ac voltage

37
AC voltage controllers EE328 Power Electronics Dr. Mutlu BOZTEPE Department of Electrical and Electronics Engineering - Ege University

Upload: s-sarath-chandra

Post on 21-Oct-2015

48 views

Category:

Documents


3 download

DESCRIPTION

power system

TRANSCRIPT

Page 1: Ac Voltage

AC voltage controllers

EE328 Power Electronics

Dr. Mutlu BOZTEPE

Department of Electrical and Electronics Engineering - Ege

University

Page 2: Ac Voltage

Introduction

An ac voltage controller is a converter that

controls the voltage, current, and average power

delivered to an ac load from an ac source.

Some aplications;

Light-dimmer circuits

Speed control of induction motors

There are two control methods;

Phase control

Integral-cycle control

Page 3: Ac Voltage

Phase control Integral-cycle

control

Page 4: Ac Voltage

Single Phase ac voltage

controllers

Switches are SCRs

Current can be either

direction

Triac can be used.

Other controlled

switches can be used

instead of SCR

Page 5: Ac Voltage

Single Phase ac voltage

controllers

SCRs can not conduct

simultaneously

The load voltage is the

same as the source voltage

when either SCR is on.

Switch voltage is zero when

SCR is on, and is equal to

source voltage when SCR

is off.

Average current in the source and load is zero.

Average current in each SCR is not zero

Rms current in each SCR is 1/2 times the rms load current

Page 6: Ac Voltage

S1 conducts if a gate signal is

applied during the positive half-

cycle of the source

S1 conducts until the current

in it reaches zero

A gate signal is applied to S2

during the negative half-cycle of

the source, providing a path for

negative load current

Negative half-cycle is identical

to that for the positive half,

except for algebraic sign for the

voltage and current

Page 7: Ac Voltage

Typical waveform that exist in a common

incandescent light-dimmer circuit.

source voltage

Output voltage is

The rms load voltage is determined by taking advantage of positive and

negative symmetry of the voltage waveform

Page 8: Ac Voltage

Note that for =0, the load voltage is a sinusoid that has the same rms value

as the source.

Page 9: Ac Voltage

power factor of the load is

The rms current in the load and the source is

Note that pf =1 for =0, which is the same as for an uncontrolled resistive

load, and the power factor for ≥0 is less than 1.

The average SCR current is Since each SCR carries one-

half of the line current, the rms

current in each SCR is

Page 10: Ac Voltage

Since the source and load current is nonsinusoidal,

harmonic distortion is a consideration

Only odd harmonics exist in the line current

because the waveform has half-wave

symmetry.

Average

is zero

Normalized harmonic content of the line

currents vs. is shown in Fig. 5-3

Base current is source voltage divided by

resistance, which is the current for =0.

Page 11: Ac Voltage

EXAMPLE 5-1

Page 12: Ac Voltage
Page 13: Ac Voltage
Page 14: Ac Voltage
Page 15: Ac Voltage

Single-Phase Controller with an RL Load

Page 16: Ac Voltage

Single-Phase Controller with an RL Load

The solution for current in this equation

The conduction angle

is defined as

Page 17: Ac Voltage

Single-Phase Controller with an RL Load

In the interval between and when the source voltage is negative and the

load current is still positive, S2 cannot be turned on because it is not forward

biased.

The gate signal to S must be delayed at least until the current in S reaches

zero, at wt=

The delay angle is therefore at least

Solid-state relay

The power delivered to the load is

continuously controllable between the

two extremes corresponding to full

source voltage and zero.

Page 18: Ac Voltage

Single-Phase Controller with an RL Load

Solid-state relay

rms load current

Page 19: Ac Voltage

Single-Phase Controller with an RL Load

Power absorbed by the load

rms current in each SCR

average SCR current

average load current is zero

Page 20: Ac Voltage

EXAMPLE 5-2

Page 21: Ac Voltage
Page 22: Ac Voltage
Page 23: Ac Voltage

Three phase voltage controllers Y-Connected Resistive Load

The power delivered to the load

is controlled by the delay angle

oneach SCR.

The six SCRs are turned on in

the sequence 1-2-3-4-5-6, at 60°

intervals.

The instantaneous voltage

across each phase of the load is

determined by which SCRs are

conducting.

At any instant, three SCRs, two

SCRs, or no SCRs are on.

The instantaneous load voltages are either a line-to-neutral voltage

(three on), one-half of a line-to-line voltage (two on), or zero (none on).

Page 24: Ac Voltage

Three phase voltage controllers Y-Connected Resistive Load

Assumed a balanced three-phase source connected

to a balanced three-phase load.

