775.834.8080 | tmwa.com | 1355 Capital Blvd. | P.O. Box 30013 | Reno, NV 89520-3013 Addendum No. 3 Donner Lake Emergency Outlet Cleanout TMWA Bid No.: 2018-002 October 11, 2017 QUESTIONS, RESPONSES AND CLARIFICATION QUESTIONS AND RESPONSES Question No. 1: Foxfire Constructors, Inc. has been in contact with Aqua-Barrier for the coffer dam to be used on the project. Their product is 18' to 20' wide and requires some friction to remain stable. They noted that the Geotechnical Report provided for the project, mentioned lose unstable soil and this will not support a water filled bladder dam. They had also mentioned that the Aqua-Barrier is not a good fit for this project. Aqua-Barrier was the coffer dam called out on Drawing C-1 for the cofferdam. Does the Owner have another option for the coffer dam to use on the project? Response to Question No. 1: A 6-foot tall backer cofferdam shall be included on the dry side of the 8-foot cofferdam for the entire length of the 8-foot cofferdam. Reference Drawing C7 with revised detail D/C7 as provided in Attachment A of this addendum. Any references in the Bid Documents to the cofferdam or 8-foot cofferdam shall be interpreted as a cofferdam system with the 8-foot primary cofferdam and a 6-foot backer cofferdam. An acceptable alternative to an Aqua-Barrier cofferdam is an AquaDam baffled cofferdam. Aqua Dam contact information: Aqua Dam, Inc. 121 Main St. / P.O. Box 144 Scotia, California USA 95565 Toll Free: (800) 682-9283 Phone: (707) 764-5099 Fax: (707) 764-2229

Upload: phamkhanh

Post on 22-Apr-2018

216 views

Category:

Documents


2 download

TRANSCRIPT

775.834.8080 | tmwa.com | 1355 Capital Blvd. | P.O. Box 30013 | Reno, NV 89520-3013

Addendum No. 3

Donner Lake Emergency Outlet Cleanout TMWA Bid No.: 2018-002

October 11, 2017 QUESTIONS, RESPONSES AND CLARIFICATION

QUESTIONS AND RESPONSES

Question No. 1: Foxfire Constructors, Inc. has been in contact with Aqua-Barrier for the coffer

dam to be used on the project. Their product is 18' to 20' wide and requires some friction to

remain stable. They noted that the Geotechnical Report provided for the project, mentioned lose

unstable soil and this will not support a water filled bladder dam. They had also mentioned that

the Aqua-Barrier is not a good fit for this project. Aqua-Barrier was the coffer dam called out on

Drawing C-1 for the cofferdam. Does the Owner have another option for the coffer dam to use

on the project?

Response to Question No. 1: A 6-foot tall backer cofferdam shall be included on the dry

side of the 8-foot cofferdam for the entire length of the 8-foot cofferdam. Reference

Drawing C7 with revised detail D/C7 as provided in Attachment A of this addendum. Any

references in the Bid Documents to the cofferdam or 8-foot cofferdam shall be interpreted as

a cofferdam system with the 8-foot primary cofferdam and a 6-foot backer cofferdam. An

acceptable alternative to an Aqua-Barrier cofferdam is an AquaDam baffled cofferdam.

Aqua Dam contact information:

Aqua Dam, Inc.

121 Main St. / P.O. Box 144

Scotia, California USA 95565

Toll Free: (800) 682-9283

Phone: (707) 764-5099 Fax: (707) 764-2229

775.834.8080 | tmwa.com | 1355 Capital Blvd. | P.O. Box 30013 | Reno, NV 89520-3013

ATTACHMENT A

Revised Drawing C7

“ ”

(Per Homeland Security Act)

