TOTAL, 0.67 SENSIBLE
WINTER OPERATION WHEEL DATA: EAT -8° Fdb, -8°Fwb; LAT 42.5° Fdb, 33.8°Fwb / CAPACITY - 78 MBH / EFFECTIVENESS - 0.66 TOTAL, 0.67 SENSIBLE
WHEEL DATA: AIRSIDE PD - 0.58" H20 / FACE VELOCITY MAX - 700 FPM / PREFILTER - 2" MERV 8
AIR SEPERATOR - HYDRONIC PIPING AIR CONTROL DEVICE
PRESS. DIMENSIONS DRY
MARK LOCATION SERVES FLOW DROP (DIA. x H) WEIGHT BASIS OF DESIGN MECH
(GPM) (FT.W.G.) (IN. x IN.) (LBS.) NOTES
AS-F01 F246 HEAT PUMP LOOP 225 1 12" x 22" 80 TACO - HIGH VELOCITY 4904ADH-125
HEAT PUMP SCHEDULE
MARK
NO. ARRANGEMENT LOCATION REFRIG.
OUTSIDE
AIRFLOW
(CFM)
DOAS
SERVED
BY
TOTAL
AIRFLOW
(CFM)
MIN. ESP
(IN WG)
WATER
FLOW
(GPM)
PRESS.
DROP
(FT WAT)
COOLING DATA HEATING DATA ELECTRICAL DATAUNIT
WEIGHT
(LB)
MANUFACTURER MODEL
NUMBEREAT DB
(DEG F)
EAT WB
(DEG F)
LAT DB
(DEG F)
TOTAL
CAP
(MBTUH)
SENS
CAP
(MBTUH)
HEAT
REJ
(BTUH)EER
COOLING
EWT
(DEG F)
COOLING
LWT
(DEG F)
EAT DB
(DEG F)
EAT WB
(DEG F)
TOTAL
CAP
(MBTUH)
HEAT
ABS
(MBTUH)COP
HEATING
EWT
(DEG F)
HEATING
LWT
(DEG F)
V/PH
MIN
CIRC
AMPS
FULL
LOAD
AMPS
MOTOR
TYPE
MAX
FUSE
AMPS
HP-F01 HORIZONTAL SEE PLANS R-410A 250 DOAS-F01 380 0.5 3.00 9.95 75.0 63.0 54.7 11.3 8.5 14,411 12.5 90 99.6 75.0 63.0 11.2 8.3 3.8 40.0 34.5 208/1 6.8 5.6 ECM 15 154 DAIKIN WGSH0121
HP-F02 HORIZONTAL SEE PLANS R-410A 250 DOAS-F01 500 0.5 3.75 6.04 75.0 63.0 57.2 14.2 11 17,482 14.7 90 99.3 75.0 63.0 13.6 10.4 4.1 40.0 34.5 208/1 10.0 8.4 ECM 15 200 DAIKIN WGSH0151
HP-F03 HORIZONTAL SEE PLANS R-410A 250 DOAS-F01 380 0.5 3.00 9.95 75.0 63.0 54.0 11.3 8.5 14,411 12.5 90 99.6 75.0 63.0 11.2 8.3 3.7 40.0 34.6 208/1 6.8 5.6 ECM 15 154 DAIKIN WGSH0121
HP-F04 HORIZONTAL SEE PLANS R-410A 250 DOAS-F01 440 0.5 3.75 6.04 75.0 63.0 54.7 14.0 10.2 17,237 14.6 90 99.2 75.0 63.0 13.6 10.2 3.8 40.0 34.5 208/1 10.0 8.4 ECM 15 200 DAIKIN WGSH0151
HP-F05 HORIZONTAL SEE PLANS R-410A 250 DOAS-F01 350 0.5 3.00 9.95 75.0 63.0 54.7 11.1 8.1 14,158 12.4 90 99.4 75.0 63.0 11.1 8.2 3.8 40.0 34.5 208/1 6.8 5.6 ECM 15 154 DAIKIN WGSH0121
HP-F06 HORIZONTAL SEE PLANS R-410A 250 DOAS-F01 800 0.5 6.00 5.36 75.0 63.0 54.0 24.3 19 29,901 14.7 90 100.0 75.0 63.0 20.8 15.8 3.7 40.0 34.6 460/3 7.0 6.1 ECM 15 254 DAIKIN WGTH0261
HP-F07 HORIZONTAL SEE PLANS R-410A 300 DOAS-F01 500 0.5 2.25 3.28 75.0 63.0 54.0 9.0 6.5 11,242 12.7 90 100.0 75.0 63.0 8.6 6.4 3.7 40.0 34.6 208/1 5.6 4.6 ECM 15 151 DAIKIN WGSH0091
HP-F08 HORIZONTAL SEE PLANS R-410A 200 DOAS-F01 500 0.5 3.75 3.89 75.0 63.0 57.2 14.0 10.9 17,338 14.2 90 99.2 75.0 63.0 13.3 10 4.1 40.0 34.5 208/1 10.0 8.4 ECM 15 200 DAIKIN WGSH0151
HP-F09 HORIZONTAL SEE PLANS R-410A 250 DOAS-F01 290 0.5 2.25 6.28 75.0 63.0 54.3 9.0 6.5 11,285 13.2 90 100.0 75.0 63.0 8.8 6.6 3.9 40.0 34.0 208/1 5.6 4.6 ECM 15 151 DAIKIN WGSH0091
HP-F10 HORIZONTAL SEE PLANS R-410A 300 DOAS-F01 1225 0.5 10.5 5.04 75.0 63.0 53.8 41.1 29.5 50,787 14.5 90 99.7 75.0 63.0 3.6 27.2 4 40.0 34.7 460/3 13.3 11.7 ECM 15 365 DAIKIN WGTH0441
HP-F11 HORIZONTAL SEE PLANS R-410A 100 DOAS-F01 900 0.5 6 5.36 75.0 63.0 54.9 24.6 20.3 30,350 14.7 90 100.1 75.0 63.0 21 16 4.1 40.0 34.8 460/3 7.0 6.1 ECM 15 254 DAIKIN WGTH0261
HP-F13 HORIZONTAL SEE PLANS R-410A 200 DOAS-F02 700 0.5 6 5.36 75.0 63.0 53.8 23.9 17.7 29,452 14.8 90 99.8 75.0 63.0 20.6 15.6 4 40.0 34.7 460/3 7.0 6.1 ECM 15 254 DAIKIN WGTH0261
HP-F14 HORIZONTAL SEE PLANS R-410A 200 DOAS-F02 700 0.5 6 5.36 75.0 63.0 53.8 23.9 17.7 29,452 14.8 90 99.8 75.0 63.0 20.6 15.6 4 40.0 34.7 460/3 7.0 6.1 ECM 15 254 DAIKIN WGTH0261
HP-F15 HORIZONTAL SEE PLANS R-410A 200 DOAS-F02 700 0.5 6 5.36 75.0 63.0 57.2 23.9 17.7 29,452 14.8 90 99.8 75.0 63.0 20.6 15.6 4.1 40.0 34.5 460/3 7.0 6.1 ECM 15 254 DAIKIN WGTH0261
HP-F16 HORIZONTAL SEE PLANS R-410A 210 DOAS-F02 700 0.5 9 9.47 75.0 63.0 53.8 35.6 25.6 43,765 14.8 90 99.7 75.0 63.0 31.9 24.2 4 40.0 34.7 460/3 11.2 9.8 ECM 15 329 DAIKIN WGTH0381
HP-F17 HORIZONTAL SEE PLANS R-410A 210 DOAS-F02 700 0.5 6 5.36 75.0 63.0 57.2 23.9 17.7 29,452 14.8 90 99.8 75.0 63.0 20.6 15.6 4.1 40.0 34.5 460/3 7.0 6.1 ECM 15 254 DAIKIN WGTH0261
HP-F18 HORIZONTAL SEE PLANS R-410A 270 DOAS-F02 800 0.5 6 5.36 75.0 63.0 53.8 24.3 19 29,901 14.7 90 100 75.0 63.0 20.8 15.8 4.1 40.0 34.8 460/3 7.0 6.1 ECM 15 254 DAIKIN WGTH0261
HP-F19 HORIZONTAL SEE PLANS R-410A 90 DOAS-F02 1125 0.5 7.5 8.03 75.0 63.0 53.8 30.2 24 37,906 13.4 90 100.1 75.0 63.0 27.2 20.6 4.1 40.0 34.8 460/3 9.5 8.4 ECM 15 256 DAIKIN WGTH0321
HP-F20 HORIZONTAL SEE PLANS R-410A 260 DOAS-F02 700 0.5 6 5.36 75.0 63.0 56.3 23.9 17.7 29,452 14.8 90 99.8 75.0 63.0 20.6 15.6 4 40.0 34.6 460/3 7.0 6.1 ECM 15 254 DAIKIN WGTH0261
HP-F21 HORIZONTAL SEE PLANS R-410A 200 DOAS-F02 2000 0.5 15 6.8 75.0 63.0 55.9 58.2 44.4 72,576 13.8 90 99.7 75.0 63.0 52.1 38.6 4.1 40.0 35.0 460/3 15.9 14.1 ECM 20 472 DAIKIN WGTH0641
HP-F22 HORIZONTAL SEE PLANS R-410A 100 DOAS-F01 1000 0.5 7.5 8.03 75.0 63.0 55.9 29.6 22 37,116 13.5 90 99.9 75.0 63.0 27 20.3 4.1 40.0 35.0 460/3 9.5 8.4 ECM 15 256 DAIKIN WGTH0321
HP-F23 HORIZONTAL SEE PLANS R-410A 120 DOAS-F01 700 0.3 6 5.36 75.0 63.0 57.2 23.9 17.7 29,452 14.8 90 99.8 75.0 63.0 20.6 15.6 4.1 40.0 34.5 460/3 7.0 6.1 ECM 15 254 DAIKIN WGTH0261
HP-F24 HORIZONTAL SEE PLANS R-410A 300 DOAS-F01 700 0.5 6 5.36 75.0 63.0 52.5 23.9 17.7 29,452 14.8 90 99.8 75.0 63.0 20.6 15.6 4 40.0 34.9 460/3 7.0 6.1 ECM 15 254 DAIKIN WGTH0261
HP-F25 HORIZONTAL SEE PLANS R-410A 150 DOAS-F02 1125 0.5 7.5 8.03 75.0 63.0 56.5 30.2 24 37,906 13.4 90 100.1 75.0 63.0 27.2 20.6 4.1 40.0 34.9 460/3 9.5 8.4 ECM 15 256 DAIKIN WGTH0321
GENERAL NOTES
1. MANUFACTURER SHALL PROVIDE ANY TOOLS OR PROGRAMMING NECESSARY FOR FIELD BALANCING OF HEAT PUMP FAN SPEEDS.
MECHANICAL NOTES:
1. PERFORMANCE MUST MEET THE MINIMUM REQUIREMENTS OF AHRI/ISO STANDARD 13256-1 FOR WATER SOURCE HEAT PUMPS. SCHEDULED EER AND COP IS BASED ON OPERATING CONDITIONS.