When three SCRs are on (one in each

phase), the voltage across each phase of the

load is the corresponding line-to-neutral

voltage

When two SCRs are on, the line-to-line voltage

of those two phases is equally divided between

the two load resistors that are connected

Page 25: Ac Voltage

Which SCRs are conducting depends on the delay angle and on the

source voltages at a particular instant.

Two or three SCRs conduct at any one time for this range of

=30°

At wt=0, S5 and S6 are ON,

Van=0

At wt=30°, S1 triggered , and begins to conduct, S1, S5 and S6 are ON

Van=VAN

Page 26: Ac Voltage

=30°

The current in S5 reaches zero at 60°,

turning S5 off.

S1 and S6 remaining on

At 90°, S2 is turned on; (60° interval)

the three SCRs S1, S2, and S6 are then ON

At 120°, S6 turns off, leaving S1 and S2 ON

At 150°, S3 is turned on

the three SCRs S1, S2, and S6

are then ON

Page 27: Ac Voltage

All three phase-to-neutral

load voltages and switch

currents for =30°

Page 28: Ac Voltage

=75°

Only two SCRs conduct at any one time when the delay angle is between

60° and 90°

Just prior to 75°, S5 and S6 are conducting

S1 is turned on at 75°, S6 continues to conduct, but S5 must turn off because

VCN is negative

Page 29: Ac Voltage

=75°

S2 is turned on at 135°, S6 is forced off

The next SCR to turn on is S3, which forces S1 off

Page 30: Ac Voltage

=120°

Only two SCRs can conduct at any one time in this mode.

There are intervals when no SCRs conduct.

just prior to 120°, no SCRs are on

S1 turned on at 120°, and S6 still has a gate signal applied. Since VAB is

positive, both S1 and S6 are forward-biased and begin to conduct.

Both S1 and S6 turn off when VAB becomes negative.

When S2 is turned on, S1 and S2 are conduct.

Page 31: Ac Voltage

For >150° Vo=0

Note that a delay angle of zero

corresponds to the load being

connected directly to the three-

phase source.

The range of output voltage for the

three-phase voltage controller is

between full source voltage and

zero.

Harmonic currents in the load and

line for the three-phase ac voltage

controller are the odd harmonics of

order 6n 1, n = 1, 2, 3, . . .

Harmonic filters may be required in

some applications to prevent

harmonic currents

Since analysis of the three-phase ac voltage controller is cumbersome,

simulation is a practical means of obtaining rms output voltages and power

delivered to a load.

Page 32: Ac Voltage

Y-Connected RL Load

The load voltages for a three-phase voltage controller with an RL load are

again characterized by being a line-to-neutral voltage, one-half of a line-

to-line voltage, or zero.

The analysis is much more difficult for an RL load than for a resis-

tive load, and simulation provides results that would be extremely difficult

to obtain analytically.

Example 5-4 illustrates the use of PSpice for a three-phase ac voltage

controller.

EXAMPLE 5-4

HOMEWORK !!!

(USING PSIM)

Page 33: Ac Voltage

Delta-Connected Resistive Load

The voltage across a load resistor is

the corresponding line-to-line volt-

age when a SCR in the phase is on.

The delay angle is referenced to the

zero crossing of the line-to-line

voltage.

SCRs are turned on in the sequence

1-2-3-4-5-6.

Page 34: Ac Voltage

Delta-Connected Resistive Load

The relationship between rms line

and delta currents depends on the

conduction angle of the SCRs.

For small conduction angles (large ), the

delta currents do not overlap (Fig. 5-10b),

and the rms line currents are

Page 35: Ac Voltage

Delta-Connected Resistive Load

For large conduction angles (small ),

the delta currents overlap (Fig. 5-

10c), and rms line current increases.

The range of rms line current

is therefore

depending on

Use of the delta-connected

three-phase voltage controller

requires the load to be

broken to allow thyristors to

be inserted in each phase,

which is often not feasible.

Page 36: Ac Voltage

INDUCTION MOTOR SPEED CONTROL

Squirrel-cage induction motor speed can be controlled by varying the

voltage and/or frequency.

Operating speed corresponds to the

intersection of the torque-speed curves of

the motor and the load.

A fan or pump is a suitable load for this

type of speed control, where the torque

requirement is approximately proportional

to the square of the speed.

Page 37: Ac Voltage

STATIC VAR CONTROL (STATCOM)

Capacitors are routinely placed in parallel with inductive loads for

power factor improvement.

If a load has a varying VAR requirement,

the fixed-capacitor is not suitable.

The power factor correction capacitance

supplies a fixed amount of reactive power,

generally greater than required by the load.

The parallel inductance absorbs a variable

amount of reactive power, depending on

the delay angle of the SCRs.