PROPERTY OFTRUCKEE MEADOWS WATERAUTHORITY, RETURN UPONCOMPLETION OF PROJECT

NOT REPRODUCIBLE DONNER OUTLET CLEANOUTTRUCKEE, CALIFORNIA LA

SANDR

A DENISE EDWARDS

C I V I L

STATE OF CAL I FORNIA

REG I

STER

ED PROFESSIONAL ENGINEER

No. C71029

9/21/17

BID SET

C7CIVIL DETAILS AND SITE PHOTOS

SECTION

PLAN

1

2

2

2

AutoCAD SHX Text
NOTE 1. CONTRACTOR SHALL MATCH EXISTING CROWNS AND/OR CROSS CONTRACTOR SHALL MATCH EXISTING CROWNS AND/OR CROSS SLOPE OF EXISTING ROADWAY SECTIONS. 2. SCARIFY A MINIMUM OF 4" AND COMPACT SUBGRADE TO A SCARIFY A MINIMUM OF 4" AND COMPACT SUBGRADE TO A MINIMUM OF 95% RELATIVE COMPACTION. 3. COMPACT AGGREGATE BASE TO 95% RELATIVE COMPACTION.COMPACT AGGREGATE BASE TO 95% RELATIVE COMPACTION.
AutoCAD SHX Text
SUBGRADE, SEE NOTE 1
AutoCAD SHX Text
TYPE "A" BASE
AutoCAD SHX Text
NOTE 1. CONTRACTOR SHALL REMOVE AND RESTORE FLOATING BARRIER AS CONTRACTOR SHALL REMOVE AND RESTORE FLOATING BARRIER AS REQUIRED.
AutoCAD SHX Text
CONTRACTOR SHALL EXCAVATE AROUND, BUT NOT REMOVE OR MODIFY ROCK
AutoCAD SHX Text
SCREEN
AutoCAD SHX Text
16" RESTRAINED BYPASS PIPE
AutoCAD SHX Text
SANDBAGS
AutoCAD SHX Text
8' COFFERDAM
AutoCAD SHX Text
AIR PURGE FITTING
AutoCAD SHX Text
PLASTIC LINED SUMP INSTALLED IF NECESSARY TO CONTAIN LEAKAGE AT BYPASS PIPE
AutoCAD SHX Text
SANDBAGS ADD MULTIPLE LAYERS AS NEEDED TO CONTAIN WATER
AutoCAD SHX Text
SUMP PUMP, SIZE AS REQUIRED
AutoCAD SHX Text
PUMP AND PIPE SIZE AS REQUIRED
AutoCAD SHX Text
24/7 900 GPM (MIN) BYPASS PUMP AND PIPING SYSTEM SEE NOTE 1
AutoCAD SHX Text
SCREEN W/1" MAX OPENINGS
AutoCAD SHX Text
16" RESTRAINED ISOLATION VALVE; TYPE BY CONTRACTOR
AutoCAD SHX Text
PUMP 900 GPM MIN. TEMPORARY BYPASS PUMP BY CONTRACTOR
AutoCAD SHX Text
APROX FIRM SOIL ELEV: 5924 ± 1'
AutoCAD SHX Text
MUD LINE ELEV: 5925.5
AutoCAD SHX Text
TO DOWNSTREAM OF DAM
AutoCAD SHX Text
NOTE: 1. DISCHARGE DOWNSTREAM OF DAM. DISCHARGE DOWNSTREAM OF DAM. PIPING SHALL RUN WITHIN CHANNEL EMBANKMENTS AND/OR ALONG EXISTING DISTURBED PATHS. PIPING MAY BE COMBINED WITH DEWATERING PIPING. 2. CONTRACTOR TO ROUTE BYPASS CONTRACTOR TO ROUTE BYPASS PIPING AS NEEDED. 3. CONTRACTOR SHALL LOCATE CONTRACTOR SHALL LOCATE COFFERDAMS IN RELATION TO PROPOSED CHANNEL AS NEEDED TO GRADE CHANNEL PER SHEET C5C5
AutoCAD SHX Text
ELEV: 5926
AutoCAD SHX Text
ELEV: 5927 TO 5929.5
AutoCAD SHX Text
8' COFFERDAM
AutoCAD SHX Text
ELEV: 5932 ±
AutoCAD SHX Text
16" ELBOW
AutoCAD SHX Text
BLOCK SEEPAGE AT FACE OF COFFERDAM
AutoCAD SHX Text