2. CAPACITY AND PRESSURE DROP ARE BASED ON A 60% WATER, 40% PROPYLENE GLYCOL SOLUTION. ESP AS SHOWN IS EXTERNAL TO THE UNIT WITH A CLEAN FILTER IN PLACE.
3. PROVIDE TWO COMPLETE SETS OF AIR FILTERS FOR EACH UNIT. ONE SET FOR CONSTRUCTION, ONE SET FOR CHANGE-OUT PRIOR TO AIR BALANCING. AIR FILTERS SHALL BE 2" MERV 8 PLEATED FILTERS, IN STANDARD AVAILABLE
SIZES PER THE SPECIFICATIONS.
4. CASING SHALL COME COMPLETE WITH SUPPLY AND RETURN DUCT COLLAR CONNECTIONS.
5. PROVIDE HANGER KITS FOR HORIZONTAL UNITS. KIT SHALL CONSIST OF STEEL BRACKETS, BOLTS, WASHERS, VIBRATION ISOLATORS AND ALL THREADED RODS.
HP-F12 HORIZONTAL SEE PLANS R-410A 100 DOAS-F01 900 0.5 6 5.36 75.0 63.0 54.9 24.6 20.3 30,350 14.7 90 100.1 75.0 63.0 21 16 4.1 40.0 34.8 460/3 7.0 6.1 ECM 15 254 DAIKIN WGTH0261
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
Rev
isio
ns
9/2
2/2
017 2
:54:0
7 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
ME
CH
AN
ICA
L S
CH
ED
ULE
SM
5.1
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
CC
-29/
20/1
7A
DD
EN
DU
M C
C-2
CC-2
DEDICATED OUTDOOR AIR SYSTEM - GAS FIRED SCHEDULE
MINIMUM MINIMUM COOLING CAPACITY AT ENTERING CONDITIONS SHOWN HEATING DATA ELECTRICAL DATA
MARK CFM OUTSIDE ESP TOTAL CAP SENS. CAP EAT DB/WB LAT DB AMB. AIR INPUT OUTPUT EAT DB LAT DB V PH MCA MAX FUSE BASIS OF DESIGN MECH
AIR (IN WG) (MBH) (MBH) (°F) (°F) ENT. COND. (F) (MBH) (MBH) (°F) (°F) AMPS NOTES
DOAS-F1 3500 3500 0.8 146.9 90.4 78.5/67.6 54 95 300 240.0 39.6 102.1 460 3 59.9 70 DAIKIN DPS012A 1 THRU 7
DOAS-F2 3700 3700 0.8 148.9 93.5 78.8/67.8 55 95 300 240.0 39.6 102.1 460 3 59.9 70 DAIKIN DPS012A 1 THRU 7
MECHANICAL NOTES:
1. EXTERNAL STATIC PRESSURE AS SHOWN IS EXTERNAL TO THE UNIT AND IS THE STATIC PRESSURE AVAILABLE FOR DUCTWORK AND ACCESSORIES.
TOTAL STATIC PRESSURE = EXTERNAL + INTERNAL STATIC PRESSURE. DESIGN FOR MID-LIFE PRESSURE DROP FOR FILTER LOADING. THIS IS IN ADDITION TO THE
CLEAN FILTER PRESSURE DROP.
2. ALL SECTIONS (FIELD OR FACTORY FABRICATED) OF THE AIR HANDLING UNIT SHALL BE DOUBLE WALL INSULATED AS PER THE SPECIFICATIONS.
3. PROVIDE ACCESS DOORS IN ALL FILTER, ACCESS AND FAN MODULES.
4. PROVIDE DOUBLE WALL DRAIN PANS UNDER ALL COIL MODULES OR SECTIONS.
5. DAMPERS LOCATED IN THE MIXING BOX / ECONOMIZER MODULE SHALL BE PROVIDED BY THE AHU MANUFACTURER. SEE SPECIFICATIONS.
6. PROVIDE WITH MODULATING HOT-GAS REHEAT WITH A SPACE HUMIDITY SENSOR.
7. RTU CONTROLS SHALL BE A SINGLE-ZONE VARIABLE-AIR-VOLUME CONFIGURATION.
8. RTU PROVIDED WITH INTEGRAL ENERGY RECOVERY WHEEL.
EXPANSION TANK SCHEDULE
MAX SYSTEM MAX. ALLOWABLE TANK ACCEPTANCE MECH
MARK SERVES TEMP VOLUME PRESSURE VOLUME VOLUME BASIS OF DESIGN NOTES
(ET-X) (°F) (GAL) (PSI) (GAL) (MIN) (GAL) (MIN)
ET-F01 GDWH-1 140 8 150 20 3.2 AMTROL MODEL ST-20VC 1
ET-F02 HEAT PUMP LOOP 115 6000 125 67 34 TACO CBX-254 1,2
MECHANICAL NOTES:
1. ASME CONSTRUCTION
2. SYSTEM VOLUME IS ESTIMATED
SUMP PUMP SCHEDULE
MOTOR DATA BASIN DATA
PUMP MINSIZE MECH
MARK SERVES LOCATION PUMP TYPE GPM HEAD EFF HP V PH HZ RPM MATERIAL DIA X DEPTH BASIS OF DESIGN NOTES
(SP-X) (EACH PUMP) (FT WG) (%) (IN)
SP-1 UNDERFLOOR SUBDRAINAGE F114 SIMPLEX SUBMERSIBLE 5 15 - 1/6 115 1 60 3450 FIBERGLASS 24" x 30" ZOELLER MODEL 42 SERIES 1, 2
SP-2 UNDERFLOOR SUBDRAINAGE F104 SIMPLEX SUBMERSIBLE 50 32 - 1/2 115 1 60 3450 EXISTING - ZOELLER MODEL 6292 1, 2
SP-3 UNDERFLOOR SUBDRAINAGE F109 SIMPLEX SUBMERSIBLE 50 32 - 1/2 115 1 60 3450 EXISTING - ZOELLER MODEL 6292 1, 2
MECHANICAL NOTES:
1. PROVIDE WITH AUTOMATIC FLOAT SWITCH.
2. PUMP SHALL HAVE 2-INCH DISCHARGE, AND 10 FOOT ELECTRICAL CORD WITH STANDARD GROUNDED PLUG.
TANK SCHEDULE
TANK SIZE
MARK LOCATION APPLICATION CAPACITY DIA HEIGHT MOUNTING BASIS OF DESIGN MECH
(GAL) (IN) (IN) NOTES
T-1 F103 HOT WATER 200 32 77 FLOOR AO SMITH MODEL TJV-200-M
NT F114 ACID NEUTRALIZATION 55 23.5 36 RECESSED BELOW FLOOR ENFIELD MODEL EZ0055 1
MECHANICAL NOTES:
1. 500 LBS LIMESTONE CHIPS
THERMOSTATICE MIXING VALVE SCHEDULE
PRESSURE COLD WATER HOT WATER HOT WATER RECIRC HOT WATER PUMP
MARK LOCATION SERVES APPLICATION LWT CAPACITY DROP INLET INLET INLET OUTLET MOUNTING MARK NO. BASIS OF DESIGN MECH
(ETMV-X / TMV-X) (°F) (GPM) (PSIG) (INCHES) (INCHES) (INCHES) (INCHES) NOTES
ETMV-1 F111 EEWS-1 EMERGANCY 60-100 1 - 31 30 1" 1" - 1-1/4" AT CEILING - HAWS MODEL 9201H
TMV-1 F103 BUILDING DOMESTIC HOT WATER 110 1 - 48 15 1" 1" 3/4" 1-1/4" WALL EXIST. LEONARD MEGATRON MODEL 3NB-LF 1, 2
TMV-2 F239 LAV KITCHEN 110 2.5 10 1/2" 1/2" - 1/2" UNDER LAV - LEONARD MODEL 170A-LF
MECHANICAL NOTES:
1. MOUNTING HEIGHT IS A MINIMUM OF 36-INCHES TO THE BOTTOM OF THE UNIT TO A MAXIMUM OF 60-INCHES TO THE TOP OF THE OUTLET.
2. PROVIDE PIPING METHOD #2 PER MANUFACTURERS RECOMMENDATIONS.
DOMESTIC WATER HEATER - GAS FIRED SCHEDULE
EXPANSIONELECTRICAL DATA
TANK TANK MINIMUM OPERATING MECH
MARK LOCATION CAPACITY MARK RECOVERY EWT LWT INPUT HP V PH HZ WT BASIS OF DESIGN NOTES
(DWH-X) (GAL) (ET-XX) (GAL/HR) (°F) (°F) (MBH) [WATTS] (LBS)
GDWH-1 F103 100 ET-1 235 40 140 199 5.0 AMPS 120 1 60 1388 AO SMITH MODEL BTH-199 (A 1
MECHANICAL NOTES:
1. WATER HEATER SHALL INCLUDE ASME RATED TEMPERATURE AND PRESSURE RELIEF VALVE AND DRAIN VALVE.
UNIT HEATER - ELECTRIC
ELECTRIC COIL DATA ELECTRICAL DATA
MOUNTING MECH
MARK LOCATION CFM KW MBH V PH Hz AMPS HEIGHT BASIS OF DESIGN NOTES
(UH-X) (FT)
UH-1 A201 350 3 10.2 208 1 60 14.5 8'-0" AFF QMARK MUH03-81 1,2,3
MECHANICAL NOTES:
1. PROVIDE LOUVER FIN DIFFUSER FOR THROW ADJUSTMENT.
2. PROVIDE INTEGRAL DISCONNECT SWITCH AND 24 VOLT LOW VOLTAGE CONTROL. WALL THERMOSTAT BY CONTROLS CONTRACTOR.
3. PROVIDE HEATER BRACKET.
SPLIT SYSTEM CONDENSING UNIT
TOTAL COMPRESSOR DATA CONDENSER DATA ELECTRICAL DATA
MARK CAPACITY NO STEPS REFRIG FAN FAN NO AMB TEMP V PH MCA MOCP BASIS OF DESIGN MECH
(MBH) (EACH) TYPE NO FLA CIRC (°F) NOTES
CU-C1 14.0 1 INFINITE R-401A 1 0.50 1 105 208 1 12.0 15.0 MITZSUBISHI MUY-GE15NA 1 THRU 5
CU-C2 17.2 1 INFINITE R-401A 1 0.93 1 105 208 1 14.0 15.0 MITZSUBISHI MUY-GE18NA 1 THRU 5
CU-F1 17.2 1 INFINITE R-401A 1 0.93 1 105 208 1 14.0 15.0 MITZSUBISHI MUY-GE18NA 1 THRU 5
MECHANICAL NOTES:
1. COOLING ONLY APPLICATION. TOTAL CAPACITY BASED ON INDOOR UNIT FAN SPEED ON HIGH.
2. REFRIGERANT PIPE QUANTITIES AND SIZE TO BE PER MANUFACTURER'S PIPING RECOMMENDATIONS AND SPECIFICATION SECTION 238126.
