acn cs controllerdocshare04.docshare.tips/files/13890/138906536.pdf ·  · 2017-02-05metso dna acn...

4
Metso DNA ACN CS controller Embedded industrial controller ACN CS is a high performance multifunc- tion controller designed for embedded and standalone applications. ACN CS is used for process controls, connectivity, fast machine controls and advanced controls like fuzzy and multivariable controls. ACN CS can be used in combination with ACN RT, ACN C20, ACN SR1 and Metso DNA VME controllers. Industrial demands Fast control cycles, as low as 20 ms No moving parts (no fan nor hard disk) IP20 enclosure protection One-to-one redundancy capability Operation, Maintenance, Reporting Star or ring topology redundant Ethernet network Remote connections Reporting, Enterprise integration Engineering and Maintenance Asset Management, Information services ACN CS Dual 100 Mbit/s Ethernet connections for commu- nication with other nodes Standard serial port links for communication with third party devices Removable CompactFlash.

Upload: phungdieu

Post on 27-May-2018

312 views

Category:

Documents


10 download

TRANSCRIPT

Page 1: ACN CS controllerdocshare04.docshare.tips/files/13890/138906536.pdf ·  · 2017-02-05Metso DNA ACN CS controller Embedded industrial controller ACN CS is a high performance multifunc-tion

Metso D

NA

ACN CS controllerEmbedded industrial controller

ACN CS is a high performance multifunc-tion controller designed for embedded and standalone applications. ACN CS is used for process controls, connectivity, fast machine controls and advanced controls like fuzzy and multivariable controls.

ACN CS can be used in combination with ACN RT, ACN C20, ACN SR1 and Metso DNA VME controllers.

Industrial demands• Fast control cycles, as low as 20 ms• No moving parts (no fan nor hard disk)• IP20 enclosure protection• One-to-one redundancy capability

Operation, Maintenance, Reporting

Star or ring topology redundant Ethernet network

Remote connections

Reporting, Enterprise integration

Engineering and Maintenance Asset Management, Information services

ACN CS

• Dual 100 Mbit/s Ethernet connections for commu-nication with other nodes

• Standard serial port links for communication with third party devices

• Removable CompactFlash.

Page 2: ACN CS controllerdocshare04.docshare.tips/files/13890/138906536.pdf ·  · 2017-02-05Metso DNA ACN CS controller Embedded industrial controller ACN CS is a high performance multifunc-tion

2 |

Mounting ACN CSACN CS is installed either vertically on a mounting plate with screws, or on a shelf mounted on a stan-dard 19” rack.

InterfacesThe interfaces available in ACN CS are:

Three Ethernet ports on the CPU board that can be used for the following purposes: • Redundant Metso DNA Ethernet network

ACN CS has two 10/100Base-T Ethernet ports used for redundant Metso DNA Ethernet network. Metso DNA Ethernet network is based on switched Ethernet technology. Ring topology is recommended, star topology is also possible.ACN CS has one Ethernet interface active at a time. In case of failure, the reserve Ethernet inter-face immediately comes online.On the Ethernet network level, the changeover to the reserve switch takes 30 ms with the recom-mended ring topology and 1...2 seconds with the star topology.

• Interface with Metso DNA I/O field busesBy default, there is one 10/100Base-T port avail-able for Metso DNA I/O field buses. The interface with ACN I/O uses an Ethernet field bus and inter-face to rack I/O uses EFC connection unit.Two PCI slots can be used for additional Metso DNA I/O field bus interfaces.

• High Speed Ethernet (HSE) Foundation Fieldbus interfaceHigh Speed Ethernet uses a standard 10/100Base-T Ethernet port to HSE Linking Device(s), which has up to four H1 buses connected per Linking Device.

Two PCI card slots:Two PCI slots can be used for additional Metso DNA I/O interfaces, Ethernet interfaces to external systems, or for field bus interfaces like PROFIBUS DP and Foundation Fieldbus. ACN CS can have different I/O and field bus interfaces combined in the same node.• PROFIBUS DP Interface

PCI card slots are used for PROFIBUS DP inter-faces. The PROFIBUS DP card is a one- or a two-channel card.

