AccuMax Multi-Point Injection Mechanics. Multi-Point, Electronic Direct Injection Proportioner. Basic Electronics. Internal Controls. Line Drivers. Power Terminals. Foam Pump. Line Controls. Master Flowmeter. Foam Inlet from Tank. Foam Manifold. Hydraulic Motor. Control Head. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: AccuMax Multi-Point Injection Mechanics

AccuMaxAccuMaxMulti-Point InjectionMulti-Point Injection

MechanicsMechanics

Page 2: AccuMax Multi-Point Injection Mechanics

Multi-Point, Electronic DirectMulti-Point, Electronic DirectInjection ProportionerInjection Proportioner

Page 3: AccuMax Multi-Point Injection Mechanics

Basic ElectronicsBasic Electronics

ProportioningValve

FoamPro HiFlowLine Control

Control OutputFlow Meter InputWater FlowPressure (Optional)

ProportioningValve

FoamPro HiFlowLine Control

Control OutputFlow Meter InputWater FlowPressure (Optional)

ProportioningValve

FoamPro HiFlowLine Control

Control OutputFlow Meter InputWater FlowPressure (Optional)

FoamPro HiFlowMaster Control

Tank Level (Optional)Control Output

HydrostaticDrive Control

Option Switch

Page 4: AccuMax Multi-Point Injection Mechanics

Internal ControlsInternal ControlsLine Drivers

Line Controls

Power Terminals

Master Flowmeter

Foam Pump

Hydraulic Motor

Foam Inletfrom Tank

Foam Manifold

Page 5: AccuMax Multi-Point Injection Mechanics

Control HeadControl Head

Lighted On/Off Button

Reset and up/down adjust pushbuttons

Display select button

Calibrate internal switchConfiguration internal switch

12 digit display

6 digit display

Page 6: AccuMax Multi-Point Injection Mechanics

Initial Power Up DisplayInitial Power Up Display

• Operate the apparatus engine and engage PTO to Hydraulic pump• Turn on electrical power to the FoamPro system

•After a system check the Control Displays will read as shown above

LineMaster

Page 7: AccuMax Multi-Point Injection Mechanics

Make Foam SolutionMake Foam Solution

• Establish water flow to the foam capable discharge•The Line Control Display will indicate the water flow rate

• Press the green I/O button on the Master Control Display• Press the green I/O button on the Line Control Display

•The foam pump will start to deliver foam at the rate preset by the operator•The Master Control Display will indicate the foam injection pressure and the total water flow of all foam capable lines

LineMaster

Page 8: AccuMax Multi-Point Injection Mechanics

Total Water FlowedTotal Water Flowed

• To read the total water used on a line, press the SELECT button on the Line Control Display until the display reads as above.• To read the total water used on all foam capable lines, press the SELECT button on the Master Control Display until the display reads as above.• To reset the value on either display, press both the UP and DOWN buttons at the same time.

LineMaster

Page 9: AccuMax Multi-Point Injection Mechanics

Reading % Injection RateReading % Injection Rate

• Press the SELECT button on the Line Control Display until the display reads the current rate.• To change the rate press the UP or DOWN button on the Line Control Display on the line you wish to change.• Pressing the UP or DOWN button will toggle between the preset values of Preset 1, Preset 2, Preset 3, and Custom rate.

Page 10: AccuMax Multi-Point Injection Mechanics

Changing Custom Injection RateChanging Custom Injection Rate

• Holding the UP or DOWN button will change the rate in 0.1% increments until the button is released. This new value will become the new custom rate until changed.

Page 11: AccuMax Multi-Point Injection Mechanics

Read Total Chemical UsedRead Total Chemical Used

• To read the total chemical used on whole the system, press the SELECT button on the Master Control Display until the display reads as shown.•To read the total chemical used on any specific line, press the SELECT button on the Line Control Display of the selected line until the display reads as shown.• To reset the value on either the Master Or Line Control Display, press both the UP and DOWN buttons at the same time.