3. PROVIDE WITH THE FOLLOWING:
A. LOW AMBIENT KIT FOR OPERATION DOWN TO -10 DEG. F.
B. WINTER START CONTROL RELAY TO BYPASS LOW PRESSURE SWITCH TO PERMIT START-UP FOR COOLING OPERATION UNDER LOW LOAD CONDITIONS
AT LOW AMBIENT TEMPERATURES.
C. CRANKCASE HEATER THAT CLAMPS ONTO THE COMPRESSOR OIL SUMP.
D. WIND BAFFLE TO IMPROVE UNIT OPERATION DURING HIGH WINDS AND FOR LOW AMBIENT CONDITIONS.
4. UNIT TO BE MOUNTED ON EQUIPMENT RAILS. SEE 230529 FOR DESCRIPTION. MOUNTING EQUIPMENT ON 4 x 4 LUMBER DIRECTLY ON ROOF IS NOT ACCEPTABLE.
5. INDOOR UNIT IS POWERED FROM OUTDOOR UNIT. MCA TOTAL IS COMBINED FOR OUTDOOR UNIT AND INDOOR UNIT.
SPLIT SYSTEM INDOOR UNIT
COOLING DATA FAN DATA ELECTRICAL DATA
CONDENSING TOT EAT CONDENSATE
MARK UNIT LOCATION CAP DB / WB CFM MOTOR V PH Hz MCA MOP BASIS OF DESIGN MOUNTING HEIGHT DRAIN SIZE MECH
(MBH) (°F) (FLA) (BOTTOM OF UNIT) (INCHES) NOTES
AC-C1 CU-C1 C228 14.0 75 / 60 385 0.76 208 1 60 1 - MITZSUBISHI MSY-GE15NA 7'-0" 3/4" 1 THRU 7
AC-C2 CU-C2 C221 17.2 75 / 60 420 0.76 208 1 60 1 - MITZSUBISHI MSY-GE18NA 10'-0" 3/4" 1 THRU 7
AC-F1 CU-F1 F113 17.2 75 / 60 420 0.76 208 1 60 1 - MITZSUBISHI MSY-GE18NA 10'-0" 3/4" 1 THRU 7
MECHANICAL NOTES:
1. DUCTLESS SYSTEM, COOLING ONLY APPLICATION. MOUNT PER MANUFACTURER'S INSTRUCTIONS.
2. MOUNTING HEIGHT SHOWN IS A MINIMUM, TO FACILITATE CONDENSATE DRAINAGE. FINAL HEIGHT MAY BE HIGHER TO ACCOMMODATE CLEARANCES OR FACILITATE ATTACHMENT TO STRUCTURE.
3. EACH UNIT SHALL BE PROVIDED WITH A WIRED WALL MOUNTED CONTROLLER (MITSUBISHI PAR-31MAA).
4. 24 VOLT CONTROL VOLTAGE.
5. MINIMUM SEER RATING SHALL BE 13.0 TO MEETING ENERGY CODE. EQUIPMENT SELECTED BELOW THIS RATING WILL NOT BE ACCEPTED.
6. INDOOR UNIT IS POWERED FROM OUTDOOR UNIT. MCA SHOWN IS FOR INDOOR UNIT ONLY. SEE SPLIT SYSTEM OUTDOOR UNIT SCHEDULE FOR TOTAL CONNECTED MCA AND MOP LOAD.
7. EACH UNIT SHALL BE PROVIDED WITH A CONDENSATE PUMP AND DISCONNECT SWITCH.
PLUMBING FIXTURE CONNECTION SCHEDULE
FIXTURE CONNECTIONS
MARK FIXTURE CW HW TEMPERED WATER WASTE VENT REMARKS
CS-1 COUNTER SINK 1/2" 1/2" - 1-1/2" 1-1/2" COUNTER-TOP MOUNTED
CS-2, 3 COUNTER SINK - ADA 1/2" 1/2" - 1-1/2" 1-1/2" COUNTER-TOP MOUNTED
EWC-1 ELECTRIC WATER COOLER 1/2" - - 1-1/4" 1-1/4" 34" TO RIM
EWC-2 ELECTRIC WATER COOLER - ADA 1/2" - - 1-1/4" 1-1/4" 36" TO SPOUT
EWC-3 ELECTRIC WATER COOLER 1/2" - - 1-1/4" 1-1/4" 31" TO ADA SPOUT
EEWS-1 EMERGENCY EYEWASH/ - - 1/2" TO EYEWASH 1-1/4" TO 1-1/4" TO 34" TO TOP OF FLOW HEADS FOR EYEWASH
SHOWER, ADA COMPLIANT 1" TO SHOWER EYEWASH EYEWASH SHOWER HEAD MTD IN CEILING
IMF-1 ICE MACHINE FITTING 1/2" - - - - 42" A.F.F.
L-1 LAVATORY 1/2" 1/2" - 1-1/4" 1-1/4" 30" TO RIM
L-2 LAVATORY, ADA COMPLIANT 1/2" 1/2" - 1-1/4" 1-1/4" 34" TO RIM
L-3 LAVATORY 1/2" 1/2" - 1-1/4" 1-1/4" 28" TO RIM
L-4 LAVATORY, ADA COMPLIANT 1/2" 1/2" - 1-1/4" 1-1/4" 31" TO RIM
MS-1 MOP SINK 1/2" 1/2" - 3" SEE PLANS FLOOR MOUNTED
SH-1 SHOWER, INDIVIDUAL 1/2" 1/2" - - - 84" TO HEAD
SH-2 SHOWER, INDIVDUAL - ADA 1/2" 1/2" - - - CONTROL VALVE AREA TO BE
38" TO 48" AFF,
84" TO HEAD
UR-1 URINAL 3/4" - - 2" 1-1/2" 24" TO RIM
UR-2 URINAL, ADA COMPLIANT 3/4" - - 2" 1-1/2" 17" TO RIM
WMF-1 WASHING MACHINE FITTING 1/2" 1/2" - 2" 1-1/2" 42" TO RIM
WC-1 WATER CLOSET 1" - - 4" 2" 15" TO RIM
WC-2 WATER CLOSET - ADA 1" - - 4" 2" 17" TO TO RIM
WC-3 WATER CLOSET 1" - - 4" 2" 15" TO RIM
WC-4 WATER CLOSET - ADA 1" - - 4" 2" 16" TO TO RIM
RH-1 WALL HYDRANT 3/4" - - - - ROOF MOUNTED Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
Revis
ions
9/2
2/2
017 2
:59:5
3 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
ME
CH
AN
ICA
L S
CH
ED
ULE
SM
5.2
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
CC
-29
/20/1
7A
DD
EN
DU
M C
C-2
CC-2
GG
HH
WW
II II
XX
JJ
KK
12 14 15 16
X
Y
Z
4" SD UP
4" SD UP
3"3" SD
4"4" SD
4"4" SD
3"3" S
D
5"5" SD
4"4" SD
4"4" SD
3"3" S
D
3"3" SD
5"5" SD 6"6" SD
4"4" S
D
4"4" SD
4" SD UP
5"5" SD
2" W UPTO TD
2" W UP TO LAV
2" V UP
3" SD UP
4" W UPTO WC4" 7 WFU4" W 7 WFU
2" W
JH BOYSLOCKER ROOM
C203
MALECOACHES
OFFICE
C206
COLLABORATIONROOM
C207
TOILET/SHOWER
C208
HS BOYSLOCKER ROOM
C209
BOYSSHOWERS
C205
GIRLSSHOWERS
C214
FEMALECOACHES
OFFICE
C215
?
?
PE STORAGE
C202
PE STORAGE
C201
HS GIRLSLOCKER ROOM
C218
ELECTRICAL
C221
STORAGE
C222
TOILET/SHOWER
C217
COLLABORATIONROOM
C216JAN
C220
2" W UPTO TD
2" W UP TO LAV
2" V UP
3" SD UP3" W UPTO WC
2" W
2" V UP
2" W UPTO FD
2" W UPTO FD
2" W UPTO LAV
2" W UPTO LAV
2" 4 WFU2" W 4 WFU
2" 8 WFU2" W 8 WFU
4" 36 WFU4" W 36 WFU
4" W UP(28 WFU)
4"4" W
4"4" W
4" W UP TOFCO-EX
3"3" W
4"4" W
4"4" W
3" E
XIS
T.
3" W
EX
IST
.3"3"
W4"4"
W4"4"
W4"4"
W
3" W UP TOFCO-EX
4" W UP (36 WFU)
2" W UPTO LAV
2" W UPTO LAV
2" V UP
2" W UPTO FD
2" W UPTO FD
2" OFFSET W UPTO TD (TYP 2)TO MISS FTG.
2" 2
WF
U2"
W 2
WF
U2"
2 W
FU
2" W
2 W
FU
2"2" W
2"2" W
2" W UPTO FCO
3" W UP TOFCO-EX
4" W UP TOFCO-EX
3" 7 WFU3" W 7 WFU
2" W UPTO FCO
2" V UP (TYP 12)
TRAPPRIMER
TRAPPRIMER
3" E
XIS
T.
3" W
EX
IST
.
3" 3 WFU3" W 3 WFU
2" V UP
3" W UPTO MS-1
2" W UPTO TD(TYP 10)
4" W
2" W
PLUMBING GENERAL NOTES
1. FOR PIPE SIZES TO INDIVIDUAL FIXTURES, SEE THEPLUMBING FIXTURE CONNECTION SCHEDULE ON SHEETM5.2.
2. INVERT ELEVATIONS ARE BASED ON A FINISHED FLOORELEVATION OF 100’.
3. RUN BRANCH MAINS FULL SIZE THE ENTIRE LENGTH OF THECHASEAND BRANCH OFF TO FIXTURES WITH SIZES PER THEPLUMBING FIXTURE CONNECTION SCHEDULE.
4. VALVES SHALL BE LOCATED ABOVE ACCESSIBLE CEILINGS. IFTHIS IS NOT POSSIBLE, ACCESS PANELS SHALL BEPROVIDED. ACCESS PANELS SHALL BE TAMPER PROOFLOCKABLE ACCESS PANELS FOR ACCESS TOALL PLUMBING VALVES THAT ARE NOT LOCATED OVER ANACCESSIBLE CEILING.