SANDBAGS OR SECONDARY COFFERDAM BLADDER PER COFFERDAM MFR. RECOMMENDATIONS TO SEAL AROUND PIPE UNDER COFFERDAM
AutoCAD SHX Text
2" VALVE AND SADDLE TO CONNECT AIR PURGE TO CLEAN SCREEN
AutoCAD SHX Text
BASE BID
AutoCAD SHX Text
BYPASS PIPING BID ITEM
AutoCAD SHX Text
16" RESTRAINED BYPASS PIPE
AutoCAD SHX Text
TEMPORARY ABOVE-GROUND BYPASS PIPING; SIZE, TYPE, AND CONFIGURATION BY CONTRACTOR
AutoCAD SHX Text
TEMPORARY ABOVE-GROUND BYPASS PIPING; SIZE, TYPE, AND CONFIGURATION BY CONTRACTOR
AutoCAD SHX Text
6' BACKER COFFERDAM ENTIRE LENGTH
AutoCAD SHX Text
6' BACKER COFFERDAM ENTIRE LENGTH
AutoCAD SHX Text
NOTES 1. ACCESS RAMPS SHALL CONSIST OF FURNISHING, INSTALLING AND ACCESS RAMPS SHALL CONSIST OF FURNISHING, INSTALLING AND REMOVING MATERIALS TO CONSTRUCT TEMPORARY ACCESS AS SHOWN ON THE PLANS. MATERIALS THAT ARE REQUIRED INCLUDE GEOTEXTILE FABRIC AND EARTH FILL. 2. FILL SHALL BE CLEAN AND FREE FROM ORGANIC MATTER AND FILL SHALL BE CLEAN AND FREE FROM ORGANIC MATTER AND OTHER DELETERIOUS SUBSTANCES. 3. A GEOTEXTILE FABRIC SHALL BE PLACED AS A SOIL SEPARATING A GEOTEXTILE FABRIC SHALL BE PLACED AS A SOIL SEPARATING BARRIER BETWEEN THE EXISTING GROUND SURFACE AND ALL SOIL MATERIAL PLACED TO CONSTRUCT THE TEMPORARY ACCESS RAMP. 4. AFTER THESE RAMPS ARE NO LONGER NEEDED, ALL SOIL.MATERIAL AFTER THESE RAMPS ARE NO LONGER NEEDED, ALL SOIL.MATERIAL AND FABRIC SHALL BE REMOVED IN A MANNER THAT PREVENTS SOIL SPILLAGE ONTO THE EXISTING GROUND SURFACE.
AutoCAD SHX Text
GEOTEXTILE FABRIC
AutoCAD SHX Text
NOTES 1. WITHIN THE PARK BOUNDARY, TEMPORARY ACCESS PROTECTION WITHIN THE PARK BOUNDARY, TEMPORARY ACCESS PROTECTION SHALL BE INSTALLED AT ALL UNPAVED VEHICLE ACCESS ROUTES AND PIPE ACCESS ROUTES THAT ARE OUTSIDE OF THE DESIGNATED LIMITS OF DISTURBANCE AS SHOWN ON THE PLANS, UNLESS OTHERWISE SPECIFICALLY EXCLUDED. 2. THE UNPAVED “FIRE ACCESS” ROAD TO THE BOULDER STAGING THE UNPAVED “FIRE ACCESS” ROAD TO THE BOULDER STAGING FIRE ACCESS” ROAD TO THE BOULDER STAGING ROAD TO THE BOULDER STAGING AREA DOES NOT REQUIRE PROTECTION PER THIS DETAIL. 3. WIDTH OF PROTECTION MAT SHALL BE AS REQUIRED TO PREVENT WIDTH OF PROTECTION MAT SHALL BE AS REQUIRED TO PREVENT VEHICLES FROM TRAVELING ON UNPAVED SURFACES OUTSIDE OF LIMITS OF DISTURBANCE. 4. PROTECTION SHALL BE PROVIDED UNDER ALL PIPING INSTALLED PROTECTION SHALL BE PROVIDED UNDER ALL PIPING INSTALLED ON UNPAVED SURFACES OUTSIDE OF THE LIMITS OF DISTURBANCE. 5. TEMPORARY PROTECTION MATS SHALL BE DURADECK, GEOTERRA, TEMPORARY PROTECTION MATS SHALL BE DURADECK, GEOTERRA, SOLIDGROUND TRACTION MATS, OR EQUAL. 6. PROTECTION SYSTEM SHALL BE INSTALLED AND REMOVED WITHOUT PROTECTION SYSTEM SHALL BE INSTALLED AND REMOVED WITHOUT DISTURBING THE EXISTING GROUND. 7. A GEOTEXTILE FABRIC SHALL BE PLACED AS A SOIL SEPARATING A GEOTEXTILE FABRIC SHALL BE PLACED AS A SOIL SEPARATING BARRIER BETWEEN THE EXISTING GROUND SURFACE AND THE PROTECTION MAT.