LineMaster

Page 12: AccuMax Multi-Point Injection Mechanics

Read Water Flow RateRead Water Flow Rate

• To read the total water flow rate of the foam system, press the SELECT button on the Master Control Display until the display reads as shown.• To read the total water flow rate of a specific foam discharge, press the SELECT button on the appropriate Line Control Display until the display reads as shown.

LineMaster

Page 13: AccuMax Multi-Point Injection Mechanics

Read Foam Injection PressureRead Foam Injection Pressure

Or

To read total water flow rate and injection pressure, press the SELECT button until the display reads as shown on the right. The top number will show the injection pressure and the larger bottom number will show the total flow rate.

Or

Press the Select button until the display reads as shown on the left for injection pressure only.

LineMaster

Page 14: AccuMax Multi-Point Injection Mechanics

Simulated Water Flow OperationSimulated Water Flow Operation

The simulated flow function of the system allows the operator to control the line injection and foam pump manually. The water flow rate and the concentrate injection percentage rate can be set by using the display readout and the rate adjustment buttons on the Line Control Display Module.

• This function provides the manual control requirement of NFPA.• This function will allow the operator to empty or fill the foam

concentrate tank for cleaning, changing foam types, or refilling . • This function also provides a means of checking the operation of the

foam pump at all normal rates of flow and injection without running the water pump.

WARNING: When operating in the simulated mode, an outlet for the

foam concentrate must be provided.

Page 15: AccuMax Multi-Point Injection Mechanics

Initiate Simulated Flow OperationInitiate Simulated Flow Operation

•Press the SELECT button until the display reads as shown on the left.

•Press the UP/DOWN buttons simultaneously. The display will read as shown on the right.

•Start the system by pressing the I/O button on both the Master Control Display and the Line Control Display.

LineMaster

Page 16: AccuMax Multi-Point Injection Mechanics

Changing Simulated Flow RateChanging Simulated Flow Rate

Press the UP button to increase the flow rate or the DOWN button to decrease the flow rate. The rate will change in increments of 100.

Page 17: AccuMax Multi-Point Injection Mechanics

Exit Simulated Flow OperationExit Simulated Flow Operation

•Press the SELECT button until the display reads as shown on the left.

•Press the UP/DOWN buttons simultaneously and the display will read as shown on the right.

•The Line Control is now in the normal operating mode.

LineMaster

Page 18: AccuMax Multi-Point Injection Mechanics

Configuration OperationConfiguration Operation

The FoamPro AccuMax system permits easy configuration setup of the system Display Controllers for proper operation. This process needs to be done at time of installation , or when a display is replaced.

To enter the Configuration Mode, remove the left hand cover screw and o-ring with a 3/32” Allen wrench, located between the I/O and the UP button. Using the Allen wrench, depress the internal switch once.

To exit the Configuration Mode, use the Allen wrench to depress the internal button once, and the Display will return to the normal operating mode. Be sure to replace both the o-ring and the screw after exiting the mode.

The following slide will show the location of the Configuration switch.

Page 19: AccuMax Multi-Point Injection Mechanics

Control HeadControl Head

Lighted On/Off Button

Reset and up/down adjust pushbuttons

Display select button

Calibrate internal switchConfiguration internal switch

12 digit display

6 digit display

Page 20: AccuMax Multi-Point Injection Mechanics

Master ConfigurationMaster Configuration

Entering the Configuration Mode of the Master Display Module will cause the display to read as shown above.

Page 21: AccuMax Multi-Point Injection Mechanics

Master ConfigurationMaster Configuration

Pressing the SELECT button once will show the display shown above. This is the group number for the bus system and will remain at 0.

Page 22: AccuMax Multi-Point Injection Mechanics

Master ConfigurationMaster Configuration

Pressing the SELECT button once will show the display on the left.

This is the sets the AUTO-START feature that will allow the system to start operations in the ON mode when powered up.

• NO is the default setting and disables the feature.