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
LEGEND NOTESLEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/2
2/2
017 2
:54:2
1 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
UN
DE
RG
RO
UN
D P
LU
MB
ING
PLA
N, M
AIN
LE
VE
L -
AR
EA
CP
0.1
C
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NORTHSCALE: 1/8" = 1'-0"
UNDERGROUND PLUMBING PLAN, MAIN LEVEL - AREA C
CC
-29/
20/1
7A
DD
EN
DU
M C
C-2
CC-2
DN
A B C
D
E F G H J K
1
2
3
4 5
6
7
8
9
10
11
GYMNASIUM
F244
KITCHEN
F239
STORAGE
F240
VEST
F247
OFFICE
F234STORAGE
F245
CLASSROOM
F233
GIRLS
F243
BOYS
F242
ELECTRICAL
F238
COORIDOR
F241
VEST
F201
EARLYEDUCATION
F202
EARLYEDUCATION
F203BOYS
F204
GIRLS
F205
BOYS
F213
GIRLS
F214
PRINCIPAL
F207
NURSE
F209
WORK ROOM
F211
GUIDANCE
F208
CLASSROOM
F222
CLASSROOM
F221
SPECIAL ED
F230
JANITOR
F216
CLASSROOM
F228
TEACHERSLOUNGE
F220
WOMENS
F217
MENS
F218CLASSROOM
F229
SCIENCE
F223
CONFERENCEROOM
F225
ELEC
F224
TOILET
F210
RECEPTION
F206
LEARNINGCOMMONS
F232
CORRIDOR
F212
ALCOVE
F236
CORRIDOR
F215
COORIDOR
F227
CORRIDOR
F219
OFFICE
F231
JANITOR
F237
STORAGE
F226
OFFICE
F235
P2.2
4
P2.2
5
P2.2
3
P2.2
6
EWC-2 EWC-1
1 1/2" 1 VFU1 1/2" V 1 VFU
1/2" CW, 1-1/2" V& 2" W DN
3/4" EXIST.3/4" CW EXIST.3/4" EXIST.3/4" CW EXIST.
WCO
5"5" SD
5" EXIST.5" SD EXIST.
4" EXIST.4" SD EXIST.
DOAS-F1
DOAS-F2ON ROOF
ON ROOF
ON ROOFRTU-F1
3/4" OFFSET GAS UP
3/4"
120
MB
H O
N R
OO
F3/
4" G
as 1
20 M
BH
ON
RO
OF
3/4"
120
MB
H O
N R
OO
F3/
4" G
as 1
20 M
BH
ON
RO
OF
3/4" 120 MBH ON ROOF3/4" Gas 120 MBH ON ROOF
3/4" 300 MBH ON ROOF3/4" Gas 300 MBH ON ROOF
3/4" 300 MBH ON ROOF3/4" Gas 300 MBH ON ROOF
3/4" 420 MBH ON ROOF3/4" Gas 420 MBH ON ROOF1" 750 MBH ON ROOF1" Gas 750 MBH ON ROOF
POUNDS TO INCHESREGULATOR ON ROOF
3/4" GAS DN(30 MBH)
GAS METER ENTRANCE TOTALBUILDING LOAD OF 950 MBH +EMERGENCY GENERATOR 260MBH AT 2 LBS
1/2"1/2" 140-HWC 1 1/2"1 1/2" 140-HW
140 HW & HWC OFFSETDN AS NEEDED
ROUTE AS HIGHAS POSSIBLE
ROUTE AS HIGHAS POSSIBLE
PROVIDE NEW SINGLE FIXTURETHERMOSTATIC MIXING VALVETMV-2 UNDER EXISTING LAVATORY.SET TEMP. TO 110 DEGREES MAX.
1/2" EXIST.1/2" 140-HWC EXIST.
1 1/2" EXIST.1 1/2" 140-HW EXIST.
1" EXIST.1" CW EXIST.
EMERGENCYGAS POWERGENERATOR260 MBH
3/4" GAS DN& TO METER
3/4" RH-1ON ROOF
1/2" DRAIN FROM ROOFHYDRANT TO MOP SINK
3/4"
3 C
FU
3/4"
CW
3 C
FU
3/4" 2.5 CFU3/4" CW 2.5 CFU
1/2" DRAIN FROM ROOFHYDRANT TO MOP SINK
GM
5
M4.2
3/4" RH-1ON ROOF
4
M4.2
3/4"
330
MB
H O
N R
OO
F3/
4" G
as 3
30 M
BH
ON
RO
OF
PLUMBING GENERAL NOTES
1. FOR PIPE SIZES TO INDIVIDUAL FIXTURES, SEE THEPLUMBING FIXTURE CONNECTION SCHEDULE ON SHEETM5.2.
2. INVERT ELEVATIONS ARE BASED ON A FINISHED FLOORELEVATION OF 100’.
3. RUN BRANCH MAINS FULL SIZE THE ENTIRE LENGTH OF THECHASEAND BRANCH OFF TO FIXTURES WITH SIZES PER THEPLUMBING FIXTURE CONNECTION SCHEDULE.
4. VALVES SHALL BE LOCATED ABOVE ACCESSIBLE CEILINGS. IFTHIS IS NOT POSSIBLE, ACCESS PANELS SHALL BEPROVIDED. ACCESS PANELS SHALL BE TAMPER PROOFLOCKABLE ACCESS PANELS FOR ACCESS TOALL PLUMBING VALVES THAT ARE NOT LOCATED OVER ANACCESSIBLE CEILING.
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
LEGEND NOTESLEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/2
2/2
017 2
:54:3
0 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
PLU
MB
ING
PLA
N, M
AIN
LE
VE
L -
AR
EA
FP
1.2
F
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NORTHSCALE: 1/8" = 1'-0"
PLUMBING PLAN, MAIN LEVEL - AREA F
CC
-29/
20/1
7A
DD
EN
DU
M C
C-2
CC-2
CC-2
CC-2
WW
II
XX
12 14 15
EWC-2
EWC-1
UR-2 UR-1 UR-1WC-1 WC-2
WC-2
2" FD-1
WC-1WC-1WC-1WC-1
2" FD-1
L-2 L-1
L-2 L-1
2" TD-1 2" TD-1
2" TD-1 2" TD-1
2" TD-1
SH-2
SH-2
2" TD-1 2" TD-1
2" TD-1
2" T
D-1
2" T
D-1
2" TD-1
2" TD-1
SH-1
SH-1SH-1
SH-1
SH-1 SH-1SH-1SH-1
SH-1 SH-1
WCO
2" 7
VF
U2"
V 7
VF
U
FCOEXIST.FCO
WCO
PE STORAGE
C202
PE STORAGE
C201BOYS
SHOWERS
C205
GIRLSSHOWERS
C214
4" RD-EX
EXIST.FCO
2" 7
VF
U2"
V 7
VF
U
2 1/2" 31 VFU2 1/2" V 31 VFU
2-1/2" V UP (38 VFU)TO EXIST. 4" VTR-EX
2" V
2" V DN (TYP 12)
2" V DN
TRAP PRIMER
4" V UP (40 VFU) TOEXIST. 4" VTR
2" V &4 W
2-1/2" V& 4" W
1-1/2" W & V
2" V &4 W
4" W DN (36 WFU)
FCO
D
WATER HAMMER ARRESTER
2" CW
2" CW DN(91.5 CFU)
1/2"
3 C
FU
1/2"
CW
3 C
FU
1/2"
3 C
FU
1/2"
CW
3 C
FU
1" 6 CFU1" CW 6 CFU3/4" HW & CWDN (TYP 5)
1 1/2" 24 CFU1 1/2" CW 24 CFU
1/2" HW & CWDN (TYP 2)
1" 6 HFU1" 110-HW 6 HFU1" 6 HFU1" 110-HW 6 HFU
SET AT0.5 GPM
1/2" 0.5 GPM1/2" 110-HWC 0.5 GPM
1/2" 0.5 GPM1/2" 110-HW 0.5 GPM1/2"
1.5
GP
M1/
2" 1
10-H
WC
1.5
GP
M
2" 1
7 C
FU
2" C
W 1
7 C
FU
1" 4
.5 H
FU
1" 1
10-H
W 4
.5 H
FU
1 1/2" 36 HFU1 1/2" 110-HW 36 HFU
1 1/2" 36 HFU1 1/2" 110-HW 36 HFU
2" 112 CFU2" CW 112 CFU
1" 6 HFU1" 110-HW 6 HFU1" 6 HFU1" 110-HW 6 HFU
2 1/
2" 1
29 C
FU
2 1/
2" C
W 1
29 C
FU
1 1/
2" 4
0.5
1 1/
2" 1
10-H
W 4
0.5
2" 52.5 HFU2" 110-HW 52.5 HFU
1 1/2" 36 CFU1 1/2" CW 36 CFU
1 1/2" 12 CFU1 1/2" CW 12 CFU
1 1/2" 12 HFU1 1/2" 110-HW 12 HFU
2" 91.5 CFU2" CW 91.5 CFU
3/4" 3 HFU3/4" 110-HW 3 HFU
3/4" 3 HFU3/4" 110-HW 3 HFU
1/2" 1.5 HFU1/2" 110-HW 1.5 HFU
3/4" 4.5 HFU3/4" 110-HW 4.5 HFU
EXISTING 3/4" HWCTOILET
C213
TOILET
C204
4" SD UP TOEXIST. 4" RD-EX
1 1/
2" 2
VF
U1
1/2"
V 2
VF
U1
1/2"
2 V
FU
1 1/
2" V
2 V
FU
1/2" 0.5 GPM1/2" 110-HW 0.5 GPM
C2
10
M4.2
4" V DN
3
M4.2
(TYP)
KK
15
TOILET/SHOWER
C208
L-2
SH-2
2" TD-1
WC-2
WCO
WCO
2" 7
VF
U2"
V 7
VF
U2"
6 V
FU
2" V
6 V
FU
3"3" SD
2" V DN &4" W DN
2" V DN
3" SD DNB
WATER HAMMERARRESTER
2" W DN
3/4" HW
1/2" CW
1/2" HW
2" 14.5 CFU2" CW 14.5 CFU
3/4" 4.5 HFU3/4" 110-HWC 4.5 HFU1" CW
1/2" 2.5 CFU1/2" W 2.5 CFU
1/2" W DN FROM RH-1ON ROOF TO DRAININTO TD-1
10
M4.2
(TYP)
Y
Z
L-2 L-1
2" FD-1
WC-2WC-1WC-1
WC-1
UR-2 UR-1UR-1 WC-2
2" FD-1
L-2 L-1
1 1/
2" 2
VF
U1
1/2"
V 2
VF
U1
1/2"
2 V
FU
1 1/
2" V
2 V
FU
2" V
DN
4" W
DN
(28
WF
U)
2" V
& 4
" W
WCO
1-1/2" V
4" W
4" V DN (8 VFU) & UP(36 VFU) TO 4" VTR
C1
2" V
& 4
" W
1" 6 HFU1" 110-HW 6 HFU
1/2"
3 C
FU
1/2"
CW
3 C
FU
3/4"
3 H
FU
3/4"