• Serial interfacesACN CS has one RS-232 port available by default. PCI slots can be used for additional serial interfaces. The serial interface card is either an 8-channel RS-232 or a two-channel isolated RS-485/RS-422. Multiple serial interface protocols are supported.

• Ethernet interfaces:Interfaces to external systems using e.g. Modbus/TCP protocol.

ACN CS nodes installed in the cabinet

Page 3: ACN CS controllerdocshare04.docshare.tips/files/13890/138906536.pdf ·  · 2017-02-05Metso DNA ACN CS controller Embedded industrial controller ACN CS is a high performance multifunc-tion

| 3

RedundancyACN CS supports redundant Metso DNA Ethernet networks, redundant controllers (one-to-one redundancy), redundant I/O field buses for ACN I/O and rack I/O, plus redundant PROFIBUS DB field buses.

EngineeringThe engineering library of the ACN CS controller provides function blocks for controls at all levels, including basic process control, advanced quality, drives, and optimization controls. Fuzzy, MPC, and Java function blocks are available as a standard.Metso DNA Engineering - Function Block CAD tool is used for designing function block diagrams for process control loops, sequences, and interface applications.Function block diagrams are saved in a common database located on the Engineering Server. At the same time, a function block diagram is a graphical document of an application, which is loaded in the runtime environment. This ensures that the docu-mentation is always up-to-date.

Capacity• The typical number of I/Os connected to ACN CS

is less than 2000. The amount depends on the control cycles.

• Control cycles from 20 ms to 64 s, typically 400 ms.

• 1-3 Metso DNA I/O field buses, 1-4 PROFIBUS DP buses, 1 FF HSE bus, max. 5 field buses in total.

Redundancy principles

Single ACN CS with single field bus

Redundant ACN CS with redundant field bus

Single ACN CS with redundant field bus

Function block diagram

Page 4: ACN CS controllerdocshare04.docshare.tips/files/13890/138906536.pdf ·  · 2017-02-05Metso DNA ACN CS controller Embedded industrial controller ACN CS is a high performance multifunc-tion

For more information, contact your local automation expert at Metso.

www.metso.com/automation

The information provided in this brochure contains descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products.

An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract. Availability and technical specifications are subject to change without notice.E8

800_

EN_0

3 0

4/20

12 ©

Met

so A

utom

atio

n In

c.

Technical specifications• compact rack or wall-mounted frame made of

bent sheet steel• fanless construction, cooling by heat pipes and a

massive heat sink• rack mounting kit (optional)

• Dimensions: 210 x 87 x 296 mm (W x H x D)• Weight: 4.5 kg• Protection: IP20

• Main board: PCI riser 2 x PCI• Memory: 1 GB DDR2 667 MHz• Processor: Intel Celeron M440 • Graphics: Integrated• 4 GB CompactFlash• Drives: N/A• Expansion: 2 x PCI

• Operating temperature: 0 °C...+50 °C• Storage temperature: -20 °C...+60 °C• Power supply: 18...36 VDC

• Operating system: Real Time Operating System

• ACN CS has LEDs indicating: power supply, CPU, system and field bus activity.

ConnectorsACN CS’s back panel connectors:• 1 x CompactFlash slot• 2 x PCI card slot• 2 x USB port• 1 x serial interface port (RS-232)• Input voltage 18 to 36 VDC• 1 x alarm input• 1 x PS/2 port for keyboard and mouse• 1 x VGA• 3 x Ethernet port (PB1, PB2, FB1)

Licenses and hardware

D201925 ACN CS node- ACN CS base unit- CompactFlash

D200825D200827

CompactFlash for network bootCompactFlash for stand-alone use

D200989 Process controller and gateway base license, per node

D200990 Process controller capacity license / 100 I/Os