• Yes, enables the feature and requires the pressing of the DOWN button once. The display will read as shown on the right.

Page 23: AccuMax Multi-Point Injection Mechanics

Master ConfigurationMaster Configuration

Pressing the SELECT button once will configure the temperature feature that will display the temperature of the circuit boards.• The default is set to read this temperature in °F.• Press the DOWN button once changes this to °C.

Page 24: AccuMax Multi-Point Injection Mechanics

Master ConfigurationMaster Configuration

Pressing the SELECT button once will place the configuration mode to the usage of a pressure transducer.• The default from the factory is set for unused as shown on the left.• Pressing the DOWN button once will enable this feature and will set the units to PSI, as shown in the center display.• Pressing the DOWN button once more will change the units to BAR as shown on the right display.Note: The Master Control Module requires the pressure feature to be used and PSI or BAR must be selected.

Page 25: AccuMax Multi-Point Injection Mechanics

Line ConfigurationLine Configuration

Entering the Configuration Mode of the Line Display Module will cause the display to read as shown above.

Page 26: AccuMax Multi-Point Injection Mechanics

Line ConfigurationLine Configuration

Pressing the SELECT button once will show the display as shown. This identifies the discharge number assigned by the Master upon system startup. To change the number, press the UP or Down button accordingly.

Page 27: AccuMax Multi-Point Injection Mechanics

Line ConfigurationLine Configuration

Pressing the SELECT button once will show the display shown above. This is the group number for the bus system and will remain at 0.

Page 28: AccuMax Multi-Point Injection Mechanics

Line ConfigurationLine Configuration

Pressing the SELECT button once will show the display on the left.This is the sets the AUTO-START feature that will allow the system to start operations in the ON mode when powered up.

• NO is the default setting and disables the feature.

• Yes, enables the feature and requires the pressing of the DOWN button once. The display will read as shown on the right.

Page 29: AccuMax Multi-Point Injection Mechanics

Line ConfigurationLine Configuration

Pressing the SELECT button once will configure the temperature feature that will display the temperature of the circuit boards.• The default is set to read this temperature in °F.• Press the DOWN button once changes this to °C.

Page 30: AccuMax Multi-Point Injection Mechanics

Line ConfigurationLine Configuration

Pressing the SELECT button once will place the configuration mode to the usage of a pressure transducer.• The default from the factory is set for unused as shown on the left.• Pressing the DOWN button once will enable this feature and will set the units to PSI, as shown in the center display.• Pressing the DOWN button once more will change the units to BAR as shown on the right display.Note: The Master Control Module requires the pressure feature to be used and PSI or BAR must be selected.

Page 31: AccuMax Multi-Point Injection Mechanics

Master Setup & CalibrationMaster Setup & Calibration

The Master Control Module needs to be setup and calibrated to run the system. To enter this mode, depress the right internal switch once. The display will read as shown.

Page 32: AccuMax Multi-Point Injection Mechanics

Master Foam Flowmeter CalibrationMaster Foam Flowmeter Calibration

Depress the SELECT button until the display reads as shown.

Since any one of the lines needs to be open to run the Foam Pump, pick one of the lines to calibrate with the Master at this time. Enter the Setup Calibration Mode of the chosen Line Control Display by depressing the right internal switch once. The Line Control Display will read as shown above.

Page 33: AccuMax Multi-Point Injection Mechanics

Master Setup & CalibrationMaster Setup & Calibration

Press the UP or DOWN button once and the Line Display will read as shown.

Page 34: AccuMax Multi-Point Injection Mechanics

Master Setup & CalibrationMaster Setup & Calibration

Depress the SELECT button until the Line Display reads as shown on the left.Depress the green I/O button on the Line Display and the line control valve will open and close. The display will read the position of the valve in these positions. When the display reads as shown on the right the control valve is calibrated.

Page 35: AccuMax Multi-Point Injection Mechanics

Master Setup & CalibrationMaster Setup & Calibration

• Depress the SELECT button until the Line Display reads as shown.• Open the Line Calibrate/Inject Valve to divert foam to a calibrated flowmeter or to a collection container of known volume.