110
-HW
3 H
FU
3/4" 3 HFU3/4" 110-HW 3 HFU
1/2"
3 C
FU
1/2"
CW
3 C
FU
1/2" 0.5 GPM1/2" 110-HW 0.5 GPM
2" 20 CFU2" CW 20 CFU
D
WATER HAMMER ARRESTER
1/2" 1.5 HFU1/2" 110-HW 1.5 HFU
2" 76 CFU2" CW 76 CFU
2" 70 CFU2" CW 70 CFU
1" 6 CFU1" CW 6 CFU
TRAP PRIMER
TOILET
C210
TOILET
C219
EXISTING 3" GAS
EXISTING 3" GAS
3/4" EXIST. 2.5 CFU3/4" CW EXIST. 2.5 CFU
10
M4.2
(TYP)
3
M4.2
EXIST.FCO
FCO
FCO
EXIST.FCO
4" VTR-EX
2" TD-1(TYP 12)
L-1
L-2
EWC-2
EWC-1
WCO
UR-2
UR-1
UR-1
WCOWC-2
WC-1WC-2
2" FD-1
2" FD-1
WC-1(TYP 4)
4" VTR-C2
L-2
L-12" 7 VFU
2" V 7 VFU
2" 7 VFU
2" V 7 VFU
2" 1
2 V
FU
2" V
12
VF
U
2" 1
2 V
FU
2" V
12
VF
U
4"4" W
3"3" W
4"4" W
3"3" W
2" 2 WFU
2" W 2 WFU
4"4" W
3"3" W
3"3" W
4" 3
6 V
FU
4" V
36
VF
U
1 1/2" 2 VFU
1 1/2" V 2 VFU
1 1/2" 2 VFU
1 1/2" V 2 VFU
2" 2 WFU
2" W 2 WFU
2" 2 VFU2" V 2 VFU
3"3" W
3"3" W
2 1/2" 31 VFU2 1/2" V 31 VFU
2 1/2" 38 VFU2 1/2" V 38 VFU
2"2" W
1 1/2" 2 VFU1 1/2" V 2 VFU4" 36 WFU4" W 36 WFU
1 1/2" 2 WFU1 1/2" W 2 WFU
1 1/2" 2 VFU1 1/2" V 2 VFU
2" 8 VFU2" V 8 VFU
4" 28 WFU4" W 28 WFU
4" 8 WFU4" W 8 WFU
2 1/2" 28 VFU2 1/2" V 28 VFU
2" 2 VFU2" V 2 VFU
2" 1 WFU2" W 1 WFU
2" 1 WFU2" W 1 WFU
2" 1 WFU2" W 1 WFU
2" 1 WFU2" W 1 WFU
4" 8 VFU4" V 8 VFU
2" 24 VFU2" V 24 VFU
1 1/2"1 1/2" Undefined
2" 2 VFU2" V 2 VFU
2" W (TYP 12)2" V (TYP 12)
2" 24 VFU2" V 24 VFU
4"4" Undefined
L-2
TD-1
WC-2WCO
2" 7 VFU2" V 7 VFU
2" 1 WFU2" W 1 WFU 4" 7 WFU4" W 7 WFU
2" 6 VFU2" V 6 VFU
2" 2 VFU2" V 2 VFU4" 4 WFU4" W 4 WFU
2" 4 VFU2" V 4 VFU
L-1
2" FD-1
WCO
WC-2
WC-1
UR-1
UR-2
WC-2
WC-1(TYP 3)
2" FD-1
L-2
L-2
L-1
4" 3
2 V
FU
4" V
32
VF
U
1 1/2" 2 VFU
1 1/2" V 2 VFU
1 1/2" 2 VFU
1 1/2" V 2 VFU
2" 24 VFU2" V 24 VFU
4" 8 VFU4" V 8 VFU 2" 2 WFU2" W 2 WFU
2" 1 WFU2" W 1 WFU(TYP 4)
2" 1 WFU2" W 1 WFU
2" 8 WFU2" W 8 WFU
4" 28 WFU4" W 28 WFU
4" 36 WFU4" W 36 WFU
2" 2 VFU2" V 2 VFU
2" 2 WFU2" W 2 WFU
2" 2 VFU2" V 2 VFU
4" 8 WFU4" W 8 WFU
2" 8 VFU2" V 8 VFU
2" 4 VFU2" V 4 VFU1 1/2" 2 VFU1 1/2" V 2 VFU
4" VENT DN & UP TO4" VTR-C1 (36 VFU)
PLUMBING GENERAL NOTES
1. FOR PIPE SIZES TO INDIVIDUAL FIXTURES, SEE THEPLUMBING FIXTURE CONNECTION SCHEDULE ON SHEETM5.2.
2. INVERT ELEVATIONS ARE BASED ON A FINISHED FLOORELEVATION OF 100’.
3. RUN BRANCH MAINS FULL SIZE THE ENTIRE LENGTH OF THECHASEAND BRANCH OFF TO FIXTURES WITH SIZES PER THEPLUMBING FIXTURE CONNECTION SCHEDULE.
4. VALVES SHALL BE LOCATED ABOVE ACCESSIBLE CEILINGS. IFTHIS IS NOT POSSIBLE, ACCESS PANELS SHALL BEPROVIDED. ACCESS PANELS SHALL BE TAMPER PROOFLOCKABLE ACCESS PANELS FOR ACCESS TOALL PLUMBING VALVES THAT ARE NOT LOCATED OVER ANACCESSIBLE CEILING.
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
LEGEND NOTESLEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/2
2/2
017 2
:54:4
9 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
PLU
MB
ING
LA
RG
E S
CA
LE
PLA
NS
& R
ISE
R D
IAG
RA
MS
P2.1
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
SCALE: 1/4" = 1'-0"P2.1
1 LARGE SCALE ROOMS C247, C251, C255 & C256SCALE: 1/4" = 1'-0"P2.1
2 LARGE SCALE ROOM C208SCALE: 1/4" = 1'-0"P2.1
3 LARGE SCALE ROOMS C210 & C219SIM/REV ROOM 259
NO SCALEP2.1
4
WASTE AND VENT RISER DIAGRAMS ROOMS C247, C251,C255 & C256
NO SCALEP2.1
5 WASTE AND VENT RISER DIAGRAMS ROOM C208NO SCALEP2.1
6 WASTE AND VENT RISER DIAGRAMS ROOM C210 & 219
CC
-29/
20/1
7A
DD
EN
DU
M C
C-2
CC-2
E F
7
8
EWC-2 EWC-1
CS-2
CS-1
CS-1
CS-1
FUME HOOD
EEWS-1
4" FD-2
DUEL GASTURRITS (TYP 4)
SCIENCE
F223
ELEC
F224
CORRIDOR
F215
CLASSROOM
F228
CORRIDOR
F212
STORAGE
F226
CONFERENCEROOM
F225
CLASSROOM
F222
2" V DN
5" EXIST.5" SD EXIST. 1 1/2" 1 VFU1 1/2" V 1 VFU
5" EXIST.5" SD EXIST.
1 1/2" 4 VFU1 1/2" AV 4 VFU
1 1/2" 2 VFU1 1/2" AV 2 VFU
2" 2
2 V
FU
2" A
V 2
2 V
FU
1 1/2" 2 VFU1 1/2" AV 2 VFU
2" 20 VFU2" AV 20 VFU
2 1/2" 28 VFU2 1/2" AV 28 VFU
EXIST. 4" FD-EX
2" AV DN & UPTO 4" AVTR-1F
2" W DN
1-1/2" TEMP. WATER DN FOREMERGENCY SHOWER ANDEYEWASH FROM ETMV
3/4" 12 MBH3/4" Gas 12 MBH
3/4" 12 MBH3/4" Gas 12 MBH
3/4" 6 MBH3/4" Gas 6 MBH
3/4" 6 MBH3/4" Gas 6 MBH
3/4" 6 MBH3/4" Gas 6 MBH
3/4"
6 M
BH
3/4"
Gas
6 M
BH
3/4" 6 MBH3/4" Gas 6 MBH
3/4" GAS DN TOTURRITS (TYP)
3/4" GAS UP(30 MBH)
3/4" 300 MBH ON ROOF3/4" Gas 300 MBH ON ROOF
3/4"
300
MB
H O
N R
OO
F3/
4" G
as 3
00 M
BH
ON
RO
OF
POUNDS TO INCHESREGULATOR ON ROOF
3/4" GAS FORFUME HOOD
1/2" CW DN
EMERGENCYGAS PANICPUCH BUTTON
EMERGENCYGAS UTILITY MASTERCONTROL PANEL
4" V UP TO 4" VTR-3F
1F
3F
1-1/2" V DN
2" AV UP TO4" AVTR-2F
2F
1-1/2" W DN
2" AV DN
1/2" DRAIN FROM ROOFHYDRANT TO MOP SINK
3/4" 2.5 CFU3/4" CW 2.5 CFU 3/4" CW UP TORH-1 ON ROOF
4
M4.2
8
M4.2
10
M4.2
3/4" 330 MBH ON ROOF3/4" Gas 330 MBH ON ROOF
B
2
NURSE
F209
TOILET
F210
4" VTR-EX4
CS-3
L-4
WC-4
2" FD-1
2" 7 VFU2" V 7 VFU
1 1/2" 2 VFU1 1/2" V 2 VFU
4" EXIST.4" SD EXIST.4" SD DN
4" W DN (5 WFU)
2" V DN
1/2" HW DN
1-1/4" CW DN
1" 750 MBH ON ROOF1" Gas 750 MBH ON ROOF
1 1/2"1 1/2" 140-HW
1/2"1/2" 140-HWC
1-1/2" 140 HW &1/2" 104 HWC DN.
10
M4.2
(TYP)
B C D
7
8
CS-3
IMF-1 MAKE FINAL CONNECTIONS TOICE MACHINE AND OR REFRIGERATOR
MS-1
3/4" H & CW TO HB-1 & REDUCED PRESSUREBACKFLOW PREVENTER @ 60" A.F.F. FORSOAP DISPENSOR
2" FD-1
WC-2
L-2
WC-2
L-1
WC-4
WC-4
WC-3 L-4
L-4UR-2
BOYS
F204
GIRLS
F205
BOYS
F213
GIRLS
F214
JANITOR
F216
TEACHERSLOUNGE
F220WOMENS
F217
MENS
F218
CORRIDOR
F215
CORRIDOR
F219
2" FS-1
1-1/2" V DN
2" FD-1
2" FD-1
2" FD-1
WC
O
1-1/2" V DN
1-1/2" V DN
1-1/2" V DN
1 1/2" 4 VFU1 1/2" V 4 VFU
3/4" 7.75 CFU3/4" CW 7.75 CFU
2" 23 CFU2" CW 23 CFU
1/2" 1.5 CFU1/2" CW 1.5 CFU
1-1/2" W DN
4" W DN (10 WFU)2" V DN (14 VFU)
1-1/2" V DN
2" CW
2" 2
1 V
FU
2" V
21
VF
U
4" 4
6 V
FU
4" V
46
VF
U
6"6" S
D
3/4"
EX
IST
.3/
4" 1
10-H
W E
XIS
T.
1/2"
EX
IST
.1/
2" 1
10-H
WC
EX
IST
.
3/4" EXIST.3/4" 110-HW EXIST.
2" EXIST.2" CW EXIST.
2" E
XIS
T.
2" C
W E
XIS
T.
2" EXIST.2" CW EXIST.
3/4" EXIST.3/4" 110-HW EXIST.
B
WATER HAMMERARRESTOR (TYP)
6" EXIST.6" SD EXIST.
6" EXIST.6" SD EXIST.
5"5" SD
5" EXIST.5" SD EXIST.