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
TEMPORARY MAT PROTECTION
AutoCAD SHX Text
AA GEOTEXTILE FABRIC
AutoCAD SHX Text
EXISTING GROUND
AutoCAD SHX Text
RECOMMENDED
AutoCAD SHX Text
SUBMITTED
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
OF
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
BY
AutoCAD SHX Text
APP
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
WORK ORDER NO.
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
DATE
AutoCAD SHX Text
CHECKED
AutoCAD SHX Text
PH 775-834-8000 / FX 775-834-8003
AutoCAD SHX Text
RENO, NEVADA 89520-3013
AutoCAD SHX Text
1355 CAPITAL BLVD. / PO BOX 30013
AutoCAD SHX Text
TMWA - 2018-002
AutoCAD SHX Text
PATH: \\BCSACFP01\PROJECTS\51000\151083 - DONNER LAKE DREDGING PROJECT _TMWA\CADD\2-SHEETS\C-CIVIL FILE: 2018-002_C7-CIVIL DETAILS AND SITE PHOTOS.DWG \\BCSACFP01\PROJECTS\51000\151083 - DONNER LAKE DREDGING PROJECT _TMWA\CADD\2-SHEETS\C-CIVIL FILE: 2018-002_C7-CIVIL DETAILS AND SITE PHOTOS.DWG FILE: 2018-002_C7-CIVIL DETAILS AND SITE PHOTOS.DWG 2018-002_C7-CIVIL DETAILS AND SITE PHOTOS.DWG October 11, 2017 - 2:31 PM, Cadd User: Larry Bullock - 2:31 PM, Cadd User: Larry Bullock2:31 PM, Cadd User: Larry Bullock, Cadd User: Larry BullockLarry Bullock
AutoCAD SHX Text
10/17
AutoCAD SHX Text
RJ
AutoCAD SHX Text
LB
AutoCAD SHX Text
ADDENDUM 3
AutoCAD SHX Text
2
AutoCAD SHX Text
10/17
AutoCAD SHX Text
RJ
AutoCAD SHX Text
LB
AutoCAD SHX Text
ADDENDUM 2
AutoCAD SHX Text
1
AutoCAD SHX Text
L. EDWARDS
AutoCAD SHX Text
9/21/2017
AutoCAD SHX Text
B. FIASTT
AutoCAD SHX Text
L. BULLOCK
AutoCAD SHX Text
L. EDWARDS
AutoCAD SHX Text
9
AutoCAD SHX Text
9
AutoCAD SHX Text
October 11, 2017
AutoCAD SHX Text
TYPICAL AC PAVEMENT DETAIL
AutoCAD SHX Text
A
AutoCAD SHX Text
1" = 1'-0"
AutoCAD SHX Text
OPTIONAL BYPASS PUMPING SYSTEM
AutoCAD SHX Text
D
AutoCAD SHX Text
NTS
AutoCAD SHX Text
TEMPORARY ACCESS RAMP
AutoCAD SHX Text
B
AutoCAD SHX Text
NTS
AutoCAD SHX Text
TEMPORARY UNPAVED ACCESS PROTECTION DETAIL
AutoCAD SHX Text
C
AutoCAD SHX Text
NTS

775.834.8080 | tmwa.com | 1355 Capital Blvd. | P.O. Box 30013 | Reno, NV 89520-3013

END OF ADDENDUM NO. 1

QUESTION CUT-OFF DATE: NOON (PST) OCTOBER 12, 2017