Page 36: AccuMax Multi-Point Injection Mechanics

Master Setup & CalibrationMaster Setup & Calibration

• Reset the calibration flowmeter totalizer to ‘0’ or empty the foam container.

• Press the green I/O button on the Line Control Display and the control valve will open.

• Press the green I/O button on the Master Control Display to start the foam pump. The value shown on the Master Display will start to rise along with the value on the Line Display.

Master Line

Page 37: AccuMax Multi-Point Injection Mechanics

Master Setup & CalibrationMaster Setup & Calibration• Allow the system to run for a short period of time. Depressing the I/O button on the Master Control Display will shut off the foam pump. The longer the system runs or the more foam that is collected, the more accurate the calibration.

• Compare the value on the Master Control Display with the value on the calibration flowmeter or the volume collected in the container.

• Increase or decrease the value on the Master Display to match the pumped amount.

• Compare the new value on the Master Display with the Line Display and increase or decrease the value on the Line Display to match the Master Display.

• Repeat the calibration process again to ensure the values are accurate.

• Exit the setup/calibration modes on both the Master and Line Control Displays by pressing the right internal button on both displays.

Page 38: AccuMax Multi-Point Injection Mechanics

Line Setup and CalibrationLine Setup and Calibration

The Line Control Displays need to be setup to match the operating conditions the apparatus will run in. Remove the right cover screw and o-ring and depress the internal switch once. The display will read as shown.

Page 39: AccuMax Multi-Point Injection Mechanics

Line Setup and CalibrationLine Setup and Calibration

Pressing the SELECT button once will display the value that the simulated flow rate is defaulted to on that Line Control Display. To change the value press the UP or Down button until the desired flow rate is displayed.

Page 40: AccuMax Multi-Point Injection Mechanics

Line Setup and CalibrationLine Setup and Calibration

Pressing the SELECT button once again will display the default rate stored in that Line Control Display, as shown, of the #1 preset rate. To change the rate press the UP or DOWN button to increase or decrease the rate.

Pressing the SELECT button once again will display the default rate stored in that Line Control Display, as shown, of the #2 preset rate. To change the rate press the UP or DOWN button to increase or decrease the rate.

Pressing the SELECT button once again will display the default rate stored in that Line Control Display, as shown, of the #3 preset rate. To change the rate press the UP or DOWN button to increase or decrease the rate.

Page 41: AccuMax Multi-Point Injection Mechanics

Line Setup and CalibrationLine Setup and Calibration

Pressing the SELECT button again will return you to the Line setup display as shown on the left.

To start the calibration process on the Line Controller, depress the UP or DOWN button once and the display will read as shown on the right.

The Line Control Display is now ready to calibrate.

Page 42: AccuMax Multi-Point Injection Mechanics

Line Setup and CalibrationLine Setup and CalibrationWater FlowmeterWater Flowmeter

• Press the SELECT button until the Line Control Display reads as shown.

• Open the water discharge line associated with the Line Controller until a steady flow rate is attained. Take a reading of the flow rate, using a calibrated water flowmeter or a pitot gauge.

• Adjust the value shown on the Line Control Display to match the actual flow rate measured by using the UP or DOWN buttons.

• When the values are the same, shut down the discharge line and proceed to the next calibration mode, or exit the calibration mode.

Page 43: AccuMax Multi-Point Injection Mechanics

Line Setup and CalibrationLine Setup and CalibrationLine Control Valve CalibrationLine Control Valve Calibration

• Depress the SELECT button until the Line Display reads as shown on the left.• Depress the green I/O button on the Line Display and the line control valve will open and close. The display will read the position of the valve in these positions. When the display reads as shown on the right the control valve is calibrated.• The Line Control Foam Flowmeter can now be calibrated.