8" DS DN
WCOC4" W DN(16 WFU)
4" V DN 4" W &2" V 2" W &
1-1/2" V
2" CW
3/4" HW DN
2" 3
8 C
FU
2" C
W 3
8 C
FU
2" CW DN
4" V UP TOEXIST. 4" VTR-EX
1/2" HWC DN
2" V DN
(TYP)1/2" DRAIN FROM ROOFHYDRANT TO MOP SINK
3/4" 2.5 CFU3/4" CW 2.5 CFU
10
M4.2
C D
5
6
7
BOYS
F105
GIRLS
F106
CUSTODIAL
F102
CORRIDOR
107
2" FD-1
2" FD-1
WC-4L-4
UR-2
WC-4
WC-3
L-4
MS-1
EWC-3
3/4" H & CW TO HB-1 & REDUCEDPRESSURE BACKFLOW PREVENTERS@ 60 A.F.F. FOR SOAP DISPENSOR
EWC-2
1/2" HWC UP
8" SD UP
1/2" CW CAP
8"8" SD
1/2" CW
2" 6 VFU2" V 6 VFU
EXIST. 1-1/4" CW
EXIST. 1-1/4" HW
2" W DN
2" W & V DN
2" V DN
EXIST. 1-1/4" CW
EXIST. 1/2" HWC
EXIST. 1/2" HWC
8" EXIST.8" SD EXIST.4" 40.5 WFU EXIST.4" W 40.5 WFU EXIST.
2" EXIST.2" CW EXIST.
1 1/4" EXIST.1 1/4" 110-HW EXIST.2" V UP
1-1/2" V UP
2" V DN
2" V UP (20 VFU)
4" W UP (X WFU)4" W DN (X WFU)
3" EXIST.3" CW EXIST.
2" E
XIS
T.
2" C
W E
XIS
T.
2" 1
14 C
FU
2" C
W 1
14 C
FU
2" CW
2" 2 WFU2" W 2 WFU
4" 42.5 WFU4" W 42.5 WFU
2" 2 WFU2" W 2 WFU
2" CW DN & UP
4" W& 2" V
3/4" HW UP & 1/2" DN
TRAP PRIMER
TRAP PRIMER
C
WATER HAMMER ARRESTOR
(TYP)
3
M4.2(TYP)
10
M4.2
E F
7
8
SCIENCE
F111
STORAGE
F114
CORRIDOR
107
CS-3
CS-4
CS-4
CS-4
4" FD-2 ETMV-1 MOUNT TOP AT CEILING
EEWS-1
2" AV UP & 2 AW DN
1/2" HW, 1/2" CW,& 1-1/2" AW UP
1/2" HW, 1/2" CW,& 1-1/2" AW UP
1/2" HW, 1/2" CW,& 1-1/2" AW UP
1/2" HW, 1/2" CW,& 1-1/2" AW UP TOFUME HOOD
1/2" HW, 1/2" CW,& 1-1/2" AW UP.1/2" HW, 1/2" CW, 1-1/2 V & 2" AW DN
1/2" CW UP,1-1/2" W UP & DN
4" 9 WFU4" AW 9 WFU
WCO
4" AW DN(18 WFU)
CO 2" 2 WFU2" AW 2 WFU 2" 5 WFU2" AW 5 WFU
4" 1
1 W
FU
4" A
W 1
1 W
FU
1 1/2" 2 VFU1 1/2" AV 2 VFU
2" F
D-2
4" AW UPTO FD
2" AW UP
2" AV DN & UPCLASSROOM
F117
CLASSROOM
F110
4" 13 WFU4" AW 13 WFU
2" 104 CFU2" CW 104 CFU2" 71.5 HFU2" 110-HW 71.5 HFU
3/4" 3 CFU3/4" CW 3 CFU
3/4" 3 HFU3/4" 110-HW 3 HFU
3/4" 3 HFU3/4" 110-HW 3 HFU
3/4" 3 CFU3/4" CW 3 CFU
2" 9
3 C
FU
2" C
W 9
3 C
FU
2" 6
1 H
FU
2" 1
10-H
W 6
1 H
FU
3/4"
3 C
FU
3/4"
CW
3 C
FU
3/4"
3 H
FU
3/4"
110
-HW
3 H
FU
1 1/2" 58 HFU1 1/2" 110-HW 58 HFU
2" 90 CFU2" CW 90 CFU
3/4" 3.5 CFU3/4" CW 3.5 CFU
CO
1-1/2" TEMP. WATERUP & DN FOR EEWS-1
2" W &1-1/2" V DN
1" FM DN TO 2"STANDPIPE 42" A.F.FWITH AIR GAP FITTING
1" FM DN TOSUMP PUMPSP-1
FCO-EX
1-1/2" V UP
1 1/2" 2 VFU1 1/2" AV 2 VFU
1 1/
2" 2
VF
U1
1/2"
AV
2 V
FU
1 1/
2" 2
VF
U1
1/2"
AV
2 V
FU
1 1/2" 2 WFU1 1/2" AW 2 WFU
1/2" HW, 1/2" CW,& 2" AW DN (TYP 4)
2" AV UP & DN
2" AV UP
2" AV DN
1-1/2" V UP
NT-1
10
M4.2
E F G
1
MS-13/4" H & CW DN TO HB-1 & REDUCEDPRESSURE BACKFLOW PREVENTER@ 60" A.F.F. FOR SOAP DISPENSOR
UR-2
WMF-1
WC-4WC-4
WC-3 WC-3
WC-3
L -4L-4
GIRLS
F243
BOYS
F242
ELECTRICAL
F238
COORIDOR
F241ALCOVE
F236
JANITOR
F237
2" 8 VFU2" V 8 VFU
2" V DN
1"1 1/2" EXIST.1 1/2" 140-HW EXIST.
1" EXIST.1" CW EXIST.
2" FD-EX 2" FD-EX
WCO
WCO
C
C
WATER HAMMERARRESTOR (TYP)
4" W DN & 4" V UP & DN
2" CW (TYP)
1/2" EXIST.1/2" 110-HW EXIST.
1 1/2" 1 VFU1 1/2" V 1 VFU
1" EXIST.1" 110-HW EXIST.
1/2" EXIST.1/2" 110-HWC EXIST.
2" EXIST.2" CW EXIST.
1/2" EXIST.1/2" 110-HW EXIST.
3/4" EXIST.3/4" CW EXIST.
2" EXIST. CW DN 2" CW
3/4" CAPS
EXIST. 4" VTR-EX
3/4" EXIST.3/4" 110-HWC EXIST.
2" EXIST.2" 110-HW EXIST.
2" EXIST.2" CW EXIST.
1 1/2" EXIST.1 1/2" 140-HW EXIST.
1" EXIST.1" CW EXIST.
1/2" EXIST.1/2" 140-HWC EXIST.
1/2"1/2" 140-HWC
1 1/2"1 1/2" 140-HW
1/2" CAP
1-1/2" CAP
10
M4.2(TYP)
1/2" DRAIN FROM ROOF HYDRANT TODRAIN INTO MOP SINK WITH 2" AIR GAP
PLUMBING GENERAL NOTES
1. FOR PIPE SIZES TO INDIVIDUAL FIXTURES, SEE THEPLUMBING FIXTURE CONNECTION SCHEDULE ON SHEETM5.2.
2. INVERT ELEVATIONS ARE BASED ON A FINISHED FLOORELEVATION OF 100’.
3. RUN BRANCH MAINS FULL SIZE THE ENTIRE LENGTH OF THECHASEAND BRANCH OFF TO FIXTURES WITH SIZES PER THEPLUMBING FIXTURE CONNECTION SCHEDULE.
4. VALVES SHALL BE LOCATED ABOVE ACCESSIBLE CEILINGS. IFTHIS IS NOT POSSIBLE, ACCESS PANELS SHALL BEPROVIDED. ACCESS PANELS SHALL BE TAMPER PROOFLOCKABLE ACCESS PANELS FOR ACCESS TOALL PLUMBING VALVES THAT ARE NOT LOCATED OVER ANACCESSIBLE CEILING.
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
KEY PLAN
LEGEND NOTESLEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET
A
NO
RT
H
Rev
isio
ns
B
C
D
E
F
9/2
2/2
017 2
:55:0
8 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
PLU
MB
ING
LA
RG
E S
CA
LE
PLA
NS
P2.2
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
SCALE: 1/4" = 1'-0"P2.2
3 LARGE SCALE ROOM F212 & F223
SCALE: 1/4" = 1'-0"P2.2
4 LARGE SCALE ROOMS F209 & F210SCALE: 1/4" = 1'-0"P2.2
5 LARGE SCALE ROOMS F213 THRU F218 & F220
SCALE: 1/4" = 1'-0"P2.2
2 LARGE SCALE ROOMS F102, F105 & F106SCALE: 1/4" = 1'-0"P2.2
1 LARGE SCALE ROOM F111 & F114
SCALE: 1/4" = 1'-0"P2.2
6 LARGE SCALE ROOMS F237, F242 & F243
CC
-29/
20/1
7A
DD
EN
DU
M C
C-2
CC-2
CC-2
CC-2
CC-2
CC-2
MS-1
EWC-3
EWC-2WC-4
WC-4
WC-3
L-4
L-4
UR-2
2" FS-1
2" FD-1
2" FD-1
2" FD-1
2" FD-1MS-1
2" FD-1
2" FD-1
4" 46 VFU
4" V 46 VFU
1 1/2" 4 VFU
1 1/2" V 4 VFU
1 1/
2" 5
VF
U1
1/2"
V 5
VF
U
3" 6 WFU
3" W 6 WFU
2" 6 VFU
2" V 6 VFU
2" 6
VF
U2"
V 6
VF
U
2" 14 VFU2" V 14 VFU1 1/2" 2 VFU1 1/2" V 2 VFU
1 1/2" 2 WFU1 1/2" W 2 WFU
2" 4 WFU2" W 4 WFU
4" 15.5 WFU EXIST.
4" W 15.5 WFU EXIST.
4" 40.5 WFU EXIST.4" W 40.5 WFU EXIST.
4" 21 WFU4" W 21 WFU
3" 5 WFU3" W 5 WFU
2" 2 WFU2" W 2 WFU
1 1/2" 2 VFU1 1/2" V 2 VFU
1 1/2" 2 VFU1 1/2" V 2 VFU
2" 2 WFU2" W 2 WFU
4" 4 WFU4" W 4 WFU
CS-3
WCO
WC-2
L-2WC-2
L-2
WC-4
WC-4
WC-3
UR-2
L-4
2" 21 VFU
2" V 21 VFU
4" 42.5 WFU4" W 42.5 WFU
2" 20 VFU2" V 20 VFU
4" 8 WFU4" V 8 WFU
4" 44.5 WFU4" W 44.5 WFU
2" 2 WFU2" W 2 WFU1 1/2" 2 VFU1 1/2" V 2 VFU
2" 2 WFU2" W 2 WFU
1 1/2" 2 WFU1 1/2" V 2 WFU
2" 8 WFU2" V 8 WFU
2" 18 WFU2" V 18 WFU
4" 8 WFU4" W 8 WFU
2" 2 WFU2" W 2 WFU
4" 16 WFU4" W 16 WFU
4" EXIST. 63 VFU4" V EXIST. 63 VFU
4" VTR-EX
4" EXIST.