Page 44: AccuMax Multi-Point Injection Mechanics

Line Setup and CalibrationLine Setup and CalibrationLine Control Foam Flowmeter CalibrationLine Control Foam Flowmeter Calibration

Press the SELECT button until the Line Display reads as shown. Since one of the lines was calibrated along with the Master foam flowmeter, the calibration of the remaining foam flowmeters is not difficult.

Page 45: AccuMax Multi-Point Injection Mechanics

Line Setup and CalibrationLine Setup and CalibrationLine Control Foam Flowmeter CalibrationLine Control Foam Flowmeter Calibration

• Open the Calibrate/Inject Valve to divert foam flow to the foam tank or to a collection container.

• Press the green I/O button on the Line Control Display and the Line Control Valve will open.

Page 46: AccuMax Multi-Point Injection Mechanics

Line Setup and CalibrationLine Setup and CalibrationLine Control Foam Flowmeter CalibrationLine Control Foam Flowmeter Calibration

• Place the Master Control Display in the Master Pump setup mode as shown on the left.

• Press the SELECT button until the Master display reads as shown on the right.

• Reset the value displayed by pressing both the UP and DOWN buttons simultaneously.

• Press the green I/O button on the Master Control Display and the foam pump will start to run. The values on both the Master and Line Controls will rise.

Page 47: AccuMax Multi-Point Injection Mechanics

Line Setup and CalibrationLine Setup and CalibrationLine Control Foam Flowmeter CalibrationLine Control Foam Flowmeter Calibration

• Run the system for approximately 5 minutes.

• Compare the values displayed on the Master Control and the Line Control.

• Increase or decrease the value on the Line Control Display until it matches the Master Control Display value.

NOTE: DO NOT change the value on the Master Control Display, or recalibration of all foam flowmeters will need to be redone.

Master Line

Page 48: AccuMax Multi-Point Injection Mechanics

Line Setup and CalibrationLine Setup and CalibrationLine Control Foam Flowmeter CalibrationLine Control Foam Flowmeter Calibration

• Return the Calibrate/Inject valve back to the inject position.

• Exit the setup/calibration mode on both the Master and Line Control Displays by pressing the internal button once on the right.

• The Line Control Display and line components are now setup and calibrated. This process will need to be repeated for each Line Control Module on the apparatus.

Page 49: AccuMax Multi-Point Injection Mechanics

Master Pressure Sensor CalibrationMaster Pressure Sensor Calibration

• Place the Master Control Display in the setup mode as shown on the left.

• Press the SELECT button until the display reads as shown on the right.

• Using the UP or DOWN buttons, adjust this number to ‘0’.

• Exit the setup mode.

Page 50: AccuMax Multi-Point Injection Mechanics

Lighted On/Off Button

Reset and up/down adjust pushbuttons

Display select button

Calibrate internal switchConfiguration internal switch

12 digit display

6 digit display

System DiagnosticsSystem Diagnostics

Page 51: AccuMax Multi-Point Injection Mechanics

System DiagnosticsSystem Diagnostics

The majority of troubleshooting can be done by accessing the diagnostics mode on the Master and each Line Control Display. In this mode it is possible to display the operating parameters of the system and the components to ensure they are working properly.

The diagnostics mode is entered by removing the cover screws and o-rings on the front of the display modules using a 3/32” Allen wrench. Once the screws and o-rings have been removed, press both internal switches simultaneously. The displayed verbiage will identify what section of the diagnostics you are in.

Exit from this mode is done by pressing either of the internal switches again. The display will flash NORMAL MODE and will return to the defaulted normal operating display and mode.

Always replace cover screws and o-rings to keep water and dirt from entering the circuitry.

Page 52: AccuMax Multi-Point Injection Mechanics

Master Display Diagnostics ModeMaster Display Diagnostics Mode

Pressing the SELECT button once will display the firmware version as shown on the left.

• Pressing the UP button will display the local bus firmware version as shown in the center.

• Pressing the DOWN button will display the display firmware version as shown on the right.

Page 53: AccuMax Multi-Point Injection Mechanics

Master Display Diagnostics ModeMaster Display Diagnostics Mode

Pressing the SELECT button once will display the current circuit board temperature as shown on the left.

• Pressing the UP button will display the maximum circuit board temperature that has occurred as shown in the center.

• Pressing the DOWN button will display the minimum circuit board temperature that has occurred as shown on the right.

Pressing the SELECT button once will return you to the HIFLOW MSTR diagnostics display.

Page 54: AccuMax Multi-Point Injection Mechanics

Master Driver Diagnostics ModeMaster Driver Diagnostics Mode

Pressing the UP or DOWN button from the HIFLOW MSTR display will place the diagnostics in the MASTER PUMP diagnostics mode as shown. The diagnostics in this section will diagnose the features in the Master Driver Control.

Page 55: AccuMax Multi-Point Injection Mechanics

Master Driver Diagnostics ModeMaster Driver Diagnostics Mode

Pressing the SELECT button will display the driver firmware version as shown on the left.

• Pressing the UP button will display the driver local bus firmware version as shown on the right.

• Pressing the DOWN button will do nothing.

Page 56: AccuMax Multi-Point Injection Mechanics

Master Driver Diagnostics ModeMaster Driver Diagnostics Mode

Pressing the SELECT button once will display the current driver circuit board temperature as shown on the left.

• Pressing the UP button will display the maximum circuit board temperature that has occurred as shown in the center.

• Pressing the DOWN button will display the minimum circuit board temperature that has occurred as shown on the right.

Page 57: AccuMax Multi-Point Injection Mechanics

Master Driver Diagnostics ModeMaster Driver Diagnostics Mode

Pressing the SELECT button will allow diagnostics of the power supply voltage as shown on the left.

• Pressing the UP button will display the voltage in the logic circuitry and should show a value of 5 volts as shown in the center.

• Pressing the DOWN button will display the voltage supplied to the various sensors and should be between 11.5 and 12.5 volts as shown on the right.

Page 58: AccuMax Multi-Point Injection Mechanics

Master Driver Diagnostics ModeMaster Driver Diagnostics Mode

Pressing the SELECT button once will enter the foam pump control circuitry displaying the % of load being supplied to the hydraulic pump as shown.

• Pressing the UP button will increase the load applied to the pump.

• Pressing the DOWN button will decrease the load to the pump.

Page 59: AccuMax Multi-Point Injection Mechanics

Master Driver Diagnostics ModeMaster Driver Diagnostics Mode

Pressing the SELECT button will display the current in the pump control circuit as shown.

• Pressing the UP or DOWN button will toggle the mode to the % load mode and increase or decrease the load %, then automatically toggle back to the load current mode and display the actual current value.

Page 60: AccuMax Multi-Point Injection Mechanics

Master Driver Diagnostics ModeMaster Driver Diagnostics Mode

Pressing the SELECT button once will display the pressure transducer voltage. This value will depend on the actual pressure in the injection system, but should be between 0.5 and 4.5 volts.

Page 61: AccuMax Multi-Point Injection Mechanics

Master Driver Diagnostics ModeMaster Driver Diagnostics Mode

Pressing the SELECT button will display the foam flowmeter pulses per second as shown.

• This is a operational mode and by using the UP or DOWN buttons the display will toggle to the % load mode of the hydraulic pump and increase or decrease the load % applied to the pump. The display will automatically toggle back to the flowmeter pulse display and show the new running value.

• Pressing the SELECT button again will return the display to the MASTER PUMP diagnostics mode.

Page 62: AccuMax Multi-Point Injection Mechanics

Line Control Display DiagnosticsLine Control Display Diagnostics

The Line Control Display diagnostics are very similar to the Master Display Control diagnostics. Pressing the two internal switches on the Line Control Display will enter the diagnostics mode on each line and will display as shown.

To exit the diagnostics mode depressing one of the internal switches will return the display to the normal operating mode.

The Firmware and temperature diagnostics are the same for the Line Control Display as the Master Control Display.