4" W EXIST.
4" EXIST.
4" W EXIST.2" E
XIST.
2" W EXIST.
4" EXIST.4" W EXIST.
4" EXIST.4" W EXIST.
2" 2 WFU2" W 2 WFU
2" 8 VFU2" V 8 VFU
1 1/2" 2 VFU1 1/2" V 2 VFU
4" EXIST.4" W EXIST.
4" 8 WFU4" W 8 WFU
2" 20 VFU2" V 20 VFU
2" 8 VFU2" V 8 VFU
2" 2 VFU2" V 2 VFU
2" 2 WFU2" W 2 WFU2" EXIST.2" W EXIST.
2" 4 WFU2" V 4 WFU
L-4
CO
CS-1
EEWS-1
CS-4
EEWS-1CS-4
CS-4
CS-3
CS-1
FUME HOOD
EWC-2
EWC-1
CS-2
CO
CS-1
4" FD-2
4" FD-1
2" FD-1
4" AVTR-1F
1 1/2" 2 VFU
1 1/2" AV 2 VFU
2" 20 VFU
2" AV 20 VFU
1 1/2" 4 VFU
1 1/2" AV 4 VFU
1 1/2" 2 VFU
1 1/2" AV 2 VFU
1 1/2" 1 VFU
1 1/2" V 1 VFU
1 1/
2" 2
WF
U1
1/2"
AV
2 W
FU
2" 2 WFU
2" AW 2 WFU
2" 5 WFU
2" AW 5 WFU
2" 1
8 V
FU
2" A
V 1
8 V
FU
2" 9
VF
U2"
AV
9 V
FU
2" 2 WFU2" AW 2 WFU
2" 2 WFU
2" AW 2 WFU
4" 14 WFU
4" AW 14 W
FU
2" 2 WFU
2" AW 2 WFU
2" EXIST.2" W EXIST.
2" EXIST.
2" W EXIST.
CO-EX
2" 6 VFU2" AV 6 VFU
2" 3 WFU2" AW 3 WFU
4" 12 WFU4" AW 12 WFU
4" 6 WFU4" W 6 WFU
4" 11 WFU
4" AW 11 W
FU
4" 6 WFU4" AW 6 WFU
2" 6 VFU2" AV 6 VFU
2" 3 WFU2" AW 3 WFU4" 9 WFU4" AW 9 WFU
1 1/2" 2 WFU1 1/2" AW 2 WFU
1 1/
2" 2
VF
U1
1/2"
AV
2 V
FU
4" EXIST.4" W EXIST.
4" 36 WFU4" AW 36 WFU
2" 2 VFU2" AV 2 VFU2" 4 WFU2" AW 4 WFU
1 1/2" 2 VFU1 1/2" AV 2 VFU
1 1/2" 2 VFU1 1/2" AV 2 VFU
1 1/2" 2 WFU1 1/2" AW 2 WFU
2 1/2" 28 VFU2 1/2" AV 28 VFU
2" 24 VFU2" AV 24 VFU 1 1/2" 2 WFU1 1/2" AV 2 WFU
1 1/
2" 1
WF
U1
1/2"
W 1
WF
U
4" AVTR-2F
4" VTR-3F
FCO-EX
2" STANDPIPE
2" EXIST.2" W EXIST.
1 1/
2" 3
VF
U1
1/2"
V 3
VF
U
2" 3
6 V
FU
2" A
V 3
6 V
FU
2" 1 WFU2" W 1 WFU
WCO
4" 1
8 W
FU
4" A
W 1
8 W
FU
1 1/2" 2 VFU1 1/2" AV 2 VFU
1 1/2" 2 VFU1 1/2" AV 2 VFU2" 2 WFU2" AW 2 WFU
1 1/2" 2 VFU1 1/2" AV 2 VFU
1 1/2" 2 VFU1 1/2" AV 2 VFU
2" 10 VFU2" AV 10 VFU
NT-1
2" 4 VFU2" AV 4 VFU
2" 22 VFU
2" AV 22 VFU
2" FD-1
WC-4
L-4
CS-3
2" 7 VFU2" V 7 VFU
4" 5 WFU4" W 5 WFU
1 1/2" 2 VFU1 1/2" V 2 VFU
2" 5 VFU2" V 5 VFU
1 1/2" 2 WFU1 1/2" W 2 WFU
4" EXIST.4" W EXIST.
4" EXIST.4" W EXIST.
4" EXIST.4" W EXIST.
4" EXIST.4" W EXIST.
WCO-EX
2" EXIST.2" V EXIST.
4" EXIST.4" V EXIST.
4" VTR-EX4
2" 2 VFU2" V 2 VFU
WMF-1MS-1
EXIST. 4" VTR-EX
2" FD-EX
2" FD-EX
L-4
L-4
WCOUR-2
WC-3
WC-4
WCO
WC-3
WC-3
WC-4
2" 8 VFU
2" V 8 VFU
2" 1 WFU
2" W 1 WFU
4" 8 WFU4" V 8 WFU
4" 8 WFU4" W 8 WFU
2" 2 WFU2" W 2 WFU
1 1/2" 2 VFU1 1/2" V 2 VFU
2" 4 VFU2" V 4 VFU
2" 8 VFU2" V 8 VFU
4" EXIST.4" V EXIST.
2" EXIST.2" W EXIST.
4" 8WFU4" W 8WFU2" 8 VFU2" V 8 VFU
2" 5 VFU2" V 5 VFU
2" 3 VFU2" V 3 VFU
3" 5 WFU3" W 5 WFU
3" 3 WFU3" W 3 WFU
4" EXIST.4" W EXIST.
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
Rev
isio
ns
9/2
2/2
017 2
:55:1
9 P
M
C:\R
evit\1
0-1
3125-3
0_M
P_2016_C
entr
al_
mm
art
z.r
vt
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
WA
ST
E A
ND
VE
NT
RIS
ER
DIA
GR
AM
SP
3.1
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
NO SCALEP3.1
1
WASTE AND VENT RISER DIAGRAMS ROOMS F101,F102,F105,F106, F213, F214, F216, F217, F218 & F220
NO SCALEP3.1
2
WASTE AND VENT RISER DIAGRAMS ROOMS F111, F212 &F223
NO SCALEP3.1
3 WASTE AND VENT RISER DIAGRAMS ROOMS F209 & 210NO SCALEP3.1
4 WASTE AND VENT RISER DIAGRAMS ROOMS F237, 242 & 243
CC
-29/
20/1
7A
DD
EN
DU
M C
C-2
CC-2
CC-2
CC-2
CC-2
Arc
hite
ctu
re E
ngin
eering
P
lan
nin
g In
teriors
©
,
DL
R G
rou
p inc., a
Ne
bra
ska
co
rpo
ratio
n, A
LL
RIG
HT
S R
ES
ER
VE
D
Revi
sio
ns
9/2
1/2
017 3
:57:0
6 P
M
C:\R
evit\1
0-1
3125-3
0_E
L_2016_C
entr
al_
mw
urs
t.rv
t
10-1
3125-3
0
8/2
9/2
017
PLA
TT
EV
IEW
JR
HIG
H &
HIG
H S
CH
OO
L R
EN
OV
AT
ION
S
ELE
CT
RIC
AL L
IGH
TIN
G S
CH
ED
ULE
SE
7.1
20
17
SP
RIN
GF
IELD
PLA
TT
EV
IEW
CO
MM
UN
ITY
SC
HO
OLS
LIGHT FIXTURE SCHEDULE
TYPE MANUFACTURER MODEL LAMP VOLTAGE APPARENT LOAD DESCRIPTION
D1 GOTHAM
PORTFOLIO
PRESCOLITE
EVO LED 4000K
1000 LUMENS
277 V 12 VA 6" DOWNLIGHT, CLEAR MATTE DIFFUSE OPEN REFLECTOR, MEDIUM WIDE DISTRIBUTION, 0-10V DIMMING, 16-GAUGE
GALVANIZED STEEL CONSTRUCTION, SELF-FLANGED REFLECTOR, LIGHT ENGINE AND DRIVER ACCESSIBLE
THROUGH APERTURE.
D2V GOTHAM
PORTFOLIO
PRESCOLITE
EVO LED 4000K
1000 LUMENS
120 V 22 VA 6" DOWNLIGHT NON-CONDUCTIVE FRONT, REGRESSED LENS, WHITE FINISH, IP65 RATED, 16-GAUGE GALVANIZED
STEEL CONSTRUCTION, SELF-FLANGED REFLECTOR, LIGHT ENGINE AND DRIVER ACCESSIBLE THROUGH APERTURE.
EM LITHONIA ELM2 LED 120 V 3 VA LOW PROFILE EMERGENCY LIGHTING UNIT, SEALED MAINTENANCE-FREE NICKEL-CADMIUM BATTERY, SELF
DIAGNOSTICS, CEILING OR WALL MOUNT. WHITE FINISH, PROVIDE WITH WIREGUARD WHERE MARKED 'WG'.
EP1 SELUX SACL LED 4000K
5500 LUMENS
277 V 70 VA EXTERIOR POST-TOP LIGHT FIXTURE, TYPE III DISTRIBUTION, 12 FOOT ROUND STRAIGHT POLE, SILVER FINISH.
EW1 LITHONIA
METALUX
WSQ LED 4000K
2000 LUMENS
277 V 24 VA WALL MOUNT EXTERIOR LIGHT FIXTURE, TYPE II DISTRIBUTION, ALUMINUM CONSTRUCTION, DARK BRONZE FINISH.
EW2 LITHONIA
METALUX
WSQ LED 4000K
2000 LUMENS
277 V 24 VA WALL MOUNT EXTERIOR LIGHT FIXTURE, TYPE IV DISTRIBUTION, ALUMINUM CONSTRUCTION, DARK BRONZE FINISH.
P1 LITHONIA
METALUX
H.E. WILLIAMS
ZL2N LED 4000K
2000 LUMENS
277 V 31 VA CRS HOUSING, DIE FORMED CHANNEL CONNECTOR FOR STRAIGHT ROWS, BAKED ENAMEL WHITE FINISH, AIR CRAFT
CABLE MOUNTED, DIFFUSE LENS.
P1V LITHONIA
METALUX
H.E. WILLIAMS
ZL2N LED 4000K
2000 LUMENS
120 V 31 VA SAME AS P1, PROVIDE AT 120V.
P2 LITHONIA
METALUX
H.E. WILLIAMS
ZL2N LED 4000K
3000 LUMENS
277 V 42 VA CRS HOUSING, DIE FORMED CHANNEL CONNECTOR FOR STRAIGHT ROWS, BAKED ENAMEL WHITE FINISH, AIR CRAFT
CABLE MOUNTED, DIFFUSE LENS.