Page 63: AccuMax Multi-Point Injection Mechanics

Line Driver Diagnostics ModeLine Driver Diagnostics Mode

When the Line Control Display is in the Display Mode as shown on the left, Pressing the UP or DOWN button will place the display in the Line Driver diagnostics mode as shown on the right.

Page 64: AccuMax Multi-Point Injection Mechanics

Line Driver Diagnostics ModeLine Driver Diagnostics Mode

Pressing the SELECT button will display the driver firmware version as shown on the left.

• Pressing the UP button will display the driver local bus firmware version as shown on the right.

• Pressing the DOWN button will do nothing.

Page 65: AccuMax Multi-Point Injection Mechanics

Line Driver Diagnostics ModeLine Driver Diagnostics Mode

Pressing the SELECT button once will display the current driver circuit board temperature as shown on the left.

• Pressing the UP button will display the maximum circuit board temperature that has occurred as shown in the center.

• Pressing the DOWN button will display the minimum circuit board temperature that has occurred as shown on the right.

Page 66: AccuMax Multi-Point Injection Mechanics

Line Driver Diagnostics ModeLine Driver Diagnostics Mode

Pressing the SELECT button will allow diagnostics of the power supply voltage as shown on the left.

• Pressing the UP button will display the voltage in the logic circuitry and should show a value of 5 volts as shown in the center.

• Pressing the DOWN button will display the voltage supplied to the various sensors and should be between 11.5 and 12.5 volts as shown on the right.

Page 67: AccuMax Multi-Point Injection Mechanics

Line Driver Diagnostics ModeLine Driver Diagnostics Mode

Pressing the SELECT button once will display the pressure transducer voltage. This value will depend on the actual pressure in the injection system, but should be between 0.5 and 4.5 volts. If the option is not used it will be 0.

Page 68: AccuMax Multi-Point Injection Mechanics

Line Driver Diagnostics ModeLine Driver Diagnostics Mode

Pressing the SELECT button once will place the diagnostics in the water flowmeter pulse mode as shown. This will display the pulses per second that the water flowmeter is sending to the driver. By opening or closing the discharge line will increase or decrease the value displayed.

Page 69: AccuMax Multi-Point Injection Mechanics

Line Driver Diagnostics ModeLine Driver Diagnostics Mode

Pressing the SELECT button once will place the display in the control valve diagnostics mode as shown. This will display the % of open condition of the control valve.

• The system does not have to run when checking this mode, but the green I/O button must be pressed.

• Pressing the UP or Down button will open or closed the control valve and will display the % of open of the valve.

Page 70: AccuMax Multi-Point Injection Mechanics

Line Driver Diagnostics ModeLine Driver Diagnostics Mode

Pressing the SELECT button will place the display in the control valve voltage mode as shown. This value will change slightly in the operation of the control valve.

• Pressing the UP or Down button will toggle the display to the control output mode. Increasing or decreasing the value will open or close the valve.

• The display will toggle back to the control valve voltage mode and display the voltage applied.

Page 71: AccuMax Multi-Point Injection Mechanics

Line Driver Diagnostics ModeLine Driver Diagnostics Mode

Pressing the SELECT button will place the display in the control valve current mode as shown. This value will change slightly as the valve is operated.

• Pressing the UP or Down button will toggle the display to the control output mode. Increasing or decreasing the value will open or close the valve.• The display will toggle back to the control valve current mode and display the current applied.

Page 72: AccuMax Multi-Point Injection Mechanics

Line Driver Diagnostics ModeLine Driver Diagnostics Mode

Pressing the SELECT button will display the foam flowmeter pulses per second as shown. • This is a operational mode and by using the UP or DOWN buttons the display will toggle to the % load mode of the hydraulic pump and increase or decrease the load % applied to the pump. The display will automatically toggle back to the flowmeter pulse display and show the new running value.

• Pressing the SELECT button again will return the display to the DISCHG VALVE diagnostics mode.