P2V LITHONIA
METALUX
H.E. WILLIAMS
ZL2N LED 4000K
3000 LUMENS
120 V 42 VA SAME AS P2, PROVIDE AT 120V.
P3-2' BARTCO BSS610 LED 4000K
8W/FT
277 V 16 VA MULTI-AXIS DIRECT LED LUMINAIRE SYSTEM, LENGTHS CONNECTED IN CONFIGURATIONS AS SHOWN ON DRAWINGS,
PROVIDE JOINING MODULES AS NEEDED, ALUMINUM HOUSING, AIR CRAFT CABLE SUSPENSION, WHITE FINISH, 0-10V
DIMMING.
P3-4' BARTCO BSS610 LED 4000K
8W/FT
277 V 32 VA MULTI-AXIS DIRECT LED LUMINAIRE SYSTEM, LENGTHS CONNECTED IN CONFIGURATIONS AS SHOWN ON DRAWINGS,
PROVIDE JOINING MODULES AS NEEDED, ALUMINUM HOUSING, AIR CRAFT CABLE SUSPENSION, WHITE FINISH, 0-10V
DIMMING.
P3-6' BARTCO BSS610 LED 4000K
8W/FT
277 V 48 VA MULTI-AXIS DIRECT LED LUMINAIRE SYSTEM, LENGTHS CONNECTED IN CONFIGURATIONS AS SHOWN ON DRAWINGS,
PROVIDE JOINING MODULES AS NEEDED, ALUMINUM HOUSING, AIR CRAFT CABLE SUSPENSION, WHITE FINISH, 0-10V
DIMMING.
P3-8' BARTCO BSS610 LED 4000K
8W/FT
277 V 64 VA MULTI-AXIS DIRECT LED LUMINAIRE SYSTEM, LENGTHS CONNECTED IN CONFIGURATIONS AS SHOWN ON DRAWINGS,
PROVIDE JOINING MODULES AS NEEDED, ALUMINUM HOUSING, AIR CRAFT CABLE SUSPENSION, WHITE FINISH, 0-10V
DIMMING.
P3-10' BARTCO BSS610 LED 4000K
8W/FT
277 V 80 VA MULTI-AXIS DIRECT LED LUMINAIRE SYSTEM, LENGTHS CONNECTED IN CONFIGURATIONS AS SHOWN ON DRAWINGS,
PROVIDE JOINING MODULES AS NEEDED, ALUMINUM HOUSING, AIR CRAFT CABLE SUSPENSION, WHITE FINISH, 0-10V
DIMMING.
P4 TECH LIGHTING 700 BSTP BRISTOL LED 3000K
700 LUMENS
120 V 9 VA BULB SHAPED GLASS PENDANT, CLEAR SMALL SHADE, BLACK FINISH, 0-10V DIMMING.
R1V LITHONIA
METALUX
GTL LED 4000K
3300 LUMENS
120 V 35 VA RECESSED GRID 1X4 TROFFER WITH PRISMATIC #12 PATTERN ACRYLIC 0.125" THICK LENS, STEEL HOUSING, WHITE
FINISH, 0-10V DIMMING TO 1%.
R2 LITHONIA
FS SERIES
2FSL2 LED 4000K
4000 LUMENS
277 V 42 VA RECESSED GRID 2X2 TROFFER WITH PRISMATIC #12 PATTERN ACRYLIC 0.125" THICK LENS, STEEL HOUSING, WHITE
FINISH, 0-10V DIMMING TO 1%.
R3 LITHONIA
METALUX
2GTL LED 4000K
3300 LUMENS
277 V 36 VA RECESSED GRID 2X2 TROFFER WITH PRISMATIC #12 PATTERN ACRYLIC 0.125" THICK LENS, STEEL HOUSING, WHITE
FINISH, 0-10V DIMMING TO 1%.
R3V LITHONIA
METALUX
2GTL LED 4000K
3300 LUMENS
120 V 36 VA SAME AS R3, PROVIDE AT 120V.
R4 LITHONIA
METALUX
2GTL LED 4000K
4000 LUMENS
277 V 39 VA RECESSED GRID 2X4 TROFFER WITH PRISMATIC #12 PATTERN ACRYLIC 0.125" THICK LENS, STEEL HOUSING, WHITE
FINISH, 0-10V DIMMING TO 1%.
R4V LITHONIA
METALUX
2GTL LED 4000K
4000 LUMENS
120 V 39 VA SAME AS R4, PROVIDE AT 120V.
R5 LITHONIA
METALUX
2GTL LED 4000K
4800 LUMENS
277 V 47 VA RECESSED GRID 2X4 TROFFER WITH PRISMATIC #12 PATTERN ACRYLIC 0.125" THICK LENS, STEEL HOUSING, WHITE
FINISH, 0-10V DIMMING TO 1%.
R6 FAIL-SAFE CLM LED 4000K
4000 LUMENS
277 V 53 VA RECESSED GRID, CLEAN ROOM, 2X4 TROFFER WITH PRISMATIC #12 PATTERN ACRYLIC 0.125" THICK LENS, INSET
STEEL GASKETED DOOR, SEALED STEEL HOUSING, WHITE FINISH.
T1 BRUCK TRACK CHROMA MAG II
ECO
LED 4000K
1000 LUMENS
120 V 600 VA AIMABLE LED 40 DEGREE SPOT FIXTURE, ALUMINUM HOUSING, CRI > 80, INTEGRAL DRIVER, ECO SINGLE CIRCUIT
TRACK, LENGTH AS INDICATED ON DRAWINGS, TRACK HEAD QUANTITIES AS SHOWN, PROVIDE ALL ACCESSORIES
FOR A COMPLETE INSTALLATION, WHITE FINISH.
X1 LITHONIA
DUAL-LITE
SURE-LITES
LQC LED 277 V 3 VA UNIVERSAL MOUNT EXIT SIGN, NICKEL-CADMIUM BATTERY BACK-UP, DIE CAST ALUMINUM CONSTRUCTION, SINGLE
FACE, RED LETTERS, ALL WHITE FINISH.
X1V LITHONIA
DUAL-LITE
SURE-LITES
LQC LED 120 V 3 VA SAME AS X1, PROVIDE AT 120V.
X2 LITHONIA
DUAL-LITE
SURE-LITES
LQC LED 277 V 3 VA UNIVERSAL MOUNT EXIT SIGN, NICKEL-CADMIUM BATTERY BACK-UP, DIE CAST ALUMINUM CONSTRUCTION, DOUBLE
FACE, RED LETTERS, ALL WHITE FINISH.
4. ZONE CONTROL VIA INDOOR PHOTOCELL, MAINTAIN 30 FOOTCANDLES.
3. SWITCH ON/OFF, SWEEP OFF AT PRESET TIME.
2. DAWN TO DUSK VIA OUTDOOR PHOTOCELL CONTROL
1. 0-10V DIMMING RELAY
LIGHTING CONTROL PANEL SCHEDULE NOTES:
Z15 L1-32 LOBBY F212 PENDANTS 120 1
Z14 LS-11 SITE LIGHTING EAST 277 2
Z13 LS-9 SITE LIGHTING WEST 277 2
Z12 LS-7 FAÇADE LIGHTING NORTH 277 2
Z11 LS-5 FAÇADE LIGHTING SOUTH 277 2
Z10 H1-3 MEDIA CENTER NE. 277 1,3,4
Z9 H1-3 MEDIA CENTER SE. 277 1,3,4
Z8 H1-3 MEDIA CENTER W. 277 1,3
Z7 H1-9 RAMP/STAIRS S. 277 1,3,4
Z6 H1-9 RAMP/STAIRS N. 277 1,3,4
Z5 H1-9 CORRIDOR MAIN LEVEL F215, F227 277 1,3
Z4 H1-9 LOBBY F212 277 1,3,4
Z3 H1-5 RECEPTION F206, F211 277 1,3
Z2 H1-9 LEARNING COMMONS F232 277 1,3
Z1 H1-3 CORRIDOR LOWER LEVEL F101, F107, F116 277 1,3
ZONE PANEL CKT LOAD DESCRIPTION VOLTAGE NOTES
LIGHTING CONTROL SCHEDULE
3. COORDINATE 8 LIGHTING PRESET BUTTONS WITH OWNER.
2. PROVIDE TOUCH SCREEN CONTROL, NLIGHT NPOD GFX OR APPROVED EQUAL.
1. FOR ZONES CONTROLLED BY PHOTOCELL, SWITCH CANNOT INCREASE LIGHT LEVEL BEYOND PHOTOCELL PRESET, SWITCH CAN DECREASE LIGHT LEVEL BELOW PRESET.
LIGHTING CONTROL SWITCH SCHEDULE NOTES:
C. SCHEDULE TRAINING THROUGH ARCHITECT/ENGINEER. DLR GROUP ENGINEER TO BE PRESENT AT OWNER TRAINING.
B. SCHEDULE ONSITE VISIT WITHIN 3 MONTHS OF SUBSTANTIAL COMPLETION TO ASSIST OWNER IN ADJUSTING SENSORS AND MODIFYING PROGRAMING.
A. SEE SPECIFICATION FOR ADDITIONAL REQUIREMENTS.
GENERAL NOTES:
15 Z13,Z14 EXTERIOR OVERRIDE ON/OFF
14 Z11,Z12 FAÇADE OVERRIDE ON/OFF
13 Z1-Z10 ALL ON/OFF/DIM
12 Z2 COMMONS ON/OFF/DIM
11 Z6,Z7 RAMP ON/OFF/DIM
10 Z4 LOBBY ON/OFF/DIM
9 Z8,Z9,Z10 MEDIA CENTER ON/OFF/DIM
LV3 RECEPTION F206 8 Z5 UPPER LEVEL ON/OFF/DIM 1,2,3
7 Z1 LOWER LEVEL ON/OFF/DIM
6 Z15 PENDANTS ON/OFF/DIM
5 Z3 RECEPTION ON/OFF/DIM
4 Z1-Z10, Z15 ALL OFF OFF
3 Z1-Z10, Z15 ALL 50% ON/OFF/DIM
2 Z1-Z10, Z15 ALL 70% ON/OFF/DIM
1 Z1-Z10, Z15 ALL 100% ON/OFF/DIM
4 OFF Z1-Z10 OFF ALL ZONES OFF
3 ON Z1-Z10 ON 50% ALL ZONES DIMMED TO 50% OUTPUT
LV2 JANITOR F237 2 ON Z1-Z10 ON 70% ALL ZONES DIMMED TO 70% OUTPUT 1
1 ON Z1-Z10 ON 100% ALL ZONES ON
4 LOWER Z8,Z9,Z10 ↓ DECREASE LIGHT LEVEL
3 RAISE Z8,Z9,Z10 ↑ INCREASE LIGHT LEVEL
LV1 MEDIA CENTER F121 2 OFF Z8,Z9,Z10 OFF ALL ZONES OFF 1
1 ON Z8,Z9,Z10 ON ALL ZONES ON
SWITCH ROOM BUTTONFUNCTION
TYPECONTROLS ZONES ENGRAVING DIRECTION NOTES
LIGHTING CONTROL SWITCH SCHEDULE
CC
-29
/21/1
7A
DD
EN
DU
M C
C-2
CC-2